Installation Instructions
MicroSet Infrared Ceiling Sensor
Model # OMR-P-0450-R
Model # OMR-P-1200-R
10-30 VDC
P/N 9850-000399-00
General Information
• Readallinstructionsonbothsidesofthissheet
first
• Planallcomponentlocationscarefully
• InstallinaccordancewithALLlocalcodes
• ForusewithGreengateSwitchpacks&Greengate
Systems.Forusewithothersystems,contact
TechnicalSupport
Coverage
• Notforusewheretemperaturesfallbelow60°F
orabove90°F
• Forindooruseonly
• DONOTrunanyGreengatelowvoltagewiringin
thesameconduitaspowerconductors
15 ft
(4.6m)
Installation
30ft
(9.1m)
Top View
10ft
(3m)
20ft
(6.1m)
5ft
(1.5m)
10ft
(3.0m)
0’
Specifications
Technology:PassiveInfrared(PIR)
Power Requirements:
Input:
• 10-30VDCfromGreengateSwitchpackorGreengate
system.Maximumcurrentneededis25mApersensor
Output
• Opencollectoroutputtoswitchuptoten
GreengateSwitchpacks
• IsolatedFormCRelay(-Rmodel)
• IsolatedFormCRelayRatings:1A,30VDC/VAC
Time Delays:
• Self-Adjustingfrom10min.to30min.
Ambient Light Features:
• Adjustablefrom10to300foot-candles
Operating Environment:
• Temperature:60°F–80°F(15°C–26°C)
• RelativeHumidity:Lessthan95%non-condensing
• Forindooruseonly
Housing:
• Mediumimpactinjectionmoldedhousing.ABS
resincomplieswithUL94V0
Size:3”diameterx1.43”deep
(76.2mmdiameterx36.32mmdeep)
LED Indicators:RedLED
TheMicroSetTechnologycontainedwithinsensorcontinuouslyself-adjustssensitivityandtimedelayautomatically
andimmediatelyinresponsetooccupantbehavior.Thereisnoneedfortimeconsumingmanualadjustmentsorto
“learn”behaviorpatternsoverextensiveperiodsoftime.
MicroSet™ Recessedt
10ft
(3.0m)
10ft
(3m)
20ft
(6.1m)
15 ft
(4.6m)
Side View
30ft
(9.1m)
0’
0’
12ft
9ft
7ft 5ft 3ft
(3.7m) (2.7m) (2.1m)(1.5m)(0.9m)
0’
12ft
7ft
9ft
3ft
5ft
(0.9m) (1.5m) (2.1m) (2.7m) (3.7m)
8ft
(2.4m)
Side View
Sensor Unit
24ft
(7.3m)
OMR-P-0450-R Coverage Diagram
Up to 450 sq. ft.
Description
TheMicroSetPassiveInfraredceilingsensorscanbeusedindividuallyorincombinationtoprovidelightingcontrol
andintegrationwithHVACcontrolthroughoutabuilding.Availableinrecessed,flushmountlowvoltagemodels.
CAUTION: Finger-tighten the nut to avoid stripping the mounting post.
0’
5ft
(1.5m)
8ft
(2.4m)
Sensor:
1.Passwiresthroughthethreadedmountingpostandinterlocktothebackplate.
2.Sensormountstonormalceilingtilethroughasingle3/4”hole.
3.Whenmounted,thesensor’sslottedgrillsmustpointalongthepathwheremotionistobedetected.
4.Anadapterplate(ACMP)isavailabletoallowmountingtoastandardfixtureringandjunctionbox.
5.Thethreadedmountingpostmaybecutdownifitistoolongtofitintothejunctionbox.
Top View
14ft
(4.3)
8ft
8ft
14ft
3ft 0’ 3ft
(2.4m) (0.9m) (0.9m) (2.4m) (4.3)
24ft
(7.3m)
OMR-P-1200-R Coverage Diagram
Up to 1200 sq. ft.
Switchpack:
Designedtobemountedexternallytoanyjunctionbox.Whenmounted,lineconnectionsareinsidetheboxand
theClass2wiringexitsthroughtherearoftheswitchpackhousing.InareaswhereClass2wiringisnotpermitted,
theswitchpackcanbemountedinternallytoanystandardelectricalbox.
Switchpack
Location
J Box
Sensor:
Followthediagramsshownconcerningmajorandminormotioncoverage.
1.Choosesensorlocationcarefully.
Note:Thesensormusthaveaclear viewoftheareatobecontrolled.Itshouldnotbeblockedfrom“seeing”peoplebyhighpartitions.Thesensorwillnot“see”
throughglass.
2.Mountingheightshouldnotexceed12ft.Topreventfalseactivation,thesensorshouldbemountedawayfromthe
pathofstrongairturbulenceaminimumof4to6ft.Fortypicalplacementrefertolocationdiagramsbelow.
Switchpack:
Theswitchpackisgenerallymountedabovetheceilingontheoutsideofthejunctionboxthatcontainsahotline,
neutralandtheexistingswitchlegfromwhichthelightingiscontrolled.Ifadditionalswitchpacksarerequired,theyare
mountedontheoutsideoftheboxescontainingtheappropriateswitchlegs.Ininstallationswheretherearenoexisting
switchlegs,theswitchpackmaybemountedontheoutsideofanyconventionalstandardjunctionbox,withorwithoutan
extensionring.
Locknut
Coverplate
20’
18’
10’
S
L - Shaped
Office
S
10’×12’ Office
S Sensor
S
15’× 20’ Conference Room
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com
Wiring
Checkout and Adjustment
MANUAL MODE OPERATION:
Nomanualadjustmentsnecessaryatinstallation.Thesensorwillautomaticallysetthetimedelaytothe
recommendedsettingof10minuteswhenleftattheinstallertestsettingafterlightsareOFFforaminimumperiodof5
minutes.Atinstallation,thesensorwillscanthecoverageareatodeterminetheoptimumsensitivitysetting.MicroSet™
PIRCeilingSensorscontinuallyself-adjustsensitivityandtimedelayautomaticallyandimmediatelyinresponseto
occupantbehavior,eliminatingtheneedto“learn”behaviorpatternsovertime.Thisreducestheneedforfollow-up
adjustments.DIPswitchoverrideallowstimedelaytobelockedat30minutes.
1. SWITCH IS REQUIRED TO TURN
LOAD ON.
2. LOAD TURNS OFF WHEN SENSOR
TIMES OUT OR WITH SWITCH.
HOT
AUTOMATIC MODE OPERATION:
LINE
RED (15VDC)
SWITCHPACK
BLUE (CONTROL)
RECOMMENDED WIRE:
18-3 AWG STRANDED WIRE SHIELDED OR
NON/SHIELDED
BLUE
3. IF DAYLIGHT SENSOR IS ENABLED AND
LIGHT LEVEL IS ABOVE SETPOINT,
SWITCHPACK CONNECTED TO YELLOW
LEAD WILL NOT TURN LOAD ON.
**HOT
**USE BLACK LEAD FOR 120VAC.
USE ORANGE LEAD FOR 277VAC.
CAP UNUSED LEAD.
2. SWITCH CAN BE USED TO TURN
LOAD ON OR OFF.
WHITE
NEUTRAL
1. WHEN SENSOR ACTIVATES,
LOAD TURNS ON.
LOAD "A"
BLUE
BLACK (COMMON)
RED (10-30VDC)
Note:NOTES
BLUE (CONTROL-OCC)
1. LOADS MAY BE ON SAME
1.LOADSMAYBEONSAME
CIRCUIT OR DIFFERENT
CIRCUITS OR VOLTAGES.
CIRCUITORDIFFERENTCIRCUITSOR
VOLTAGES.
2. SP20-MV SWITCHPACK SHOWN.
120/277VAC 20AMP RATING.
2.SP20-MVSWITCHPACKSHOWN.
20/277VAC20AMPRATING.
BLACK (COMMON)
PURPLE (NORMALLY CLOSED)
YELLOW (CONTROL-OCC/DAY)
GRAY (COMMON)
MODEL GMDS - LOAD "A"
(NORMALLY OPEN
MOMENTARY SWITCH)
BROWN (BLUE CONTROL)
ORANGE (NORMALLY OPEN)
DIP Switches 1-8
DIP Switch Settings
1
DIP Switches 1-8
2
3
4
Note:Thepreferredmodeistoleave
1 - Auto/Manual Mode -
5
6
7
8
2 - Enable Lighting Sweep allDIPswitchesinthedefaultposition.
A
ON
3
4
5
6
7
6 - Light Level A
50 FC
8 - Light Level C
1
2
Lighting
Sweep
On
Mode
Position2
ManualON
Enabled
Position1
(Default)
AutoON
NotEnabled
3
Time
Delay
5
4
Override
Lockedat
30minutes
SelfAdjusting
Daylight
Logic
20 FC
7
LightLevel
B
1.FlipDIPswitch2toposition2.
2.LeaveDIPswitchatposition2for1second.
3.FlipDIPswitchbacktoposition1.
4.Remainstill.TheLEDwillnotflash.ThelightsshouldturnOFFafter15seconds.(Ifnot,see“Troubleshooting.”)
5.Moveaboutthecoveragearea.ThelightsshouldcomeON.
10 FC
Not Enabled
6
LightLevel
A
Daylight Adjustments
Full and Half Logic Modes (See DIP Switch legend):
InbothFullandHalfLogicmodes,lightsconnectedtotheyellowcontrolleadwillnotturnONuponoccupancy
activation,shouldtheambientlightlevelexceedthepresetfoot-candlelevel.
After activation:
FullLogicMode-shouldtheambientlightlevelexceedthepresetfoot-candlelevel,thelightsconnectedtothe
yellowcontrolleadwillturnOFF.ThelightswillremainOFF,untiltheambientlightlevelfallsbelowthesetpoint.
HalfLogicMode–theoutputstateoftheyellowcontrolleadwillnotchangewithambientlightchanges,after
occupancyactivation.
delayis15seconds.However,sensorautomaticallyadjuststothesurroundingenvironment;thustestingthesensorisnotrequired.
30 FC
See “Light Level
Settings” chart
7 - Light Level B See Chart
Lighting Sweep
Whensensorsareusedinconjunctionwithcomputerlightingsweepsystems,youMUSTenabletheLightingSweep
featurebyturningDIPswitch2toposition2.Enablingthisfeaturepreventsanunneccecessary“lightsON”followingthe
computerpower-onsweep.
Note:SensorisnowinTestmode.SensorwillremaininTestmodeaslongaslightsarenotcontinuouslyOFFfor5minutes.DuringtheTestmode,thetime
70 FC
5 - Half/Full Daylight Logic - Full Logic
8
C
100 FC
4 - Enable Default to ON - ON (Override)
2
B
150 FC
3 - Locked 30 Minute Delay - ON (Self Adjust )
1
LIGHT LEVEL SETTINGS
ON
Troubleshooting
8
LightLevel
C
Override
FullLogic
Enabled
Enabled
Enabled
Normal
HalfLogic
NotEnabled
NotEnabled
NotEnabled
Issue
Possible Causes
Suggestions
WallSwitchOFF
TurnWallSwitchON.
Lights
Will Not
Turn ON
automatically
Iflowvoltageswitchoptionisused,lightsmay
havebeenturned-offmanually.
Presslow-voltageswitch.
DaylightFeatureEnabled
IfalllightsarerequiredtoturnONadjustDIPSwitch10and/
ordaylightpotentiometer
Powerinterruption
Checkincomingvoltageand/orwiring
DaylightFeatureEnabled
IfalllightsarerequiredadjustDIPswitch10and/ordaylight
potentiometer.
Powerinterruption
Checkincomingvoltageand/orwiring
Lights
Will Not
Turn ON
manually
If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879
Lights
Will Not
Turn OFF
automatically
Testingisnowcomplete.Simplyleavethearea.LightsshouldturnOFFafter15seconds.After5minutesofthelights
beingOFF,sensorwillautomaticallygointousermode.
Lights Will Not
Turn OFF
manually
Override
MakesuresensorisnotinOverrideMode(DIPSwitch8up).
UltrasonicSensitivitysetHigh
LowersensitivitybyturninggreenpotentiometerCCWin
smalldecrements.
Sensorinstalledclosetoanairvent
Sensorsshouldbeinstalledminimum4-6feetawayfrom
anyairventandoutofpathofheavyairflow.
Sensorinstalledclosetoindirectlighting.
Sensorsshouldbemountedawayfromindirectlighting.
Self-adjust
Itmaybepossiblefortheunittohaveself-adjustedthetime
delaytoa30minutedelay.IfthelightsdonotturnOFFafter
30minutesfollownextstep.
30MinuteDelay
Maximumtimedelayis30Minutes.CheckDIPSwitchesto
verifyDIPSwitchsettings.IflightsdonotturnOFFattheset
timedelay,checknextstep.
PIRactivatedbyheatsourceotherthanoccupant
MoveDIPSwitch5up.
Bypass
Checkwiringtomakesuresensororswitchpackarenot
bypassed.
Override
MakesuresensorisnotinOverrideMode(DIPSwitch8up).
If lights will still not turn OFF, call Technical Services at 1-800-553-3879