ME-AGS-N* or ME-AGS-S wiring diagram – For Generac (7000EXL) ON inside Gen Run Signal (input to pin 2 must be 10 to 40 DC volts only while generator is running); can be the generator hour-meter or a 12vdc pilot/run light 5 amp fuse Dip-switch configuration (Portable Mode) Inside Generator 13A 5 amp fuse Battery Bank (monitored for gen turn on) 86 13A ELECTRIC START SWITCH 30 START RELAY 85 16 13A 18 87 87A 18 ENGI NE RUN SWITCH GRN 0 85 30 NUT ON ENGI NE BLOCK OFF RELAY NOTE 1: If the generator engine is cold, the choke knob must be manually pulled out to close the choke or a auto choke kit may be available from your Generac dealer. Input DC voltage jumper (set to battery bank voltage) 1 2 3 4 inside IMPORTANT: Each wire between the external relays and generator must be sized to handle the required amperage of that circuit. 12/24/48V * ME-AGS-N is shown 86 Already connected On Generator 120VAC Out let 87 87A 12V Gen Battery NOTE 2: The engine switch must be on or disconnected when used in conjunction with the AGS. If engine switch is off and connected you will not be able to start the generator with the AGS. NOTE 3: The Idle Control switch must be in the “off” position. 120V AC I N 12V DC OUT TRA NSFORM ER DC Fuse (5A max) Relay 2 (pins 6 & 7) Relay 3 (pins 1 & 8) OFF ON RUN TIME HOURS START Delay Relay 1 (pins 5 & 6) Delay START and OFF Relays = SPDT 30 Amp, 12 VDC coil relay; popular in automotive sound and security installations. Equivalent to Bosch #0 332 209 150 or TYCO #V23234-A1001-X036. RY3 Delay Time START Time RY3 Time Time between start attempts Total Start attempts 2 seconds 10 seconds 5 seconds 2 minutes 4 Relay timing for Portable Mode Magnum Energy, Inc. provides this diagram to assist in the installation of the Auto-Generator Start controller. Since the use of this diagram and the conditions or methods of installation , operation and use are beyond the control of Magnum Energy, Inc., we do not assume responsibility and expressly disclaim liability for loss, damage or expense arising out of the installation , operation and use of this unit. 10-30-2014DM