Download LP-FXZAN13-0 Zone Controller and Actuator

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Rotary encoder wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Control theory wikipedia , lookup

Power engineering wikipedia , lookup

Rectifier wikipedia , lookup

Stray voltage wikipedia , lookup

Solar micro-inverter wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Voltage optimisation wikipedia , lookup

Power electronics wikipedia , lookup

Alternating current wikipedia , lookup

Buck converter wikipedia , lookup

Control system wikipedia , lookup

Two-port network wikipedia , lookup

Light switch wikipedia , lookup

Metadyne wikipedia , lookup

Mains electricity wikipedia , lookup

Switched-mode power supply wikipedia , lookup

National Electrical Code wikipedia , lookup

Opto-isolator wikipedia , lookup

Electrical wiring wikipedia , lookup

Electrical wiring in the United Kingdom wikipedia , lookup

Transcript
Installation Instructions
Issue Date
LP-FXZAN13-0
March 16, 2007
LP-FXZAN13-0 Zone Controller and Actuator Assembly
Application
The LP-FXZAN13-0 Zone Controller and Actuator
Assembly (hereafter referred to as the FXZAN) is a
digital controller and actuator assembly designed
specifically for use with the Facility Explorer
Commercial Zoning Package.
2.
Position the actuator on the damper shaft so that
the damper shaft protrudes through the actuator
coupler.
3.
Verify that the actuator is in the desired mounting
position, parallel to the mounting surface.
4.
Hold the actuator in place on the damper shaft,
and insert a No. 10 self-drilling sheet metal screw
through the shoulder washer.
5.
Place an 8 mm (5/16 in.) socket on the screw and
use a drill and extension to drill the screw into the
mounting surface. Drive the screw until it is tight
against the washer. Do not overtighten the
mounting screw; it may strip the threads.
6.
Make a note of the rotation range and direction,
either Clockwise (CW) or Counterclockwise
(CCW), required to open the damper. See
Figure 2.
Installation
Prepare the FXZAN for mounting using the following
procedure:
1.
Check that you have the essential equipment and
tools and ensure the installation site meets
environmental requirements.
2.
Make sure the mounting location has adequate
clearance for future servicing.
Mounting
Location Considerations
Consider the following when positioning and orienting
the FXZAN:
•
Mount the FXZAN on a vertical, flat surface where
it functions best, such as the side of the zone
damper.
•
Verify wiring terminals are accessible.
•
Ensure that no extra mounting brackets, linkage,
or couplers are required for standard mounting.
•
Locate the FXZAN so that it has adequate
clearance for future servicing and is protected
from moisture and corrosive fumes.
To mount the FXZAN:
1.
Check that the damper blade is accessible or its
position is permanently marked on the end of the
damper shaft as illustrated in Figure 1.
7.
Figure 2: Damper Rotation
Grasp the damper shaft firmly with pliers and
either manually close the damper (90° boxes) or
manually open the damper (45 or 60° boxes).
Figure 1: Damper Position Icons
© 2007 Johnson Controls, Inc.
Part No. 24-10173-5, Rev. C
1
www.johnsoncontrols.com
8.
Press and hold the gear release lever, and rotate
the actuator coupler until it contacts the
mechanical end stop at either the fully closed (90°
boxes) or fully open (45 or 60° boxes) position.
Read these precautions before touching the terminals
or wiring the FXZAN and its accessories:
•
Make all wiring connections in accordance with the
National Electrical Code (NEC) and state and local
regulations. For transformer primaries above
150 VAC, the secondary must be earth-grounded
at the transformer to meet NEC. Since the power
supply for the FXZAN is not isolated, earth ground
can be introduced into the system. Avoid multiple
earth ground paths and use isolation transformers
if necessary.
•
Locate the equipment and route the wiring so that
twisted pair signal wiring is separated from power
wiring by at least 150 mm (6 in.).
•
Make all wiring connections to the FXZAN using
only copper conductors. To establish tight, reliable
electrical connections, use the correct wire sizes
for the terminals. Avoid very thin solid wires, such
as 26 AWG or less than 0.6 mm, which tend to
break.
•
Use a daisy-chained configuration for the N2 Bus.
The use of Y or T connections without a repeater
installed as the T-tap may cause a loss of
communications. Make sure there is at least one
End-of-Line termination on the N2 Bus (the FX16
or FX40 Series controller).
•
Do not run N2 Bus, Analog Input (AI), Binary Input
(BI), Analog Output (AO), or Binary Output (BO)
wiring in the same conduit as line voltage wiring
(above 30 VAC), or with wiring that switches
power to highly inductive loads such as
contactors, coils, motors, or generators.
•
Run AI, AO, and BI wiring in the same bundle or
conduit where convenient. If the BO wiring is not
wired through other switches or contacts, such as
actuator end-of-travel switches, bundle it with the
other Input/Output (I/O) wiring where convenient.
If the damper for the 90° boxes closes
counterclockwise, then rotate the coupler to the
counterclockwise mechanical limit. If the damper
for the 90° boxes closes clockwise, then rotate
the coupler to the clockwise mechanical limit.
The open end stop is automatically set for 90°
boxes. Hard stops must be provided for 45° and
60° boxes at both fully closed and fully open
damper positions. By installing the FXZAN at the
fully open position, the FXZAN provides the open
stop for 45° and 60° boxes.
9.
Using a crescent wrench, an 8 mm (5/16 in.)
square wrench, or a 10 mm (3/8 in.), 12-point
socket wrench, tighten the actuator set screw to
the damper shaft to 17 to 21 N⋅m (150 to
185 lb in. [14 lb⋅ft]).
10. Push the gear release lever down and turn the
actuator coupler by hand to ensure that the
damper can rotate from full closed to full open
without binding.
Note:
For proper operation, the actuator’s
mechanical stop should engage when the
damper is fully open. The damper seal should
engage when the damper is fully closed.
Wiring
!
WARNING: Risk of Electric Shock.
Disconnect each of multiple power supplies before
making electrical connections. More than one
disconnect may be required to completely
de-energize equipment. Contact with components
carrying hazardous voltage can cause electric shock
and may result in severe personal injury or death.
IMPORTANT:
Binary outputs DO1 and DO2
are connected to the M9104-AGA-3S actuator. If
disconnected, do not allow the outputs to short when
they are energized.
Use the following general wiring considerations:
•
The FXZAN includes isolated N2 and isolated
binary outputs DO3 – DO6.
•
The 24 VAC power input is not internally
transformer-isolated by the FXZAN.
•
The FXZAN is not meant for high voltage.
To wire the FXZAN:
1. Terminate wiring per the engineering drawings.
2. Install the N2 Bus to the FX16 Master Controller in
a daisy chain only (see Figure 3.)
3. Connect power to the FXZAN.
4. Commission and balance the FXZAN.
2
LP-FXZAN13-0 Zone Controller and Actuator Assembly Installation Instructions
Figure 3: FXZAN Wiring Diagram
LP-FXZAN13-0 Zone Controller and Actuator Assembly Installation Instructions
3
Setup and Adjustments
Table 1: FXZAN Wiring List
Name
Description
Connection
AI1
A99
temperature
input
Zone temperature
(room sensor
terminal 2)
AI2
A99
temperature
input
Warm/cool
adjustment (room
sensor
terminal 1)
AI3
A99
temperature
input
Unused
AI4
A99
temperature
input
Unused
AICOM
Analog input
commons
Room sensor
terminal 3
DI1
Voltage-free
contact
Temporary
occupancy (room
sensor
terminal 5)
DI2
Voltage-free
contact
Unused
DI3
Voltage-free
contact
Unused
DI4
Voltage-free
contact
Unused
DI5
Voltage-free
contact
Unused
DICOM
Digital input
commons
Room sensor
terminal 6
AO
0 – 10 V, 5
mA maximum
Auxiliary heat valve
AOCOM
Analog output
common
Auxiliary heat valve
common
DO1
Triac output
Connected to CW
terminal of the
M9104
DO2
Triac output
Connected to CCW
terminal of the
M9104
Setting N2 Addresses
To set up the FXZAN, you must set the N2 address.
The factory default address is 255.
Figure 4: FXZAN Front Panel Display
To set the N2 address:
1. Supply power to the unit. Once powered, the
FXZAN front panel displays the current damper
position (in percentage open).
2. Press the Down button to cycle through the
available parameters until Add appears.
3. When the FXZAN Front Panel displays Add, press
the Enter button.
4. Using the Up and Down buttons, select the
N2 address for the FXZAN. See Table 2 for proper
addresses.
5. Press the Enter button to confirm your N2 address
selection and accept the change.
6. Cycle power to the FXZAN to set the N2 address.
Table 2: Zone Addresses
Zone
N2 Address
Zone
N2 Address
1
3
9
11
2
4
10
12
5
11
13
DO3
SPST Relay
Auxiliary heat stage
1 or parallel fan
3
4
6
12
14
DO4
SPST Relay
Auxiliary heat stage
2
5
7
13
15
6
8
14
16
7
9
15
17
8
10
DO5
SPST Relay
Unused
DOM 3, 4,
5
Digital Output
Commons
Auxiliary heat
commons
DO6
SPST Relay
Unused
DO6COM
Digital Output
Common
Unused
4
LP-FXZAN13-0 Zone Controller and Actuator Assembly Installation Instructions
Temporarily Overriding the Current Position of the
Damper Motor
To temporarily override the current position of the
damper motor, do the following:
1.
2.
Press the Down button to cycle through available
parameters until ord appears. Press the Enter
button.
Press the Down button to cycle through the
display and choose one of the following:
•
AUT – Auto. The damper follows the
commanded position.
•
oPE - Open. The damper drive is fully open.
•
CLo - Closed. The damper drive is fully
closed.
•
Table 3: FXZAN Front Panel Display – Available
Parameters
Parameter
Description
0 to 100
Default display. Current damper
position appears as 0 to 100%
open.
Add
Current N2 address. 255 is the
factory default.
rT
Current value of the zone
temperature sensor
SPo
Current value of the zone sensor
setpoint offset with
warmer/cooler adjustment setting
ord
Override. Used to override the
damper position.
PoS
Commanded damper position.
Used when ord is set to PoS
PoS - Position. The damper drives to position
specified by the PoS parameter (0 to 100%
open).
Table 4: FXZAN Front Panel Display –
Light-Emitting Diode (LED)
Important
Damper position overrides may
be lost once the FXZAN comes online with the FX16
Master Controller.
Table 2: FXZAN Front Panel Display – Buttons
Button
Button Image
Description
Down
Cycle through
available parameters
Up
Cycle through
available parameters
Enter
View, change, and
confirm value of
selected parameter
Function
Escape
LED
Status
Description
1
Right
On
Unreliable zone sensor
Off
Normal zone sensor
Repairs and Replacement
Table 5: Available Models and Accessories
Code Number
Description
LP-FXZAN13-0
Zone controller and actuator
assembly
LP-KIT006-005C
Zone temperature sensor with
push button for temporary
occupancy and warm/cool
adjustment dial; includes wall
mounting base and hardware
LP-FXZAN13-0 Zone Controller and Actuator Assembly Installation Instructions
5
Technical Specifications
FXZAN Zone Controller and Actuator Assembly (LP-FXZAN13-0)
Power Requirements
24 VAC ±15% at 50/60 Hz; 7.3 VA at Maximum Power Supply; Class 2
Supply Voltage
24 VAC (±15%)
Power Consumption
7.3 VA
Ambient Operating Conditions
0 to 52°C (32 to 125°F)
Ambient Storage Conditions
-29 to 66°C (-20 to 150°F)
Electrical Terminations
I/O: 1/4-in. spade lugs with pluggable blocks
N2: pluggable block
Housing
Galvanized sheet metal, IP20
Actuator: Plenum rated, IP40
Dimensions (H x W x D)
Actuator Torque
110 x 171.5 x 138.9 mm (4.34 x 6.75 x 5.47 in.)
4 N⋅m (35 lb.in) minimum
Shipping Weight
1.27 kg (2.8 lb)
Electrical Inputs
AI1-4: A99 sensors (-40 to 100°C/-40 to 212°F)
Non-isolated - spare inputs must be connected to common
DI1-5: Voltage free contacts, non-isolated
Electrical Outputs
AO: 0 – 10 VDC @ 5 mA max. Non-isolated
DO1, 2: 24 VAC Triac 500 mA. Isolated (used to drive the actuator)
DO3, 4, 5: SPST relays. 24 VAC @ 500 mA max
Isolated from electronics
Shared common
DO6: SPST relay. 24 VAC @ 500 mA
Isolated
Standards Compliance
M9104-AGA-3S:
UL Listed, File 27734, CCN XAPX (United States)
XAPX7 (Canada)
Plastic housing is plenum rated per CSA C22.2 No. 236/UL 1995 Heating and
Cooling Equipment
CE Mark, EMC directive 89/336/EEC
C-Tick Mark, Australia/NZ Emissions Compliant
LP-FXZAN13-022F:
CE Directives 73/23/EEC, EN60730; 89/336/EEC, EN50081-1, EN50082-2
UL 873
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls® office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication
or misuse of its products.
Controls Group Global Headquarters
507 E. Michigan Street
P.O. Box 423
Milwaukee, WI 53201
6
LP-FXZAN13-0 Zone Controller and Actuator Assembly Installation Instructions
Published in U.S.A. and Europe
www.johnsoncontrols.com