Download Type K Current Limiting Fuse Canister Technical and Installation

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Ground (electricity) wikipedia , lookup

Mains electricity wikipedia , lookup

Current source wikipedia , lookup

Rectifier wikipedia , lookup

History of electric power transmission wikipedia , lookup

Buck converter wikipedia , lookup

Mercury-arc valve wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Rectiverter wikipedia , lookup

Three-phase electric power wikipedia , lookup

Metadyne wikipedia , lookup

Single-wire earth return wikipedia , lookup

Alternating current wikipedia , lookup

Surge protector wikipedia , lookup

Earthing system wikipedia , lookup

Transformer wikipedia , lookup

Fuse (electrical) wikipedia , lookup

Transcript
Type K Current Limiting Fuse Canister
Technical and Installation Guide
Table of contents
1
2
3
4
5
6
7
8
Page 2 of 8
Introduction ...................................................................................................................3
Ratings...........................................................................................................................3
Details ............................................................................................................................3
Interlocking....................................................................................................................4
Mounting........................................................................................................................4
Fuse Compatibility........................................................................................................4
Ordering Details ............................................................................................................5
Outline Drawing ............................................................................................................7
1 Introduction
The Type K, current limiting fuse canister provides an air-insulated receptacle for generalpurpose current limiting fuses used on pad mounted or submersible transformers. The canister is mounted, typically, on the front wall of a single or three-phase distribution transformer
or the cover of a submersible transformer. The Type K canister allows the operator easy access to the current limiting fuse for inspection or replacement. The Type K canister is of
dead front construction once it is properly
installed onto the transformer. Figure 1
shows the internal and external details of
the canister.
2 Ratings
The Type K current limiting canister is
available in three voltage / BIL
combinations:
1) 8.5 kV / 95 kV BIL, 175 A
2) 15 kV / 125 kV BIL, 175 A
3) 23 kV / 125 kV BIL, 175 A
3 Details
The Type K current limiting canister
features dead front construction, hermetic
sealing, self-aligning spring contacts and
stainless
steel,
corrosion-resistant
components. The fuse canister is a dead
break device and ABB recommends that it
be used in conjunction with an interlocked
LBOR, load break oil switch.
The Type K, current limiting fuse canister
consists of two major components: the first
is a reinforced fiberglass tube welded to the
tank by means of a stainless steel flange or
bolted to the tank by means of an optional
plated steel clamp and gasket. The second
component is a removable fuse assembly
consisting of the top closure, an insulated
operating shaft, the fuse attachment clamp,
top spring contact and guide washer. See
Figure 3 and Figure 4.
Figure 1
An operating lever combined with the
internal cylindrical gasket creates an over
toggle mechanism which when in the closed position provides a “bottle stopper” type seal between the inside of the canister and the atmosphere. Moving the operating lever into the
closed position compresses the cylindrical gasket against the inside walls of the canister.
Page 3 of 8
This action seals the canister. Moving the operating lever into the open (upright) position relaxes the gasket and the internal assembly can be removed for fuse replacement or inspection. Two spring clips provide the grounding of external metal parts. The spring clips are
fixed to the body of the canister by the stainless steel hose clamp. The coil spring contacts at
the top and bottom of the fuse assure positive fuse to transformer circuit connections. The
top spring fits over the fuse attachment clamp on the holder assembly. The bottom spring is
part of fiberglass tube assembly and makes contact when the fuse assembly is inserted into
the holder and locked into position
4 Interlocking
The Type K current limiting canister is a dead break device. ABB recommends that the fuse
canister be mechanically interlocked to an LBOR, load break oil switch or other mechanism
so that the fuse cannot be removed from or inserted into an energized transformer.
5 Mounting
The Type K canister provides two means for attaching the canister to the transformer tank.
The canister may be either welded to the transformer tank or bolted to the transformer tank.
If the canister is welded onto the transformer, you must use heat sinks to prevent the welding
heat from damaging the canister. The fuse canister can be bolted onto the transformer by
using the optional mounting clamp and nitrile gasket. The mounting flange has a lip to capture the mounting gasket for these applications. Note that the grounding clips must be removed in order to slide the mounting flange into place. Once the mounting flange is secured,
reinstall the grounding clips.
6 Fuse Compatibility
The Type K canister accepts current limiting fuses of the type known as Full Range or General Purpose such as the Hi-Tech Trans-Guard™ FX fuse. The table below provides the
maximum fuse dimensions for proper fit into the Type K canister.
Voltage Class
Maximum OD
A (in)
8.3 kV
15.5 kV
23 kV
2.25
2.25
2.25
Figure 2
Page 4 of 8
Maximum Total
Length
B (in)
10.2
14.4
17.3
Connector
Length
C (in)
1.05
1.05
1.05
Connector OD
D (in)
0.625
0.625
0.625
7 Ordering Details
Item Number
Voltage
Dimensions
See Figure 4
BIL
A
B
C
Clamp
Gasket
Welded to the Transformer
4260079-901
8.5 kV
95 kV
18.75
20.31
9.97
n/a
n/a
4260079-902
15 kV
125 kV
23.13
24.69
14.35
n/a
n/a
4260079-903
23 kV
125 kV
25.94
27.50
17.16
n/a
n/a
Bolted to the Transformer
4260079-904
8.5 kV
95 kV
18.75
20.31
9.97
9820A33H01
1210221-021
4260079-905
15 kV
125 kV
23.13
24.69
14.35
9820A33H01
1210221-021
4260079-906
23 kV
125 kV
25.94
27.50
17.16
9820A33H01
1210221-021
.
Page 5 of 8
Figure 3: Type K Canister Part Detail
Page 6 of 8
8 Outline Drawing
Figure 4
Page 7 of 8
ABB Inc
Components & Insulation
Product Group
1128 South Cavalier Drive
Alamo, Tennessee 38001, USA
+1 731 696 5561
+1 800 955 8399
Fax: +1 731 696 5377
Email:
Alamo.customer_service @us.abb.com
www.abb.com/electricalcomponents
Page 8 of 8
DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY
THERE ARE NO UNDERSTANDINGS,
AGREEMENTS, REPRESENTATIONS OR
WARRANTIES, EXPRESSED OR IMPLIED,
INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OTHER THAN THOSE
SPECIFICALLY SET OUT BY AN EXISTING
CONTRACT BETWEEN THE PARTIES. ANY
SUCH CONTRACT STATES THE ENTIRE
OBLIGATION OF SEELER.
THE CONTENTS OF THIS DOCUMENT
SHALL NOT BECOME PART OF OR MODIFY ANY PRIOR OR EXISTING AGREEMENT, COMMITMENT OR RELATIONSHIP.
THE INFORMATION, RECOMMENDATIONS, DESCRIPTION AND SAFETY NOTATIONS IN THIS DOCUMENT ARE BASED
ON OUR EXPERIENCE AND JUDGEMENT
WITH RESPECT TO BUSHINGS. THIS INFORMATION SHOULD NOT BE CONSIDERED TO BE ALL INCLUSIVE OR COVERING ALL CONTINGENCIES. IF FURTHER
INFORMATION IS REQUIRED. ABB INC.
SHOULD BE CONSULTED.
NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR
MERCHANTABILITY, OR WARRANTIES
ARISING FROM COURSE OF DEALING OR
USAGE OF TRADE, ARE MADE REGARDING THE INFORMATION, RECOMMENDATIONS, DESCRIPTIONS AND SAFETY NOTATIONS CONTAINED HEREIN. IN NO
EVENT WILL ABB INC BE RESPONSIBLE
TO THE USER IN CONTRACT, IN TORT
(INCLUDING NEGLIGENCE), STRICT LIABILITY OR OTHERWISE FOR ANY SPECIAL. INDIRECT. INCIDENTAL OR
CONSEQUENTIAL DAMAGE OR LOSS
WHATSOEVER INCLUDING BUT NOT
UMITED TO DAMAGE TO OR LOSS OR
USE OF EQUIPMENT, PLANT OR POWER
SYSTEM, COST OF CAPITAL, LOSS OF
PROFITS OR REVENUES, COST OF REPLACEMENT POWER, ADDITIONAL EXPENSES IN THE USE OF EXISTING
POWER FACILITIES, OR CLAIMS AGAINST
THE USER BY ITS CUSTOMERS RESULTING FROM THE USE OF THE INFORMATION, RECOMMENDATIONS, DESCRIPTION AND SAFETY NOTATIONS CONTAINED HEREIN
Copyright 2009, ABB Inc. Document Number 1ZUA5670-301