Download B-05: Rack In/Rack Out Breakers

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Pulse-width modulation wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Power over Ethernet wikipedia , lookup

Fault tolerance wikipedia , lookup

Alternating current wikipedia , lookup

History of electric power transmission wikipedia , lookup

Electrification wikipedia , lookup

Protective relay wikipedia , lookup

Electric power system wikipedia , lookup

Surge protector wikipedia , lookup

Mains electricity wikipedia , lookup

Ground (electricity) wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Distribution management system wikipedia , lookup

Power engineering wikipedia , lookup

Amtrak's 25 Hz traction power system wikipedia , lookup

Electrician wikipedia , lookup

Ignition system wikipedia , lookup

Electrical wiring in the United Kingdom wikipedia , lookup

Earthing system wikipedia , lookup

Residual-current device wikipedia , lookup

Electrical substation wikipedia , lookup

Circuit breaker wikipedia , lookup

Transcript
Electrician Training
Duty B: Power Distribution (600V and below)
Page 1 of 7
B-05: Rack In/Rack Out Breakers
SAFETY FIRST
o Follow all Caterpillar facility safety standards when performing this
task.
o Explosive hazard can result if a breaker is improperly sized or wired.
o Electrical hazard exists whenever lock and tag is removed. Stand to
the side when opening or closing the breaker.
o OSHA regulations require wearing insulated safety gloves when
working on energized circuits over 50 VAC.
EQUIPMENT
o breaker cranking mechanism
o Electrician hand tools
RESOURCES
o Substation one line diagram
Rack In/Rack Out Breakers
Note: The following steps are performed on a Westinghouse Breaker. Some
steps may not apply to the ITE breakers.
1.
Communicate with the Electrician reporting the problem.
o Determine what machine(s) are affected and which feeder branch(es)
need to be racked out.
o Use the required substation one-line diagram to identify the required
feeder branch.
Issued 01/99
Electrician Training
2.
Duty B: Power Distribution (600V and below)
Page 2 of 7
Go to the required substation.
o Identify the corresponding feeder number and/or machine number on
the breaker door. See the figure below.
Substation Breaker Identification
3.
Open the feeder circuit breaker door.
4.
Check the breaker status indicator.
o The indicator should display “Closed” if it has not tripped or “Breaker
Open” if the breaker has been tripped. See the figure below.
Note the Breaker Status
Issued 01/99
Electrician Training
5.
Duty B: Power Distribution (600V and below)
Page 3 of 7
Check the solid-state trip indicator device for a warning signal. See
the figure below.
Indicates the Nature of a Fault
o Check for an illuminated red indicator light on the device.
o Determine the nature of the fault: Long Time, Short Time,
Instantaneous, or Ground.
WARNING: IF A GROUND FAULT OR INSTANTANEOUS TRIP IS
INDICATED, YOU MUST DETERMINE WHAT CAUSED THE TRIP
BEFORE CLOSING THE BREAKER AGAIN.
6.
Issued 01/99
Slide out the drawer rails at the bottom of the breaker. Pull out until it
drops down.
Electrician Training
7.
Duty B: Power Distribution (600V and below)
Page 4 of 7
Rack out the breaker.
o Push the trip button and hold it to install the cranking mechanism.
Slide the mechanism door up and place the wrench end of the
mechanism on the bolt head. See the figure below.
Breaker Cranking Mechanism
o Turn the cranking mechanism counterclockwise until it stops to loosen
the breaker.
o Pull out on the breaker handle.
o The breaker should slide easily away from the rack.
8.
Visually inspect the breaker.
Caution!
Voltage is present at the top set of electrical contacts in the
cubicle.
o Loosen the screws. Next, lift the arc chutes.
o Check the breaker contacts for signs of arcing, such as discoloration or
smoke.
o Check all wiring for discoloration or disconnection.
Issued 01/99
Electrician Training
Duty B: Power Distribution (600V and below)
Page 5 of 7
o Check the arc chutes for signs of arcing. See the figure below.
Suppressors on a Westinghouse Breaker
o Perform any maintenance indicated by the visual inspection.
9.
Tag the racked-out breaker.
o Put a Warning tag on the breaker if it is to be left racked-out. See the
figure below.
10.
Issued 01/99
Verify that any fault on the line has been corrected.
Electrician Training
11.
Duty B: Power Distribution (600V and below)
Page 6 of 7
Rack in the breaker.
o Alert all Operators, Electricians, and other personnel that the line will
be reenergized.
o Push the breaker back into the cell.
o Push the drawer rails back in.
o Crank the mechanism clockwise until it stops and the indicator shows
that the breaker is connected.
Note: Indicator settings include “Remove”, “Disc”, “Test”, and “Conn.”
12.
Reset the trip indicator on the solid-state device.
o Use a small pointed device, such as a screwdriver, to press the <Reset>
button.
Solid-State Indicator Reset Button
13.
Reset the DC trip switch.
o Press the metal reset pushbutton once.
o The button is located on the bottom left of the breaker face.
14.
Recharge the spring and close the breaker.
o Standing to the side of the breaker, pull the spring arm down once to
charge the springs.
o Push the <Push to Close> button to close the breaker.
o On an ITE breaker, pull down the Tee handle to close the breaker.
Issued 01/99
Electrician Training
Issued 01/99
Duty B: Power Distribution (600V and below)
Page 7 of 7
15.
Close the feeder circuit breaker door.
16.
Document the work history.