Download INSTRUCTION MANUAL FOR VOLTAGE REGULATOR Model: APR

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

List of vacuum tubes wikipedia , lookup

Amplifier wikipedia , lookup

Immunity-aware programming wikipedia , lookup

TRIAC wikipedia , lookup

Decibel wikipedia , lookup

Spark-gap transmitter wikipedia , lookup

Transistor–transistor logic wikipedia , lookup

Oscilloscope history wikipedia , lookup

Analog-to-digital converter wikipedia , lookup

Multimeter wikipedia , lookup

Radio transmitter design wikipedia , lookup

CMOS wikipedia , lookup

Valve RF amplifier wikipedia , lookup

Integrating ADC wikipedia , lookup

Ohm's law wikipedia , lookup

Josephson voltage standard wikipedia , lookup

Operational amplifier wikipedia , lookup

Power MOSFET wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Current mirror wikipedia , lookup

Schmitt trigger wikipedia , lookup

Surge protector wikipedia , lookup

Power electronics wikipedia , lookup

Opto-isolator wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Rectiverter wikipedia , lookup

Voltage regulator wikipedia , lookup

Transcript
CONFIDENTIAL INFORMATION
BASLER ELECTRIC,
Publication:
INSTRUCTION MANUAL
FOR
VOLTAGE REGULATOR
Model: APR 63-5
of Basler Electric, Highland, IL. It is loaned for
confidential use, subject to return on request, and
with the mutual understanding that it will not be
used in any manner detrimental to the interest of
Basler Electric.
BOX 269,
9 1687 00 991
© 1997-2000, Basler Electric, Highland, IL 62249
First Printing November 1986
Revision E
ECO: 9609
HIGHLAND, IL 62249
PHONE 618/654-2341
INTRODUCTION
Basler Electric
Highland, Illinois
COM
200
SOLID-STATE
VOLTAGE REGULATOR
50
HZ
Sensing: 240, 480 Vac
Power: 190-277 Vac
650VA
Output: 63 Vdc 5A
Oper. Freq. 50/60 Hz
4.75
(121)
CB-
CB+
R
F-
Model: APR 63-5
5.66
(144)
F+
FREQ
4
Regulation is provided by sensing the generator output voltage, converting it to a dc signal
and comparing the signal to a reference voltage signal. An error signal is developed and
used to control the dc field power in order to
maintain a constant generator output.
6
STAB
7
240
480
0.45
(12)
D2717-07
11-18-97
1.58
(40)
1.68 (43)
0.625
(15.88)
Voltage Adjust Range (Internal):170 to 264
Vac (240 V tap) or 340 to 528 Vac (480 V tap).
External Voltage Adjust Rheostat: 1,000
ohms, 2 W (supplied as an optional item).
Voltage Build-Up: Internal and automatic from
generator residual voltage (6 Vac minimum).
Overexcitation Shutdown: Output power removed under the following conditions: Exciter
field voltage exceeds 100 ±5 Vdc for a time
inversely proportional to voltage magnitude,
or instantaneously if voltage exceeds 135 ±5
Vdc.
0.375
(9.53)
Storage Temperature: –65°C (–85°F) to
+85°C (+185°F)
FUSES
Install 5 A, 250 V, high interrupting capacity,
fast-blowing fuses in lines 3 and 4. See interconnection diagrams.
MOUNTING
The regulator may be mounted in any position.
Refer to the outline drawing for dimensions.
The regulator may be mounted directly on the
generator set using ¼” hardware. Select the
proper hardware to withstand any expected
shipping or transportation conditions.
0.125
(3.18)
0.81
(20.64)
120
100
110
120
130
FIELD VOLTS (dc)
140
150
135 5+-
a.
Set generator RPM to desired frequency
roll-off.
b.
Adjust FREQ control until voltage starts
to drop off.
c.
Speed up generator to rated speed. Voltage should be at nominal.
"CORNER FREQUENCY"
STAB CONTROL
100
50
HZ
80
This control allows the generator response
time (and thus voltage stability) to be adjusted.
Use an oscilloscope or other voltage recording device to set this control.
60
60
HZ
40
a.
Rotation of STAB control CW will slow
voltage response time.
b.
Rotation of STAB control CCW will speed
response time. If rotated too far, generator voltage will hunt (oscillate).
c.
Rotate STAB control CW just past point
where voltage oscillation occurs.
20
0
90
This control prevents generator and regulator
damage by dropping the generator output voltage when the generator frequency drops.
NOTE: ALL DIMENSIONS ARE IN INCHES (MILLIMETERS)
External Voltage Adjust Potentiometer
(Optional), Basler P/N 17727
Operating Temperature: –40°C (–40°F) to
+60°C (+140°F).
80
FREQ CONTROL
1.094
(27.78)
D2717-08.vsd
06-06-00
70
Typical Inverse Time
Delay Characteristic Curves
0.53
(13.49)
0.25
(6.35)
GENERATOR OUTPUT
(% FROM NOMINAL)
AC Sensing Input: 190 to 240 Vac (240 V
tap), 380 to 480 Vac (480 V tap), single-phase,
50/60 Hz. Burden: 5 VA maximum.
D2717-06
11-18-97
REGULATOR CONTROLS
0.625
(15.88)
Exciter Field DC Resistance: 12.6 ohms minimum, 100 ohms maximum.
10
8
6
5
4
3
1
3.16 (80)
APR 63-5 Outline Diagram
DC Output Power: 5.0 Adc @ 63 Vdc (315
W) maximum continuous, 8.5 Adc @ 105 Vdc
(893 W) one minute forcing.
20
0.90
(23)
NOTE: ALL DIMENSIONS ARE IN INCHES (MILLIMETERS)
Certification: UL Listed, CSA Certified
100
80
60
50
40
30
2
1.35
(34)
SPECIFICATIONS
AC Input Power: 190 to 277 Vac ±10%, singlephase, 50/60 Hz. Burden: 650 VA.
3
VOLT
TIME DELAY (SECONDS)
R
FAX 618/654-2351
500
400
300
60
HZ
The Basler APR 63-5 Voltage Regulator is a
CSA/UL approved unit contained in an encapsulated plastic case. The regulator controls
the dc exciter field power of conventional, 50
or 60 hertz brushless generators that have a
63 Vdc field to regulate the output voltage.
June 2000
0
10
20
30
40
50
60
D2717-05
11-18-97
FREQUENCY (HZ.)
Frequency Compensation Curves
OVEREXCITATION SHUTDOWN
If the exciter field voltage exceeds 100 ±5 Vdc,
the regulator automatically removes the field
current after a time delay. The time delay is
inversely proportional to the magnitude of the
detected overvoltage condition. At approximately 135 ±5 Vdc, the field voltage is removed
instantaneously. Refer to the following figure.
Upon detection of overexcitation and the resulting field voltage shutdown, the regulator
will not reset or return to an operational condition until the generator output drops to less
than 6 Vac for 10 seconds minimum.
VOLT CONTROL
Rotation of VOLT control CW will increase generator output voltage.
Removing jumper (terminals 6 and 7) and connecting external potentiometer (1,000 ohms,
2 watts) allows a ±10% adjustment of voltage
range with nominal set by VOLT control.
INTERCONNECTION
Refer to the following interconnection diagrams.
a.
Connect the jumper from COM to either
the 50 Hz or 60 Hz terminal depending
upon the generator frequency.
b.
Remove the jumper and connect terminals CB– and CB+ to the CBS 305 inputs
(if used). If the CBS 305 is not being used,
leave the jumper in place.
c.
A
B
GEN
C
FIELD
ISOLATION
TRANSFORMER
If an external voltage adjust control is
being used, connect the potentiometer to
terminals 6 and 7 as shown. If not, connect a jumper between terminals 6 and 7.
Connect the input power to the generator stator to provide power to terminals 3
and 4. Fuse both leads. Install the optional shutdown switch, if desired.
f.
Connect the sensing input to either 240
or 480 depending on voltage. The sensing should be connected line-to-line.
Parallel Compensation - APM2000 and Current Transformer
E1
Current Boost System - CBS305 and Current
Transformer
SHUTDOWN
SWITCH
EXTERNAL
VOLTAGE
ADJUST
Connect the exciter field to terminals F+
and F–. Be sure to observe polarity.
e.
Power Isolation Transformer - BE 18674 001
Manual Voltage Control - MVC-300
4
3
TO CBS 305
(OPTIONAL)
1
OPERATIONAL TEST
CW
}
d.
2
2
ACCESSORY EQUIPMENT
a.
Connect the test setup as shown below
and apply 240 Vac as shown.
b.
Adjust the VOLT control fully CCW. Observe that the lamp is not lit.
c.
Adjust the VOLT control fully CW. Observe that the lamp is lit.
d.
Adjust the VOLT control until the lamp
just goes out.
4
3
60
HZ
COM
50
HZ
CB-
CB+
F-
F+
4
6
APR 63-5
VOLTAGE REGULATOR
7
3
240
480
D2717-11
11-18-97
1
JUMPER FOR 60HZ
OR 50HZ.
2
250V, 5A, FAST BLOW, HIGH
INTERRUPTING CAPACITY FUSES.
3
REMOVE JUMPER IF CBS
305 IS USED.
4
IF EXTERNAL ADJUST RHEOSTAT
IS NOT BEING USED, JUMPER
TERMINAL 6 TO TERMINAL 7.
Isolation Transformer Interconnection Diagram
A
B
GEN
C
FIELD
OPERATION
60
HZ
The following system operation procedures
provide instructions for adjusting the APR 635 Voltage Regulator.
R
J1
Basler Electric
Highland, Illinois
COM
SOLID-STATE
VOLTAGE REGULATOR
50
HZ
Sensing: 240, 480 Vac
Power: 190-277 Vac
650VA
Output: 63 Vdc 5A
Oper. Freq. 50/60 Hz
CB-
J3
CB+
10 OHMS
R
2
2
F-
CAUTION
EXTERNAL
VOLTAGE
ADJUST
CB-
CB+
F-
F+
4
6
7
3
240
To prevent damage to the regulator, complete
the following steps before proceeding with
system startup.
480
D2717-09
11-18-97
1
JUMPER FOR 60HZ
OR 50HZ.
2
250V, 5A, FAST BLOWING,
HIGH INTERRUPTING
CAPACITY FUSES.
3
REMOVE JUMPER IF
CBS 305 IS USED.
4
IF EXTERNAL ADJUST RHEOSTAT
IS NOT BEING USED, JUMPER
TERMINAL 6 TO TERMINAL 7.
a.
Verify that the voltage regulator specification conforms with the generator system requirements.
b.
Ensure that the regulator is correctly
connected to the generator. See interconnection diagram.
c.
Install fuses per FUSES paragraph.
240 Vac, 1-Phase Interconnection Diagram
A
B
480V
GEN
C
N
FIELD
a.
TO CBS 305
(OPTIONAL)
Slowly adjust VOLT control until voltage
reaches nominal value. If used, adjust
remote voltage adjust to set generator
output to exact value desired.
c.
Apply and remove load to check stability.
Adjust per STAB CONTROL paragraph
if voltge is unstable.
d.
Reduce generator frequency (speed) to
55 Hz (on 60 Hz systems) or 45 Hz (on
50Hz systems). Check that generator
output decreases from this point. If it does
not, adjust per FREQ CONTROL paragraph.
}
CW
4
3
CB-
CB+
Start the prime mover and bring it up to
rated speed. Voltage should build up. If a
minimum residual of 6 Vac is not present,
perform field flashing.
b.
EXTERNAL
VOLTAGE
ADJUST
50
HZ
240 VAC
3
F-
F+
4
6
7
3
APR 63-5
VOLTAGE REGULATOR
240
480
D2717-10
11-18-97
1
JUMPER FOR 60HZ
OR 50HZ.
2
250V, 5A, FAST BLOWING,
HIGH INTERRUPTING
CAPACITY FUSES.
3
REMOVE JUMPER IF
CBS 305 IS USED.
4
IF EXTERNAL ADJUST RHEOSTAT
IS NOT BEING USED, JUMPER
TERMINAL 6 TO TERMINAL 7.
480 Vac Interconnection Diagram
Operational Test Setup
FIELD FLASHING
When the regulator is operated with the generator for the first time, the polarity of residual
magnetism may not be correct or the magnitude may not be enough. If the generator does
not build up, shut down the prime mover and
proceed as follows.
a.
With the prime mover at rest, apply a dc
source (not grounded) of not more than
48 Vdc to terminals F+ and F– in series
with a limiting resistor. Use 1 ohm of resistance for each volt from the dc source
with a power rating of at least 1 watt per
volt.
b.
Allow approximately 30 seconds before
removing the dc source.
c.
Start the prime mover and measure the
voltage at the regulator leads 3 and 4. If
the voltage is greater than 6 Vac, voltage
buildup should occur. Repeat flashing if
less than 6 Vac residual is measured.
SYSTEM STARTUP
SHUTDOWN
SWITCH
COM
VOLT
During periods of prime mover idling, use the
excitation shutdown switch.
2
2
60
HZ
J2
7
PRELIMINARY SETUP
APR 63-5
VOLTAGE REGULATOR
1
6
240
CW
}
50
HZ
4
STAB
D2717-12
11-18-97
4
COM
100 W
LIGHT BULB
480
TO CBS 305
(OPTIONAL)
3
60
HZ
10 W
F+
FREQ
Meggers and high potential test equipment
must not be used. Incorrect use of such
equipment could damage the semiconductors contained in the regulator.
SHUTDOWN
SWITCH
1
Model: APR 63-5