Download Fundamentals of Harmonics

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Stepper motor wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Nominal impedance wikipedia , lookup

Electrical ballast wikipedia , lookup

Coilgun wikipedia , lookup

Power factor wikipedia , lookup

Current source wikipedia , lookup

Power engineering wikipedia , lookup

Rectifier wikipedia , lookup

Tube sound wikipedia , lookup

Ohm's law wikipedia , lookup

Stray voltage wikipedia , lookup

Islanding wikipedia , lookup

History of electric power transmission wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Three-phase electric power wikipedia , lookup

Opto-isolator wikipedia , lookup

Zobel network wikipedia , lookup

Power inverter wikipedia , lookup

Electrical substation wikipedia , lookup

Metadyne wikipedia , lookup

Power electronics wikipedia , lookup

Mains electricity wikipedia , lookup

Transformer wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Distribution management system wikipedia , lookup

Capacitor wikipedia , lookup

Buck converter wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Voltage optimisation wikipedia , lookup

Alternating current wikipedia , lookup

Transcript
• Locating Harmonic Sources
• System Impedance
• Impacts of Harmonics
• K-factor
• Interharmonics
1
System Effects
• Harmonic currents in a radial distribution
system will generally flow back to the
source (fig 5.23) unless they are diverted
to a nearby capacitor bank (fig 5.24).
• System impedance is generally inductive
reactance XL = w L, so remember that for
harmonic h, the reactance is
Xh = h w0 L = h X1
2
Capacitor banks
• Capacitor impedance Zc = -j Xc where
reactance Xc = 1/(w C) = 1/(2p f C)
• Since capacitor banks are rated in terms
of voltage and reactive power:
Xc = (kV)2/MVAr = 1000(kV)2/kVAr
• Again remember that Xc is proportional to
1/f, so at harmonic h: Xch = Xc1/h
3
Effects of resistance
• Resistance does not “damp out
harmonics”
• Resistance will tend to damp out
resonance, which may alleviate (to some
extent) effects of harmonics
• Power factor correction capacitors are
likely to cause some low-order harmonic
resonance problems even with resistance
in the circuit
4
Effects of harmonics
• Impact on Capacitors
• Impact on Transformers
• Impact on Motors
• Impact on Telecommunications
• Impact on Energy and Demand Metering
5
Effects of Capacitors
• Capacitors have some tolerances in
ratings according to IEEE Standard 181992:
135% of nameplate kVAr
110% of rated rms voltage (including
fundamental and harmonics)
180% of rated rms current (including
fundamental and harmonics)
120% of peak voltage
6
Effects on Transformers
• Harmonics affect transformers by
– increasing the rms current which increases
the transformer copper loss (winding
resistance loss)
– increasing the eddy-current losses, which
usually increase as the square of the
frequency
7
Ploss  Pcu  Pfe  R I2  Phy st  PEC
Ploss  R I2  PEC
PEC  V 2h2
If voltage distortion is being caused by
harmonics in the load current:
2 2
PECh  I h
PEC  PECR  I h
2 2
h
8
Type
Dry
Oil filled
MVA
0<S<1
PEC-R
3-8%
1<S<1.5
12-20%
S>1.5
8-15%
0<S<2.5
1%
2.5<S<5
1-5%
S>5
9-15%
PEC  PECR  I2h2
h
9
PEC  PECR  I2h2
K
 I
h
h
2
h
 
 Ih
h
h2

2
 
2
PEC  KPECR  Ih  KPECR Irms
h
K indicates how much extra loss is
incurred due to harmonic currents
increasing eddy-current losses.
10
K factor
• Harmonics increase losses in transformers
• K factor is used to derate transformers
K
 I
h
2
h
 
 Ih
h
h2

2
11
• Interharmonics and Losses
12