Download IEC Separable Connectors 17.5 kV/24 kV, 630A

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Alternating current wikipedia , lookup

Portable appliance testing wikipedia , lookup

Dynamic range compression wikipedia , lookup

Mains electricity wikipedia , lookup

Aluminium-conductor steel-reinforced cable wikipedia , lookup

Stray voltage wikipedia , lookup

Printed circuit board wikipedia , lookup

Skin effect wikipedia , lookup

Telecommunications engineering wikipedia , lookup

Loading coil wikipedia , lookup

National Electrical Code wikipedia , lookup

Industrial and multiphase power plugs and sockets wikipedia , lookup

Coaxial cable wikipedia , lookup

Phone connector (audio) wikipedia , lookup

Transcript
IEC Separable Connectors
17.5 kV/24 kV, 630A
Front T-Body / Coupling (Rear) T-Body Connector
Application
The Chardon T-Body connectors are used to terminate polymeric cable
to dead front apparatus such as transformers, switchgear, and other
equipment. They can be used at 17.5 kV and 24 kV. They can be used
for indoor or outdoor applications, and can be used for all polymeric
cable types (XLPE, EPR, etc.) with copper or aluminum conductors.
Key Features
• Provides a fully shielded and submersible connection when
mated with the proper bushing or plug.
• Type “C” 630A Interface.
• Mounting can be vertical, horizontal, or any angle in between.
• No minimum phase clearance requirements.
• 100% electrical tested at factory.
Product Ratings
Maximum Voltage Class (Um):
24 kV
AC 5 Minute Withstand:
54 kV
Minimum Corona Voltage Level:
20 kV < 3 pC
BIL and Full Wave Crest (Impulse):
125 kV
Thermal Short Circuit (Conductor, 2 sec.)
23kA/2s
Dynamic Short Circuit (Conductor, 10 sec.)
82 kA/10ms
Continuous Current
630A
Overload Current (8 hours maximum)
900A
Production Tests
Tests conducted in accordance with IEC 60502-4
• Minimum Corona Voltage Level – 20 kV<3pC
• AC 5 Minute Withstand – 54 kV
Tests conducted in accordance with Chardon manufacturing process requirements:
• Physical Inspection
• Periodic Dissection
• Periodic X-Ray analysis
17KV-IEC-SC-REV010615
www.chardongroup.com
Detailed composition of the Chardon
17.5 kV/24 kV Front T-Body Connector
INSULATING PLUG
STUD
Zinc plated, threaded steel stud.
Molded epoxy insulating plug provides excellent
electrical, thermal and mechanical reliability.
CONDUCTING INSERT
Precision molded peroxide cured conducting
insert provides corona-free electrostatic
shielding of the compression connector.
RUBBER END CAP
Molded EPDM conducting rubber end
cap protects and grounds the insulating
plug test point.
INSULATION LAYER
High quality peroxide cured EPDM
Insulation is mixed and formulated in-house
for complete control of rubber characteristics.
DRAIN WIRE
CONDUCTING SHIELD
Precision molded peroxide cured
conducting shield provides ground
shield continuity.
Drain wire tabs provide a convenient point to
connect drain wire to ensure grounding of the
connector shield.
COMPRESSION CONNECTOR
Compression connector made of aluminum,
copper, or bi-metal (aluminum/copper).
CABLE ADAPTER
Molded cable adapter, sized to fit cable
insulation diameters from (15.5 mm to 37 mm)
0.61 inches to 1.46 inches, provides stress
relief for the terminated cable.
Detailed composition of the Chardon
17.5 kV/24 kV, Coupling
(Rear) T-Body Connector
INSULATING PLUG
STUD
Molded epoxy insulating plug provides excellent
electrical, thermal and mechanical reliability.
Zinc plated, threaded steel stud.
CONDUCTING INSERT
Precision molded peroxide cured conducting
insert provides corona-free electrostatic
shielding of the compression connector.
INSULATION LAYER
High quality peroxide cured EPDM
Insulation is mixed and formulated in-house
for complete control of rubber characteristics.
CONDUCTING SHIELD
Precision molded peroxide cured
conducting shield provides ground
shield continuity.
CABLE ADAPTER
Molded cable adapter, sized to fit cable
insulation diameters from (15.5 mm to 37
mm) 0.61 inches to 1.46 inches), provides
stress relief for the terminated cable.
RUBBER END CAP
Molded EPDM conducting rubber
end cap protects and grounds the
insulating plug test point.
DRAIN WIRE
Drain wire tabs provide a convenient
point to connect drain wire to ensure
grounding of the connector shield.
COMPRESSION CONNECTOR
Compression connector made of
aluminum, copper, or bi-metal
(aluminum/copper).
ORDERING INFORMATION
24 -
___
630 -
STEP 1
STEP 1
_
___
STEP 2
___
Selection of Front / Rear T-body
STEP 3
STEP 4
_
STEP 4
_
Selection of Compression Connector Material
Front T-Body
Coupling (Rear) T-body
STEP 2
_
Selection of Cable Insulation Dimension
ORDERING EXAMPLE:
For a CHARDON 24kV Front T-body with cable
insulation outer dimension of 26.4mm and a conductor
size of 185mm² with copper compression connector, the part
number would be as fallows:
STEP 3
___
24-FDT630C185C
Selection of Conductor Size
www.chardongroup.com
Chardon Taiwan Corporation
No. 37 Min-Chie Road
Tung Lo Industrial Park
Miao Li, Taiwan 366
Phone: 886-3-798-4385
Fax: 886-3-798-4770
Shanghai Chardon Electric, Ltd.
No. 9, Lane 55, Fenggong Road
Malu, Jiading
Shanghai, China
Phone: 86-21-3910-5900
Fax: 86-21-3910-5916
Den Mar Utility Products, Inc.
1032 Lido Court
Ft. Lauderdale, FL 33326 USA
Phone: 1-954-384-6217
Fax: 1-866-812-9344
Chardon Korea
203-24 Goji-ri 191-28Gajang-ro
Jeongnam myeonHwaseong-si
445-962 Gyeonggi-do, Korea
Phone: 82-10-8928-9074
Fax: 82-2-6322-2727