Liquid
Big bore size, High performance coriolis flowmeter
GENERAL SPECIFICATION
"CN100"
Transmitter : MT9411
■ GENERAL
The know-how and experience gained in our specialized
domain of manufacturing flowmeters have been used in the
development of a new general-purpose coriolis flowmeter,
the ULTRAmass MKII, which is characterized by ease of
operation, increased performance and safety for the plant
operator.
■ FEATURES
1. Exceptional accuracy (±0.1% ±zero stability error of reading
for liquid service) and high sensitivity (measuring range 1 to 100).
2. Accepts both liquid measures accurately with small pressure loss over a broad flow range.
3. Measures density and temperature accurately in addition to mass flowrate.
4. Minimum pockets for the process fluid to stand (in vertical installation) offers ease of cleaning.
5. Applicable to many kinds of process fluids thanks to stainless steel components.
6. Exceptionally high mechanical strength. The result is ease of
handling, installation space saving, and increased process safety.
GS.No.GBN056E−3
Transmitter
Rack mount Type
MT9411
7. Explosionproof construction permits meter installation in a hazardous location.
8. Can produce an alarm output when preset density range is exceeded due to bubble entrapment, for example. (option)
■ GENERAL SPECIFICATIONS
●
Sensor unit
Model
Nominal size
Materials
Description
CN100
Item
100mm or 4″
Wetted
Housing
150mm or 6″
SUS316L
SUS304
JIS 10, 20, 30, 40, 63K RF, ASME 150, 300, 600RF
Liquids
0.3 to 2 g/mL
Max.1000mP・s
−200 to +200℃
−20 to +120℃
−20 to +90℃
13.56MPa (Reference: 9.39MPa at 200℃)
Depends on flange rating
Forward and reverse, both available
Intrinsically safety explosionproof (Exib IIB T3)
Connection rating
Applicable fluids
Density range
Viscosity range
Non-explosionproof type
Temperature
Ex. temp. grade T3
range
Ex. temp. grade T4
Max. operating Tube withstand (at 20℃)
pressure
Flow direction
Explosionproof configuration
※ : Miscellaneous: For products conforming to the high pressure gas safety regulations and consult our representative.
●
Rack-mount transmitter (MT9411)
Item
Companion Flowmeter
Rangeability
Power supply
Power Consumption
Ambient Temperature
Transmission Length
Explosionproof configuration
Design and Installation
Finish
Approx. Weight
Communication Interface
Remote Zero
Pulse Output
Analog Output
ANA 1
ANA 2
Description
OVAL Coriolis flowmeter Type”D” sensor face-to-face interchangeable ULTRAmass MK II sensor unit
Flowrate
Per general performance table for flow sensor
Temperature
Per general performance table for flow sensor (Transmitter measuring range −200 to +200℃)
85 to 264VAC 50/60Hz or 20 to 30VDC
Max. 25VA, or Max. 10W
−10 to +50℃
200 meters max. (7-conductor interconnect cable) ※3
Intrinsically safe explosionproof [Exia] IIB
Rack mount type
Munsell N6.0 (grey)
1.8kg approx.
Bell202 (under HART protocol) ※2
Communication, zeroing button, or status input
Open collector output (Max.30V, 50mADC) or voltage pulse "0" : 0V, "1" : 15V Output impedance 2.2kΩ FS 0.1 to 10000Hz
4 to 20mADC Max. load resistance 600Ω
2 outputs frpm mass flowrate and temperature
Added damping : 0 to 200 sec.
Status Input
Contact-closure input (Form "a" contact) Close : 200Ω max. Open : 100kΩ min.
Remote zero or (option feature), OFF in default setting
Status Output
Open collector output (30Vmax., 50mADC) Normal : ON; Error : OFF
Select one from error (default), flow direction, auto zeroing in progress, or Hi/Low alarm.
Drive Voltage Output
Output to Density Computer
DC voltage output (test output)
Natural frequency output : EL 4000 series
※1 : Cannot test insulation resistance and dielectric breakdown voltage.
※2 : Signal for Bell 202 is superimposed over analog output 1. (Smart Communication Unit: Link Top connected)
※3 : If it exceeds 200 meters, consult the factory.
http://www.oval.co.jp
Head Office (Tokyo): Phone. 81-3-3360-5121. Fax. 81-3-3365-8605
Beijing Office: Phone. 86-10-5867-4711. Fax. 86-10-5867-4713
Overseas Branch Offices: Seoul, Singapore and Taipei
ULTRAmass MKII「CN100」
GBN056E-3
■ GENERAL PERFORMANCE
Model
Item
Description
Normal flow range (kg/min.)
0 to 5700
CN100
Allowable flow range (kg/min.)
Flowrate
(Liquids)
0 to 6200
Min. range (kg/min.)
0 to 285
Lower limit rate (kg/min.)
57
Accuracy in factory calibration
[±0.1% ± zero stability error] of RD
Repeatability
[±0.05% ± 1/2 zero stability error] of RD
Zero stability (kg/min.)
Density
(Liquids)
0.57
Measuring range
0.3 to 2 g/mL
Accuracy in factory calibration (option)
±0.001g/mL
Analog accuracy
±0.1% of FS added to each accuracy
Zero stability (kg/min.)
Zero stability error=
× 100%
Flowrate at that time (kg/min)
※ : For volume fowrate measurement in custom or custody transfer application, contact us.
Meter Error (%)
■ METER ERROR
Flowrate % (Normal flow range)
■ PRESSURE LOSSES
∆P Factor: C
1
0.1
0.01
1000mPa・s
0.001
100mPa・s
0.0001
0.00001
How to determine pressure loss
1. Find the pressure loss factor C from flowrate (kg/min)
and viscosity (mPa • s) of parameter.
Dividing the obtained value C by specific gravity d
(1 for water) gives the pressure loss. That is,
C
∆P=
(MPa)
d
10mPa・s
1mPa・s
10
0.01mPa・s
100
Flowrate (kg/min)
1000
10000
ULTRAmass MKII「CN100」
GBN056E-3
■ REMOTE MEASURING SYSTEM
Rack maunted
transmitter
MT9411
●
Totalizer
EL0122, EL0123
Batch controller
EL1810
Analog output (flowrate, temp. or density)
4 to 20mADC
(※1)
●
Flow rate pulse output
Voltage or open collector
DCS, computer
etc
Personal
computer
Hazardous area
Non-hazardous area
Recorder
Smart
communication unit
EL2310 (※2)
(Applicable to
Ver.5.0.0 and after)
Controllers
(※1):The sensor unit and transmitter are connected with exclusive cable.
(※2):Smart communication unit. See general specification sheet No.GEL104E.
■ PRODUCT CODE EXPLANATION
●
Sensor unit
Item
Code No.
Model
C N
Nominal size
1
0
0
Configuration
Material
Connection type
A −
B −
S S −
3
Connection standard
1
2
3
Pressure rating
Transmitter mounting construction
●
Description
① ② ③ ④ ⑤ ⑥ − ⑦ ⑧ − ⑨ ⑩ ⑪ ⑫
1
2
3
6
R
ULTRA mass MK II
100 mm (4″) or 150 mm (6″)
Nominal size 100mm (4″)
Nominal size 150mm (6″)
SUS316L
Flange connection
JIS
ASME
JPI
JIS10K
JIS20K, ASME 150, JPI 150
JIS30K, ASME 300, JPI 300
ASME 600, JPI 600
Rack mounted type transmitter MT9411
Rack-mount type transmitter (MT9411)
Item
Model
Code No.
① ② ③ ④ ⑤ ⑥ − ⑦ ⑧ ⑨ ⑩ ⑪ ⑫
M T
9
Power supply
4
1
1
Rack mount transmitter
20 to 30VDC
85 to 264VAC 50/60Hz
Mass flowrate analog 2 output (single output inclusive)
Mass flow + Density
Mass flow + Temperature
Mass flow + Volume flow
Density + Temperature
Volume flow + Density
Volume flow + Temperature
Mass flow voltage pulse
Volume flow voltage pulse
Mass flow open collector pulse
Volume flow open collector pulse
Error output
2
Flow direction
3
Auto zero in progress
1 −
6
7
M M
M D
Analog output (※1)
M T
M V
D T
V D
V T
1
Pulse output
2
3
4
Status output
Description
4
Explosionproof
Hi/Low alarm
0
Non-explosionproof
1
TIIS (Technical Institute of Industrial Safty, Japan) Temperature class T3
8
TIIS (Technical Institute of Industrial Safty, Japan) Temperature class T2 (※1)
※1 : “8” in the ⑫ applies to high pressure service only.
ULTRAmass MKII「CN100」
GBN056E-3
■ GENERAL SPECIFICATIONS
●
センサユニット
L
φ108 80
100
Terminal box
Ground screw
φD
Electoric wire
Connector G3/4
Flow
1015
Case
1251
660
Flange
Boss
Rc1/4
300
15
800
Model
L
Approx. weight
kg
JIS 10K
992
231
JIS 20K
1006
235
JIS 30K
1016
241
ASME/JPI 150
1018
237
ASME/JPI 300
1036
245
ASME/JPI 600
1082
255
JIS 10K
1300
246
JIS 20K
1320
253
JIS 30K
1330
265
ASME/JPI 150
1318
248
ASME/JPI 300
1338
265
ASME/JPI 600
1388
292
Flange
Con. standard
Nom. size
100mm
4″
CN100
150mm
6″
89
■ GENERAL SPECIFICATIONS
LED Indicator
2- 7
per unit
135
144
178
Multiple Installation Dimensions
200
Zeroing Button
Terminals,
Non-intrinsic Safety Side
Rack Mount Fitting Hole
2- 4.5
3.8
37
160±0.5
144
96
160
Terminals,
Intrinsic Safety Side
Min. Min.
110 110
Rack
ULTRAmass MKII「CN100」
GBN056E-3
■ WIRING
Exclusive cable
Sensor terminal box
MT9411
Cut off shield wires here except for the
shield wire over BRN and RED lines.
Barrier cover to be applied
in a hazardous area
Shield
(Protected by black tube)
Hazardou area
Shield wires
Interconnect cable (Max. 200m)
Non-hazardou
area
Brown
Red
Brown
Red
Green
White
cut
Green
White
Brown
Red
Orange
Yellow
Green
Blue
Grey
cut
Blue
Purple
Grey
White
Blue
Grey
Purple
Yellow
Orange
Purple
Yellow
Orenge
cut
Sensor terminal box
0 Shield
(Protected by black tube)
NOTE :
1. Do not fail to use exclusive cable.
2. Shield wire preparation
(1) Transmitter end:
Bundle shield wires for brown/red, green/white, blue/grey, purple/orange/yellow wire, slip a black insulating sleeve over them, and connect to the tie-point strip
as shown in the figure.
(2) Sensor end:
Slip a black insulating sleeve over the shield wires for brown/red wire and connect to the tie-point strip as shown in the figure. Exercise care not to come in contact with the housing or other metal parts. Cut off all shield wires except for the shield wire over red and brown lines as shown.
■ Terminal Identification (MT9411)
Power
Nonintrinsically Safe Side
Terminal
No.
1
2
E
3
4
0
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
L1
L2
G
Lablel
DRIVE SIG.
DRIVE 0V
EARTH
TEMP. B
SHIELD TEMP. b
SHIELD
(+) LPO
(+) RPO
TEMP. A
(−) RPO
(−) LPO
Description
Cable
Color
Drive output to flow tube
Sensor Connection
Intrinsically Safe Side
Item
Kind A ground work
Temperature input
Common
Shield
L. pos. pickoff sensor input
R. pos. pickoff sensor input
Temperature input
R. pos. pickoff sensor input
L. pos. pickoff sensor input
BRN
RED
ORD
YEL
BLK
GRN
BLU
PUR
GRY
WHT
MT9411
INTRINSICALLY SAFE SIDE
1
BRN
DRIVE
SIG.
3
ORN
TEMP.
B
5
GRN
LPO (+)
8
GRA
RPO (−)
2
RED
DRIVE
0V
4
YEL
SHIELD
TEMP.b
6
BLU
RPO (+)
9
WHT
LPO (−)
E
EARTH
0
BLK
SHIELD
7
VIO
TEMP.
A
10
NON INTRINSICALLY SAFE SIDE
PERIOD
N.C.
COM.
D.GAIN
(+)ANALOG 1
(−)ANALOG 1
(+) PULSE
(−) PULSE
(+)ANALOG 2
(−)ANALOG 2
(+) STATUS OUT
(−) STATUS OUT
(+) STATUS IN
(−) STATUS IN
(+) POWER
(−) POWER
GND
Flow computer
combination
Tube frequency output
1
PERIOD
5
2
N.C.
6
Frequency output :
Voltage pulse or open collector pulse
3
COM.
7
Analog output 2
4
Common
Drive gain output : Common terminal : 3
+
ANALOG
1
−
+
ANALOG
2
10 −
9
13
+
14
−
STIN
Analog output 1
Error, flow diretion, zeroing during adjustment, or
hi/low alarm output
Remote zero input (From "a" contact)
+
11
PULSE
D.GAIN
8
−
+
15
ST OUT
12
−
16
POWER SUPPLY
L1 (+)
GND
L2 (−)
OVAL Corporation
Do not fail to connect EARTH terminal to the ground earth of
Power supply
kind A (explosionproof) or kind D (Non-explosionproof).
Kind D ground work
ULTRAmass MKII「CN100」
GBN056E-3
■ STANDARD INSTALLATION
1. Typical installation (See figure at right.)
1) Avoid pipeline stresses on the ULTRAmass MKII.
2) The ULTRAmass MKII should be supported at the process pipelines near to the connections with the meter.
3) Avoid supporting the ULTRAmass MKII body directly.
4) Pipeline should be arranged such that the ULTRA mass MKII is constantly filled with the process fluid.
Avoid, however, to install it in a pocket where slurries may build up.
5) Provide a valve downstream of the meter to allow zeroing by obtaining a true zero flow. We recommend to provide another valve upstream of the meter for servicing or maintenance.
Inflow direction arrow
Valve
Valve
Flow
2. Precautions at installation
1) Locate the ULTRAmass MKII at least one meter from
large transformers, motors, or other sources of
electromagnetic induction. Also avoid installation near
the sources of excessive vibration, such as motors and
pumps.
2) If it is desired to make a measurement of a process
fluid requiring heat retention, heat trace may be
applied directly to the sensor body. Heat trace should
be held below 200°C. Explosionproof models require
the temperature to be held below their maximum
allowable levels.
3) In density measurement, heat retention is suggested
for stability of readings.
4) The sensor unit is of gastight construction. To prevent
dew condensation inside in a low temperature
application, it is filled with argon gas. For this reason,
avoid dropping or giving it impact shocks.
5) A control valve should be located downstream of
the ULTRAmass MK II. In an arrangement where
cavitation may possibly take place, locate it at least 5
meters away.
6) To ensure consistent and accurate measurement, the
Coriolis flowmeter should be placed in an environment
where pipeline oscillation is held below 0.3G.
3. Physical orientation
Recommended physical orientation varies with the type of process fluid. No. 2 in the figure below shows the representative
orientation for liquid service.
No.1
No.
Horizontal run
Orientation
Sensor unit
Flow
direction
Terminal box
Fluids
Sensor unit
Terminal box
Flow
direction
●
Slurries
Flow
direction
Sensor unit
Terminal box
●
Liquids
※ : Do not forget to specify the physical orientation when you order.
Vertical run
No.3
No.2
●
●
Slurries (requiring cleaning)
Liquids
ULTRAmass MKII「CN100」
GBN056E-3
ULTRAmass MKII「CN100」
GBN056E-3
■ PLEASE SUPPLY THE FOLLOWING INFORMATION WHEN YOU INQUIRE
(Fill in the form below to the extent possible. Further details will be finalized in later consultation.)
・Fill in the blanks. Tick the boxes □ that apply.
1. Application
2. Process fluid (※1)
3. Nominal size
4. Flanged connection
Name
SP. gr
Solution concentration
Viscosity
%
□ 150mm or 6″
□ 100mm or 4″
□ JIS 10K
□ JIS 20K
□ JIS 30K
□ ASME 150
□ ASME 300
□ ASME 600
□ JPI 150
□ JPI 300
□ JPI 600
5. Flow range
Max.
6. Fluid temperature
Max.
℃
Normal
℃
Min.
℃
7. Operating pressure
Max.
MPa
Normal
MPa
Min.
MPa
8. Ambient temperature
Max.
℃
Min.
9. Fluid flow direction
□Left→Right □Right→Left □Bottom→Top(□Top→Bottom)See sketch on pege 6. No.
Full scale
Normal
□ kg/min.
□ kg/h
℃
10. Explosionproof
□Not required □TIIS/Temp. grade:Sensor T3 □TIIS/Temp. grade:Sensor T4
11. Power supply
□ 20 to 30VAC
□ 85 to 264VAC(50/60Hz)
□mass flow rate or □volume flow rate
□Open collector (std.) or
Pulse
12.
Output
specifications
Analog
Status
13. Receiver
14.
Transmission
distarce
□Volt. pulse(Option, analog output has limitations.)
Pulse freq.:
Hz(at full scale)or
Pulse unit:
□ kg/P □ L/P
□instant. flow rate(□×2) □volume flow rate
□density
(2 outputs from, mass flow rate×2 selectable)
□Error (std.) □Flow direction
□Totalizer □Indicator
□Computer
□temperature
□Recorder
□Flow controller □Batch controller
□ Others (
Sensor unit to Transmitter
Transmitter to Receiving instrument
□Hi/Low Alarm(Select only one.)
)
m (200 meters max. using interconnect cable.)
m
15. Other considerations
(※1) Special fluids, such as slurries, should be stated accurately and in detail.
The specification as of Feb., 2013 is stated in this GS Sheet. Specifications and design are subject to change without notice.
S
Sales Representative:
icenta Controls Ltd
Unit 3 The Woodford Centre, Lysander Way, Old Sarum Park, Salisbury, SP4 6BU8.
Tel: +44 (0)1722 410777 Fax: +44 (0)1722 326818
GS.No.GBN056E
初版 改訂 印刷
Email: [email protected]
07.10 13.02
www.icenta.co.uk