Download Product Presentation

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Electric battery wikipedia , lookup

History of electric power transmission wikipedia , lookup

Electrification wikipedia , lookup

Rectifier wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Power over Ethernet wikipedia , lookup

Audio power wikipedia , lookup

Islanding wikipedia , lookup

Mains electricity wikipedia , lookup

Alternating current wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Power engineering wikipedia , lookup

Buck converter wikipedia , lookup

Rechargeable battery wikipedia , lookup

Opto-isolator wikipedia , lookup

Power inverter wikipedia , lookup

Power electronics wikipedia , lookup

Switched-mode power supply wikipedia , lookup

AC adapter wikipedia , lookup

Solar micro-inverter wikipedia , lookup

Uninterruptible power supply wikipedia , lookup

Transcript
Powerware 9330
9910 - P93
p93pres.ppt rev 4.16.03
!
Developed for global market
!
Incorporated proven technology
previously only available at
higher kVA levels
!
Meets uptime and low cost of
ownership requirements
1
P93 Features
• Double-conversion, online
technology protects against the
9 power problems
• One year ProActive Service
• UPS installation and start-up
service included when purchase
with Powerware Field
Installation (IBM PN 97P3604)
• Lowest cost of ownership
• Complete battery care package
• Compact footprint
• Easy to use interface panel
• Flexible communication
capability
Product Snapshot
Power Rating:
20 kVA / 14 kW
Input Voltage:
208 Vac, three-phase
Output Voltage:
208/120 Vac
Frequency:
50/60 Hz
Input Connection:
Hardwired
Output Receptacles:
(2) IEC-309, 3P, 4W, 60A;
(3) NEMA (varies)
2
P93 Applications
The P93 was specifically designed, engineered and
approved for IBM applications
•
•
•
•
•
•
•
•
•
iSeries and AS/400
pSeries and RS/6000
xSeries and other eServers
Storage and networking devices
Server farms
Networking
Telecommunications
Medical
Small data centers
P93 is the ideal power protection
for pSeries 690 Regatta (image
shown above) and the iSeries 890
(image shown on the left).
3
Applications
4
5
6
Series 9 Power Protection
The P93 provides double-conversion online power
protection from all 9 of the most common power problems
that threaten your equipment and data
Power failures
High voltage spikes
Power sags
Frequency variations
Power surges
Switching transients
Brownouts
Harmonic distortion
Line noise
7
Lowest Cost of Ownership
– In normal operational mode (online, double conversion) continuous power protection with very high efficiency (>96%
@ 0.7 pf and greater than 92% @ unity pf)
– In Energy Optimizer Mode* - dynamically optimized
performance
• Stable utility power - continuous line filtering with highest
efficiency
• Unstable or out-of-tolerance utility power – automatically resumes
online double conversion operations without operator intervention
– Intelligent programmable operation allows switching between
modes without operator intervention.
– *>97% w/unity power factor loads
There is NEVER a trade off between
EFFICIENCY and AVAILABILITY
8
Highest Availability
From component selection to system configuration, the
P93 is designed to deliver the highest availability with
premium standard features such as:
•
Air filters
•
Internal maintenance
bypass
Battery care
Dual input
Generator compatible
Powerware Hot Sync redundant and capacity
systems
•
•
•
•
9
Comprehensive Battery
Management Package
A UPS is only as good as the batteries that support it.
Therefore, we rely on the best technology available to prevent
unexpected battery disruption.
• DC ExpertTM
– Provides battery string state of health and dynamically updates
battery time available when on battery or utility.
• Advanced Battery Management (ABM®)
– Patented charging technique that extends battery service life
• Battery Circuit Test
– Pulses the battery periodically to ensure the battery circuit is intact.
• Temperature Compensated Charging
– Optimizes the charge voltage throughout the operating
temperature range.
10
Compact Footprint
H
Dimens ions :
Height
20 kVA (mm)
(in)
1132
45
Width Depth
557
22
786
31
F ootprint includes 17 minutes of
battery back up time at full load and
maintenance bypas s s witch
D
W
11
P93 Capabilities
Internal features
• 17 minutes of back up time for the highest kVA rating
• 10% Input current THD filter (optional)
• (4) Programmable building alarms
• (2) Summary contacts
• Integrated AS/400 interface card and 25-foot (7.62m),
interface cable and serial card (for Remote Monitoring
feature)
• Accepts up to two optional communication cards:
– Web/SNMP card (IBM Feature Code 2934)
– AS/400 interface card (IBM Feature Code 2936)
12
Informative User Interface
•
Large LCD panel is tilted upward 15 degrees for
easy viewing
•
Illuminated indicators for UPS status
•
Navigation is straightforward with the soft keys
•
Smart Load Off button
13
Flexible Communication
Capability
• Local communication
– Monitor panel
– Illuminated indicators (LED status)
– Control panel
• Remote communication
–
–
–
–
–
–
Relay interface contacts
Building alarm contacts (programmable)
Summary alarm contacts
RS232 ports
EPO kit
Remote monitor panel
14
Technical Specifications
Input
– 120/208 Volt, 60 Hz
• 3 wire + G - Rectifier
• 3 wire + G + N - Bypass
– ~ 0.96 Input PF
– Input Range +10% to -15%
– < 10% input current THD
with internally mounted filter
Output
–
–
–
–
120/208 Volt, 60 Hz
0.7 Output PF
~92% Efficiency
Voltage Distortion
• <3% - Linear Load
• <5% - Non-linear Load
– Voltage Regulation
• < ± 3 % with 100%
unbalanced load
• < ± 5 % dynamic at 100%
load change
• < 5 Ms recovery time to
3% of nominal
15
System Descriptions
• Input
– Soft start circuit charges capacitors (boost circuit)
– Backfeed contactor closes and uncontrolled rectifier
provides raw DC
– Discharge circuit discharges capacitors in < 5 seconds
when all power sources removed
– Black start from battery
• Boost converter/neutral regulator
– Boost stage powers DC Link (Inverter primary power
source) from raw DC
– Boost circuit includes neutral regulator which regulates
the neutral voltage, allows for 100% unbalanced loads
16
System Description
• Inverter
– A pulse-width-modulated IGBT inverter is powered from
regulated DC Link (+/- 210 Volts)
– Inverter output contactor closes to power load
• Bypass
– Backfeed contactor normally on
– SCR switches gated to power load as required
• Maintenance Bypass
– A wrap-around maintenance bypass with service test
position completely isolates UPS for service
– Shrouded to provide safe service environment without
interruption to the critical load
17
System Description
Battery/Charger
– 144 cells
– Independent charger powered from raw DC
– Isolated from power except for charge and reserve
mode operation to maximize battery life (ABM)
– High speed SCR/contactor switch connects battery
at power failure, powering boost converter
18
Normal Mode
Traditional Double Conversion Online Operation
B YP AS S
UT IL IT Y
OUT P UT
B AT T E R Y
P OWE R F L OW
Inverter powers load with bypass in standby
– Inverter powered by utility via rectifier and boost converter
– Battery in standby, (charging or resting)
• Conditions: Input within specified range (typically +/- 15%)
Selected preferred mode
Bypass quality unacceptable
19
Energy Optimizer Mode
User selectable, high efficiency parallel source operation
BYPASS
UTILTIY
OUTPUT
BATTERY
POWER FLOW
Bypass and inverter operate (inverter in hot-standby)
– Bypass provides power (kW) and inverter stands ready to operate when
and if input voltage exceeds preset range
– Battery in standby, (charging or resting)
• Conditions:
Bypass within specified range (typical +/- 5%)
Bypass quality acceptable
Not on generator
20
Battery Mode
BYPASS
UTILITY
OUTPUT
BATTERY
POWER FLOW
Inverter powers load from battery source
– Inverter powered by battery
• Conditions: Utility failed or outside acceptable window
21
Bypass Mode
BYPASS
UTILITY
OUTPUT
BATTERY
POWER FLOW
Bypass circuit powers load
– Load powered by bypass with inverter off
• Conditions: UPS output overload
Inverter circuit failure
Temporary user-selected mode
22
Powerware Extensions
Software for IBM Director
•
•
•
•
•
Seamless UPS and software
integration into IBM Director
Network Management System
(NMS)
Real time monitoring,
management and alarm
notification of all UPSs in the
network: e.g. battery status,
battery replacement, load level
and metering information
Automatically launches LanSafe
and ConnectUPS Web/SNMP
Card applications from within
Director
Available on Powerware web
FREE-OF-CHARGE
23
Power Management Software
Powerware Software Suite
The industry’s most comprehensive software bundle, The Powerware
Software Suite, is free and included with every P93.
Software Wizard guides you through software
selection and installation. In addition to multimedia
demonstrations, product data sheets, and video clips,
the Software Suite contains the following power
management software:
•
•
•
LanSafe™ Network UPS shutdown and monitoring
software
PowerVision® (30-day trial version) UPS performance
analysis and monitoring software
Foreseer® (demonstration) facility and data center
management software
24
Software Application
Application
LanSafe
Single pSeries (serial/TTY) non-LPAR
"
Single pSeries (network) non-LPAR
"*
Multiple pSeries (LPAR)
"*
"*
Single pSeries (LPAR)
Multiple pSeries (non-LPAR)
Powerware
Extensions for
NetWatch IBM Director
"
"*
"*
IBM Director Network Device
*
"*
Co-requisite FC 2934 or 2935 ConnectUPS Web/SNMP network card.
Note: UPS for iSeries applications utilize OS/400 UPS monitoring functions.
25
Software Comparison
Application
LanSafe
NetWatch
ConnectUPS Web/
SNMP Card
SSL/SSH1
Security
Ambient
Temperature
Humidity
Monitoring
Shutdown
GUI
Email/
SMTP
Yes
Yes
Yes
Yes / Yes
No/No
No/No
-
Yes
-
No/No
No/No
No/No
Yes2
Yes3
Yes
Yes / Yes
Yes / Yes
Yes / Yes4
1SSL
= Secure Sockets Layer. SSH = Secure Shell. 2Via Web Browser, LanSafe or Network Management System (e.g.
IBM Director, Tivoli). 3In conjunction with NetWatch software. 4With optional FC 2938 EMP (Environmental Monitoring
Probe) device attached.
26
Connectivity
What you need by application
Software Solution
zSeries
iSeries
LanSafe
"
LanSafe and ConnectUPS
MultiServer card (IBM FC 2933)
NetWatch and ConnectUPS
Web/SNMP card
(IBM FC 2934 or 2935)
"
pSeries
xSeries
"
"
"!
LPARs
ConnectUPS Relay card and
AS/400 cable (IBM FC 2936)
"
Networking
"
"
"
"
"
"
"
"
"
"
Powerware Extensions for
IBM Director
NetWatch
Storage
"
"
!Use
ConnectUPS Web/SNMP/xHub card, IBM FC 2934 or 2935 to support LPAR (POWER 4 Chip Set) servers. For
pSeries configurations, each LPAR needs a network connection and will install Powerware provided NetWatch or LanSafe
5 software.
27
Connectivity
• Optional
• FC 2933 ConnectUPS MultiServer
• FC 2934 ConnectUPS Web/SNMP/xHub
• FC 2936 ConnectUPS Relay & interface cable
– Min: 0, Max: 2
Description
IBM Part No.
Feature
Code
Powerware
Part No.
Minimum
# of FC
Maximum
# of FC
ConnectUPS
X-Slot Web/
SNMP/xHub Card
53P4619
2934 103002974-5501
0
2*
ConnectUPS
X-Slot
MultiServer Card
04N7027
2933
05146447-3901
0
2*
ConnectUPS
X-Slot Relay Card
& 25 ft. cable
97P3886
2936
103003564
0
2*
*Maximum combination of optional ConnectUPS cards is two
28
ConnectUPS-X Web/SNMP/xHub
Interface Card Option
The Web/SNMP/xHub card is ideal for managing
UPSs providing protection for network devices
and gives network managers the ability to monitor
and control UPS over the network via web browser,
SNMP or Telnet. Features include:
• Enables network administrators to remotely monitor
and reset hung network devices
Web/SNMP/xHub card shown
• Ability to remotely control selected power outlets
• Built-in three port switching hub with UPS protection
• Compatible with leading SNMP network management software packages (IBM
NetView, HP OpenView, SunNet Mgr, etc.). Powerware’s PowerMIB and UPS
Standard MIB software included
• Compatible with 100Mb and 10Mb networks
• Unattended graceful shutdown of client operating systems
• Automatically records UPS events and alarms
• Alarm notification through email, SMNP or NetWatch client software
• Monitor multiple web cards simultaneously through MultiView Software
• Fast and easy firmware upgrades available at no charge
• Configurable over the network via BOOTP
• IBM FC 2934, IBM PN 53P4619, Powerware PN 103002974-5501
Software included with ConnectUPS Web/SNMP/xHub card: NetWatch, MultiView and PowerMIB
29
ConnectUPS-X Multi-Server
Interface Card Option
The Multi-Server card connectivity device that
provides direct serial connection to up to five
computers for unattended, graceful shutdown and
power monitoring. The card operates in
conjunction with LanSafe software (included with
the UPS). Features include:
• Real-time monitoring of critical power
parameters
• Graceful, unattended shutdown of multiple
computers
• Supports simple signaling (relay contacts)
through additional DB-9 Port
• IBM FC 2933, IBM PN 04N7027,
Powerware PN 05146447-3901
Multi-Server card shown
30
ConnectUPS-X Relay
Interface Card Option
The Relay Interface card provides monitoring of
UPS status through isolated, dry contact, Form-C
relays. It also provides the interface for AS/400
(iSeries) computers as well as many industrial
applications.
Features include:
• Isolated, dry contact Form-C relays for “utility
failure”, “low battery”, “UPS Alarm/OK” or “on
bypass”
• User-selectable “normally open” or “normally
closed” contacts
• Remote shutdown of UPS through integrated
shutdown functions
• Hot-swappable - - UPS maintains power to critical
applications while changing cards
• 25 foot MT 9406 interface cable included
• IBM FC 2936, IBM PN 97P3886, Powerware PN
103003564*
*Single part number for Relay card and 25 ft. interface cable
Relay card shown
31
P93 Base Configuration Overview
• UPS
• Connectivity
– Relay card & 25 foot cable (iSeries)
– Serial card and modem (ProActive service)
• Input filter
• Options Cabinet
• 42 Pole Panel
• Maintenance bypass
• Output distribution housing
• Output power cords*
• FC 9880
• FC 9881**
two (2) 60A 3 phase 4 wire IEC 309 460R9W
three (3) 15A to 30A NEMA receptacles
*Upon ordering, customer must stipulate length of power cord (up to 50 ft.) for FC 9880 and 9881. Power cords are
supplied by installer.
** Customer must choose NEMA type for FC 9881. FC 9881 are NEMA receptacles and are not water tight
connections
32
Extended Battery Cabinet
(EBC)
•
•
•
•
•
•
•
Optional feature
IBM Part Number: 97P2663
IBM Feature Code: 6635
Powerware Part Number: A13031
Connect up to two EBCs to extend battery runtime
Line up and match battery cabinet
If Base Installation purchased, installation of EBC
included (concurrent to P93)
33
P93 Battery Runtimes
Battery Runtime (in minutes)*
Watts
7000
10500
14000
Standard (Std)
+1 EBM
Internal Batteries (FC 6635)
45
90
26
65
17
48
+2 EBMs
(FC 6635)
155
90
75
34
Options Cabinet
• Distribution housing*
• Connections to output power cords for
loads including eServer CPU and I/O
cabinets
– FC 9880 included as part of P93 base
configuration (in configurator)
– FC 9881 quantity and types dependent on
server configuration and number of
cabinets
Description
IBM Part No.
Feature
Code
Powerware
Part No.
Minimum
# of FC
Maximum
# of FC
Output Power
Cords NEMA
15A to 30A
97P2660
9881
103003673
0
6
Out Power
Cords IEC 309
3P4W (460R9W)
97P2659
9880
103003672
1
1
*Must purchase P93 Installation to order output power cords.
Options
Cabinet
Cutaway
35
UPS,
Options &
Battery
Cabinet
Front
View
36
ProActive Service
• Optional
– Additional years of ProActive Service
–
–
–
–
–
7x24 corrective maintenance coverage
7x24 annual performance check
Annual power protection audit
7x24 remote monitoring advance response service
Monthly UPS performance report with web access to
account information and site service activity
• FC 7001
• FC 7002
IBM Part No.
Feature
Code
Powerware
Part No.
ProActive
Concurrent
97P2657
7001
155102012-001
0
4
ProActive
Non-concurrent
97P2658
7002
155102013-001
0
4
Description
Minimum Maximum
# of FC
# of FC
37
P93 ProActive Service
•Concurrent & Non concurrent
•Delivered in an envelope
•Min: 0, Max: 4
Envelope & labeling
Document inside of envelope38
P93 Base Installation
• Description delivered in an
envelope
• Installation on site by
contractor
• Min: 1, Max: 1
Text: Field Installation of one 9330-20 20kVA UPS
(A21201110133113) 208V input with standard
internal batteries and/or options cabinet with Output
Distribution Housing (A3BBAS0MR3) for bypass and
42 circuit load panel within the 50 United States. All
installations performed using locally licensed and
insured contractors. Installed as per NEC, State,
Local codes and manufacturer's guidelines.
Installation is warranted for five years by installation
vendor. Installation includes: move UPS and Options
Cabinet from customer's loading dock or ground level
to installation area using customer provided freight
elevator if different floor and/or level, uncrate, set-inplace and dispose of packaging materials. Run AC
input feeder a maximum of 150 feet from existing
building service to UPS. Include feeder breaker and
supplemental ground. Installation performed during
normal business hours (Monday - Friday) 8AM to
5PM. Adequate space must be available to complete
installation.
Document inside of envelope
39
P93 Install Package A
• Description delivered
in an envelope
• Installation on site by
contractor
• Min: 1, Max: 1
Document inside of envelope
40
P93 Install Package B
• Description delivered in
an envelope
• Installation on site by
contractor
• Min: 0, Max: 6
Document inside of envelope
41
P93 Site Evaluation
• Powerware site evaluation is available five days a
week during normal business hours (5x8) prior to
installation.
• During the evaluation, the Powerware Power
Consultant will:
– Work with IBM IPR to determine output connection
requirements
– Contact customer to discuss UPS installation and output
configuration. If only new IBM supplied equipment will be
connected to the UPS, a site visit will not be required.
– Provide site visit report to IBM.
42
Scope of Work
Tasks to be performed by the IBM Installation Planning Representative (IPR) once the configuration
and customer contact information is supplied:
1. Run a power profile on the configuration. Identify the type and quantity of line cords and the
maximum power consumption.
2. Review the 9910-P93 configuration. Key features on the order are:
a. #9880 – Specifies quantity two (2) 60 A, 3 phase, 4 wire receptacles.
b. #9881 – Specifies quantity three (3) 15 A to 30 A NEMA non or locking receptacles.
3. Work with the customer to determine if there is any other equipment he /she wants to protect
with the UPS. A site visit is recommended, whether is it by the IPR or an IPR designee, but a
phone call or other means of contact is acceptable.
4. Determine if there are any 9910-P93 limitations in receptacles or capacity that need to be
immediately addressed. Important UPS items to know:
a. Besides the 20kVA / 14 kWatts maximum output, the amount of imbalance on any
one phase cannot exceed 1/3 of the total UPS capacity.
c. Voltage input and output is 208 Vac line-to-line.
d. The Options Cabinet that is always part of the base 9910-P93 configuration contains
a maintenance bypass and 42 pole circuit breaker panel.
5. Provide a summary report to key contacts in IBM and Powerware.
43
Options
Cabinet
Cutaway
Install
Install Package
Package A
A and/or
and/or
B.
B. Output
Output power
power cord
cord up
up
to
to 50’
50’ length.
length. Rated
Rated for
for
raised
raised floor.
floor.
44
UPS
Cabinet
Rear
View
P93
P93 X-Slots:
X-Slots:
#1
#1 Populated
Populated with
with Serial
Serial
Card
Card and
and Modem
Modem
#2
#2 Populated
Populated with
with Relay
Relay
Card
Card
#3
#3 &
& #4
#4 unpopulated
unpopulated
45
P93 Collateral
• Additional information available at
www.oem.powerware.com/ibm-ups
– Select your region. Click “Products”, click “9910
Solutions” then click “Powerware pSeries” or
“Powerware iSeries”
• Materials available
–
–
–
–
Data sheet
Application overview chart
Product presentation
Documents (Installation and Operation Manual,
IBM Applications Installation Guide)
46