Download RI-R38

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Control system wikipedia , lookup

Solar micro-inverter wikipedia , lookup

Electrical substation wikipedia , lookup

Relay wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Buck converter wikipedia , lookup

Rectifier wikipedia , lookup

Power electronics wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Ground (electricity) wikipedia , lookup

Voltage optimisation wikipedia , lookup

Protective relay wikipedia , lookup

Metadyne wikipedia , lookup

Distribution management system wikipedia , lookup

Alternating current wikipedia , lookup

Portable appliance testing wikipedia , lookup

Opto-isolator wikipedia , lookup

Automatic test equipment wikipedia , lookup

Stray voltage wikipedia , lookup

National Electrical Code wikipedia , lookup

Three-phase electric power wikipedia , lookup

Mains electricity wikipedia , lookup

Electrical wiring in the United Kingdom wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Earthing system wikipedia , lookup

Transcript
INSTRUCTION MANUAL
IM810-U v0.3
RI-R38
DEVICE FOR INSULATION PERMANENT CONTROL FOR NEUTRAL NETWORKS (IT)
GENERAL
RI-R38 is a device that allows to control the insulation to earth in alternating neutral networks up to 440 V (IT
systems).
Putting a continuous component measure signal between the insulated line and earth it’s possible to control the
insulation resistance reading the dispersion current generated to earth.
On the frontal panel of RI-R38 there is the signalling of device ON, the signalling of tripping TRIP (low insulation), a
test and a reset push-buttons and a series of micro-switches to regulated the threshold of trip.
It’s available a changeover contact relay to use the low insulation signalling in a remote panel.
OPTIONS
Standard version 230 Vac, option version 115 Vac
INSTALLATION
The installation must be carried out by qualified and authorized personnel and in absence of voltage. Make sure that
the instrument is O.K. and it has not suffered any damage during transport. Make sure that the voltage supply are
compatible with the operating voltage of instrument.
The device is a 3 modules (17.5mm) DIN version with snap on 35mm DIN rail. It has a sealable transparent frontal
protection cover.
The green LED ON will bright after the connections are set and the instrument is power on.
DESCRIPTION
7
8
9
10
11
1. green LED ON
signalling of the instrument working
12
2. red LED TRIP
signalling of trip for low insulation
1
4
3. TEST button to test the instrument functionality
RI-R38
RESET
2
150
100
50
30
10
4. RESET button to cancel the trip signalling (manual reset)
ON
INSU LATION
MONITOR
5. micro-switches to select the threshold of trip
TRIP
TEST
kΩ
5
3
1
2
3
4
5
6
MICRO-SWITCHES SETTING
The frontal micro-switches allow to set the threshold of trip between 10 and 150 kΩ as it’s showed in the following
figure:
100
50
30
10
RI-R38
150
100
50
30
10
150
100
50
30
10
instruction manual
150
100
50
30
10
150
IM810-U v0.3
100
50
30
10
150
pag. 1 / 4
WIRING CONNECTION
insulation monitor
RI-R38
Vaux
1
2
AUX1
3
4
5
AUX2
6
VC
7
8
9
10 11 12
OUT-NO OUT-C OUT-NC
PE RESET
Vaux:
220-240Vca
opzionale:
100-130Vca
PE
N
L3
Max 400V L-N
CARICO
L2
L1
Vaux
Vaux
10 11 12
1
AUX1
2
3
4
AUX2
5
VC
1
2
AUX1
3
4
AUX2
PE RESET
5
VC
RESET
Max 400V L-N
Max 760V L-L
N
L3
L
L2
N
L
L1
RI-R38
instruction manual
IM810-U v0.3
pag. 2 / 4
LEGEND
Auxiliary power supply
Terminals 1-3
The auxiliary power supply could be the same of the network to control.
Insulation control
Terminals 5-11
The two terminals must be connected between the line under control and the earth of measure reference.
The terminal 5 must be connected to the neutral conductor of the single-phase or the three-phase line of the line to
control. If the three-phase network is at three wires, the terminal must be connected to a phase.
The maximum voltage required between these terminals is 440V and for this reason it’s possible to put the
insulation controller on single-phase line or on three-phase line with 3 wires without neutral up to 440V and with 4
wires with neutral up to 760V.
Relay output connections
Terminals 7-8-9
To remote signalling by relays with changeover contact max 5A 250V on resistive load.
Automatic or remote RESET connection
terminal 12
Connecting the terminal 12 to the 11 (ground) it’s possible to have a manual RESET functioning (using the pushbutton on the frontal of the instrument). Without the connection on the terminal 12 the instrument will function with
automatic RESET when the low insulation stops.
It’s possible to connect an external N.C. contact push-button between the monitoring device and the ground.
FUNCTIONALITY
In normal condition, with insulation value higher than the set threshold, the instrument has the green LED on.
Pressing the TEST button the TRIP LED of alarm signalling and the output relay will be activated.
Depending of the connection the RESET will be automatic when the TEST button is reIeased or using a remote
button or manual using the RESET button on the front panel.
If there is a low insulation on the line (resistance value under the set threshold) will be activated the TRIP signalling
and the output relay. When the insulation on the line will come back higher than the set threshold, the trip signalling
will disappear.
RI-R38
instruction manual
IM810-U v0.3
pag. 3 / 4
DIMENSIONS
58
52,5
Snap on DIN rail 35mm
(DIN 50022)
3 modules 17,5 mm
45
85,5
44
kΩ
65
TECNICAL FEATURES
Auxiliary voltage supply
Maximum consumption
Network to control
Measure voltage
Measure current
Internal impedance
Threshold tripping
Tripping delay
Signalling and button
Output
Working and storing temperature
Relative humidity
Insulation test
Mounting position
Wiring type
Protection degree
Mounting according DIN 50022
Weight
Standards
230V 50-60Hz ± 20% or 110V 50-60Hz ± 20%
3 VA
24 ÷ 440Vca +10% (760V on three-phase line with neutral)
Max 24V
Max 0,5 mA
100 kohm
Settable 10 ÷ 150 kohm (4 level with micro-switches)
About 1 second
Led ON, led TRIP; TEST and RESET button
Relay changeover contact NA-C-NC max 5A 250Vca
-10 ÷ 60°C / -20 ÷ 70°C
≤ 95 %
3 kV 60 sec. / 4 kV imp. 1,2/50µs
Any
Screw terminals / cross section cables 4 mm2
Frontal with cover: IP 40 – Enclosure: IP 20
Snap on DIN rail 35mm / 3 modules 17,5 mm
About 300 g
Safety CEI-EN 61010-1
Product CEI-EN 61557-8
Electromagnetic compatibility CEI-EN 61326-1
For application not described in this manual it’s better to see specific document or to contact the technical service.
RI-R38
instruction manual
IM810-U v0.3
pag. 4 / 4