Download FlexBar HRT Pressure Transmitter

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

History of electric power transmission wikipedia , lookup

Spark-gap transmitter wikipedia , lookup

Islanding wikipedia , lookup

Ground (electricity) wikipedia , lookup

Telecommunications engineering wikipedia , lookup

Buck converter wikipedia , lookup

Stray voltage wikipedia , lookup

Metadyne wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Voltage optimisation wikipedia , lookup

Alternating current wikipedia , lookup

Earthing system wikipedia , lookup

Mains electricity wikipedia , lookup

Electrical wiring in the United Kingdom wikipedia , lookup

Transcript
FlexBar HRT Pressure Transmitter
Safety instructions
This instrument is built and tested according to the current EU-directives and packed in technically safe condition. In order to maintain this
condition and to ensure safe operation, the user must follow the hints
and warnings given in this instruction.
During the installation the valid national rules have to be observed.
Ignoring the warnings may lead to severe personal injury or substantial
damage to property.
The product must be operated by trained staff. Correct and safe
operation of this equipment is dependent on proper transport, storage,
installation and operation.
All electrical wiring must conform to local standards. In order to prevent
stray electrical radiation, we recommend twisted and shielded input
cables, as also to keep power supply cables separated from the input
cables. The connection must be made according to the connecting
diagrams.
Before switching on the power supply take care that other equipment
is not affected. Ensure that the supply voltage and the conditions in the
environment comply with the specification of the device.
Before switching off the supply voltage check the possible effects on
other equipment and the processing system.
WARNING
For electrical installation and commissioning of explosion protected
devices, the data given in the conformity cer tificate as also the local
regulations for installation of electrical apparatus within explosion protected areas must be considered. The intrinsically safe versions can be
mounted in the explosion hazarded area according to its specification
only connected to a certified intrinsically safe supply loop with the corresponding electrical values.
This Ex-approved product is manufactured by:
Baumer A/S
Jacob Knudsens Vej 14
DK-8230 Aabyhoej
Denmark
www.baumerprocess.com
Design and specifications subject to change without notice
Installation Manual
Page 1
Installation
1)
Factory guarantee is void on mechanical damages on the diaphragm.
Die Werksgarantie erstreckt sich nicht auf mechanische Schäden der Membran.
Les détériorations mécaniques de la membrane ne sont pas couvertes par la garantie .
Mekanisk skade på membranen er ikke omfattet af fabriksgarantien.
Mekaniska skador på trycktransmitterns membran omfattas inte av garantin.
Takuu ei koske käytön aikana tullutta mekaanista vauriota kalvossa.
3)
2)
4...20 mA
>22 mm
1
6.5...35 Vdc
2
Opto-relay
4
3
+ 1
2 -
Plug M12
4)
+ 1
2 -
3
- 2
Plug
DIN 43650 B
www.baumerprocess.com
Design and specifications subject to change without notice
1+
Plug
DIN 43650 A
Installation Manual
Page 2
FlexBar HRT Electronics Module
Screw terminals 1 & 2: 4...20 mA loop
Test terminals:
With a multimeter (Ri < 2 Ohm)
the loop current can be measured
without breaking the loop.
LED, lights during
Auto Zero adjustment
Screw terminals 3 & 4: Opto-relay
Voltage, standard: max. 230Vac
Auto Zero push button
Voltage, GL. approval: max. 60Vac
DC-voltage: max. 50 Vdc
Pin 1 & 2: Connection
of FlexProgrammer
Current, continuous: max. 50 mA
Current, pulse: max. 500 mA
Ground connection
Non-Ex-application, Point-to-point, HART
230 Vac
3 4
+
1 2
2
-
1
+
-
24 Vdc
4...20 mA
Resistance
> 250 Ohms
www.baumerprocess.com
Design and specifications subject to change without notice
Power supply
(or master)
FlexBar HRT pressure transmitter
with FlexView display (optional)
Installation Manual
Page 3
Installation
Unpacking the transmitter
The correct zero point pressure must be established prior to adjustIf the transmitter is visibly damaged, it should not be put into operation. ing the zero point. Tank and pressure transmitter must have the same
temperature. If the pressure transmitter has a relative measuring cell
Mechanical installation and cleaning
from 0 bar, the zero point pressure is the same as the atmospheric
The pressure diaphragm must not be touched during installation.
pressure or the level in a tank selected as zero point level. A pressure
Cleaning with pressurised cleaners and tools may damage the
transmitter measuring absolute pressure has a zero point lower than 1
diaphragm (Fig.1).
mbar abs.
When the required zero point pressure has been established, the Zero
Precautions prior to the installation:
push button inside FlexBar must be pressed and held. The LED will
If the transmitter has a 1/2" threaded neck, check before mounting
respond with one blink per second. When the actual zero pressure
in a blind hole that the thread length is at least 22 mm (Fig.2). Use
level has been stored in the memory of the FlexBar the LED will blink
a gasket ø28.6 x ø21.5 mm, made from a material proof against the
twice a second.
measuring medium, and do the clamping with an NV27 mm engineer's You can revert to the zero point correction set by Baumer by reconfigwrench. FlexBar HRT can be mounted on a Baumer pressure gauge
uring the FlexBar HRT with the FlexProgrammer.
connection type no. 81 26-92X (see data sheet).
The pressure transmitter can change zero point slightly, owing to
mechanical tension
For a correct 3A installation refer to page 7.
and the fitting direction selected for the pressure diaphragm. Optimal
results are therefore achieved if the zero point is adjusted after the
Mounting the pressure transmitter in closed systems (e.g. a stop cock) pressure transmitter has been mounted in place.
can create overpressure in excess of that permitted (400%), which
could deform the diaphragm and damage the pressure sensor.
Electrical installation
Suitable cables should be used to secure maximum tightness in the
The transmitter must not be exposed to pressure or surge exceeding
gland. For models having a plug for electrical connection the inner part
4 x span, max. 600 bar though.
of the plug must be oriented in a way so that the opening is turning
downwards (Fig4).
The freezing point of process media and condensates must be
To avoid measuring errors resulting from insufficient supply voltage,
checked to prevent unintentional pressure rise when it is freezing.
the transmitter must be supplied with min. 6.5 Vdc at 23 mA.
The transmitter has a high immunity against high-frequency interferRadiated heat may create excessively higher operating temperatures
ence. In environments with a high radiation we recommend to use
than the allowed -10...70°C (14...154°F).
screened and twisted cable (Fig. 3).
Disposal of product and packing
Installation procedure
According to national laws or by returning to Baumer
a) Remove protection-cap.
b) Install FlexBar.
(G1/2A versions: Tighten up at 20 Nm.)
c) Configure Span by the FlexProgrammer or a HART
configurator.
d) Connect the power supply, press and hold the Auto Zero button
or use the facility in the FlexProgrammer or the HART configurator.
Adjusting the zero point
With FlexBar HRT the electronic zero point can be adjusted from
-10...10% of the total measuring range.
Ex-Configuring
Warnings
None of the two types of FlexProgrammer configuring unit must be
connected to the FlexBar HRT within the hazardous area.
WARNING
This product contains no replaceable parts.
In case of malfunction the product must be shipped to Baumer for
repair.
Configuring procedure:
a) Disconnect mains from the 4...20 mA loop circuit.
b) Disconnect the FlexBar HRT from the circuitry within
the hazardous area.
c) Uninstall and bring the FlexBar HRT to the safe area.
d) Connect the FlexProgrammer and perform the
configuring session.
e) Re-install the FlexBar HRT in the hazardous area.
f) Connect the power supply to the circuit.
Configuration of the FlexBar HRT can be made within the hazardous
area by means of the handheld configurator model 275, providing the
precautions and guidelines described in the product´s manual are
observed.
www.baumerprocess.com
Design and specifications subject to change without notice
WARNING
Products with painted and/or plastic surfaces (e.g. display) imply a risk
of electrostatic charging.
To prevent electrostatic hazard - do only clean with a moist cloth.
After mounting the device - do check that the housing has a ground
potential.
Installation Manual
Page 4
Ex ia IIC T5/T6, ATEX II 1G
Opto-relay
Ex-data
Supply range
6.5...30 VDC
Voltage, standard
Max. 230 VAC
Internal inductivity
Li < 10 µH
Voltage, GL-approved
Max. 60 VAC
Internal capacity
Ci < 1 nF
DC-voltage
Max. 50 VDC
Barrier data
U < 30 VDC ; I < 0.1 A ; P < 0.75 W
Current, continuously
Max. 50 mA
Temperature class
T1...T5:
T6:
Current, pulse
Max. 500 mA
Relay function
Set/reset
-10 < Tamb < 70°C
-10 < Tamb < 50°C
Ex ia - Installation
A FlexBar HRT with the type number 81 6x2 xxx xxxx is Ex ia IIC
T5/T6 and ATEX II 1G approved for application in hazardous areas in
accordance with the current EU-directives.
If the FlexBar HRT has the relay option (type numbers 81 62 xxxx
xxxx and 81 64 xxxx xxxx) the connections to the relay must be carried
out according to the rules for an intrinsically safe installation.
A certified Ex ia or isolation barrier with the maximum values
Umax = 30 VDC ; Imax = 0.1 A ; Pmax = 0.75 W must be used.
The FlexBar HRT must be connected in the 4...20 mA loop circuit only.
Zone 0/1
Safe area
230 VAC
3 4
Lamp
1 2
+
3
Relay
24 VDC
4...20 mA
4
4..20 mA 1
2
Zone 0/1
230 VAC
Safe area
3 4
FlexBar HRT
with relay and cover
-
+
1 2
+
4...20 mA
Barrier
www.baumerprocess.com
Design and specifications subject to change without notice
FlexView display
(Optional)
24 VDC
Power
Supply
Installation Manual
Page 5
Ex nA II T4/T5, ATEX II 3G
Opto-relay
Ex-data
Supply range
6.5...35 VDC
Temperature class
T1...T4:
T5:
Voltage, standard
-10 < Tamb < 85°C
-10 < Tamb < 60°C
Max. 230 VAC
Voltage, GL-approved
Max. 60 VAC
DC-voltage
Max. 50 VDC
Current, continuously
Max. 50 mA
Current, pulse
Max. 500 mA
Relay function
Set/reset
Ex nA - Installation
A FlexBar HRT with the type number 81 6x3 xxx xxxx is Ex nA II
T4/T5 and ATEX II 3G approved for application in hazardous areas in
accordance with the current EU-directives.
If the FlexBar HRT has the relay option (type numbers 81 62 3xxx
xxxx and 81 64 3xxx xxxx) the connections to the relay must be carried
out according to the rules for an intrinsically safe installation.
The FlexBar HRT must be installed in accordance with prevailing
guidelines for zone 2 without a barrier.
The FlexBar HRT must be connected in the 4...20 mA loop circuit only.
Electrical Connection
Electrical Connection
Cable diameter
mm
Torque
Nm
Gland M20, plast
Plug DIN-B
8...13
6...8
8
4
Plug DIN-A
8...10
3
Gland M16
3...9
8
Plug M12
-
4
Warning: If the FlexBar HRT is to be installed in ambient
temperature exceeding 70°C a proper cable should be installed.
Ex nA - Installation
230 VAC
-
+
-
+
4...20 mA
+
-
24 VDC
FlexBar HRT
www.baumerprocess.com
Design and specifications subject to change without notice
FlexView display
(Optional)
Power
Supply
Installation Manual
Page 6
Mounting of 3A Approved Products
Max. ± 85°
4)
5)
1)
2)
3)
Installation of 3A approved products:
1) Use only a 3A approved counter part.
Max. ± 175°
Refer to the data sheet “FlexBar Accessories” for O-rings, gaskets and
other accessories.
2) The inspection hole should be visible and drained.
3) Mount the instrument in a self drained position.
4) Level the inner surface of the pipe with the counter part.
5) Weldings should be grinded to Ra= 0.8