Download Power plants layout Gas Engines

Document related concepts
no text concepts found
Transcript
Caterpillar confidential: none
Power plants layout
with
Gas Engines
(Planning and Installation Notes)
06-2014
Caterpillar Energy Solutions GmbH Carl-Benz-Straße 1 D-68167 Mannheim Phone: +49(0)621 384-Fax: +49(0)621 384-8612
Caterpillar confidential: none
This handbook including all illustrations is protected by copyright. All rights for it are reserved, including rights
to the extracts. Any use outside of the limits prescribed by copyright law without written consent is prohibited
and punishable. This particularly applies to reproduction, translation, microfilming and storage and
processing in electronic systems.
© Caterpillar Energy Solutions GmbH
Mannheim 2014
The reproduction of trademarks, utility names, trade names, descriptions of goods, etc. in this document,
even where not specifically marked, does not justify the assumption that such names may be considered to
be free within the meaning of the laws governing the protection of trademarks and brand names and may
therefore be used by anyone.
Should any reference be made, directly or indirectly, in this document to or quotations cited from any laws,
regulations or directives (e.g. DIN,VDI, VDE…) neither the authors nor Caterpillar Energy Solutions GmbH
can accept any guarantee with regard to correctness, completeness or currency. It is recommended, should
your own work require it, that you read the complete regulations or directives in the currently applicable
version.
Figures, drawings, diagrams and circuit diagrams within the handbook represent general information for the
project planning. The relevant order documentation is binding for orders.
There is no revision service for the drawings of the installation guidelines. They will only be updated with the
next edition of the installation guidelines.
Masthead
Caterpillar Energy Solutions GmbH
VD-S
Carl-Benz-Str. 1
68167 Mannheim
Germany
Tel.: +49 (0) 6 21 3 84-0
Fax: +49 (0) 6 21 3 84-86 12
© 2014
All rights reserved
Chapter_00 - Contents.docx
02999408
Page 2 / 4
VD-S 2014-06 DE
Caterpillar confidential: none
FOREWORD
The guidelines of this handbook are not operating instructions for the final machine user. They apply to all
designers and manufacturers of products who use one of our gensets. Thus the guidelines are not user
information as defined by DIN standard 8418, but fulfil a similar purpose, because their observance ensures
the engine functioning and thus protects the product user from danger which could result from genset use.
Operating safety and a long service life can only be expected from perfectly installed systems. This also
allows maintenance work to be carried out simply and quickly. These guidelines provide information for
mounting and give information about limit values to be observed.
The safety provisions, which are a component of the gensets and/or system documentation, must be
complied with during layout, maintenance and operation of the systems.
The wide range of installation options does not allow for generally applicable and strict rules. Experience and
special knowledge are necessary in order to ensure optimum installation. The standards, directives and
regulations listed have no claim to completeness. Therefore the local requirements must be investigated and
duly taken into account in each individual case.
Therefore we recommend an installation consultation with Caterpillar Energy Solutions GmbH or an
authorized sales partner during the planning stage.
Caterpillar Energy Solutions GmbH does not accept warranty claims and is not responsible for damage or
loss occurring from failure to comply with the information and instructions given in this handbook.
Your suggestions on how to enhance or supplement these guidelines are always highly appreciated.
Caterpillar Energy Solutions GmbH, VD-S, 06-2014
Chapter_00 - Contents.docx
02999408
Page 3 / 4
VD-S 2014-06 DE
Caterpillar confidential: none
Contents
Chapter
Title
1
Layout of gas engine-powered gensets
2
Genset output
3
CHP genset
4
Requirements for genset installation
5
Engine room ventilation
6
Engine cooling systems
7
Fuel system
8
Lubricating oil system
9
Combustion air system
10
Exhaust system
11
Compressed air system
12
Measuring, monitoring and limiting devices
13
Requirements for CHP systems in accordance with the medium-voltage
directive
14
Electrical switchgear systems
15
Isolated operation mode with gas engines
16
Load steps
17
Cabling
18
Transport and positioning of gensets
19
Genset installation and alignment instructions
20
Laying pipes
21
Health and safety at work, accident prevention, environmental protection
Chapter_00 - Contents.docx
02999408
Page 4 / 4
VD-S 2014-06 DE
Caterpillar confidential: none
Power plants layout
Chapter 1
Layout of gas engine-powered gensets
for combined power and heat generation at power
plants (CHP's)
06-2014
Caterpillar Energy Solutions GmbH Carl-Benz-Straße 1 D-68167 Mannheim Phone: +49(0)621 384-0 Fax: +49(0)621 384-8612
1
Caterpillar confidential: none
Contents
1.
Layout of gas engine-powered installations for combined power and heat generation at
power plants (CHPs) ................................................................................................................... 3
1.1
Types of use .................................................................................................................................. 3
1.1.1
Heat-led operation ......................................................................................................................... 3
1.1.2
Electricity-led operation ................................................................................................................. 4
1.1.2.1
Mains parallel operation ................................................................................................................ 4
1.1.2.2
Isolated operation mode................................................................................................................ 4
1.1.2.2.1
Back-up power operation .............................................................................................................. 4
1.1.2.2.2
Black start...................................................................................................................................... 5
1.1.3
Operation dependent on the availability of combustion gas ......................................................... 5
1.1.4
Dual gas operation ........................................................................................................................ 5
Chapter_01 - Layout of gas engine-powered gensets.docx
02999408
Page 2 / 8
VD-S 2014-06 DE
Caterpillar confidential: none
1.
Layout of gas engine-powered installations for combined power and heat
generation at power plants (CHPs)
A gas engine-powered genset comprises a combustion engine, generator, coupling, base frame and
mounting arrangement. The engine and generator are rigidly mounted on the base frame. This unit is
described as a CHP genset and is used to generate electricity and heat.
A CHP set comprises a CHP genset and the following components:
•
•
•
•
•
•
•
Cooling water heat exchanger
Exhaust heat exchanger
Exhaust silencers
Exhaust gas cleaning system
Fuel tank or gas supply
Lube oil supply
Monitoring system
A CHP plant may comprise one or more CHP sets: the electrical switchgear with control system, the air
supply system and the exhaust air system.
The basic principles, requirements, components, implementation and maintenance of electricity generating
sets are described in DIN 6280, Part 14 (see Fig. 1.1).
Attention !
It is not allowed to change any parts in the gensets, components and control cabinets which are delivered by
the manufacturer.
To avoid EMC problems, the parts on the system side, e.g. frequency converters, must be connected with
shielded lines in accordance with the manufacturer's specifications. See also Chapter 14 and 17.
1.1
Types of use
Depending on its use, the system may be primarily used to generate either electricity or heat.
1.1.1
Heat-led operation
In the case of heat-led operation, the demand for heat is the lead factor which determines the output of the
CHP plant. To cover the demand for heat during peaks, the CHP plant may be supported by other heating
systems.
Chapter_01 - Layout of gas engine-powered gensets.docx
02999408
Page 3 / 8
VD-S 2014-06 DE
Caterpillar confidential: none
1.1.2
Electricity-led operation
In the case of electricity-led operation, the demand for electricity is the lead factor which
determines output of the CHP plant.
1.1.2.1
Mains parallel operation
In system-parallel operation, the CHP plant supplies consumers e.g. until the maximum electrical output is
reached according to the nominal power of the engine. Any further additional demand is covered from the
mains power supply. During high-tariff periods, the gensets can be used to offset peak loads.
In the event of a mains fault, the CHP plant can be operated in isolated mode.
1.1.2.2
Isolated operation mode
When operating in isolated mode, the CHP plant supplies the power demand of the consumers by itself.
The gensets are required to supply the power for all connected consumers at any time of operation. This
applies both to load switching and load shedding.
The switching system's load management has to ensure that the gensets are never overloaded. Load surges
should not exceed the maximum permissible load steps as specifically determined for each engine type
under any circumstances (refer to Chapter "Load steps"). This applies both to load switching and load
shedding. The required switching power of the respective consumers is of particular consideration here, not
the nominal power (See also Chapter 15 "Isolated operation mode" and Chapter 16 "Load steps").
1.1.2.2.1 Back-up power operation
Taking due account of the appropriate additional measures required, the CHP plant can also be used to
provide a back-up power supply, covering the demand for power in the event of a network power failure as
per :
DIN VDE 0100-710 and DIN VDE 0100-560
DIN EN 50172 and DIN VDE 0100-718
The back-up power operation must be clarified and approved in each individual case. Not all gensets are
capable of providing a back-up power supply as stated by the standards mentioned above. The enginespecific load steps must be adhered to.
The heat energy simultaneously produced by the CHP plant should, if possible, be utilized (e.g. for heating or
refrigeration), for which purpose heat accumulators should be employed where necessary. When providing a
back-up power supply, heat dissipation must be guaranteed under all circumstances, if necessary with the
aid of dump cooling facilities and/or accumulators.
Chapter_01 - Layout of gas engine-powered gensets.docx
02999408
Page 4 / 8
VD-S 2014-06 DE
Caterpillar confidential: none
1.1.2.2.2
Black start
The black start is an emergency function of the gas gensets and should be used only for emergency
situations. If a gas genset is "black-started", it starts without auxiliary drive power for prelubrication and
cooling water pumps. The gas genset is started directly after the TEM demand contact has been closed. The
cooling pumps start as soon as the auxiliary drive power supply is available. Furthermore, the gas genset will
be started without prior leak monitoring of the gas control line.
The engines of the series TCG 2016 and TCG 2020 are capable of black-starting. The engines of the series
TCG 2032 cannot be black-started. (See also Chapter 15.7).
1.1.3
Operation dependent on the availability of combustion gas
With this type of operation, the lead factor is the available supply of combustion gas (e.g. landfill gas, sewage
gas, biogas, etc.). In the case of multi-engine systems, gensets are switched on or off depending on the
amount of gas available. For single engine systems, the engine power is adjusted to the available gas
amount.
1.1.4
Dual gas operation
For special applications, the gas gensets can be equipped with two gases for the operation. If, for example,
natural gas and sewage gas are available, it is possible to change over from sewage gas to natural gas if
sewage gas is lacking. For the changeover between the two gases, the genset must be stopped.
Chapter_01 - Layout of gas engine-powered gensets.docx
02999408
Page 5 / 8
VD-S 2014-06 DE
Caterpillar confidential: none
Fig. 1.1
Definition and demarcation of CHP components as per DIN 6280-14
A
Combined heat and power plant (CHP)
B
CHP set
C
CHP genset
1
Reciprocating pistons, internal combustion engine
2
Generator
3
Coupling and flexible mounting
4
Combustion air filter
(optionally installed separately from the engine)
5
Exhaust heat exchanger
6
Cooling water heat exchanger
7
Exhaust silencers
Chapter_01 - Layout of gas engine-powered gensets.docx
02999408
Page 6 / 8
VD-S 2014-06 DE
Caterpillar confidential: none
8
Exhaust gas cleaning system
9
Fuel tank or gas supply
10
Lube oil supply
11
Monitoring system
12
Switchgear with control system
13
Air supply system
14
Exhaust air system
Chapter_01 - Layout of gas engine-powered gensets.docx
02999408
Page 7 / 8
VD-S 2014-06 DE
Caterpillar confidential: none
Chapter_01 - Layout of gas engine-powered gensets.docx
02999408
Page 8 / 8
VD-S 2014-06 DE
Caterpillar confidential: none
Power plants layout
Chapter 2
Genset output
06-2014
Caterpillar Energy Solutions GmbH Carl-Benz-Straße 1 D-68167 Mannheim Phone: +49(0)621 384-0 Fax: +49(0)621 384-8612
Caterpillar confidential: none
Contents
2.
Genset output .............................................................................................................................. 3
2.1
Demand for heat ........................................................................................................................... 3
2.2
Demand for electricity ................................................................................................................... 3
2.3
Available fuel supply ..................................................................................................................... 3
2.4
Performance data on the rating plates .......................................................................................... 4
2.4.1
Rating plate of the engine ............................................................................................................. 4
2.4.2
Rating plate of the generator......................................................................................................... 4
2.4.3
Rating plate of the genset ............................................................................................................. 4
Chapter_02 - Genset output.docx
02999408
Page 2 / 4
VD-S 2014-06 DE
Caterpillar confidential: none
2.
Genset output
To plan the size of the genset, it is necessary to determine the demand for electricity and heat on the basis
of annual consumption curves.
2.1
Demand for heat
The heat demand curve can be used to determine the size and number of gensets required for heat-led
operation. However, with heat-led operation, it is essential to consider the generation and demand for
electricity. The choice of operating mode may lead to negative feed and/or to power being drawn from the
mains.
2.2
Demand for electricity
The electricity demand curve is decisive in determining the demand for electricity in mains parallel operation.
At the same time, it is necessary to investigate whether it is appropriate to split the total output between
several gensets. For back-up power operation, in addition to the demand for electricity in mains parallel
operation, the back-up power output must also be considered. A distinction must be drawn between
"important" and "non-important" consumers and their permitted downtimes.
Not all consumers are connected or achieve their maximum current consumption simultaneously
(simultaneity factor).
Some consumers purely consume real power, while others merely consume an apparent power output
(power factor “cos phi”). Particular consumers, such as those with impact load characteristics or which make
extreme demands in terms of constant voltage and frequency, must be taken into account.
Under special climatic mounting conditions (high altitude, high air temperatures and air humidity), the engine
and generator are unable to produce their normal output (reduction in output as per ISO 8528-1, DIN VDE
0530 and DIN EN 60034).
2.3
Available fuel supply
The genset output and number of gensets will be dependent on the available gas volume. The gensets must
be operated only in the 50 – 100 % output range. For continuous operation, the output should be above
70%.
Chapter_02 - Genset output.docx
02999408
Page 3 / 4
VD-S 2014-06 DE
Caterpillar confidential: none
2.4
Performance data on the rating plates
In the case of a generator genset, the engine, generator and genset each have their own rating plate.
2.4.1
Rating plate of the engine
In the case of gas engines, the output SCN (continuous output, cannot be overloaded) is outlined according
to DIN 3046-7. On the test bench, gas engines are run with natural gas. In the case of engines which are run
with other types of gases in later operation, the output for the type of gas is additionally outlined on the rating
plate. The type of gas is specified after the output description.
For example, the following outputs can be indicated on the rating plate:
SCN n:
continous output during operation with natural gas; n means natural gas; the output
is run on the test bench.
SCN n:
continuous output during operation with biogas; b means biogas
Further extensions may be:
2.4.2
m
mine gas
s
sewage gas
l
landfill gas
Rating plate of the generator
The rating plate of the generator lists the apparent power of the specific type according to IEC 60034 and the
power factor (cos Phi) of the generator. The specification is given in kVA (Kilo Volt-Ampere), the power factor
is dimensionless.
2.4.3
Rating plate of the genset
The electric nominal output of the genset is given on the rating plate. The name of the output category is
outlined according to DIN 8528-1. The output is given in KWel (Kilowatt electric).
Gensets with gas engines are designed for continuous operation; therefore, the genset rating plate shows
the power category COP (continuous power of the genset).
Chapter_02 - Genset output.docx
02999408
Page 4 / 4
VD-S 2014-06 DE
Caterpillar confidential: none
Power plants layout
Chapter 3
CHP genset
06-2014
Caterpillar Energy Solutions GmbH Carl-Benz-Straße 1 D-68167 Mannheim Phone: +49(0)621 384-0 Fax: +49(0)621 384-8612
Caterpillar confidential: none
Contents
3.
CHP genset .................................................................................................................................. 3
3.1
Genset design ............................................................................................................................... 3
3.2
Genset ........................................................................................................................................... 3
3.2.1
Engine monitoring and cabling ...................................................................................................... 3
3.2.2
Genset examples ........................................................................................................................ 14
3.3
Generators .................................................................................................................................. 19
3.3.1
General ........................................................................................................................................ 19
3.3.2
Generator voltage regulation....................................................................................................... 20
3.3.2.1
Basic function of the voltage regulator ........................................................................................ 21
3.3.2.2
Setpoint adjustment of the voltage regulator .............................................................................. 21
3.3.3
Generator protection ................................................................................................................... 21
3.3.3.1
Monitoring facilities for generators as per ISO 8528, Part 4 ....................................................... 21
3.3.4
Earthing ....................................................................................................................................... 22
Chapter_03 - CHP genset.docx
02999408
Page 2 / 22
VD-S 2014-06 EN
Caterpillar confidential: none
3.
CHP genset
3.1
Genset design
Gensets comprise the following main components:
•
Gas engine
•
Generator
•
Torsionally flexible coupling
•
Base frame
•
Flexible bearing elements
Engine and generator are linked by a torsionally flexible coupling and rigidly mounted to the base frame. The
base frame is mounted to the foundation by flexible bearing elements.
All flexible connections for the operating media are installed at the genset. Auxiliary units such as
prelubricators and lubricating oil level monitors are mounted to the base frame.
Preheating must be provided for every engine. Dependent on the design of the system, this may be installed
either at the genset or in the system.
3.2
Genset
3.2.1
Engine monitoring and cabling
The gas engine is equipped with sensors for monitoring and control purposes. The sensors are wired to a
multifunction rail at cylinder rows A and B. A bus cable runs from each multifunction rail to the TEM system
(TEM see Chapter 14.1). At the engine, all parts needing to be grounded are connected to the copper rail.
This rail must therefore be connected to the earthing system of the switchgear. An overview of the monitoring
facilities is shown in the following engine drawings.
Chapter_03 - CHP genset.docx
02999408
Page 3 / 22
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 3.1a Engine TCG 2016 V08 C, V12 C and V16 C – Sensor arrangement
1
Mixture temperature sensor in front of turbocharger
in the TEM system parameter intake air
2
Coolant temperature sensor (low-temperature circuit, inlet)
3
Ignition coil
One ignition coil per cylinder
4
Flywheel pulse sensor –location depending on model
5
Starter relay
6
Starter
7
Knock sensor
One sensor for every two cylinders
9
Coolant temperature sensor (engine outlet)
10
Camshaft sensor
11
Crankcase pressure sensor
13
Stepper motor gas-air mixer
Chapter_03 - CHP genset.docx
02999408
Page 4 / 22
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 3.1b Engine TCG 2016 V08 C, V12 C and V16 C – Sensor arrangement
1
Multifunction rail cylinder row B
2
Charging mixture temperature sensor after mixture cooler
in TEM system parameter receiver
3
Combustion chamber temperature sensor
One sensor per cylinder
4
Coolant temperature sensor (high-temperature circuit inlet)
5
Prelubrication pump
6
Lube oil temperature sensor
7
Lube oil pressure sensor
Chapter_03 - CHP genset.docx
02999408
Page 5 / 22
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 3.2a Engine TCG 2020 V12(K) and V16(K) – Sensor arrangement
1
Coolant temperature sensor before mixture cooler
2
Knock sensor
One sensor for every cylinder
3
Combustion chamber temperature sensor
One sensor for every cylinder
4
Starter
5
Starter relay
6
Crankcase pressure sensor
7
Lubricating oil level sensor
8
Prelubrication pump
9
Lube oil pressure sensor
10
Camshaft sensor
11
Multifunction rail cylinder row A
12
Proximity switch gas-air mixer
13
Intake air temperature sensor
V16 engine
14
Intake air temperature sensor
V12 engine
15
Ignition coil
One ignition coil for every cylinder
Chapter_03 - CHP genset.docx
02999408
Page 6 / 22
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 3.2b Engine TCG 2020 V12 and V16 – Sensor arrangement
1
Multifunction rail cylinder row B
2
Coolant temperature sensor (engine outlet)
3
Mixture temperature sensor
4
Coolant temperature sensor (engine inlet)
5
Lube oil temperature sensor
6
Lube oil pressure sensor
7
Knock sensor
One sensor for every cylinder
8
Combustion chamber temperature sensor
One sensor for every cylinder
9
Flywheel pulse sensor
10
Ignition control unit
11
Actuator
12
Stepping motor gas-air mixer
13
Ignition coil
One ignition coil for every cylinder
14
Exhaust turbocharger speed sensor
15
Exhaust turbocharger temperature sensor
Chapter_03 - CHP genset.docx
02999408
Page 7 / 22
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 3.3a Engine TCG 2020 V20 – Sensor arrangement
1
Exhaust turbocharger temperature sensor
2
Intake air temperature sensor
3
Ignition coil
One ignition coil for every cylinder
4
Starter relay
5
Combustion chamber temperature sensor
One sensor for every cylinder
6
Knock sensor
One sensor for every cylinder
7
Crankcase pressure sensor
8
Camshaft sensor
Chapter_03 - CHP genset.docx
02999408
Page 8 / 22
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 3.3b Engine TCG 2020 V20 – Sensor arranagement
1
Exhaust turbocharger speed sensor
2
Coolant temperature sensor (engine outlet)
3
Mixture temperature sensor
4
Coolant temperature sensor (engine inlet)
5
Lube oil temperature sensor
6
Lube oil pressure sensor
7
Knock sensor
One sensor for every cylinder
8
Combustion chamber temperature sensor
One sensor for every cylinder
9
Actuator
10
Flywheel pulse sensor
11
Coolant temperature sensor before mixture cooler
12
Ignition control unit
13
Proximity switch gas-air mixer
14
Stepping motor gas-air mixer
Chapter_03 - CHP genset.docx
02999408
Page 9 / 22
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 3.4a Engine TCG 2032 V12 and V16 – Sensor arrangement
1
Coolant temperature sensor (high-temperature circuit inlet)
2
Proximity switch gas-air mixer
One switch for each gas-air mixer
3
Coolant temperature sensor (high-temperature circuit outlet)
4
Mixture temperature sensor
One sensor for each gas-air mixer
5
Stepping motor gas-air mixer
One stepping motor for each gas-air mixer
6
Depending on version – Base bearing temperature sensor
7
Multifunction rail cylinder row A
8
Camshaft sensor
9
Crankcase pressure sensor
10
Electric pump for preheating unit (coolant)
11
Electrical preheater
for coolant and lubricating oil
12
Electric pump for preheating unit (lubricating oil)
Fig. 3.4b Engine TCG 2032 V12 and V16 – Sensor arrangement
Chapter_03 - CHP genset.docx
Page 10 / 22
02999408
VD-S 2014-06 EN
Caterpillar confidential: none
1
Lube oil temperature sensor
2
Start backup for engine turning device
3
Solenoid valve for compressed air starter
4
Flywheel sensor – installation location depending on version
5
Multifunction rail cylinder row B
6
Charging mixture temperature sensor
One sensor each for A and B side
V12 engine: Between cylinder A4 and A5 as well as before B6
V16 engine: Between cylinder A6 and A7 as well as before B8
Chapter_03 - CHP genset.docx
02999408
Page 11 / 22
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 3.4c Engine TCG 2032 V12 and V16 – Sensor arrangement
1
Exhaust turbocharger speed sensor
One sensor for every exhaust turbocharger
2
Actuator
3
Coolant temperature sensor (high-temperature circuit inlet)
4
Lubricating oil level sensor
5
Lube oil pressure sensor
(Lube oil pressure before lubricating oil filter)
6
Coolant temperature sensor (low-temperature circuit, inlet)
7
Charging mixture pressure sensor A side, mixture cooler – Depending on
version
Chapter_03 - CHP genset.docx
02999408
Page 12 / 22
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 3.4d Engine TCG 2032 V12 and V16 – Sensor arranagement
1
Flywheel sensor – installation location depending on version
2
Lube oil pressure sensor
(Lube oil pressure after filter)
3
Ignition coil
One ignition coil for every cylinder
4
Ignition control unit
5
Combustion chamber temperature sensor
One sensor for every cylinder
6
Knock sensor
One sensor for every cylinder
7
Charging mixture pressure sensor
One sensor each for A and B side
Chapter_03 - CHP genset.docx
02999408
Page 13 / 22
VD-S 2014-06 EN
Caterpillar confidential: none
3.2.2
Genset examples
Figures 3.6 to 3.9 illustrate gensets with gas engines of the series 2016, 2020, 2032.
Binding genset dimensions are contained in the contract-specific genset drawing.
Chapter_03 - CHP genset.docx
02999408
Page 14 / 22
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 3.5Engine TCG 2016 V16 C with Marelli generator MJB 450 MB 4
Genset weight approx. 8450 kg (transport)
Chapter_03 - CHP genset.docx
02999408
Page 15 / 22
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 3.6Engine TCG 2020 V16 with Marelli generator MJB 500 LA4
Genset weight approx. 13320 kg (transport)
Chapter_03 - CHP genset.docx
02999408
Page 16 / 22
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 3.7Engine TCG 2020 V20 with Marelli generator MJB 560 LB 4
Genset weight approx. 17900 kg (transport)
Chapter_03 - CHP genset.docx
02999408
Page 17 / 22
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 3.8Engine TCG 2032 V16 with Marelli generator MJH 800 MC6
Genset weight approx. 51400 kg (transport)
Chapter_03 - CHP genset.docx
02999408
Page 18 / 22
VD-S 2014-06 EN
Caterpillar confidential: none
3.3
Generators
3.3.1
General
The types used as standard are brushless synchronous generators, which, depending on the application,
may be suitable for mains parallel and/or back-up power operation.
Depending on output and the available mains supply, these may be 400 V to 690 V three-phase generators
or 3 kV to 15 kV medium-voltage generators.
The efficiency of the generators dependent upon size and power factor value (cos phi) is between 95.0 %
and 97.8 %.
Thus, for example, a 494 kVA generator with a power factor of 0.8 has an efficiency level of 95.5 % and a
5336 kVA medium-voltage generator with a power factor of 0.8 has an efficiency level of 97.2 %. If the
generator is operated at a power factor of 1, efficiency is increased by approx 1-1.5 %.
As per DIN VDE 0530 / DIN EN 60034, the generators are designed for an ambient temperature of 40° C
and an installation altitude of 1000 m. At higher ambient temperatures or higher altitude, the output must be
reduced in accordance with the manufacturer's specifications.
These generators can operate as standard in a power factor range of 0.8 - 1 inductive (lagging). Thus, in the
case of mains parallel operation, it is possible to improve the mains handover power factor in the event that
the generators are to be used as "phase shifters".
Generators must be specially designed for use in the capacitive range! There are different country-specific
regulations for static and dynamic mains support, which have to be considered when designing the gas
engine gensets.
In back-up power operation, the max. permissible unbalanced load for the generator must be taken into
account. (Dependent upon generator output and manufacturer, 30 % between maximum and minimum
phase current)
Fig. 3.9 Generator
Chapter_03 - CHP genset.docx
02999408
Page 19 / 22
VD-S 2014-06 EN
Caterpillar confidential: none
3.3.2
Generator voltage regulation
The voltage regulator keeps the generator voltage constant. The voltage regulator is generally either
installed in the generator's terminal box or in the switchgear. The principle function of the voltage regulator is
shown in Figure 3.10.
Fig. 3.10 Generator voltage regulation
1
2
4
3
1
Setpoint adjuster
2
Voltage regulator
3
Rotor
4
Stator
G1
Three-phase main machine
G2
Three-phase exciter
G3
Auxiliary exciter
Chapter_03 - CHP genset.docx
02999408
Page 20 / 22
VD-S 2014-06 EN
Caterpillar confidential: none
3.3.2.1
Basic function of the voltage regulator
The power supply of the voltage regulator is provided from the auxiliary exciter G3. The brushless threephase exciter G2 receives its voltage supply from the actuating element of the voltage regulator. The voltage
delivered from the three-phase rotor winding of the exciter G2 is rectified and supplied as direct current to the
rotor of the generator G1. In order to obtain a constant voltage level at the generator terminals with
alternating load, it is necessary to adjust the current supply to the rotor accordingly. This function is assumed
by the voltage regulator.
3.3.2.2
Setpoint adjustment of the voltage regulator
The inputs to the voltage regulator are the voltage setpoint from the setpoint adjuster and the actual
generator voltage measured at the terminals U,V and W. The readjustment of the generator voltage is done
via adjustment of the current supply to the rotor.
The adjustment of the voltage setpoint has to be done on site with regard to the voltage level at the local
conditions. The range for the voltage adjustment is normally within 5% to 10% of the generator's nominal
voltage.
3.3.3
Generator protection
To protect the generators, monitoring facilities as per ISO 8528 must be employed.
Those monitoring facilities are not included in the TEM system.
3.3.3.1
Monitoring facilities for generators as per ISO 8528, Part 4
The following generator monitoring facilities are absolutely essential and must be provided in the switchgear:
•
Protection in case of short circuit
•
Protection in case of overload
Chapter_03 - CHP genset.docx
02999408
Page 21 / 22
VD-S 2014-06 EN
Caterpillar confidential: none
The following protection facilities are urgently recommended:
•
Protection in case of time-delayed overcurrent
•
Protection in case of voltage-related overcurrent
•
Protection in case of directionally dependent overcurrent
•
Reverse power protection
•
Mains isolation facility
•
Reactive current restriction
•
Differential current protection
Also, the following protection facilities are recommended:
3.3.4
•
System earth fault protection
•
Stator earth fault protection
•
Unbalanced load protection
Earthing
The generator is connected to the base frame by an earthing wire. The earthing connection of the genset
must be connected to the earthing system for the CHP system.
The local power supply company rules or safety regulations must be complied with in order to ensure that the
genset earthing is correct.
Chapter_03 - CHP genset.docx
02999408
Page 22 / 22
VD-S 2014-06 EN
Caterpillar confidential: none
Power plants layout
Chapter 4
Requirements for genset installation
06-2014
Caterpillar Energy Solutions GmbH Carl-Benz-Straße 1 D-68167 Mannheim Phone: +49(0)621 384-0 Fax: +49(0)621 384-8612
Caterpillar confidential: none
Contents
4.
Requirements for genset installation ............................................................................................. 3
4.1
Genset room ....................................................................................................................................... 3
4.1.1
Site ..................................................................................................................................................... 3
4.1.2
Requirements for the genset room ..................................................................................................... 3
4.2
Foundation and vibration damping ..................................................................................................... 5
4.2.1
Foundation block ................................................................................................................................ 5
4.2.2
Elastic support .................................................................................................................................... 6
4.2.3
Assessing vibrations........................................................................................................................... 7
4.2.4
Cable and pipe ducts.......................................................................................................................... 7
4.3
Noise issues ....................................................................................................................................... 7
4.3.1
Acoustic dependencies ...................................................................................................................... 8
4.3.2
Possible means of mitigating noise .................................................................................................. 10
4.3.3
Noise data in genset data sheets ..................................................................................................... 11
4.3.3.1
Conversion of sound power levels into sound pressure levels ........................................................ 13
4.3.3.2
Measuring surfaces for the genset ................................................................................................... 13
4.3.3.3
Measuring surfaces for the exhaust sound ...................................................................................... 14
4.3.3.4
Examples of conversion sound power level – sound pressure level ............................................... 15
Chapter_04 - Requirements for genset installation.docx
02999408
Page 2 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
4.
Requirements for genset installation
4.1
Genset room
Having carefully selected and established the output of the genset, there are a series of preconditions which
must be fulfilled by the client to achieve a safe, low-maintenance, and fault-free operation.
The most important questions associated with the setup and installation of the genset must therefore be
clarified at the time when buildings intended to house the energy generation units are being planned.
Alterations and special solutions introduced at a later date are generally expensive and often unsatisfactory.
Right from the start, consideration should be given to possible future expansion.
4.1.1
Site
The planning process begins with the selection of the site at which to set up the genset. In order to minimize
losses in the transmission of energy to the consumer, it makes practical sense to arrange the genset in the
vicinity of the consumer. However, requirements in terms of noise and vibration often lead to gensets being
set up far away from residential properties.
Where a building is reserved for energy generation, the problems of ventilation, vibration damping, fuel
supplies and storage, and also of bringing in and providing access to the genset are generally easier to
resolve.
Genset rooms inside large buildings such as e.g. department stores, hospitals and administration buildings
should be located as near as possible to an outside wall, so there is no difficulty in drawing in and
discharging air for cooling and ventilation. The genset room can be designed at ground level, below ground,
or in the case of smaller gensets, even on one of the upper floors.
The choice of building materials must take account of the need for sound and vibration damping.
4.1.2
Requirements for the genset room
The genset room should be of adequate size. Aside from the added complication of operation and
maintenance, the problem of ventilation in small rooms is also not easy to resolve.
For TCG/TCD 2016 and 2020, a clear space of approx. 1 m in width should, under all circumstances, be
allowed for all round the genset, increasing to 2 m for bigger engines. Care must be taken to ensure that the
starter batteries are installed as close as possible to the electric starter. For installations with engines TCG
2032, it is necessary to provide a free area of 2 meters by 5 meters suitable for acceptance of heavy
weights. Preferably, this area should be arranged close to the engine in order to achieve access by the same
crane both for the pre-assembly area and the engine itself. Furthermore, the size of the room will be
determined by the other components to be installed, such as e.g. heat utilization unit, switchgear, gas control
line, fuel tank, lube oil tank, batteries, exhaust pipe and silencer. The silencers for the inlet and exhaust air
Chapter_04 - Requirements for genset installation.docx
02999408
Page 3 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
also require enough available room.It is essential to design large enough openings to bring in the genset,
and to ventilate the system (see Chapter 5, Engine room ventilation).
No genset room should be without permanently installed lifting gear (crane), the load-bearing capacity of
which corresponds to the heaviest single item in the room. It must, however, in all cases be guaranteed that,
when carrying out maintenance work, dependent on the engine type, e.g. pistons, con-rods, cylinder heads
or even a complete engine can be lifted. Both assembly and subsequent maintenance can then be carried
out more quickly and more practically.
The genset room should be of sufficient height to allow pistons and connecting rods to be withdrawn
upwards, taking into account the lifting gear. The size of the room must permit work to be carried out
unobstructed at all points around the genset and there must be space to park individual genset components
and spares.
Together with the planning of the engine room, the elastic mounting, the design of the foundation block, the
pipe and cable work must be clarified. Also to be considered in the early stages of planning is the
implementation of any special noise protection and anti-vibration insulation measures.
For smaller installations, the genset and the switchgear can generally be set up in one room. For larger
installations, it may be more practical to install the switchgear in a separate, sound-proofed operating room.
When planning the genset room, consideration must also be given to the transport route, so that if
necessary, an engine or generator can be dismantled and reinstalled (floor loading and space available).
The example in figure 4.1 illustrates a practical and proven genset installation.
If access to the genset and its components is heavily restricted due to the engine room not being designed
large enough, the manufacturer may claim additional costs when performing maintenance or repair work
within the scope of the manufacturer's warranty.
When operating and when performing maintenance work on the genset, lubricating oil and/or coolant can
enter the genset room under certain circumstances. Restraining devices must be provided in the genset
room drainage system which reliably prevent environmental damage from these materials.
Chapter_04 - Requirements for genset installation.docx
02999408
Page 4 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 4.1 Typical installation TCG 2016 V16 C
Before detailed planning work starts, the manufacturer would also assist prospective clients with further
documentation on standard installations. For major planning tasks, construction or draft construction
drawings are requested by us.
4.2
Foundation and vibration damping
In the case of gensets with piston engines, gravity forces and moments of inertia cannot, in all cases, be
completely balanced. The transmission to the foundation of the vibration and noise thus created can be
significantly reduced by the use of elastic mountings. When installing gensets, the elastic mounting elements
must therefore always be provided between the base frame and the foundation block.
4.2.1
Foundation block
For the base of the foundation, which must be implemented with special care, it is recommended that a soil
investigation be carried out by an expert. The costs for this bear no relation to the expense involved in the
subsequent work required, if, for example, it is found that vibration is being transmitted to the surrounding
area.
There must be no groundwater veins either beneath or in the vicinity of the foundation block, as these can
transmit vibrations over very long distances. This also applies to a high groundwater level which leads to
Chapter_04 - Requirements for genset installation.docx
02999408
Page 5 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
stronger transmission of vibration than occurs in dry ground. Depending on local conditions, the foundation
block may have to be set on a sole plate or pilework.
Sinking and basing the foundation are in any case the responsibility of the construction company or architect.
The latter must assess the load-bearing capacity of the soil and determine the solidity of the foundation block
by specifying the requisite concrete mix and reinforcements to suit the local conditions.
For calculation purposes, clients will be provided with data on the foundation load imposed by the genset
and the natural frequencies of the elastic bearings.
With the reasons mentioned above the foundation block as built should not have any contact with the
foundation walls of the building or with the floor. The gap between the foundation block and the floor can be
sealed with an elastic material. To accept the elastic bearing elements, the surface of the foundation must be
horizontal and disked, without being smoothed with a trowel. The foundation surface must be flat to a
tolerance of max. ± 2 mm. It is not permissible to mount the genset on tiles or pavement.
4.2.2
Elastic support
In order to insulate the genset as far as possible from the foundation in terms of vibration and structure-borne
noise, steel spring bearing elements are used. These bearing elements reduce the transmission of dynamic
forces to the foundation. The insulation of low frequencies in buildings is of great importance. This is also
achieved with a soft steel spring bearing support. Structure-borne noise insulation is guaranteed by means of
reflection from the base plate of the bearing, thanks to the insulation effect of the steel / rubber plate
arrangement.
The elastic support must be recalculated for each application. The natural frequency of the system
constituted by the genset / elastic support must be sufficiently far below the operating speed of the genset.
Insulation levels of approx. 88 - 94 % are achieved with the bearing elements used.
The spring elements which are used in gensets can be adjusted in height over a certain range. They have to
be properly adjusted; meaning the load on each element has to be equal. A wrong setting of the spring
elements leads to their destruction on a long term basis and the oscillations cannot be isolated anymore.
Spring elements can compensate unevenness of the foundation only to some extent. Due to an uneven load,
too great an unevenness of the foundation and a wrong setting of the spring elements lead to the
deformation of the genset's base frame. As a consequence, the alignment between the generator and the
engine is no longer efficient. This can result in an incalculable destruction of the components.
Chapter_04 - Requirements for genset installation.docx
02999408
Page 6 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
4.2.3
Assessing vibrations
DIN ISO 8528 - 9 must be applied for gensets. This standard deals with the measurement and evaluation of
the mechanical vibrations in electricity generating units with reciprocating piston combustion engines.
4.2.4
Cable and pipe ducts
Cooling water and exhaust pipes can be laid in ducts beneath the floor. The requisite dimensions must be
adapted to the size of the pipes and to local conditions.
In general, care must be taken to ensure that ducts for pipes and ducts for cables are implemented
separately from one another, whereby a further distinction must be drawn between power cables, control
cables and signal cables. Ducts are laid with a fall leading away from the foundation block, with drains fitted
with oil separators provided at the lowest points. The ducts can be covered with treadplate or grilles. Ducts
and covers must always be provided by the client.
4.3
Noise issues
Since the acoustic requirements imposed by various laws and regulations on the installation of gensets with
combustion engines are constantly increasing, a brief reference is appropriate here to the contexts and
possible solutions to noise problems.
Noise sources mainly include the combustion noise of the engine, mechanical engine noises and the air
intake and exhaust noises from the engine. The fans, pumps and other auxiliary drives can also be the
cause of nuisance noise.
Likewise, excessive air speeds can cause noise (see Chapter 5.5, Planning notes).
There is nothing that effective resources can do to reduces the source of noise themselves. Thus most
measures to mitigate noise are directed towards reducing the transmission of noise outside of the genset
room.
Chapter_04 - Requirements for genset installation.docx
02999408
Page 7 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
4.3.1
Acoustic dependencies
Noise is made up of pressure waves of varying frequencies. All measurements of noise are thus frequency
dependent pressure measurements. Lower-frequency noises are more easily tolerated by human beings
than those of higher frequencies. Sound waves above 16,000 - 20,000 Hertz, on the other hand, are
generally beyond detection by the human ear.
The need to compare the loudness of sound events at different locations has led to the development of
objective measuring procedures. Assessments are conducted in accordance with specific frequency curves,
as defined in DIN EN 61672-1 and DIN EN 61672-2. These are assessment curves A, B, C and D (Table
4.1). The assessment curves replicate in a somewhat simplified manner the frequency response of the ear to
narrow-band noises. Curve A applies to the low-volume range, Curves B and C cover the range of loud and
very loud noises, whilst D applies to aircraft noise.
Table 4.1
Frequency
Hz
Assessment curve
A
B
C
D
dB
dB
dB
dB
31.5
-39.4
-17.1
-3.0
-16.5
63
-26.2
-9.3
-0.8
-11.0
125
-16.1
-4.2
-0.2
-6.0
250
-8.6
-1.3
0.0
-2.0
500
-3.2
-0.3
0.0
0.0
1000
0.0
0.0
0.0
0.0
2000
1.2
-0.1
-0.2
8.0
4000
1.0
-0.7
-0.8
11.0
8000
-1.1
-2.9
-3.0
6.0
Chapter_04 - Requirements for genset installation.docx
02999408
Page 8 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
Engine noises are normally assessed in dB (A).
A measured value at 125 Hz is for example perceived as 16.1 dB quieter than the same value at 1000 Hz.
The strength of the noise is dependent on the range at which it is measured and on the installation site.
When measured a short distance from the source, the sound pressure level is higher, and at long distance it
is lower. This reduction in sound level is referred to as dispersion damping.
For point sources, the following applies:
L( r 2 )
 r2 
= L( r1) − 10 log 
 r1 
2
L(r1)
= sound pressure level 1
L(r2)
= sound pressure level 2
r1
= distance 1
r2
= distance 2
Example:
L(r1) = 70 dB
r1 = 10 m
r2 = 20 m
As the distance doubles, the sound pressure level falls by 6 dB.
For installations comprising several gensets, the total noise level may be determined according to the laws of
acoustics:
n
Li
L∑ = 10 log ∑ 1010
i =1
L∑
= total level
Li
= individual level
Example:
71, 5
72 , 5
75, 5
77 , 0
 7010,5

10
10
10
L∑ = 10 log10 + 10 + 10 + 10 + 10 10  = 81,1


L1 = 70.5 dB
L2 = 71.5 dB
L4 = 75.5 dB
L5 = 77.0 dB
dB
L3 = 72.5 dB
Chapter_04 - Requirements for genset installation.docx
02999408
Page 9 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
In simplified terms, when adding n equal levels L, the following applies:
L∑ = L + 10log n
When 2 equal sound levels are added, the level rises by 3 dB.
Where a genset is erected in a closed room, the noise is greater than in the open air as a result of the
impeded dispersal of the noise. In small rooms with no acoustic material, the noise distribution is equal
almost everywhere.
Large rooms with sound-absorbent walls offer acoustic benefits; tiles or similar construction materials should
be avoided.
4.3.2
Possible means of mitigating noise
Normal wall thicknesses of 24 cm or 36 cm damp the noise coming from within by 40 to 50 dB. Nevertheless,
silencer sections 2 to 3 m in length must be provided for the air inlet and exhaust ducts, with approx. 40 dB
noise reduction. Taking into account the volume of cooling air (see Chapter 5, Machine room ventilation) in
the silencer section, the air speed should not exceed approx. 8 m/s on the delivery side and approx. 6 m/s on
the extraction side.
If acoustic materials such as sound insulating panels are installed in the genset room, the noise level can be
reduced by approx. 3 dB, and indeed at considerable expense even by approx. 10 dB. Particular care should
be taken to control the exhaust noise. With suitable silencers, reductions in noise levels of up to approx. 60
dB can be achieved here.
Questions of sound insulation can only be solved on an individual basis, as they are highly dependent on
local circumstances. By way of assistance, the manufacturer provides octave analyses of exhaust gas and
engine noises.
Sound insulation measures should be designed in collaboration with specialist firms.
Such measures might, for example, include :
•
Exhaust silencing with the aid of reflection silencers, absorption silencers, active sound
deadening
•
Installing the genset so as to insulate against structure-borne noise
•
Arrangement of absorption baffles for the genset room air inlet and outlet openings
•
Housing the genset inside a sound-insulating enclosure
•
Fitting the engine room with sound insulation and installing a floating floor (tasks for
specialist firms).
Chapter_04 - Requirements for genset installation.docx
02999408
Page 10 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
No fiber materials (e.g. Heraklit) may be used to clad the interior of the room. Vibrations in the air cause
particles to be released which then block the air filters and can even destroy the engine.
When sound-proofing the building, it is necessary to consider not only the walls but also the windows, doors
and so on.
Technical sound-proofing considerations should also extend to additional sound sources such as auxiliary
drives or horizontal-type radiators which are located outside of the engine room. Also gas control lines, prepressure control lines or zero-pressure control lines, which are installed outside the engine room or outside a
sound capsule, can represent an additional noise source and must be considered in the technical sound
design.
4.3.3
Noise data in genset data sheets
In the genset data sheets, the noise values for airborne noise and exhaust noise are specified as sound
power levels. There are third octave spectra for the airborne noise and octave spectra for the exhaust noise.
The specified levels in the third octave and octave bands are linear levels, meaning that no correction was
made according to one of the assessment curves A, B, C and D. The overall noise levels are specified as
total levels with an A assessment of the individual levels. In Table 4.2, the correction values are listed
according to assessment A, B, C and D for the third octave bands.
Fig. 4.2 Noise data for a TCG 2020 V12
Chapter_04 - Requirements for genset installation.docx
02999408
Page 11 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
Tab. 4.2 Correction values for the third octave bands according to curves A,B,C and D
Frequency
Hz
Assessment curve
A
B
C
D
dB
dB
dB
dB
25
-44.7
-20.4
-4.4
-18.5
31.5
-39.4
-17.1
-3.0
-16.5
40
-34.6
-14.2
-2.0
-14.5
50
-30.2
--11.6
-1.3
-12.5
63
-26.2
-9.3
-0.8
-11.0
80
-22.5
-7.4
-0.5
-9.0
100
-19.1
-5.6
-0.3
-7.5
125
-16.1
-4.2
-0.2
-6.0
160
-13.4
-3.0
-0.1
-4.5
200
-10.9
-2.0
0.0
-3.0
250
-8.6
-1.3
0.0
-2.0
315
-6.6
-0.8
0.0
-1.0
400
-4.8
-0.5
0.0
-0.5
500
-3.2
-0.3
0.0
0.0
630
-1.9
-0.1
0.0
0.0
800
-0.8
0.0
0.0
0.0
1000
+0.0
0.0
0.0
0.0
1250
+0.6
0.0
0.0
+2.0
1600
+1.0
0.0
-0.1
+5.5
2000
+1.2
-0.1
-0.2
8.0
2500
+1.3
-0.2
-0.3
+10.0
3150
+1.2
-0.4
-0.5
+11.0
4000
+1.0
-0.7
-0.8
11.0
5000
+0.5
-1.2
-1.3
+10.0
6300
-0.1
-1.9
-2.0
+8.5
8000
-1.1
-2.9
-3.0
+6.0
10000
-2.5
-4.3
-4.4
+3.0
Chapter_04 - Requirements for genset installation.docx
02999408
Page 12 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
4.3.3.1
Conversion of sound power levels into sound pressure levels
The sound power is of a size that is independent on the distance and room and is suitable as a starting point
for all technical sound calculations. It is not directly measurable and is established via specified measuring
procedures.
The sound power level Lw is the specified technical sound size for a sound source. Contrary to the sound
pressure level Lp, the sound power level Lw is completely independent on the sound field; in other words, it
is independent on the size of the room and the distance to the source. The emitted sound power of a sound
source is determined here by the measurement of the sound pressure at several points of a closed
measuring surface S. The sound power of a source is calculated using the sound pressures measured on
the defined cover surface. The sound pressure levels are calculated at different distances to the sound
source using the established sound power.
The following correlation applies to the sound pressure level at a distance of x from the sound source:
Lp = LW – 10 * log (S/S0) [dB]
The following results from specification with A-assessed levels:
LpA = LWA -10 * log (S/S0) [dB(A)]
The following apply here:
Lp
Sound pressure level, linear (without assessment)
LpA
Sound pressure level, assessment according to curve A
LW
Sound power level, linear (without assessment)
LWA
Sound power level, assessment according to curve A
S
Measuring surface at a distance of x to the sound source
S0
Reference surface, always 1m²
4.3.3.2
Measuring surfaces for the genset
When determining the sound power level for the genset, a cuboid measuring surface at a distance of one
meter from the genset is implied, see Fig. 4.3. The measuring surface is divided into a grid with a measuring
point in the center of each individual grid surface. This procedure corresponds to DIN EN ISO 3476.
Chapter_04 - Requirements for genset installation.docx
02999408
Page 13 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 4.3 Cuboid measuring surface for the genset
4.3.3.3
Measuring surfaces for the exhaust sound
With exhaust sound, a spherical measuring surface at a distance of one meter from the outer edge of the
exhaust pipe is implied. The measuring surface is calculated with the equation:
S = 4 * π * (D/2 + d)² [m²]
The following apply here:
S
measuring surface [m²]
D
Diameter of the exhaust pipe [m]
d
Measurement distance [1 m]
Fig. 4.4 Spherical measuring surface for the exhaust gas
d
2
1
∅D
1
Exhaust pipe
2
Measuring surface S
Chapter_04 - Requirements for genset installation.docx
02999408
Page 14 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
4.3.3.4
Examples of conversion sound power level – sound pressure level
Example 1:
How high is the sound pressure level for a genset TCG 2020 V12 at a 1 meter and 10 meter distance?
The sound power level of the genset is specified in the data sheet as 121 dB(A).
The measuring surface S at a 1 meter distance is specified in the data sheet as 114 m².
The basic dimensions of a TCG 2020 V12 genset are:
Length L
[m]
5.7
Width W
[m]
2.1
Height H
[m]
2.5
An equivalent cuboid at a distance of 10 m has the dimensions:
Length L
[m]
5.7 + 2*10
Width W
[m]
2.1 + 2*10
Height H
[m]
2.5 + 10
This results in a measuring surface S of approx. 1763 m² at a distance of 10 meters.
The following calculations are obtained with the equation mentioned above:
Sound pressure level at a 1 meter distance:
LpA = LWA -10 * log (S/S0)
LpA = 121 -10 * log (114/1)
LpA = 121 -10 * log 114 = 121 – 10 * 2.06
LpA = 100.4 dB(A)
Sound pressure level at a 10 meter distance:
LpA = LWA -10 * log (S/S0)
LpA = 121 -10 * log (1763/1)
LpA = 121 -10 * log 1763 = 121 – 10 * 3.25
LpA = 88.6 dB(A)
Chapter_04 - Requirements for genset installation.docx
02999408
Page 15 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
Example 2:
How high is the exhaust sound pressure level for a genset TCG 2020 V12 at a 1 meter and 10 meter
distance from the exhaust outlet?
The sound power level for the exhaust gas is specified in the data sheet as 132 dB(A).
The reference surface S for a spherical surface with a radius of 1 m is specified in the data sheet as 15.5 m².
The surface S of a sphere with a 10 meter radius is 1257 m²:
The following calculations are obtained with the equation mentioned above:
Sound pressure level at a 1 meter distance:
LpA = LWA -10 * log (S/S0)
LpA = 132 -10 * log (15.5/1)
LpA = 132 -10 * log 15.5 = 132 – 10 * 1.19
LpA = 120.1 dB(A)
Sound pressure level at a 10 meter distance:
LpA = LWA -10 * log (S/S0)
LpA = 132 -10 * log (1257/1)
LpA = 132 -10 * log 1257 = 132 – 10*3.1
LpA = 101 dB(A)
Chapter_04 - Requirements for genset installation.docx
02999408
Page 16 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
Power plants layout
Chapter 5
Engine room ventilation
06-2014
Caterpillar Energy Solutions GmbH Carl-Benz-Straße 1 D-68167 Mannheim Phone: +49(0)621 384-0 Fax: +49(0)621 384-8612
Caterpillar confidential: none
Contents
5.
Engine room ventilation ............................................................................................................. 3
5.1
Ventilation systems ....................................................................................................................................... 4
5.1.1
Pressurized system (recommended) ............................................................................................................ 4
5.1.2
Extraction system (not recommended) ......................................................................................................... 4
5.1.3
Combined system (recommended) ............................................................................................................... 4
5.1.4
Ventilation by use of frequency-controlled fans ............................................................................................ 5
5.1.5
Circulating air temperature control ................................................................................................................ 5
5.2
Determining the demand for air .................................................................................................................... 8
5.2.1
Combustion air requirement.......................................................................................................................... 8
5.2.2
Cooling air requirement for the engine and components .............................................................................. 8
5.3
Determining the radiation heat ...................................................................................................................... 9
5.3.1
Radiation from the engine............................................................................................................................. 9
5.3.2
Radiation from the generator ........................................................................................................................ 9
5.3.3
Radiation from auxiliaries ............................................................................................................................. 9
5.3.4
Radiation from the heat recovery unit ........................................................................................................... 9
5.3.5
Total radiated heat ...................................................................................................................................... 10
5.3.6
Required ventilation air (excluding the combustion air for the engine)........................................................ 10
5.4
Ventilation system components .................................................................................................................. 12
5.4.1
Weather protection grille ............................................................................................................................. 12
5.4.2
Sound-proofing baffles................................................................................................................................ 12
5.4.3
Louvres ....................................................................................................................................................... 12
5.4.4
Filter............................................................................................................................................................ 12
5.4.5
Ventilators ................................................................................................................................................... 13
5.4.6
Air ducts ...................................................................................................................................................... 13
5.5
Planning notes ............................................................................................................................................ 14
5.5.1
Changes of air ............................................................................................................................................ 14
5.6
Notes on operating ventilation systems for gas engines ............................................................................. 14
5.7
Position of supply and exhaust openings.................................................................................................... 15
Chapter_05 - Engine room ventilation.docx
02999408
Page 2 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
5.
Engine room ventilation
An engine room is heated by convection and radiation from the engines, generators, heat recovery and
piping systems installed therein.
To avoid impermissibly high temperatures for the engines, components and switchgear, this heat must be
dissipated with the aid of a ventilation system.
Also, for systems operating in areas with extremely low ambient temperatures, it must be ensured that the
minimum intake air temperatures specified in the genset data sheet are complied with. For this, it is
recommended to utilize the radiation heat of the components to heat the engine room. In these cases, the
engine room walls must be tight and good thermal insulation should be provided.
In this respect, the design of the ventilation system is of particular importance; on the one hand, for the
removal of the radiation heat in summer, and on the other hand, for the utilization of the radiation heat for
engine room heating in winter.
General note: Intake air temperatures (and minimum temperatures) must comply with the values
specified in the genset data sheets!
It must be ensured that the intake air temperature does not fall below the permissible starting
temperature. See also Chapter 9.2, Requirements for the combustion air.
In the case of multi-engine systems, each genset should have its own adjustable ventilation system if
possible.
The kind of ventilation systems feasible for engine rooms may be divided into three types (see Fig. 5.1):
Chapter_05 - Engine room ventilation.docx
02999408
Page 3 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
5.1
Ventilation systems
5.1.1
Pressurized system (recommended)
Air at ambient temperature is drawn in from the outside by a fan, forced through the engine room and
returned to the environment via exhaust openings. An overpressure prevails inside the engine room.
The use of this system is especially recommended in environments with a high dust content (desert regions,
etc.). The overpressure inside the engine room prevents dust from penetrating into the room through leaks in
the walls of the building or through open doors or windows. The ventilation systems must be fitted with
appropriate filters to separate out the dust, e.g. inertia cyclone filters, dry type filters, etc. The filtration
efficiency of the supply filters for the ventilation system must be of the degree achieved by filters class G3.
See also Chapter 5.4.4.
5.1.2
Extraction system (not recommended)
Outside air is sucked into the engine room via the air supply system (weather protection grille, filter, silencer
and louvre); it then flows through the engine room before being extracted by a fan and returned to the
environment. Negative pressure prevails inside the engine room.
The ventilation system is arranged on the suction side in such a way that the underpressure adjusting in the
engine room lies considerably below 1 mbar. Particularly in the case of gas engine systems that extract
combustion air from the engine room, there may be complications on startup if the underpressure in the
engine room is too high (see also Chapter 5.6, Notes on operating the ventilation system for gas engines).
Furthermore, the doors of the engine room, which serve as escape doors in emergencies and open
outwards, are not easy to open if the underpressure is too high. The system works like a large vacuum
cleaner and unfiltered secondary air enters as a result of leaks in the engine room doors and windows, which
leads to the engine room becoming contaminated more and more over time. The degree of separation to be
reached with the air supply filters used must correspond with the degree of separation of a class G3 filter.
See also Chapter 5.3.4.
5.1.3
Combined system (recommended)
The air to ventilate the engine room is blown into the engine room by a supply air fan and extracted by
another fan on the exhaust side. By suitably tuning the supply and exhaust systems, the air pressure in the
engine room is approximately equal to the external ambient pressure.
This system must definitely be used for systems which exhibit significant pressure losses at both the supply
side and the exhaust side. This is particularly the case where the air for the engine room ventilation must be
drawn in and discharged again over great distances and the pressure loss is compounded by components
such as weather protection grilles, sound-proofing baffles, louvres and filters.
Chapter_05 - Engine room ventilation.docx
02999408
Page 4 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
5.1.4
Ventilation by use of frequency-controlled fans
When operating gas engines, the intake air temperature must be kept in a relatively narrow range. The
minimum air temperature indicated in the data sheet must not be fallen below, as otherwise the compressor
of the exhaust turbocharger will pump. Engines with an exhaust wastegate permit a further range of the
intake air temperature.
In the case of a ventilator with a fixed speed that is designed for summer conditions, the required minimum
intake temperatures for the engine may not always be maintained in winter. By adapting the ventilation
volumetric flow rate and the use of radiant heat from the engine and generator, the use of frequency
controlled ventilators allows the intake air temperature to be kept in the permissible range even at varying
ambient temperatures using a control. It is possible to control the intake air temperature by adapting the
ventilation volumetric flow up to ambient air temperatures of approx. 0°C; a circulation system is required for
lower ambient temperatures.
5.1.5
Circulating air temperature control
To avoid unacceptably low temperatures in the engine room, the room temperature can be controlled by
mixing exhaust air in with the supply air.
For all systems, the air flow must be so designed as to ensure that the air flows through the entire engine
room; there must be no short-circuit currents from the supply opening to the exhaust opening, thus ensuring
that there is adequate air circulation around the heat-producing components. If necessary, air ducts must be
installed which provide an air flow specifically targeted towards the individual components in the engine
room.
In order to minimize the radiated heat occurring in the engine room and thus the volume of air required,
silencers and exhaust pipes inside the engine room must be insulated. It is generally necessary to insulate
exhaust systems inside buildings.
In many cases, the combustion air for the engines is drawn from the engine room. This additional volume of
air must be taken into consideration when designing the supply air fans. Dependent on the design of the
system, the engine air filters could be located in areas in which the air has already undergone considerable
heating. In such cases, cold air must be conducted to the air filters via separate ventilation ducts.
Chapter_05 - Engine room ventilation.docx
02999408
Page 5 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 5.1a Ventilation systems
Pressurized system
2
1
3
4
5
6
8
7
5
3
Extraction system (not recommended)
2
1
3
4
5
9
7
1
Supply air
2
Exhaust air
3
Weather protection grille
4
Filter
5
Sound-proofing baffle
6
Supply air fan
7
Supply air louvre
8
Exhaust air louvre
9
Exhaust air fan
Chapter_05 - Engine room ventilation.docx
02999408
Page 6 / 16
8
5
3
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 5.1b Ventilation systems
System with circulating air temperature control (recommended)
10
11
2
1
3
4
5
6
8
7
5
3
Combined system (recommended)
2
1
3
4
5
6
9
7
1
Supply air
2
Exhaust air
3
Weather protection grille
4
Filter
5
Sound-proofing baffle
6
Supply air fan
7
Supply air louvre
8
Exhaust air louvre
9
Exhaust air fan
10
Circulating air duct
11
Circulating air louvre
Chapter_05 - Engine room ventilation.docx
02999408
Page 7 / 16
8
5
3
VD-S 2014-06 EN
Caterpillar confidential: none
5.2
Determining the demand for air
The required volume of air to be determined in order to design the ventilation system is composed of the
following individual requirements:
5.2.1
Combustion air requirement
If the combustion air is drawn from inside the engine room, it must be included in the layout of the ventilation
air system for the engine room. The combustion air temperature is one of the factors which influence the
location-dependent output achievable by the engine. It must therefore be guaranteed that the air temperature
in the area of the intake neither exceeds nor falls short of the value established to determine the locationdependent output.
5.2.2
Cooling air requirement for the engine and components
The radiation heat from the engine, the generator and / or other components in the engine room which
radiate heat, such as e.g. auxiliaries, including pumps, separators, heat exchangers, boilers, etc must be
discharged via the engine room ventilation system.
Components such as e.g. compressors which operate only intermittently are likely to be neglected in most
cases when determining the demand for cooling air.
Chapter_05 - Engine room ventilation.docx
02999408
Page 8 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
5.3
Determining the radiation heat
To determine the demand for air, the heat radiated from the engine and generator must be determined first.
5.3.1
Radiation from the engine
The heat levels radiated from the engine (QM) are always stated in the current data sheets.
5.3.2
Radiation from the generator
The heat levels radiated from the generator (QG) are always stated in the current data sheets.
5.3.3
Radiation from auxiliaries
The heat radiated from pipes, especially exhaust pipes, exhaust silencers, radiators and pump units can be
determined only with considerable effort. Experience indicates that this radiated heat equates to approx.
10 % of the heat radiated from the engine.
Q H = 0,1∗ Q M
QH
QM
5.3.4
[kW]
[kW]
heat radiated from auxiliaries
heat radiated from the engine
Radiation from the heat recovery unit
If components are installed in the engine room to utilize the heat energy, experience indicates that the heat
radiated from the cooling water and exhaust heat exchangers will be approx. 1.5 % of the respective
available heat as per the data sheet.
QWN
QKW
QAbg
Chapter_05 - Engine room ventilation.docx
02999408
[kW]
[kW]
[kW]
heat radiated from the heat recovery unit
engine cooling water heat
available engine exhaust heat
Page 9 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
5.3.5
Total radiated heat
The total radiated heat QS is the sum of the above-mentioned proportions:
Depending on ambient conditions, some of the radiated heat is dissipated via the engine room walls. This
proportion can be determined only with great difficulty owing to variable circumstances such as e.g. the
ambient temperature or the design of the engine room walls, and is therefore not taken into account.
5.3.6
Required ventilation air (excluding the combustion air for the engine)
Finally, the required air is a function of the total radiated heat, the permissible rise in air temperature in the
engine room and the specific heat capacity of the air:
mLerf
QS
∆T
cpL
[kg/h]
[kW]
[K]
[kJ/kgK]
required air mass flow for cooling
total radiated heat
permissible rise in temperature
specific heat capacity of the air (1.005 kJ/kgK)
The above equation calculates the required air mass flow. To determine the required volume flow, the
density of the air must be taken into account.
The density depends on the air temperature, the air pressure and the relative humidity. The required volume
flow is:
mLerf
VLerf
ρL
[kg/h]
[m³/h]
[kg/m³]
required air mass flow
required air volume flow
air density (e.g. 1.172 kg/m³ at 1002 mbar and 25°C)
The air pressure reduces as the geodetic altitude increases. The following table indicates pressures and
densities depending on temperature and the geodetic altitude.
The specified values apply to dry air. With moist air, the density falls as relative humidity rises. At a relative
humidity of 60 %, the drop in density can be up to 10 %.
Chapter_05 - Engine room ventilation.docx
02999408
Page 10 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
Table 5.2
Air pressure and air density at 25°C depending on geodetic altitude
Geodetic
Geodetic
Geodetic
height
Temperature
height
Temperature
height
Temperature
in m
25°C
in m
25°C
in m
25°C
mbar
kg/m³
mbar
kg/m³
mbar
kg/m³
0
1013
1.184
700
940
1.099
1800
835
0.976
100
1002
1.172
800
930
1.087
2000
817
0.955
200
991
1.159
900
920
1.075
2200
800
0.935
300
981
1.147
1000
910
1.064
2400
783
0.915
400
970
1.135
1200
890
1.041
2600
766
0.896
500
960
1.122
1400
871
1.019
2800
750
0.877
600
950
1.11
1600
853
0.997
3000
734
0.858
The densities can be converted for other temperatures by applying the following equation:
ρL(t) = ρL(25°C) *
(273 + 25)
(273 + t)
ρL(25°C)[kg/m³] air density at 25°C
[kg/m³] air density at temperature t
ρL(t)
t
[°C]
air temperature
In the case of systems which extract air from the engine room, on the supply side, the volume of air for
combustion in the engine must also be taken into account. Chapter 9.2 contains guide values for the specific
combustion air volume required for the individual engine models.
Chapter_05 - Engine room ventilation.docx
02999408
Page 11 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
5.4
Ventilation system components
The principal components of an engine room ventilation system are the weather protection grilles, silencers,
louvres, filters, air ducts and fans.
5.4.1
Weather protection grille
Weather protection grilles are installed on the outside wall of the engine room on both the supply and the
exhaust sides. They prevent rain and snow from entering into the ventilation system. A bird screen must also
be integrated into the weather protection grille to stop small animals, etc., from entering the system.
5.4.2
Sound-proofing baffles
Especially when systems are installed in residential areas or areas with restricted noise levels, significant
effort may be required in terms of measures to sound-proof the ventilation system. In such cases, soundproofing baffles must be fitted at the air supply and exhaust air sides. The principal data required for their
design are the air flow to be supported through the screen, the required level of sound-proofing and the
available duct opening. Thereafter, the depth of the baffles, their thickness and distance to each other are
determined.
The sound-proofing baffles must be designed by specialized companies, a task which calls for an
appropriate degree of care, as subsequent improvements are very costly if the required figures are not
achieved.
5.4.3
Louvres
Louvres are used to block the ventilation system link between the engine room and the external environment
when the system is at a standstill, especially in winter to prevent excessive cooling of the room. The louvres
are activated by electric drives which are controlled from the switchgear. In large systems, cool air can be
admitted to certain areas of the system by actively controlling the louvres. In winter, the engine room
temperature can be regulated by controlling the louvres.
5.4.4
Filter
Generally, filters should be installed in the ventilation system. This particularly applies to systems located on
industrial sites where the ambient air is heavily contaminated, e.g. landfills, coal mines, cement works,
metallurgical plants, etc. It is also applicable for systems located in regions where sand storms may occur.
Here the appropriate filter type must be selected according to the degree of the contamination. Heavy
particles are easily separated via inertia filters, whilst for example, where lightweight fibers occur,
Chapter_05 - Engine room ventilation.docx
02999408
Page 12 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
conventional fibrous filters must be fitted, which in view of the relatively large quantities of air, can achieve
considerable dimensions.
Filters as per DIN EN 779, Filter Class G3, are suitable. In case of specific requirements, a correspondingly
higher filter class needs to be chosen. An effective filter monitoring is necessary.
5.4.5
Ventilators
The ventilators are designed mostly as axial fans - rarely as radial fans - and must be of a suitable size
depending on the required quantity of air and pressure difference. To control the engine room temperature,
the volume of air being blown can be adjusted by using variable-speed fans or by switching individual fans
on and off.
Important: When using individual fans - particularly axial types -, it must be considered that standing fans
can be driven in reverse by a difference in pressure. With large fans, this can lead to problems.
When determining the size of the fans, the pressure reserve must be correctly selected with respect to the
components installed in the ventilation system, such as weather protection grilles, sound-proofing baffles,
louvres, etc., in order to ensure that the designed quantity of air is actually achieved.
5.4.6
Air ducts
Depending on the design of the system or the location of the engine room inside a larger building, e.g. in the
basement in the case of emergency power systems, the air to ventilate the engine room may have to be
brought in over longer distances. For this purpose, air ducts are employed. The pressure losses in these
ducts must be considered when designing the fans. To avoid condensation, outside air ducts should be
insulated.
Chapter_05 - Engine room ventilation.docx
02999408
Page 13 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
5.5
Planning notes
Having determined the required quantities of air, the openings and ducts must be so designed as to ensure
compliance with the following air speeds.
Table 5.3
Component
Air speed (m/s)
Supply / exhaust opening
1.5 - 2.5 / 2.5 - 4
Ventilation duct
10 - 20
Free flow in the engine room
0.3
Silencer section
6-8
Additional restrictions owing to flow noise must be taken into account.
5.5.1
Changes of air
The number of air changes also may be taken as a characteristic figure for a ventilation system.
It represents the number of air changes per hour, i.e. saying how often the complete volume of air in the
engine room is exchanged.
From experience, the number of air changes should not exceed 100 for big systems in buildings.
With extremely small engine rooms (e.g. containers) or at high ambient temperatures, the number of air
changes may rise up to 500 per hour.
5.6
Notes on operating ventilation systems for gas engines
The operation of the ventilation system may affect the pressure conditions at the combustion air intake of the
engine in such a way as to cause engine starting problems, or even making starting impossible. In such
cases, before starting the engine, only the supply and exhaust louvres must be opened. During start or
synchronization, the fans must operate without pressure peaks in the engine room, i.e. during the genset
starting phase, the fans must be operated with constant speed.
Chapter_05 - Engine room ventilation.docx
02999408
Page 14 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
5.7
Position of supply and exhaust openings
Supply openings must be positioned in such a way that the air drawn in is as clean and cool as possible.
The position for the outlet of exhaust air must be selected so that the function of other system components
such as cooling systems are not restricted by the warm exhaust air flow.
Chapter_05 - Engine room ventilation.docx
02999408
Page 15 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
Chapter_05 - Engine room ventilation.docx
02999408
Page 16 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
Power plants layout
Chapter 6
Engine cooling systems
06-2014
Caterpillar Energy Solutions GmbH Carl-Benz-Straße 1 D-68167 Mannheim Phone: +49(0)621 384-0 Fax: +49(0)621 384-8612
Caterpillar confidential: none
Contents
6.
Engine cooling systems ............................................................................................................. 3
6.1
Single-circuit cooling ..................................................................................................................... 3
6.2
Dual-circuit cooling ........................................................................................................................ 3
6.2.1
Gas engines .................................................................................................................................. 3
6.2.1.1
Example for the layout of cooling systems with gas engines ........................................................ 4
6.3
Reference values for the layout of cooling systems...................................................................... 7
6.3.1
Pressures ...................................................................................................................................... 7
6.3.1.1
Minimum pressure ......................................................................................................................... 7
6.3.1.2
Maximum pressure ........................................................................................................................ 7
6.3.2
Pump location................................................................................................................................ 7
6.3.3
Max. permissible temperature gradient ......................................................................................... 7
6.4
Cooling water system components ............................................................................................... 8
6.4.1
Cooling water heat exchanger ...................................................................................................... 8
6.4.1.1
Implementation of cooling water heat exchangers with emergency cooling by raw water ........... 9
6.4.2
Exhaust heat exchanger ............................................................................................................. 10
6.4.3
Cooling systems .......................................................................................................................... 10
6.4.3.1
Table cooler................................................................................................................................. 10
6.4.3.1.1
Table cooler control ..................................................................................................................... 11
6.4.3.1.2
Sandwich table cooler (not recommended) ................................................................................ 12
6.4.3.1.3
Installation and design of table coolers ....................................................................................... 12
6.4.3.2
Cooling towers............................................................................................................................. 14
6.4.4
Layout of components - Reserves .............................................................................................. 15
6.4.5
Chillers ........................................................................................................................................ 15
6.4.6
Cooling water pumps .................................................................................................................. 16
6.4.7
Expansion vessels ...................................................................................................................... 17
6.4.8
Temperature regulators ............................................................................................................... 17
6.4.9
Cooling water monitoring group .................................................................................................. 17
6.4.10
Cooling water preheating ............................................................................................................ 17
6.5
Pipes ........................................................................................................................................... 18
6.6
Ventilation of the cooling systems ............................................................................................... 18
6.7
Quality of the coolant .................................................................................................................. 18
6.8
The heating circuit ....................................................................................................................... 19
6.9
Coolant in the heating circuit ....................................................................................................... 19
6.10
Heating circuit design regulations ............................................................................................... 22
6.11
Emergency/dump cooling circuit ................................................................................................. 22
Chapter_06 - Engine cooling systems.docx
02999408
Page 2 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
6.
Engine cooling systems
The coolants employed have water as a cooling medium and from an engine perspective must be closed
systems.
The genset engines essentially feature two types of cooling: single-circuit and dual-circuit.
The layout must follow the illustrations included hereinafter. Deviations require approval in writing.
6.1
Single-circuit cooling
The coolant of gas engines with a single-circuit passes through the lubricating oil cooler, the mixture coolers
and the engine, i.e. the total heat is discharged in one single circuit.
6.2
Dual-circuit cooling
Along with an engine water cooling circuit, engines with a dual-circuit also have a low-temperature
mixture/charge air cooling circuit. As the temperature level in the mixture cooling circuit is comparably low,
the heat from those circuits is normally discharged to the environment via fan coolers or cooling towers with
a separate circuit.
6.2.1
Gas engines
All gas engines of the series TCG 2016 C, TCG 2020 and TCG 2032 are equipped with a two-stage mixture
cooler on the engine. The high temperature stage is integrated into the engine cooling circuit and the heat
from low temperature stage is discharged in the external mixture cooling circuit.
For the engines TCG 2032, the lube oil cooler is not mounted on the engine and has to be installed in zhe
external cooling system. Depending on the layout of the system as a whole, it can be installed on the water
side in the engine circuit, in the low temperature mixture circuit or in the heating water circuit. Please see
also Chapter 8.2.
Chapter_06 - Engine cooling systems.docx
02999408
Page 3 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
6.2.1.1
Example for the layout of cooling systems with gas engines
The heat absorbed by the cooling water is transferred via a heat exchanger to be provided by the client for
use in a heating water circuit or other technical process. If there is no means of heat recovery to hand, it
must be discharged into the atmosphere via a radiator or cooling tower. It is not permitted to run the cooling
tower water straight through the engine! A decoupling heat exchanger or closed cooling tower must be
provided.
The inlet temperature of the cooling water is generally controlled, whereby dependent on the design of the
system, the temperature regulator may be installed directly in the engine circuit or in the heating circuit.
Electric pumps are always used as cooling water pumps, the fine adjustment of the cooling water flow being
achieved via an adjustable throttle. The expanding volume is accommodated in a diaphragm expansion
vessel, the level in the cooling water circuit being monitored by the so-called monitoring group. Integrated in
this group are a safety valve, venting and blow-off valves and the low-water level safety device.
As with the engine circuit, the mixture circuit is equipped with an electrical circulating pump, diaphragm
expansion vessel, monitoring group and temperature regulator.
With multi engine plants, it is not permitted to connect the jacket water circuits together, because the
definitive regulating of each HT-inlet-temperature cannot be guaranteed.
Fig. 6.1 shows a cooling system without heat utilization.
Fig. 6.2 shows a cooling system with heat utilization.
Chapter_06 - Engine cooling systems.docx
02999408
Page 4 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 6.1 P&I flowchart for system without heat utilization
A
A
Combustion gas
ASD
Exhaust silencer
1
Genset
DV
Throttle valve
2
Gas control line
EVH
Electric pre-heating
5
Engine cooling system
FU
Frequency converter
6
Mixture cooling system
KAT
Catalyst
TK
Table cooler
Chapter_06 - Engine cooling systems.docx
02999408
Page 5 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 6.2 P&I flowchart for system with heat utilization
A
A
Combustion gas
ASD
Exhaust silencer
1
Genset
AWT
Exhaust heat exchanger
2
Gas control line
BK
Bypass flap
4
Heat utilization
DV
Throttle valve
6
Mixture cooling system
EVH
Electric pre-heating
7
Emergency/dump cooling circuit
FU
Frequency converter
KAT
Catalyst
KWT
Cooling water heat exchanger
NK
Emergency cooler
TK
Table cooler
Chapter_06 - Engine cooling systems.docx
02999408
Page 6 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
6.3
Reference values for the layout of cooling systems
6.3.1
Pressures
All pressures for fluids are generally indicated in bar overpressure.
All heat exchangers, pumps and table coolers should be designed as standard for 10 bar, the lube oil heat
exchanger of the TCG 2032 for 16 bar.
6.3.1.1
Minimum pressure
The minimum required operating pressure at the engine outlet is 1.5 bar. All gas engines have a monitoring
of the pressure at the cooling water outlet in the cooling circuit. If the pressure falls below 1.5 bar, there is a
warning; if it falls below 1.0 bar, the engine is switched off. The diaphragm expansion vessels should be
dimensioned in such a way that a minimum pressure of 1.5 bar is obtained when the system is stopped.
6.3.1.2
Maximum pressure
The maximum permissible pressure at the engine outlet is 2.5 bar. The safety valve mounted close to the
engine outlet opens at approx. 3 bar.
6.3.2
Pump location
If there are high pressure losses as a result of external resistance in the engine circuit (heat exchangers,
regulating valves, etc.), the pump must be installed on the outlet side of the engine, otherwise the maximum
permitted pressure on the outlet side or the minimum pressure is out of limit.
6.3.3
Max. permissible temperature gradient
If the inlet temperature of the engine, mixture cooling and emergency cooling circuit as well as the inlet
temperature of the heating circuit are regulated by the customer, the max. temperature modification speed of
1 K/min needs to be maintained.
In order to maintain a stable behavior of the temperature control for the engine cooling circuits, it is
necessary to minimize the influence of disturbing parameters from external systems.
It is essential that all coolers and pumps have an adequate reserve in capacity and flow rate.
Chapter_06 - Engine cooling systems.docx
02999408
Page 7 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
6.4
Cooling water system components
6.4.1
Cooling water heat exchanger
Reserve capacity and surface area reserve according to Table 6.3 must be observed. The specified engine
inlet and outlet temperatures must be observed (see engine data sheet).
In order to keep the heat exchangers in a good condition from an economic point of view, the logarithmic
temperature difference should not be lower than 4K. The temperature difference between in- and outlet
(primary / secondary circuit) should be greater than 2K (see also Fig. 6.4).
In the case of liquid coolants, plate heat exchangers or pipe radiators are used on the secondary side. Plate
heat exchangers are highly compact in construction and easy to clean. Their performance can, within certain
limits, be varied at a later date by altering the number of plates.
Fig. 6.3 Logarithmic temperature difference
ϑ'1
∆ϑA
ϑ''2
∆Θ =
A 1
Medium
ϑ''1
B 2
Medium
∆ϑE
ϑ'2
ln
∆Θ
(∆ϑA − ∆ϑE )
∆ϑA
ln
∆ϑE
= natürlicher Logarithmus
A
Medium
= logarithmische
Temperaturdifferenz
1
B
Medium 2
ln
Natural logarithm
∆θ
Logarithmic temperature difference
Example
A cooling water heat exchanger in the heating circuit has the following design data:
Engine side:
Heating circuit side:
This yields:
Inlet temperature ϑ'1:
90°C
Outlet temperature ϑ''1
84°C
Inlet temperature ϑ'2:
70°C
Outlet temperature ϑ''2
85°C
∆ϑA:
(90°C-85°C)
=5K
∆ϑE:
(84°C-70°C)
= 14 K
(∆ϑA-∆ϑE):
(5-14) K
= -9 K
ln(∆ϑA/∆ϑE):
ln(5/14)
= -1.0296
∆Θ:
(-9 K/-1.0296)
= 8.74 K
This plate heat exchanger therefore complies with the minimum requirements ∆Θ ≥ 4 K, ∆ϑA and ∆ϑE ≥ 2 K.
Chapter_06 - Engine cooling systems.docx
02999408
Page 8 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
6.4.1.1
Implementation of cooling water heat exchangers with emergency cooling by raw water
For emergency cooling systems with raw water cooling via heat exchanger, the temperature control for the
emergency cooler outlet temperature should be arranged in the primary circuit (see Fig. 6.5a).
With this design, hot water flow over the emergency cooler will only occur when emergency cooling is
requested. The water outlet temperature on the secondary (raw water) side of the emergency cooling heat
exchanger must be kept below 45° C in order to prevent sedimentation of lime.
In any case, the temperature control should not be as per Fig. 6.5b. In this case, there is always hot water
flow through the emergency cooling plate heat exchanger. In the case of no or low water flow rate on the
secondary side, the raw water temperature in the heat exchanger will rise and reach the temperature level of
the hot water side. The plate heat exchanger will become calcified over time.
The temperature gradient on the raw water side must not exceed +/- 1 K/min.
For the actuators of the temperature control valves, the I/O controller of the TEM-system has a digital output
+/- (24V signal) for opening/closing the valve. In order to achieve a reasonable control behavior, the running
time of the valve from limit position open to limit position close and vice versa should be in the range of 1
minute.
Fig. 6.4a Correct layout
Fig. 6.4b Incorrect layout
C
A
C
A
NK
NK
B
B
A
Engine cooling circuit
B
Primary side (engine / heating circuit)
C
Secondary side
NK
Emergency cooler
Chapter_06 - Engine cooling systems.docx
02999408
Page 9 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
6.4.2
Exhaust heat exchanger
Reserve capacity and surface area reserve according to Table 6.3 must be observed. For the setting of the
exhaust gas cooling temperature, the amount of H2S and sulfur in the combustion gas must be considered.
This setting is to avoid acid condensate in the exhaust which will damage the exhaust heat exchanger.
Recommended exhaust gas cooling temperatures:
Natural gas:
≥ 120 °C
Sewage gas:
≥ 150 °C
Landfill gas and NAWARO gas:
≥ 180 °C
The minimum volume flow specified by the manufacturer must be complied with in order to guarantee
sufficient cooling of the exhaust heat exchanger. After stopping the genset, it is necessary to keep the
cooling water pump running for a while in order to discharge the accumulated heat from the exhaust heat
exchanger. This function is part of the TEM system.
6.4.3
Cooling systems
Each cooling system must be capable of discharging the generated heat even with maximum
ambient temperatures.
Where air is used as the secondary side coolant, fan coolers and cooling towers are employed.
Up to a certain size, fan coolers can be implemented as front coolers (vertically arranged cooling network);
larger systems take the form of table coolers. In the case of front cooling systems, the fans push the air
through the cooling network; with table cooling systems, the air is pulled through the cooling network.
The occasionally high noise level of the fans must be taken into account when installing systems in
residential areas. Either slow-moving fans can be used here, or special sound-proofing measures will be
needed.
6.4.3.1
Table cooler
Reserve capacity and surface area reserve according to Table 6.3 must be observed. Where there is a risk
of contamination resulting from the environment (e.g. leaves, pollen, sand, carbon dust etc.), an appropriate
fin spacing must be selected. An enlarged space between the fins prevents the cooler from becoming
clogged too fast. Otherwise the heat can not be discharged anymore due to the deterioration of the heat
transfer.
In the case of air coolers, because of the risk of freezing, anti-freeze must be added to the cooling water.
When installing the table cooler, it must be ensured that there is sufficient space beneath to allow a proper
air flow. Where several coolers are installed, there must be an adequate spacing between them to prevent a
short-circuit.
Chapter_06 - Engine cooling systems.docx
02999408
Page 10 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
If the table coolers are arranged at a level higher than 15 m above the engine level, it is necessary to install
a heat exchanger in order to keep the pressure level in the engine in the permissible range mentioned in
section 6.3.1.2.
6.4.3.1.1 Table cooler control
The capacity of table coolers is influenced both by the ambient temperature and the number of running fans
or the fans' speed. When controlling the table cooler capacity via the number of operating fans, we talk about
step control; for control via the speed of the fans via FU control. The FU control offers the advantage of
continuous adaptation of the cooler capacity to thermal output which should be discharged. For the different
engine types, the fan control for the table coolers in the different cooling circuits should be as per Table 6.2.
For the discharge of the heat in the mixture cooling circuit, and/or engine/emergency cooling circuit, the
following assignment must be ensured for the gas engines.
Table 6.2:
Cooler GK
Cooler MK
Cooler NK
TCG 2032
FU controlled
FU controlled
FU controlled
TCG 2020
FU controlled
FU controlled
FU controlled
TCG 2016 C
FU controlled
≥ 6 steps
≥ 6 steps
FU = frequency converter; GK = mixture cooling circuit; MK = engine cooling circuit ; NK = emergency
cooling circuit;
In summary, the heat in the mixture cooling circuit must be discharged via frequency controlled table coolers
for all gas engine types.
For the engine type TCG 2016, the engine cooling circuit (MK) and the emergency cooling circuit (NK) may
be equipped with at least a 6-step cooler (6 fans). Less than 6 steps is not permissible. Alternatively, the FU
controlled variant is recommended.
With extremely low ambient temperatures, i.e. regularly low temperatures below -15°C, all cooling circuits
must be FU controlled.
By this requirement, the boundary conditions for proper operation of the gas engines can be kept for a wide
range of altering ambient conditions.
Chapter_06 - Engine cooling systems.docx
02999408
Page 11 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
6.4.3.1.2 Sandwich table cooler (not recommended)
One special design of the table cooler is the sandwich table cooler. With this fan cooler type, there are two
cooling stages arranged one upon the other and the air supply is provided by common fans. The first stage is
the LT-stage (LT=Low Temperature), the second stage the HT-stage (HT=High Temperature). Normally, the
heat from the mixture cooling circuit is discharged in the LT-stage and the heat from the engine in the HTstage. This cooler type is applied for systems with power generation, because, only for this application, the
load on both stages is uniform for the whole power range of the engine. For CHP systems, normally the HTstage of a sandwich table cooler is used for emergency cooling purposes. With heat utilization (no heat
rejection via emergency cooler), the speed of the common fans is defined by the heat to be discharged from
the mixture cooling circuit. For this mode of operation, the emergency cooler (HT-stage of the sandwich table
cooler) might be ineffectively oversized and, as a consequence, the temperature control for the system might
become unstable. Therefore the use of sandwich coolers is not agreed for CHP systems.
6.4.3.1.3 Installation and design of table coolers
Reserve capacity and surface area reserve according to Table 6.3 must be observed. Where there is a risk
of contamination resulting from the environment (e.g. leaves, pollen, sand, carbon dust etc.), an appropriate
fin spacing must be selected. An enlarged space between the fins prevents the cooler from becoming
clogged too fast. Otherwise the heat cannot be dissipated anymore due to the worsening of the heat
transfer.
In the case of air coolers, because of the risk of freezing, anti-freeze must be added to the cooling water.
When installing the table cooler, it must be ensured that the installation height above the ground is sufficient
to allow a proper air flow. The free inflow area for the air supply must correspond at least to the floor space of
the table cooler. Where several coolers are installed, the short-circuiting of air flows must be prevented.
Table coolers should therefore be installed either flush next to each other or with sufficient space between
them. When doing so, erect the table coolers so that the required inflow area for the air supply is ensured at
the free sides.
Chapter_06 - Engine cooling systems.docx
02999408
Page 12 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
Abb. 6.5a Installation of table coolers
1
_A_
_A1_
2
A1 + A2 > A
1
Floor space odf an individual table cooler A
2
Inflow areas for cooling air A1 and A2 (niot visible) for this table cooler
Abb. 6.5b Installation of table coolers
3
_A_
A2
A4
_A1_
4
A1 + A2 + A3 + A4 > A
3
Floor place for all table cooler A
4
Inflow areas for cooling air A1, A2, A3 (nit visible and A4
Chapter_06 - Engine cooling systems.docx
02999408
Page 13 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
6.4.3.2
Cooling towers
Cooling towers exploit the evaporation cooling effect and are used in both closed and open forms. With an
open cooling tower, part of the circulating cooling water (approx. 3 %) evaporates. The volume of water lost
to evaporation must always be replenished. In addition, a blow-down device is to be provided in order to
avoid an undue increase in concentration of dissolved salts in the supplementation water in the cooling
tower.
Since all corrosion- and/or frost-protected engine cooling circuits require the use of treated water, these
cooling circuits may only be connected to an open cooling tower via a decoupling heat exchanger.
With open cooling towers, it is necessary to clean the decoupling heat exchanger more often because the
open water circuit favors the formation of algae polluting the heat exchanger. The thicker the layer of algae in
the heat exchanger, the worse the heat transfer. No more heat is dissipated in the circuits to be cooled.
In the case of closed cooling towers, the cooling water tubes are sprayed with water, causing the water to
evaporate and thereby cooling the medium in the tube. Since there is no loss of water in the cooling circuit
itself, closed cooling towers can be linked directly to the engine cooling circuit. The most important design
parameters for economic cooling tower operation are the air temperature and, above all, the humidity.
Chapter_06 - Engine cooling systems.docx
02999408
Page 14 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
6.4.4
Layout of components - Reserves
In the case of the layout of components for the cooling water system, the reserves must be observed. The
heat amounts given in the data sheets are nominal values, which do not consider tolerance for possible
increased fuel consumption. In the following table, the reserves for capacity and area are specified which
have to be considered for the design.
Tab. 6.3
Components
Reserve capacity [%]
Surface area reserve [%]
Heat exchanger water/water
15
5
Heat exchanger water/oil
15
5
Ventilator cooler
15
5
Exhaust heat exchanger
7
10 for natural gas
0 for biogas, sewage gas
and landfill gas etc.
Example:
In a data sheet for a TCG 2020 V20, a cooling water heat of 1000 kW is specified.
The cooling water heat exchanger must be designed for a capacity of 1150 kW with an area reserve of 5%.
6.4.5
Chillers
Chillers should not be directly integrated in the engine cooling circuit. In case of leakages, the engine cooling
water might be contaminated by Li Br. This is prevented by the coupling heat exchanger in the engine
cooling circuit.
There are cases in which the required water-temperature level of the chiller can only be achieved via a direct
integration in the cooling water circuit of the engine. In this case, one has to comply with the following
conditions:
•
The requirements with respect to the quality of the cooling water of the engine, corrosion
protection or freezing protection have to be met
•
The cooling water additives which are released by the manufacturer of the engines need to
be released for the chiller as well
•
In case of leakages in the heat exchanger of the chiller, both the cooling system and the
engine can be damaged. The manufacturer of the engine accepts no liability for those
damages.
Chapter_06 - Engine cooling systems.docx
02999408
Page 15 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
6.4.6
Cooling water pumps
Cooling water pumps with fixed speed which are driven by electric motors are installed in all series.
In the case of systems with heat recovery from the cooling water, to achieve the maximum efficiency and
component service life, the engine inlet temperature and outlet temperature must be exactly maintained. In
order to more accurately and individually coordinate the required pump capacity and the lift needed for each
installation, electric pumps are used for these systems. The heat reserve capacities as mentioned already in
6.4.1, 6.4.2 and 6.4.3.1 must be considered by an increased volume flow, whilst maintaining the design
temperatures as per the genset data sheet. When determining the size of the pump, the increased volume
flow according to the reserve and the associated higher pressure losses must be taken into account. The
exact setting of the cooling water flow rate is done by manual control valves/throttles. The adjustment of
flows is done with regard to the design temperature differences for the individual cooling circuits.
For the engine cooling circuit, the mixture cooling circuit and for the cooling circuits incorporating an exhaust
heat exchanger, it is absolutely necessary to maintain a constant flow rate, whereby the flow rate must not
fall below the given minimum flow rate. Otherwise the engine or the exhaust heat exchanger might overheat
or become damaged. Therefore, it is not allowed to use frequency-controlled water pumps in those circuits.
Chapter_06 - Engine cooling systems.docx
02999408
Page 16 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
6.4.7
Expansion vessels
Diaphragm expansion vessels are provided in the cooling system to balance the volume expansion as the
cooling water heats up.The expansion in volume as the cooling water heats up is compensated for by
compressing a gas bubble. The resulting static increase in pressure in the system is dependent on the size
of the expansion vessel selected. Expansion vessels must be connected on the inlet side of the pump.
Where a diaphragm expansion vessel is used, the cooling water circuit must be protected against
overpressure by a safety valve. In the engine and mixture cooling circuit, safety valves with a response
pressure of 3.0 bar are generally used. The installation site should be as close as possible to the engine
cooling water outlet.
When designing the expansion vessel, the static pressure, the flow pressure loss between the safety valve
and the expansion vessel must be considered, as must the water supply. The water supply in the engine and
mixture cooling circuit must equate to 10-15 % of the cooling water content, subject to a minimum of 20 liters.
6.4.8
Temperature regulators
The temperature regulators are electronic regulators with electric actuators.
Electronic temperature regulators can control the set temperature at a constant setpoint value; the regulating
variable may be located in an external circuit. Precise temperature regulation is needed, especially in the
case of systems where heat is recovered and, at the same time, high overall efficiency is called for.
The nominal diameters of the temperature regulators must be determined so as to ensure that, at the
respective rate of flow, the pressure loss via the regulator lies within a range of 0.2-0.5 bar in straight flow
(bypass closed).
6.4.9
Cooling water monitoring group
There are three functions integrated into the cooling water monitoring group: security against overpressure,
venting the cooling circuit and cooling water level monitoring. The cooling water monitoring group must be
installed at the highest point in the cooling water system directly after the engine and the vent line from the
engine TCG 2016 C must run to the monitoring group. For engines of the series TCG 2016 C, a ventilation
line must be fed to the monitoring group.
In addition, it is also necessary to monitor the flow of cooling water through the engine via differential
pressure.
6.4.10
Cooling water preheating
Gas engine gensets must, as a matter of principle, be equipped with a cooling water preheating to ensure
reliable engine starting. For the engine series TCG 2032, complete preheating gensets with a pump, heat
exchanger with heating elements and electrical control are used as a preheating system for the engine water
Chapter_06 - Engine cooling systems.docx
Page 17 / 24
VD-S 2014-06 EN
02999408
Caterpillar confidential: none
and oil. For the series TCG 2016 and TCG 2020, a preheating system has also been developed which is
installed in the cooling water line ahead of the engine. The electrically driven cooling water pump is used for
circulation. It is controlled via the TEM system.
6.5
Pipes
The pipes for the cooling water systems must, on principle, be implemented using seamless steel tube.
Galvanized steel or copper pipes are not permissible.
Please also see the relevant notes in Chapter 20.
When determining the size of the pipes, the following guide values must be observed:
•
Flow speed, system-side pipework:
•
The economic speed for fluids in pipes from DN 50 to DN 300 lies in the range of 2 m/s
•
For the design volume flow, the flow pressure loss in the cooling circuit must be lower than
< 3.5
m/s
the discharge pressure head of the pump being used
Piping should be kept short and laid without tension. All components must be firmly fixed in place and, if
necessary, vibration-decoupled. Sharp pipe elbows and reducers must be avoided. The materials used for
seals, rubber sleeves and hoses must be resistant to anti-corrosives and to the external effects of fuel and
lubricating oil.
6.6
Ventilation of the cooling systems
The cooling water system must be constantly vented. In systems with balance tanks, permanently rising vent
lines must be run from below to vent into the balance tank. The cooling water system must be constantly
vented. In plants with diaphragm expansion vessels, the system is vented via the vent valve integrated into
the monitoring group or a vent valve which is installed in the pipe. The cooling water pipes must be run in
such manner as to avoid air becoming trapped in the system; if necessary, permanent vents or vent cocks
need to be provided at the systems high points.
For a safe operation of the cooling system without any pressure surges, it is necessary that the system is
ventilated properly and that the air bubbles which might have formed are automatically exhausted.
In systems with balance tanks, the balance line must run constantly downwards with the minimum resistance
to the inlet side of the circulating pump.
6.7
Quality of the coolant
For liquid cooled engines, the coolant must be treated and monitored, as otherwise damage may arise due to
corrosion, cavitation or freezing.
Chapter_06 - Engine cooling systems.docx
02999408
Page 18 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
The Technical Circular for coolant contains comprehensive details of water quality, anti-corrosives and
antifreeze. There is also a list of approved coolant additives from reputable manufacturers. No substances
may be used other than those which are approved.
6.8
The heating circuit
In the case of systems with heat recovery, the heat generated by the engine is transferred to the heating
circuit. The principal components integrated into the heating circuit on the module side are the cooling water
heat exchanger, the exhaust heat exchanger, the circulating pump, the throttle valve and the three-way
temperature regulating valve. The heat output from the engine contained in the cooling water and the
exhaust gas, and the associated flow rates and temperature differences have been established for the
engines in their respective operating modes. The capacity of the circulating pump in the heating circuit is
determined by the temperature difference between the flow and return in this circuit. When determining the
size of pump, the increased volume flow according to the reserve and the associated higher pressure losses
must be taken into account. See also Fig. 6.2 System boundary 4.
The heating circuit must also include a pressure keeping device; generally this is arranged as a collecting
system in the return flow.
The heating circuit should be designed in such a way that, independent of the adjusting and regulating
processes, the flow, which is described on the heating network section (Chapter 6.7, part 1), has to be
ensured without fluctuation of differential pressure (hydraulic disconnection). Heat storage tanks are
particularly suited for this purpose (see Fig. 6.6). They decouple the heat generating side from the heat
utilizing side.
6.9
Coolant in the heating circuit
The heating circuit is a closed circuit. In this circuit too, a certain water quality must be maintained. Oxygen,
chlorides and hydrogen sulfide in particular promote corrosion in the system. Salts in solution are
precipitated as crystals at high heat transfer locations, leading to deposits, which have a negative impact on
heat transfer (e.g. boiler scale). Especially in the exhaust heat exchanger because of the high water
temperatures at the heat transfer points, there is a risk of crystalline deposits.
These phenomena can be reduced by adding inhibitors to the heating water medium and by selecting
suitable materials for the heat exchangers. This must be investigated for each individual application.
The minimum water quality for heating circuits is summarized in the Technical Circular for cooling water. If
the exhaust heat exchanger is installed in the heating circuit and if the water quality in the heating circuit
does not comply with the figures stated in the Technical Circular, it is necessary to provide a separate
decoupling circuit with an additional heat exchanger between the exhaust heat exchanger and heat
consumer. Now the exhaust heat exchanger is protected against damage from contamination in the heating
water.
Chapter_06 - Engine cooling systems.docx
02999408
Page 19 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 6.6 P&I flowchart with hydraulic decoupling of heat generation from heat utilization
Chapter_06 - Engine cooling systems.docx
02999408
Page 20 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
Legend for P&I flowchart in Fig. 6.6
1
Genset
2
Gas control line
4
Heat utilization
6
Mixture cooling system
7
Emergency cooler
8
Lube oil supply
13
Boiler
ASD
Exhaust silencer
AWT
Exhaust heat exchanger
DV
Throttle valve
KAT
Catalyst
KWT
Cooling water heat exchanger
NK
Emergency cooler
TK
Table cooler
Chapter_06 - Engine cooling systems.docx
02999408
Page 21 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
6.10
Heating circuit design regulations
The regulations for water heating systems and steam boiler systems also apply to the design of the heating
circuit.
These are inter alia:
DIN EN 12828
Heating systems in buildings (for max. operating temperature to 105°C)
When planning or designing CHP systems requiring temperature monitoring/limiting
temperatures above 110°C, it is recommended to consult the local authority responsible
for the certification of the system. The favored scope of necessary equipment and the
setting of the inspection periods (German Health and Safety at Work Regulations) can be
agreed between both parties.
DIN EN 12953
Shell boilers
TRD 604 Sheet 1 Operation of steam boiler systems with Group IV steam generators without constant
supervision
TRD 604 Sheet 2 Operation of steam boiler systems with Group IV hot water generators without constant
supervision
TRD 702
Steam boiler systems with Group II hot water generators
Depending on the flow temperature in the heating water circuit (90°C, 100°C or 120°C), the appropriate
sensors must be installed to protect and maintain the security chain for the exhaust heat exchanger and to
secure the heating circuit. The signals from the sensors are processed by the TEM system.
An approval has been granted by the TÜV for the monitoring systems (sensors plus processing of signals via
the TEM system), with the result that the individual inspections to be carried out on each system by the TÜV
can be completed quickly.
6.11
Emergency/dump cooling circuit
In systems where the dispersal of heat via a heating circuit is not always guaranteed, yet the electrical output
of the system must still be available, the heat generated by the engine is dissipated via the so-called
emergency cooling circuit. The arrangement of the emergency cooling circuit depends on the system design.
Depending on the arrangement of the exhaust heat exchanger or the lube oil cooler for systems with TCG
2032 engines, the emergency cooling must ensure a safe heat discharge from those components even if
there is no heat discharge via the heat utilization of the system.
Normally, the heat is dispersed via an emergency cooling heat exchanger integrated into the heating circuit
and linked to a table cooler or cooling tower. See Fig. 6.7. When determining the size of pump, the increased
volume flow according to the reserve and the associated higher pressure losses must be taken into account.
Chapter_06 - Engine cooling systems.docx
02999408
Page 22 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 6.7 Emergency cooling with coupling heat exchanger in the heating circuit
AWT
Exhaust heat exchanger
KWT
Cooling water heat exchanger
NK
Emergency cooler
TK
Table cooler
If the heat produced by the engine cooling water, the exhaust and lube oil (for 2032) is transferred to the
heating circuit by one common heat exchanger, the emergency cooler can be implemented directly into the
engine cooling circuit without an additional coupling heat exchanger. See Fig. 6.8.
Fig. 6.8 Direct implementation of emergency cooling system into the engine circuit
Chapter_06 - Engine cooling systems.docx
02999408
AWT
Exhaust heat exchanger
KWT
Cooling water heat exchanger
TK
Table cooler
Page 23 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
Chapter_06 - Engine cooling systems.docx
02999408
Page 24 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
Power plants layout
Chapter 7
Fuel system
06-2014
Caterpillar Energy Solutions GmbH Carl-Benz-Straße 1 D-68167 Mannheim Phone: +49(0)621 384-0 Fax: +49(0)621 384-8612
Caterpillar confidential: none
Contents
7.
Fuel system.................................................................................................................................. 3
7.1
Gaseous fuels ............................................................................................................................... 3
7.1.1
Methane number ........................................................................................................................... 3
7.1.2
Accompanying gases / materials .................................................................................................. 3
7.1.3
Water vapor, hydrocarbon vapors, dust in the gas ....................................................................... 4
7.1.4
Gas cool drying ............................................................................................................................. 4
7.1.5
Activated carbon filter .................................................................................................................... 5
7.1.6
Mixture treatment .......................................................................................................................... 7
7.1.7
Gas control line ............................................................................................................................. 9
7.1.7.1
Pre-pressure control line ............................................................................................................. 10
7.1.7.2
Dual gas operation ...................................................................................................................... 11
7.1.7.3
Combustion gas system with multi-engine systems and high gas pressures ............................. 11
7.1.7.4
Notes on installing gas control lines ............................................................................................ 12
7.1.7.5
Blow-off and breather lines for gas control lines ......................................................................... 12
7.1.8
Gas mixer .................................................................................................................................... 13
7.1.9
Throttle valve ............................................................................................................................... 15
7.1.10
Startup of biogas systems ........................................................................................................... 15
7.2
Notes on installing and maintaining gas systems ....................................................................... 15
7.2.1
Regulations ................................................................................................................................. 15
7.2.2
Servicing and maintenance ......................................................................................................... 16
Chapter_07 - Fuel system.docx
02999408
Page 2 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
7.
Fuel system
7.1
Gaseous fuels
The engines operated by combustible gas work as 4-stroke engines following the Otto cycle. The gas-air
mixture is fed to the combustion chamber; combustion is then initiated by external ignition via a spark plug.
The fuel gases mainly used are natural gas, sewage gas, landfill gas and biogas. Because of their low heat
value compared to natural gas, sewage gas, landfill gas and biogas are also known as weak gases. The
principal constituents of these gases are hydrocarbons (methane, ethane, butane and propane) as well as
nitrogen and carbon dioxide.
The minimum combustion gas characteristics must be maintained according to the data given in the
Technical Circular for fuel gas.
Operating engines with special gases such as flare gas, mine gas etc. is subject to technical approval from
the head office.
7.1.1
Methane number
An important characteristic determining the use of a gas in a gas engine is its knock resistance, i.e. the gas
mixture must not self-ignite before ignition, nor must any self-ignition effect cause it to explode suddenly after
ignition.
Its methane number gives the knock resistance of a gas. This indicates when a combustion gas in a test
engine shows the same knock characteristics as a comparable mixture of methane and hydrogen. To ensure
knock-resistant operation with different gases to be used, the methane number must comply with the data
sheets. If a gas analysis is available, the respective methane number can be evaluated by the head office. A
job card describes the procedure on how to take gas samples. This job card is included in each operating
manual.
7.1.2
Accompanying gases / materials
Sewage gases and biogases are primarily accompanied by a proportion of hydrogen sulfide. Landfill gases
are mainly contaminated with chlorinated and fluorinated hydrocarbons. As a result, during combustion,
sulfuric, hydrochloric and fluoric acids are produced, which damage the motor, the service life of the oil and
the entire exhaust gas system. In order to avoid damages to the external exhaust system because of acid
temperatures falling below dew point, the exhaust temperatures should not fall below 180°C. With exhaust
temperatures below 180°C, it is necessary to provide suitable treatment of the combustion gas (e.g.
desulfurization).
Chapter_07 - Fuel system.docx
02999408
Page 3 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
Additionally, landfill gases are often contaminated with gaseous siloxanes. During the combustion in the gas
engine, those landfill gases become silicon dioxide and form deposits, which leads to premature wear in the
motor, pistons and cylinder liners. A gas treatment is necessary here.
The minimum combustion gas characteristics are outlined in the Technical Circular for combustion gas.
These data apply only to the use of gases in gas engines. If systems are to be equipped with catalytic
converters in the exhaust system, in addition to the minimum characteristics specified for the engine, further
restrictions must be taken into account depending on the catalytic procedure selected. In general, a gas
treatment has to be planned.
The gases to be used must be carefully tested for pollutants and assessed on the basis of the respective
limit values.
7.1.3
Water vapor, hydrocarbon vapors, dust in the gas
In order to exclude condensation in the engine under all operating conditions which may arise (including cold
starting), the water vapor content in the engine must be limited. The relative humidity of the combustion gas
must not exceed 80% for the lowest gas temperature. Higher humidity levels require approval.
Vaporized higher hydrocarbons lead to a reduction in the methane number. When these vapors condense in
the intake tract, the result is heterogeneous droplet combustion. There is a risk of knocking combustion.
Also, it is no longer possible to comply with the exhaust emissions cleansing limits.
The dust content (particle size 3-10 μm) of the gas is limited to 10 mg/m³nCH4 in the combustion gas. Higher
dust contents of this grain size lead both to the possibility of deposits in the combustion chamber and to
increased contamination of the lubricating oil, which causes increased wear.
7.1.4
Gas cool drying
The combustion gas must be dried for all biogenic special gases and all gases that exceed the limit of 80%
relative humidity. A technically effective variant of this is gas cool drying. Biogas (from renewable raw
materials), sewage gas and landfill gas are generally saturated with moisture and hence too damp for direct
use. As a side effect of the gas cool drying, pollutants are also washed out of the gas. In particular, watersoluble substances (e.g. ammonia) can be found in the condensate.
The minimum setup for gas cool drying comprises a gas cooling system, a drop separation and a heating of
the gas. The gas cooling system, mostly equipped with a cold water chiller, lowers the dew point and hence
the absolute moisture content in the combustion gas. The drop separation must ensure that small drops that
are carried away by the gas flow are also separated and do not vaporize again in the reheating phase.
Although the reheating does not change the absolute humidity, it does change the relative humidity. The gas
can only be dried in this step. The reheating comprises either a water-heated gas heater, a gas-gas heat
exchanger, which utilizes the heat of the gas entering the cooling system, or the heat input of a compressor.
Chapter_07 - Fuel system.docx
02999408
Page 4 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
Other structures are possible if the function is ensured. Gas lines laid in the ground are not really advisable
in the power classes in which the genset manufacturer offers products, because they are not usually suitable
for cooling the gas throughout the year.
7.1.5
Activated carbon filter
Doped/impregnated activated carbon has proven to be effective for fine desulfurization. Although the higher
hydrogen sulfide contents in the biogas can be degraded very reliably and cheaply with biological methods,
biological methods are not usually enough to desulfurize the biogas to the extent that an oxidation catalyst
with subsequent exhaust heat exchanger can be safely installed in the exhaust tract.
The doped/impregnated activated carbon (frequently potassium iodine) adsorbs the hydrogen sulfide (H2S)
on the carbon surface and oxidizes it there catalytically to elementary sulfur (S). While H2S as gas can also
be desorbed again (one reason can be warm or damp combustion gas, e.g. due to failure of the gas cool
drying), elementary sulfur cannot be desorbed. As a result of this chemical reaction, the sulfur is therefore
bound more strongly on the carbon. The load-bearing capacity of the activated carbon is also therefore
higher. Thus the loading-bearing capacity with good activated carbon in good operating conditions (see
manufacturer's notes) is 500 g sulfur per 1 kg activated carbon and more. As a result, relatively long
operating times of 2000-8000 operating hours can be attained in many biogas systems.
If the activated carbon of the gas flow (flowing speed and pressure loss) is correctly designed and the
necessary retention times of the combustion gas in the activated carbon layer are complied with, iodized
activated carbon will be able to lower the H2S flow to the extent that this can no longer be validated with the
field measuring instrumentation. This degree of purification is retained over the entire service life. The
reactivity of the activated carbon is very high with the result that the activated carbon can theoretically be
divided into three layers: The unpolluted activated carbon before the adsorption zone, the adsorption zone in
which the adsorption occurs (small in relation to the container) and the polluted layer after the active layer.
The adsorption zone migrates in the direction of gas flow through the adsorber. At the gas outlet, this
migration of the adsorption zone cannot be measured by measuring the H2S content. It is therefore not
possible to determine the pollution of the adsorber at the outlet.
When the adsorption zone reaches the outlet from the adsorber, the H2S flow rises within a few days to the
full input concentration. This process is referred to as break point and must be prevented technically because
it progresses rapidly.
One option is to provide a permanent H2S monitoring in the activated carbon layer at some distance to the
gas outlet, so that an advanced warning can be generated by sampling the gas from the activated carbon
layer. In this way, the activated carbon can be replaced before the break point of the adsorption front by the
activated carbon, whereby a certain amount of non-polluted activated carbon has to be disposed of.
Another approach is to reserve two separate activated carbon fillings. A working filter, in which adsorption
occurs, and a control filter, which ensures at the break point of the working filter that the gas continues to be
finely desulfurized. A continuous H2S concentration measurement between the two layers makes a
statement concerning the break point of the working filter possible. Upon replacement, the working filter,
Chapter_07 - Fuel system.docx
02999408
Page 5 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
which is now fully polluted, is disposed of, the control filter becomes the new working filter and the control
filter is filled with fresh activated carbon. This can be realized by refilling or by means of a corresponding flap
system. If the control filter is designed large enough (e.g. as large as the working filter), replacement of the
working filter can be delayed. In this way, the activated carbon replacement can be synchronized with
maintenance work on the engine.
The activated carbon must not be able to be bridged with a bypass. Firstly, it is then difficult to demonstrate
that this bypass has not been activated and that the combustion gas therefore had the required quality.
Secondly, short operating times with combustion gas containing H2S are also sufficient to form sulfuric acid
via the exhaust gas catalyst, which condenses in the exhaust heat exchanger.
The load-bearing capacity of the activated carbon also depends on the gas humidity and temperature. In
general, the gas should be dried (but not be too dry) and should not be too cold either, as the chemical
reaction on the surface of the activated carbon is impeded by this. The exact target values can be found in
the data sheets of the activated carbons. Owing to the gas states that are better to control, gas cool drying
with reheating should take place upstream for conditioning when using activated carbon.
The adsorption of silicon-organic hydrocarbons cannot be compared with the H2S adsorption. These can be
found in sewage gas and landfill gas and sometimes also in the combustion gas of biogas systems serving
for waste recycling.
Non-doped activated carbon filters are used for silicon-organic compounds. These adsorb the pollutants on
the surface. However, no chemical reaction occurs there, meaning that the adsorbed substances can be
desorbed again.
Two further hurdles are: firstly, that the loading capacity for hydrocarbons is not very high and tends to be in
the magnitude of percent, and secondly, not only silicon-organic compounds are adsorbed but all
hydrocarbons are adsorbed (although pure hydrocarbons in the engine combustion do not present any
problems and would not therefore have to be cleaned).
Although no economical system is available for the fine desulfurization, the removal of other pollutants using
activated carbon is significantly more complex and expensive with the result that a corresponding estimation
has to be made here.
Chapter_07 - Fuel system.docx
02999408
Page 6 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
7.1.6
Mixture treatment
The exhaust emissions of the gas engine are regulated by controlling the air-gas ratio. The principal
components for the processing of the air-gas mixture before it enters the combustion chamber are the gas
control unit, the venturi mixer and the throttle valve.
Fig. 7.2 shows, among others, the components for air-gas mixture treatment for lean-burn combustion.
Chapter_07 - Fuel system.docx
02999408
Page 7 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 7.2
Principle of lean-burn combustion with turbocharging, dual-circuit cooling and
combustion chamber temperature control
1
2
3
12
4
5
6
11
9
7
10
8
1
Combustion air
2
Exhaust gas
3
Turbocharger
4
Combustion chamber temperature measurement
5
Cooling water
6
Engine
7
Gas mixture cooler
8
LT mixture cooling water
9
Throttle valve
10
Gas
11
Gas control line
12
Mixer with actuator for mixture formation
Chapter_07 - Fuel system.docx
02999408
Page 8 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
7.1.7
Gas control line
Generally, gas engines may only be operated with gas control lines approved by genset manufacturer.
Before the gas and air are mixed in the venturi mixer, the pressure of gas must be reduced to atmospheric
pressure. This is performed by the membrane zero pressure regulator in the gas control line. Fig. 7.3 shows,
in principle, how the gas control line is designed. The zero pressure regulators have no auxiliary energy
supply. At the inlet to the gas control line is a manually operated ball valve. This is followed by a gas filter as
protection against major impurities. The filter insert comprises a filter mat; filtration rate is approx. 85 % for
particles >5 μm. Then come two shut-off valves, which are implemented as solenoid valves or pneumatically
operated valves depending on the nominal width. When using combustion gases which may contain oxygen,
e.g. landfill gas and sewage gas, a deflagration device with temperature monitor is fitted after the shut-off
valves. Finally, there is the zero pressure regulator. A minimum pressure sensor is always installed in
advance of the solenoid valves. Dependent on the safety requirements for the system, the gas control lines
may be equipped with leakage sensors, intermediate vent valves or maximum pressure monitors.
Zero-pressure gas control lines are operated at an pre-pressure of up to 200 mbar. In the case of higher prepressures, either a special design of gas control line or a pre-pressure control line will be required.
Fig. 7.3 Gas control line
PSA=BP124
TSA+
=BT147
1
23 4
5
6
6
7 8 9
1
Gas
6
Solenoid valve*
2
Ball valve
7
Deflagration device*
3
Pressure gauge
8
Temperature sensor
4
Gas filter
9
Zero pressure controller
5
Pressure monitor
Chapter_07 - Fuel system.docx
02999408
* not for natural gas
Page 9 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
7.1.7.1
Pre-pressure control line
The pre-pressure control line reduces the gas pressure below 200 mbar. The principal components of the
pre-pressure control line are the ball valve at the entry to the unit, the gas filter, the gas pressure regulator
with safety shut-off device (SAV) and the safety blow-off valve (SBV). The safety shut-off valve shuts off the
gas supply when the outlet pressure after the pre-pressure control line exceeds the preset limit value. Small
pressure surges which occur e.g. when the solenoid valves close in the downstream gas control line are
intercepted by the blow-off valve which opens against spring force. Fig. 7.4 shows a pre-pressure control
line.
Fig. 7.4 Pre-pressure control line
GOSA+
=BP379
GO 9
7
1
2
3
4
5
6
8
3
1
Gas
6
Pressure regulator
2
Ball valve
7
Air vent cock
3
Pressure gauge
8
Safety blow-off valve (SBV)
4
Gas filter
9
Gas leakage display
5
Safety shut-off valve (SAV)
Chapter_07 - Fuel system.docx
02999408
Page 10 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
7.1.7.2
Dual gas operation
Each type of gas requires its own gas control line with filtration, shut-off valves and precise pressure
keeping. After passing through the gas control lines, the two gases are fed to the engine via a common
pipeline.
Dual gas operation is possible only with a multigas mixer (adjustable gap).
The changeover from one gas to another takes place automatically when the engine is at a standstill by
switching over the solenoid valves at the gas control lines.
In addition, when specially requested, the gas can be mixed before the gas control line. This must be tested
and designed in each case.
7.1.7.3
Combustion gas system with multi-engine systems and high gas pressures
With multi-engine systems that are connected to a gas network with higher pre-pressures (0.5-10 bar), it is
recommended to equip each genset with a pre-pressure and zero-pressure control line. This design has the
advantage that the gas collection line to the gensets can be designed with a smaller cross section.
Furthermore, the system has a higher stability against pressure fluctuations, which are caused by starting
and stopping the individual gensets.
Chapter_07 - Fuel system.docx
02999408
Page 11 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
7.1.7.4
Notes on installing gas control lines
The gas control line must be arranged in the same room as the gas engine in order to allow the pressure
regulator to respond to changes in intake air pressure.
For corrosive gases like landfill gas, biogas or sewage gas, non-ferrous metal (brass) must not be used for
parts carrying gas.
Gas pressure regulating devices and pipelines must not be installed under tension. The arrow on the
actuator housing must point in the direction of flow. The gas control line must be installed horizontally.
Regulators and control devices must, as a matter of principle, be arranged in a normal position.
Blow-off lines from the safety blow-off valve (SBV) must be routed from the engine room into the open air
with a sufficient cross section.
The gas control lines must be arranged as close to the gas engine as possible. The maximum distance
between the outlet from the gas control line and the inlet into the gas mixer at the engine must not exceed 3
m and there may be a maximum of three 90° elbows in this line.
Note: As no further filtration of the gas occurs before the inlet into the gas engine, the line between the gas
control line and gas mixer must be cleaned inside. See also Chapter 20.1.
In combustion gas mixtures which also contain oxygen as a component (e.g. sewage gas, biogas and landfill
gas), backfiring may occur in the gas line. To prevent flames from penetrating the gas supply line, standard
gas control lines include long-term fire-resistant deflagration devices with temperature monitoring. Where
deflagration devices are installed, the maximum permitted distance between the engine and the gas control
line is 40xDN of the gas line. Where the distance is greater, a long-term fire-resistant anti-detonation device
must be provided.
The connection to the engine is made via a flexible hose which is laid as a 90° bend, or a specially designed
expansion joint which must be installed without tension.
Depending on the system, a gas flow meter may be installed in the feed line to the engines ahead of the
control line.
The evaluation units for temperature monitoring at the deflagration device, the SAV in the pre-pressure
control line and the gas flow meter must be integrated in the switchgear.
To safeguard the gas engine system, there must be a shut-off device in the gas connection line suitable for
manual operation outside of the engine room in a non-hazardous location. This shut-off device must be
closed quickly in the event of danger. Remote-operated valves with a permanent auxiliary energy supply
(e.g. closing spring) are recommended.
7.1.7.5
Blow-off and breather lines for gas control lines
Lines to atmosphere have to be laid without restriction in the diameter (observe pressure loss) as indicated
by the manufacturer of the gas pressure regulator and safety device.
Shut-off valves are not allowed in breather lines. Blow-off and relief lines must not be connected to breather
lines into a collection line. Only lines to atmosphere are exempted where breather and safety blow-off
Chapter_07 - Fuel system.docx
02999408
Page 12 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
devices are already connected inside the units. Fig. 7.5 shows a pre-pressure control line, which does not
fulfil this requirement as the blow-off and breather lines are connected to one common line. This is not
permissible.
The outlets of the discharge lines into the open air have to be far enough away from ignition sources,
protected against external corrosion, equipped with protection against blocking and arranged in a way that
no leaked gas can penetrate the closed rooms or cause other annoyance or danger.
Fig. 7.5 Pre-pressure control line with impermissible arrangement of blow-off and breather lines
7.1.8
Gas mixer
Chapter_07 - Fuel system.docx
02999408
Page 13 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
Air and gas are combined in the mixer, which is designed as a venturi pipe. The air flows through a nozzlelike constriction and then through a gradually expanding diffuser. The constriction accelerates the flow, which
is then slowed down again with minimal loss in the diffuser. The acceleration at the constriction (nozzle)
creates an underpressure, so that the gas is automatically drawn in through a gap at the point of minimum
cross-section. Thanks to the subsequent deceleration, the pressure then increases again until it is virtually
equal to atmospheric pressure, with the result that the mixing process takes place without any great loss of
pressure.
The advantage of this type of mixing is that the quantities of air and gas remain in the same proportion to
one another even when output is varied by altering the throttle valve setting and thereby varying the central
air volume flow.
A multi-gas mixer is used with which the gap geometry in the mixer itself can be altered via a actuator. The
exact maintenance of the gas-to-air ratio in the mixture depends on the gas pressure ahead of the mixing
gap being equal to the air pressure ahead of the venturi pipe. Fig. 7.6 shows the principle of a gas-air mixer
with adjustable gap.
Fig. 7.6 Multi-gas mixer
1
Gas inlet
2
Air inlet
3
Gas-air mixture outlet
4
Connection piping to the stepper motor
5
Gas gap
Chapter_07 - Fuel system.docx
02999408
Page 14 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
7.1.9
Throttle valve
The power output or the speed of the engine is regulated via the throttle valve by means of controlling the
amount of the compressed mixture to the engine.
7.1.10
Startup of biogas systems
If there is no biogas in the initial phase, alternative gases can be used to start the engine. Permissible
alternative gases and engine settings are defined in a Technical Circular.
The installed biogas control line is normally a little too big because of the restricted maximum mechanical
power and probably a higher heat value Hu of the alternative gas. Therefore, the inlet pressure of the
alternative gas must be adjustable in order to achieve as low a pressure level as possible (approx.
5-30 mbar).
It is not possible to install fixed faceplates in order to lower the inlet pressure because the flow rate
necessary for engine startup and engine idling is too low.
The zero-pressure regulator must be correspondingly adjusted by an authorized commissioning engineer.
7.2
Notes on installing and maintaining gas systems
7.2.1
Regulations
When installing gas lines and gas system components, increased safety requirements must be complied
with.
Both when carrying out works on the system and when selecting components, the DIN, TRD, DVGW, etc.
regulations must be complied with. The most important ones are listed in the following table:
DIN 6280-14
"Combined power and heat generation at power plants (CHPs) with reciprocating internal
combustion engines –
basic principles, requirements, components, designs and maintenance"
DIN 6280-15
"Combined power and heat generation at power plants (CHPs) with reciprocating internal
combustion engines - testing"
DIN EN 161
"Automatic shut-off valves for gas burners and gas appliances"
DIN EN 14382
Safety devices for gas pressure regulating systems and installations – Gas
safety shut-off devices for operating pressures up to 100 bar
DIN 3394
"Automatic actuators" (Part 2 of DIN 3394 has been replaced by DIN EN 161)
G 262
"Use of gases from regenerative sources for the public gas supply"
Chapter_07 - Fuel system.docx
02999408
Page 15 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
G 490/I
"Gas pressure regulating systems for inlet pressures up to 4 bar"
G 491
"Gas pressure regulating systems for inlet pressures above 4 to 100 bar"
G 493/I
"Qualification criteria for manufacturers of gas pressure regulating and measuring systems"
G 495
"Gas pressure regulating systems and bulk gas measurement systems – Monitoring and
maintenance"
G 600
"Technical regulations for gas installation"
GUV-R 127
"Safety regulations for landfills"
GUV 17.5
"Safety regulations for waste water treatment plants – construction and equipment"
BGV – D2 50
"Working with gas lines"
•
Following the installation of the gas line and valves, an expert must be commissioned to
confirm that the installation has been performed in a technically correct manner and in
accordance with the legal regulations.
•
Before commissioning the gas line, a corresponding application must be submitted in good
time to the relevant authorities.
7.2.2
Servicing and maintenance
When working on gas lines, among others, the regulation BGV-D2 and DVGW worksheet G 495 must be
complied with. In particular it must be ensured that works to the gas system (e.g. opening a gas train,
disassembling and servicing a device) are carried out only when the system is depressurized. Such works
must be carried out by trained and qualified specialist personnel only. With regard to service intervals, it is
essential to comply with the manufacturer's recommendations for the particular type of operation in terms of
visual checks, inspections, function testing and maintenance.
Chapter_07 - Fuel system.docx
02999408
Page 16 / 16
VD-S 2014-06 EN
Caterpillar confidential: none
Power plants layout
Chapter 8
Lubricating oil system
06-2014
Caterpillar Energy Solutions GmbH Carl-Benz-Straße 1 D-68167 Mannheim Phone: +49(0)621 384-0 Fax: +49(0)621 384-8612
Caterpillar confidential: none
Contents
8.
Lubricating oil system ................................................................................................................ 3
8.1
Genset ........................................................................................................................................... 3
8.2
System .......................................................................................................................................... 3
8.2.1
Clean oil tank................................................................................................................................. 4
8.2.2
Waste oil tank ................................................................................................................................ 4
8.2.3
Service tank................................................................................................................................... 4
8.2.4
Container applications ................................................................................................................... 4
8.3
Lubricating oil treatment ................................................................................................................ 4
8.3.1
Lubricating oil filter ........................................................................................................................ 4
8.4
Lubricating oil types ...................................................................................................................... 5
8.5
Lube oil with biogas applications................................................................................................... 5
8.6
Engine prelubrication .................................................................................................................... 5
8.7
Changing and replenishing the lube oil ......................................................................................... 5
Chapter_08 - Lubricating oil system.docx
02999408
Page 2 / 8
VD-S 2014-06 EN
Caterpillar confidential: none
8.
Lubricating oil system
8.1
Genset
The lubricating oil systems of the engines are implemented as wet sump lubricating systems. Table 8.1
shows the various lubricating oil systems used for the different engine series.
Table 8.1
Engine type
Wet sump
Oil pan at engine
TCG 2016 C
TCG 2020


TCG 2032

Extended
External
oil tank in base
oil tank
frame
in the system


All engine series have integral lubricating oil pumps; the oil is filtered and cooled by either engine-mounted or
separate filters and oil coolers.
The external oil-coolers and assembly parts have to be designed for a minimum-pressure of 16 bar.
The gensets with engines of the series TCG 2020 can optionally be implemented with an additional oil tank
in the base frame. With the series TCG 2016 C there is the option of providing an external oil tank. Due to an
increased lubricating oil volume, considerably increased lubricating oil service lives are achieved depending
on the oil quality and type of combustion gas.
8.2
System
For the TCG 2032 engines, the external lubricating oil circuit components (e.g. heat exchanger) must be
arranged at the same level as the genset or lower in order to prevent the oil from draining back into the oil
pan when the engine is at a standstill. For systems with TCG 2032, the external lube oil cooler should be
installed as close to the genset as possible so that the lube oil volume is kept as low as possible in the plant
system.
Chapter_08 - Lubricating oil system.docx
02999408
Page 3 / 8
VD-S 2014-06 EN
Caterpillar confidential: none
8.2.1
Clean oil tank
The fresh oil tank must be arranged in a way which prevents it from emptying into the engine due to gravity.
In general, lubricating oil is replenished using a gearwheel pump, which provides a defined filling amount.
Compared to replenishment with gravity flow a replenishing by gearwheel pump is preferred. The size of the
supply tank will be dependent on the operating mode of the plant and the associated oil supply required. The
minimum recommended size is equal to the quantity required for one oil change plus the amount consumed
during two intervals between changes.
8.2.2
Waste oil tank
The minimum recommended size is equal to the quantity yielded by two oil changes.
8.2.3
Service tank
If a service tank is provided for refilling, it should hold sufficient lube oil for approx. 200 oh (e.g. for TCG
2032, approx. 600 dm3).
8.2.4
Container applications
In containers, the available free space might be heavily restricted due to the size of the genset itself and also
due the auxiliary equipment. For those applications, the recommendations given above for the size of the oil
tanks do not have to be fully adhered to.
8.3
Lubricating oil treatment
The quality of the lubricating oil is one of the main criteria determining the service life of the engine
components in contact with the oil and hence also the fault-free operation of the system. Particular attention
should therefore be paid to maintaining the lubricating oil filters and, if appropriate, the separators.
8.3.1
Lubricating oil filter
The lubricating oil filters fitted to gas engines are designed for unlimited operation and no further measures
are required on the part of the client to treat the lubricating oil.
Chapter_08 - Lubricating oil system.docx
02999408
Page 4 / 8
VD-S 2014-06 EN
Caterpillar confidential: none
8.4
Lubricating oil types
Technical circulars for lube oil contain a list of lubricating oils available from notable manufacturers and
approved for gas and diesel engines. No other lubricating oils may be used without written approval. Also
included in these Circulars are details of lubricating oil change intervals, used oil analyses and maintenance
of the lubricating oil filters fitted to the engine.
Before commissioning, an analysis of the fresh oil supplied must be compared with the manufacturer's
specification.
8.5
Lube oil with biogas applications
Further information regarding the lube oil with biogas applications can be found in the technical circular
"Optimizing the lube oil management for biogas applications."
8.6
Engine prelubrication
Prelubrication is generally provided for all engine types, as this significantly reduces engine wear. For this
purpose, electrically driven pre-lubricating pump modules are used, which in most cases are mounted on the
genset base frame. The prelubricating pump must be integrated in the lubricating oil system in such a way
that when prelubrication is activated, oil flows through all components (filters, coolers) installed between the
oil pump and the engine. The capacity and supply pressure of the pump modules must be matched to the
respective engine type.
Engine prelubrication takes place immediately before the start when the engines are at a standstill.
Optionally, a process called interval prelubrication can be provided, i.e. the engine is prelubricated at preset
intervals for a defined period of time.
In the case of systems equipped with gas engines, prelubrication is controlled by the TEM system.
Prelubrication is inactive when the engine is running.
The TCG 2032 does not have an interval prelubrication and therefore it must be prelubricated before
each start.
8.7
Changing and replenishing the lube oil
Lube oil changes must be carried out in accordance with the operating instructions for the respective engine,
and in the case of modules in continuous operation, lube oil consumption must be compensated by topping
up the system with fresh oil.
When changing the lube oil, make sure that the oil in the system-side components e.g. pipes, heat
exchangers etc. is changed. Drainage options for the lube oil are provided at the lowest points of the system
for this. Depending on the system layout, it is effective to provide a permanently installed or mobile emptying
pump.
Chapter_08 - Lubricating oil system.docx
02999408
Page 5 / 8
VD-S 2014-06 EN
Caterpillar confidential: none
Fresh lube oil is filled from the fresh oil tank via the top-up pump. This operation can be either manual or
automatic. In the case of systems equipped with gas engines, the lube oil replenishment is controlled via the
TEM system.
Two solenoid valves are installed in series in the lubricating oil top-up line before the engine. When the
minimum level in the oil pan is reached, the solenoid valves are opened by the TEM system (and/or the topup pump is started) and oil is replenished. When the maximum level is restored, the solenoid valves close
(and/or the top-up pump is stopped).
When topping up under gravity from the service tank, it must be ensured that the lines are large enough and
that the oil does not become too viscous due to low temperatures.
To empty out the oil pan when changing the lubricating oil, the pressure line from the pre-lubricating pump
must be connected to the used oil tank via a three-way valve. To change the lube oil, the three-way valve is
switched over and the lubricating oil is pumped out of the oil pan and into the used oil tank. The top-up pump
is then used to fill up with clean oil. The three-way valve behind the prelubricating pump is switched back to
the "prelubricate" position. By activating the prelubricating pump, the complete lubricating oil system is
refilled with oil.
Safety and other legal regulations for the use and storage of clean and/or waste oils must be
observed at all costs.
Chapter_08 - Lubricating oil system.docx
02999408
Page 6 / 8
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 8.1 Lubricating oil system
LICSA+
=BL234
LICSA+
=BL234
LICSA+
=BL234
PISA+
=BP145
PISA+
=BP145
PISA+
=BP145
TISA+
=BT208
TISA+
=BT208
TISA+
=BT208
PISA=BP196
PISA=BP196
PISA=BP196
1
2
3
4
5
LSA++
=BL8511
6
LSA++
=BL8520
LA=BL8510
LA+
=BL8524
LSA-=BL8509
PSA+
=BP8519
PSA+
=BP8529
7
1
Gas engine
2
Lubricating oil filter
3
Lube oil cooler
4
Prelubrication pump
5
Oil tank base frame
6
Clean oil pump
7
Clean oil tank
8
Waste oil tank
Chapter_08 - Lubricating oil system.docx
02999408
Page 7 / 8
8
VD-S 2014-06 EN
Caterpillar confidential: none
Chapter_08 - Lubricating oil system.docx
02999408
Page 8 / 8
VD-S 2014-06 EN
Caterpillar confidential: none
Power plants layout
Chapter 9
Combustion air system
06-2014
Caterpillar Energy Solutions GmbH Carl-Benz-Straße 1 D-68167 Mannheim Phone: +49(0)621 384-0 Fax: +49(0)621 384-8612
Caterpillar confidential: none
Contents
9.
Combustion air system .............................................................................................................. 3
9.1
Definitions ...................................................................................................................................... 3
9.1.1
Ambient air .................................................................................................................................... 3
9.1.2
Intake air / combustion air ............................................................................................................. 3
9.2
Requirements for the combustion air ............................................................................................ 3
9.2.1
Combustion air temperature and pressure ................................................................................... 3
9.2.2
Composition of the combustion air ................................................................................................ 4
9.2.3
Cleanliness of the combustion air ................................................................................................. 6
9.2.4
Tropical conditions ........................................................................................................................ 7
9.3
Combustion air quantity ................................................................................................................ 7
9.4
Types of filtration for the combustion air ....................................................................................... 8
9.4.1
Air filter – Paper/Plastic ................................................................................................................. 8
9.5
Silencer ......................................................................................................................................... 8
9.6
Air intake line ................................................................................................................................. 8
9.7
Pressure losses ............................................................................................................................. 9
9.8
Venting the crank case.................................................................................................................. 9
Chapter_09 - Combustion air system.docx
02999408
Page 2 / 10
VD-S 2014-06 EN
Caterpillar confidential: none
9.
Combustion air system
9.1
Definitions
9.1.1
Ambient air
The air of the free environment and the air with which a gas engine is supplied is called ambient air. The
ambient air temperature is the temperature measured close to the ground, normally 2 meters above ground
level, neither with influence from sunlight nor influence from ground heat or effects of thermal conduction.
9.1.2
Intake air / combustion air
The intake air or combustion air is provided to the gas engine directly before its combustion air filter. It
passes through the plant's ventilation system before reaching the engine's combustion air filters. The
ventilation system includes filtering of the air, and depending on the layout of the ventilation system (layout of
air ducts and amount of ventilation air), the intake or combustion air may face a certain temperature rise
against the ambient air temperature.
9.2
Requirements for the combustion air
9.2.1
Combustion air temperature and pressure
In the data sheets, the engine power is indicated as per ISO 3046-1 and the electrical terminal power of the
power supply unit as per ISO 8528-1. In both standards, the following standard reference conditions are
defined in respect to the combustion air parameters:
Air temperature:
298 K (25°C)
Air pressure:
1000 mbar (100 kPa)
Relative humidity:
30%
These standard references are sometimes deviated from and special reference conditions defined
depending on the engine type for the power data in the Caterpillar Energy Solutions GmbH standard data
sheets.
The power is reduced for combustion air temperatures and installation heights diverging upwards from the
reference conditions.
Chapter_09 - Combustion air system.docx
02999408
Page 3 / 10
VD-S 2014-06 EN
Caterpillar confidential: none
The following requirements in respect to the combustion air temperature apply for the start and operation of
the engines:
When operating the engines, the combustion air temperatures (minimum / design) have to be kept
within the limits as per the data sheets or P&I flow diagrams.
For the start of engines, the following combustion air temperatures have to be maintained in the
engine room:
Gas engines with air preheating or wastegate:
≥ 5 – 10°C
Gas engines without air preheating and wastegate:
≤ 10 K below design temperature as
stated per data sheet and/or P&I diagram
9.2.2
Composition of the combustion air
The normal composition of combustion air is considered to be dry air with a certain amount of steam. The
steam content in the air is defined by the relative humidity at a defined air pressure and air temperature.
Basically the combustion air must be free of components forming acids or bases; e.g. sulfur dioxide (SO2)
forms sulfurous acid when combined with water (H2O). The main components of dry air at sea level (NN) are
given in Table 9.1.
Table 9.1
Main components of dry air
gas storage
Volume fraction [%]
Nitrogen N2
78.084
Oxygen O2
20.946
Carbon dioxide CO2
0.035
Argon Ar
0.934
Total
99.999
The remaining 0.001% of the volume fraction are trace gases, mainly the inert gases like neon (18 ppm),
helium (5 ppm) and krypton (1 ppm).
In the surrounding area of industrial or chemical plants, the composition of the combustion air may face
some negative influence from process gases such as, for example, hydrogen sulfide (H2S), chlorine (Cl),
fluorine (F), ammonia (NH3) etc.
The technical circular states limit values for the content of "harmful" attending gases like sulfur (S), hydrogen
sulfide (H2S), chlorine (Cl), fluorine (F) and ammonia in the combustion gas. Those given limiting values
imply that the composition of the combustion air itself is as per above in Table 9.1, i.e. the combustion air is
Chapter_09 - Combustion air system.docx
02999408
Page 4 / 10
VD-S 2014-06 EN
Caterpillar confidential: none
free of any sulfur, hydrogen sulfide, chlorine, etc. With the given limiting values for the combustion gas, it is
possible to deduce limiting values for the content of "harmful" gases in the mixture combution gas /
combustion air and combustion air alone.
Example:
3
The technical circular states the limit value for ammonia in the combustion gas at 30 mg/mn CH4. When
burning natural gas (100% CH4 assumed), for example, 17 standard cubic meters of combustion air are
required per cubic meter of natural gas. By use of this ratio, it can be stated that the content of ammonia in
3
the combustion air must not exceed 1.8 (30/17) mg/m n in order to keep a condition corresponding to the limit
3
value of 30 mg/mn CH4 given for the combustion gas. If the fuel gas itself contains ammonia too, the limit
value for the combustion air must be reduced accordingly.
Similarly, the upper limit values for other "harmful" gases in the combustion air can be calculated. Those
values are given in Table 9.2.
Table 9.2
Permitted contamination of the combustion air
Component
Content [mg/mn³ air]
Sulfur (total) S or
< 130
Hydrogen sulfide H2S
< 135
Chlorine (total) Cl
< 5.9
Fluorine (total) F or
< 2.9
Total chlorine and fluorine
< 5.9
Ammonia NH3
< 1.8
Oil vapors >C5<C10
< 176
Oil vapors >C10
< 14.7
Silicon (organic) Si
< 0.59
As a rule, it is not permissible for acid formers such as SO2, SO3, HCl or HF (but also other substances) to
be in the combustion air. As condensation can occur in the mixture cooler, especially in hot and humid
conditions (e.g. tropics), acid attacks would result here. Acid formers in the exhaust tract are less critical
because the dew point is not fallen below here.
Components in the combustion air as mentioned in Table 9.2 might be a reason for shortening the
maintenance intervals and they may damage or even destroy emission lowering systems located
downstream.
When designing combustion air systems, care must be taken that the air is not drawn from areas in which
increased concentrations of these accompanying gases exist or might exist as a result of the equipment
installed (e.g. refrigeration systems) or the processes conducted therein.
Chapter_09 - Combustion air system.docx
02999408
Page 5 / 10
VD-S 2014-06 EN
Caterpillar confidential: none
9.2.3
Cleanliness of the combustion air
Fine sand or dust as well as chemically aggressive vapors significantly reduce the service life of the engine if
they are directly drawn in by the engine.
The combustion air supplied to the engine must therefore fulfil certain requirements in terms of cleanliness. It
is essential to provide air filters which must be implemented as Class F6 to F7 fine dust filters. The mean
efficiency of these filters in combating atmospheric dust is specified in DIN EN 779. The separation rates to
be achieved with these filter classes are given in Table 9.3:
Table 9.3
Particle size
Separation rate in %
>µm
Class F6
Class F7
0.5
30
65
1.0
50
85
1.5
70
95
2.0
80
98
2.5
85
>99
3.0
95
>99
4.0
>99
>99
Mean efficiency (%) as per
60≤ Em≤80
80≤ Em≤90
DIN EN 779
Depending on the ambient conditions under which the engine obtains its combustion air, a type of filtration or
filter combination must be selected suitable for these conditions.
As already mentioned in Chapter 5 (engine room ventilation), it is required to provide a ventilation system for
the engine room including a coarse filtering acc. to filter class G3. After the coarse filter, the particle size of
the dust in the air is in the range of 1 μm and the dust concentration in the air should be in the range of 0.5 –
1 mg/m³. This concentration corresponds to a dust concentration assumed for the design of combustion air
filters of truck engines operating in normal European traffic.
Chapter_09 - Combustion air system.docx
02999408
Page 6 / 10
VD-S 2014-06 EN
Caterpillar confidential: none
9.2.4
Tropical conditions
In tropical and subtropical areas, the rainfall exceeds the possible atmospheric evaporation for some months
of the year. This circumstance causes a high humidity at comparably high medium ambient temperature,
about 25°C average annual temperature. The water content (steam) in the air/combustion air is therefore
very high.
When operating high charged combustion engines with charge air cooling or mixture cooling, there may be
condensation of the steam entering the engine together with the combustion air. This condensate may lead
to corrosion and wear for engine components like charge air/mixture cooler, throttle, receiver, valves etc. If,
in addition, the combustion air is affected by acid or base-forming attending gases like sulfur dioxide (SO2),
this might lead to accumulation of sulfurous acid. The corrosion for the above mentioned components will
escalate.
Depending on the engine type, a "tropical version" is available under these operating conditions in order to
reduce corrosion of the affected components. It is also necessary to prevent the intake air from containing
acid formers.
9.3
Combustion air quantity
The combustion air quantity required for gas engines varies with the composition of the combustion gas and
with the combustion air ratio being used. The specific combustion air values given in Table 9.4 apply to the
most frequent gas engine application, i.e. operation with natural gas on the lean-burn principle.
Table 9.4
Engine type
Combustion air quantity
mL [kg/kWh]
TCG 2016 C
5.2
TCG 2020(K)
5.2
TCG 2032
5.0
For precise data, please refer to the specific data sheets.
Chapter_09 - Combustion air system.docx
02999408
Page 7 / 10
VD-S 2014-06 EN
Caterpillar confidential: none
9.4
Types of filtration for the combustion air
9.4.1
Air filter – Paper/Plastic
In the majority of applications where the air is relatively clean (dust concentration < 1 mg/m³), paper filters
are used for air filtration: these may be either plate type filters, pocket or circular air filters. With the series
TCG 2016,TCG 2020 V12 and TCG 2020 V16, such filters with appropriate filter housings are fitted to the
engine. For the TCG 2032 engines a separately mounted filter, containing four filter elements each, is
planned per cylinder row. Depending on the design, this filtering unit also incorporates the heat exchanger
for the combustion air preheating. The same filtering unit may be used optionally with engines of the series
TCG 2020, especially with regard to low ambient temperatures.
Because of the sharp increase in pressure loss in the event of contamination, where these filters are used, a
negative pressure monitoring facility or vacuum pressure indication must, on principle, be provided. The
cleaner the combustion air, the slower the filter gets contaminated. A contaminated filter consumes more
energy than a clean filter. Consequently, this leads to a slight increase of the fuel consumption and to an
unfavorable operating point of the compressor. In extreme cases, the compressor pumps and the genset
cannot be operated safely anymore. The filter needs to be renewed before it leads to a critical operational
state.
9.5
Silencer
In the case of air filters installed outside of the genset room, the compressor noise of the turbocharger in
particular can be transmitted outside via the air supply pipe, where it makes its presence felt as a highfrequency whistle. In such cases, silencers must be provided in the intake lines, the size of the silencers
being determined in accordance with the respective plant.
9.6
Air intake line
Where the air filters are not installed in the engine, an intake line must be installed between the engine and
the air filter. Smooth and clean, e.g. painted or galvanized piping must be used for these lines. The line must
not bear directly on the engine, i.e. there must be a rubber sleeve or corrugated hose fitted between the air
inlet housing and the air line. Sleeves and hoses must not be constricted by bending. All joints in the intake
line between the filter and the engine connection must be tightly sealed. If the intake line is routed with a fall
towards the engine, a water trap must be provided with a drain-off in front of the engine.
A useful guide to determining the correct size for the air lines is the air speed in the intake pipe. The air
speed should be ≤ 20 m/s.
Chapter_09 - Combustion air system.docx
02999408
Page 8 / 10
VD-S 2014-06 EN
Caterpillar confidential: none
9.7
Pressure losses
The air intake system with pipes, elbows, filters, silencers, etc. is itself the cause of pressure losses. The
pressure loss occurring at nominal volume flow must not exceed the values laid down for the individual
engine series.
These values are given in Table 9.5.
Table 9.5
Engine series
Max. permissible
underpressure
[mbar]
TCG 2016 C
5*
TCG 2020(K)
5*
TCG 2032
5*
* permissible underpressure before air filter
9.8
Venting the crank case
Series TCG 2016 and TCG 2020 and TCG 2032 engines have a closed crankcase venting system, i.e.
vapors from the crankcase are directed back to the intake manifold via an oil separator. The separated oil is
routed back to the engine crankcase.
Chapter_09 - Combustion air system.docx
02999408
Page 9 / 10
VD-S 2014-06 EN
Caterpillar confidential: none
Chapter_09 - Combustion air system.docx
02999408
Page 10 / 10
VD-S 2014-06 EN
Caterpillar confidential: none
Power plants layout
Chapter 10
Exhaust system
06-2014
Caterpillar Energy Solutions GmbH Carl-Benz-Straße 1 D-68167 Mannheim Phone: +49(0)621 384-0 Fax: +49(0)621 384-8612
Caterpillar confidential: none
Contents
10.
Exhaust system ........................................................................................................................... 3
10.1
Permissible exhaust backpressure ............................................................................................... 3
10.2
Exhaust system components ........................................................................................................ 7
10.2.1
Catalytic converters ....................................................................................................................... 7
10.2.1.1
Planning notes for catalytic converters ......................................................................................... 7
10.2.1.1.1
Lifting lugs ..................................................................................................................................... 7
10.2.1.1.2
Insulation ....................................................................................................................................... 7
10.2.1.1.3
Installation ..................................................................................................................................... 8
10.2.1.1.4
Inspection .................................................................................................................................... 10
10.2.1.2
Installation specification oxidation type catalysts ........................................................................ 10
10.2.1.2.1
Seals ........................................................................................................................................... 10
10.2.1.2.2
Screws......................................................................................................................................... 10
10.2.1.2.3
Installation ................................................................................................................................... 11
10.2.1.3
Cleaning the catalyst ................................................................................................................... 12
10.2.1.4
Operating recommendations for oxidation type catalysts ........................................................... 12
10.2.1.5
Limit values for exhaust composition .......................................................................................... 14
10.2.1.6
Oxidizing catalysts for bio- and sewage gas engines ................................................................. 15
10.2.2
Exhaust silencers ........................................................................................................................ 15
10.2.3
Exhaust heat exchanger ............................................................................................................. 16
10.2.4
Exhaust components in biogas systems ..................................................................................... 18
10.2.5
Exhaust flaps ............................................................................................................................... 18
10.2.5.1
By-passing of components in the exhaust system ...................................................................... 19
10.2.5.2
Multi-engine installations with common exhaust pipe ................................................................. 19
10.2.6
Laying exhaust pipes .................................................................................................................. 22
10.2.7
Additional hints for the design of exhaust heat exchangers and silencers ................................. 23
10.2.7.1
Lifting lugs ................................................................................................................................... 23
10.2.7.2
Structure-borne noise .................................................................................................................. 23
10.2.7.3
Installation ................................................................................................................................... 23
10.2.7.4
Cleaning of exhaust heat exchangers ......................................................................................... 23
10.2.8
Exhaust stacks ............................................................................................................................ 24
Chapter_10 - Exhaust system.docx
02999408
Page 2 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
10.
Exhaust system
The function of the exhaust system is to transfer gases produced by combustion in the engine to the
atmosphere. In order to comply with the environmental regulations that apply at the installation site in respect
to both the emission of exhaust gases and noise, the exhaust system must be designed to fulfil these
necessary requirements.
If the internal combustion process in the engine itself cannot be made to fulfil the local regulations for the
emission of exhaust gases, it will be necessary to treat them, e.g. by use of catalytic converters or thermal
reactors.
The exhaust noise emissions can be minimized by installing silencers.
Every engine must be fitted with a fully independent exhaust system.
10.1
Permissible exhaust backpressure
Besides the exhaust mass flow and the exhaust temperature, the most important design parameter
determining the size of the exhaust system is the permissible exhaust backpressure.
Exceeding the permissible exhaust backpressure has a significant influence on performance, fuel
consumption and the thermal load of the engine. The exhaust backpressure is measured immediately behind
the turbine at full load and must not be exceeded.
Flow resistance in pipes, elbows, expansion joints, exhaust heat exchangers, catalytic converters, silencers,
spark arresters, deflection hoods and stacks creates the exhaust backpressure. All resistance must be taken
into account when determining the backpressure.
The volume flow dependent resistance in exhaust pipes and elbows can be determined with the aid of the
diagram in Fig. 10.1.
For the resistance of components installed in the exhaust system, please refer to the data sheets of these
components.
The permissible exhaust backpressures for the individual engine series are listed in Table 10.1.
Chapter_10 - Exhaust system.docx
02999408
Page 3 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
Table 10.1
Engine model series
Permissible exhaust backpressure
Minimum / Design
[mbar]
TCD 2016
- / 35
TCG 2016 C
30 / 50
TCD 2020
- / 20
TCG 2020(K)
30 / 50
TCG 2032
30 / 50
Exhaust backpressure measured behind the turbine
In designing the exhaust system, the information contained in the data sheets for the individual engine series
must be taken into account.
A useful guide to the design of the exhaust system is the speed of the exhaust gas in the exhaust pipe. This
should be in the range of 20-35 m/s.
When selecting materials, the temperature increase in the partial load range must be borne in mind.
Chapter_10 - Exhaust system.docx
02999408
Page 4 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 10.1 Flow resistance for exhaust pipes
[m
]
VA * 10³ [m³/h]
TA ca. 400 °C
EL
∆p [hPa / m]
1 Hektopascal = 1 mbar
Chapter_10 - Exhaust system.docx
02999408
Page 5 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
Legend to Fig. 10.1
VA
Exhaust volume flow
TA
Exhaust reference temperature
∆p
Pressure loss per meter of straight pipe
EL
Substitute length for a pipe bend 90°
NW
Nominal width of the exhaust pipe in millimeters
R
Radius of the bend
d
Pipe diameter in millimeters
Example for Fig. 10.1
Specified:
VA = 9000 m³/h
Straight pipe:
l = 10 m
Bends:
3 bends 90° with R/d=1
Wanted:
∆p of the pipe
Solution:
NW 250
approx. 44 m/s
∆p = 0.32 hPa / m straight pipe
Substitute length
for a bend:
4.95 m
Total pipe length:
Lges = 10+(3*4.95) = 24.85 m
∆pges = 24.85 * 0.32 = 8 hPa (mbar)
Chapter_10 - Exhaust system.docx
02999408
Page 6 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
10.2
Exhaust system components
10.2.1
Catalytic converters
All gas engines operate on the lean-burn principle, where thanks to the large surplus of air, the NOx
emissions produced by the combustion process are already below the limits prescribed in TA-Luft
1
(NOx ≤ 500 mg/m ). Dependent on engine type and emissions requirements, it may be necessary to install
3
an oxidation catalyst for the further reduction of CO components. The process is particularly economical and,
with regard to all aspects of operation, it is both clean and reliable over the long term. Of all catalytic
converter systems, the oxidation type catalyst is the most resistant to harmful components in the fuel gas.
The catalytic converter must be the first element in the exhaust system.
10.2.1.1 Planning notes for catalytic converters
10.2.1.1.1
Lifting lugs
As the catalyst housing can weigh more than 100 kg (especially for big engines), installation should be
considered at an early stage of planning. Housings fitted with cones on both sides can be suspended using
round slings. In very tight spaces or with other housing shapes, it may also be advisable to provide lifting
eyelets. This is important for larger catalyst disks, which are installed on the heads of heat exchangers or
silencers.
10.2.1.1.2
Insulation
The catalyst insulation must be designed in such a way that it can be easily dismounted in order to clean or
replace the catalytic converter. This is also beneficial for retightening the flange connections.
1
TA-Luft = Technische Anleitung zur Reinhaltung der Luft (Technical instructions on air quality control)
Chapter_10 - Exhaust system.docx
02999408
Page 7 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
10.2.1.1.3
Installation
If not otherwise specifically indicated, catalysts can be installed in any position, i.e. horizontally, vertically or
diagonally. The flow direction only needs to be taken into account where the housings have different length
cones. The inlet cone is usually longer and slimmer than the outlet cone.
When installing a catalytic converter, it is very important that the exhaust gas flow is even through the
catalyst. If this is not the case, the emission conversion is not at its optimum and the stress on certain parts
of the catalyst is out of proportion and can cause damage.
To avoid this, two different installation options are available:
Where the unit is to be installed in the exhaust line, the diameter of the line must be adapted to that of the
exhaust catalyst with the aid of a cone. To ensure that the flow into the catalytic converter is as even as
possible, the taper of the cone on the inlet side must be between 10° and 20° and the exhaust line must be
arranged accordingly (smoothing path) (Fig. 10.2). The nominal bore of the exhaust pipe in front of the taper
of the cone on the inlet side must be large enough to ensure an exhaust speed of < 40 m/s.
In case of installation into a silencer or an exhaust heat exchanger, a head pipe with radial exhaust inlet
according to figure 10.3 is used which guarantees an even flow into the catalyst. The distance between the
center line of the inlet pipe and the flange connection of the catalyst should at least be as long as the
catalyst's diameter. The nominal bore of the inlet nozzle in front of the catalyst must be large enough to
ensure an exhaust speed of < 40 m/s.
Both the installation into the head pipe of the silencer described and the design with cones serve to achieve
as high a homogeneous flow into the catalyst as possible. Only a homogeneous flow will achieve the full
effect of the catalyst.
During operation, the catalysts and their housings must remain free of tensions which result from expansion
of the exhaust pipes at operating temperature. Expansion joints must be in suitable positions in the exhaust
system.
Chapter_10 - Exhaust system.docx
02999408
Page 8 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 10.2
Fig. 10.3
4
2
2
L≥D
1
3
5
1
Exhaust flow direction
2
Catalyst
3
Temperature measuring nozzle
4
Exhaust inlet
5
Head pipe
D
Catalyst diameter
L
Spacing from catalyst inlet to center of exhaust inlet
Chapter_10 - Exhaust system.docx
02999408
Page 9 / 24
3
VD-S 2014-06 EN
Caterpillar confidential: none
10.2.1.1.4
Inspection
The catalyst should be checked against mechanical damage or contamination at regular intervals. If the
engine runs with particle free natural gas and low oil consumption, a yearly inspection is sufficient. For other
types of gases or in case of high oil consumption, an inspection is recommended every 2-6 months.
These regular inspections should prevent the system from being shut down.
It must be ensured that good access to the catalyst is possible and that inspections can be carried out
efficiently right from the planning stage.
10.2.1.2 Installation specification oxidation type catalysts
The catalytic converters are supplied complete with hole flange housing for installation in the silencer (head
pipe) or as cone catalysts with connection flanges for installation in the exhaust pipe.
For the catalyst flange connection, the installation specification 1240 2390 UE 0499-41 must be complied
with:
10.2.1.2.1
Seals
The seals are designed for medium temperatures up to max. 650 °C. The seals are made up of segments;
one seal set comprises two layers. It is essential to ensure that the segment butt joints are offset between
the individual layers. The special properties of the seal in the high temperature range require that these
installation specifications be adhered to exactly.
10.2.1.2.2
Screws
The screws are composed of high-temperature resistant steel, which is especially suitable for use at high
temperatures.
Chapter_10 - Exhaust system.docx
02999408
Page 10 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
10.2.1.2.3
Installation
•
The system must be cooled.
•
Direction of flow through the catalyst; cross bracing for the matrix on the outflow side.
•
Clean and check the sealing surfaces.
•
Install the catalyst and seals, fit the screws with a little high-temperature paste and tighten
gently by hand.
•
Check that seals are positioned correctly.
•
Tighten the screws in alternate groups of 2-6 with a torque wrench to 40 Nm.
•
Then tighten all the screws one after another around the perimeter to the nominal torque of
50 Nm.
•
The system can now be commissioned.
•
For exhaust temperatures above 400 °C, because of the characteristics of the seal, the
flange connection must be retightened with the nominal torque after approx. 20 hours in
operation. This must be done when the flange connection has cooled down.
•
In order to avoid damage to the housing during operation, it is important not to put pressure
or tensile stress onto the catalyst housing. For this reason, catalyst housings always have to
be installed stress free.
•
As the catalyst must be placed as close as possible to the engine for temperature reasons,
there are usually no long pipes or other components running from the catalyst. For this
reason, a simple expansion joint which can withstand axial and radial forces by means of a
pipe elbow is sufficient. If there is a longer pipe after the catalyst housing, an additional
expansion joint is recommended.
•
In the event that the catalyst housing is installed in the piping, this must be supported by
means of one or more columns on the foundation or on a steel structure. Suspensions are
also possible. If the catalyst housing is installed in the head pipe of a heat exchanger or a
silencer by means of a flange connection, it may be necessary to support the head pipe
separately by means of a sliding seat. The fixing point in this case must be on the heat
exchanger or the silencer. This will not only ensure that the housing is installed free of
tension, but also that it can be easily installed and removed.
Chapter_10 - Exhaust system.docx
02999408
Page 11 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
10.2.1.3 Cleaning the catalyst
If the flange connection is opened to clean the catalyst, new seals and screws must subsequently be fitted.
Remnants of the old seals must be completely removed beforehand.
Installation must take place as described above.
10.2.1.4 Operating recommendations for oxidation type catalysts
Removing hydrocarbons and carbon monoxide with an oxidation type catalyst is a simple method of cleaning
the exhaust and this catalyst has a wide operating range.
To ensure reliable catalytic converter operation, the following points must be noted:
•
Misfiring must be avoided as non combusted fuel in the catalytic converter can lead to
undesired after-burning with unduly high exhaust temperatures. Even temperatures below
the melting temperature of the supporting material (above 700 °C) cause premature aging.
Increasing temperatures may also lead to damage of the catalyst.
•
Explosive ignitions in the exhaust pipe can lead to the mechanical destruction of the catalyst
if the client has not provided explosion flaps.
•
To avoid thermal aging, the exhaust temperature on admission to the catalytic converter
should be between 400 - 560 °C. Because of the exothermic reaction in the catalytic
converter, the temperature of the exhaust is increased. This temperature must not exceed
650 °C. A temperature-monitoring device must therefore be provided after the catalytic
converter, which will cut off the fuel supply if this limit is exceeded.
•
Low-ash, low-alloy engine oils must be used in order to minimize deposits in the catalytic
converter. Blockages of the ducts caused by lube oil incineration ash can significantly impair
the functioning of the catalyst.
Moisture or solvents must be prevented from affecting the catalyst; passing through the dew
point when starting up and shutting down the system is an exception to this rule.
•
If the catalyst is wet, it must be protected from the effects of freezing. The only exception is
residual moisture, which comes out from the condensate caused by a cold start at low
external temperatures. For example, an installation above a container is permissible if it is
ensured that moisture never gets into the exhaust pipe from outside.
Chapter_10 - Exhaust system.docx
02999408
Page 12 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
•
In the case of biogas systems, the use of oxidation catalysts is only possible if the
combustion gas has been break-proof fine desulfurized beforehand (see Chapter 9
Combustion Gas). The oxidation catalysts even age through the sulfur compounds.
However, the greater damage occurs in the exhaust heat exchanger. The oxidation of SO2
(resulting from sulfur compounds in the engine exhaust gas) to SO3 shifts the dew point so
that the dew point is fallen below here with conventional designs of exhaust heat
exchangers, and sulfuric acid condenses correspondingly. This leads to massive
contamination of the exhaust heat exchanger and to subsequent acid attacks through to
destruction of the exhaust heat exchanger.
•
When running on landfill or sewage gas, there is only limited potential for the use of oxidation
type catalysts, even when a gas purifier is fitted ahead of the engine
•
The following substances are harmful to the catalyst and must be avoided in the fuel gas:
silicon, silicon products, sodium, calcium, lead, bismuth, mercury, manganese, potassium,
iron, arsenic, antimony, cadmium; under certain circumstances also compounds of chlorine,
sulfur and phosphorus; as well as organic and inorganic compounds.
•
The catalytic converter should be installed before the silencer, in order to prevent obstruction
of the catalytic converter due to the detachment of absorbent wool. Obstruction of the
catalyst will lead to an increase in the exhaust backpressure and the reduction of pollutants
becomes worse. It is not easy to remove the wool from the channels of the catalyst. On the
other hand, installation after a pure reflection silencer without sound-absorbent wool is
permissible provided that exclusively stainless steel parts are used.
•
In order to protect the catalyst against overheating, the catalyst should only be installed in
the exhaust system when the engine has been adjusted and is running trouble free. This
applies to both initial commissioning and subsequent maintenance work.
•
Sulfur in the form of SO2 has hardly any influence on the catalytic converter at temperatures
over 420 °C. However, it must be ensured that some of the SO2 is oxidized to SO3 in the
catalytic converter. So if the dew point in the exhaust system is undershot, sulfurous acid is
generated for SO2 and for SO3. Sulfuric acid. The dew point is approx. 140 °C.
•
Even though solid substances, which are found in the exhaust gas flow and deposited on the
catalyst, will not directly damage the catalyst, the emission reduction will be degenerated
over time. The active surface will be partially covered. If there is an increase in the amount of
deposits, the individual channels will become blocked. The exhaust gas then has to go
through the channels still open. Therefore, the flow velocity and the emission reduction will
decrease. The increase of the backpressure results in a power reduction, or worse still, the
shut down of the engines. This can be monitored by measuring the differential pressure.
Chapter_10 - Exhaust system.docx
02999408
Page 13 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
10.2.1.5 Limit values for exhaust composition
2
The life expectancy of the catalyst largely depends on the concentration of catalyst toxins. Therefore, the
exhaust should be free from the known compounds which cause damage to the catalyst, e.g. silicon, silicon
products, sulphur, phosphorus, arsenic and heavy metals. The concentration of catalyst toxins should not
exceed the following values:
Catalyst toxin
2
Warranty period
Warranty period
8000 operating hours or
16000 operating hours or
1 Year
2 years
Silicone
0 µ g / Nm
3
0 µ g / Nm
3
Silicon
0 µ g / Nm
3
0 µ g / Nm
3
Arsenic
< 1 m g / Nm
3
< 1 m g / Nm
3
Mercury
< 1 m g / Nm
3
< 1 m g / Nm
3
Lead
< 2 m g / Nm
3
< 1 m g / Nm
3
Cadmium
< 10 m g / Nm
Zinc
< 100 m g / Nm
Bismuth
< 1 m g / Nm
3
< 1 m g / Nm
3
Antimony
< 1 m g / Nm
3
< 1 m g / Nm
3
Hydrogen sulfide
< 10 mg / Nm
3
< 5 mg / Nm
3
Sulfur
< 10 mg / Nm
3
< 5 mg / Nm
3
Ammonia
< 100 mg / Nm
Phosphorous compounds
and halogens
< 5 mg / Nm
Chlorine
< 10 m g / Nm
3
< 10 m g / Nm
3
Sodium
< 10 m g / Nm
3
< 10 m g / Nm
3
Calcium
< 10 m g / Nm
3
< 10 m g / Nm
3
Manganese
< 10 m g / Nm
3
< 10 m g / Nm
3
Potassium
< 10 m g / Nm
3
< 10 m g / Nm
3
Iron
< 10 mg / Nm
3
< 5 mg / Nm
3
3
3
< 10 m g / Nm
3
< 50 m g / Nm
3
< 100 mg / Nm
3
< 1 mg / Nm
3
3
3
Source: Air Sonic
Chapter_10 - Exhaust system.docx
02999408
Page 14 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
10.2.1.6 Oxidizing catalysts for bio- and sewage gas engines
3
Most manufacturers will not cover their catalysts for warranty if the engine is operated with landfill or sewage
gas. The terms of warranty need to be clarified in the design stage in case a catalyst should be installed for
bio and sewage gas operation.
The problem with these systems is that no operator can forecast what the pollutants will be in the exhaust in
the coming weeks, months or years.
Even a comprehensive analysis, which shows low pollutants, is only a momentary record. In most cases, the
exhaust is not tested for all possible pollutants, and on the other hand, the composition may already be
different after a few days.
This is also confirmed by the fact that similar sewage gas systems do achieve different life expectancy for
the same catalysts.
For biogas, the situation is a little different. In special cases, it can be considered whether a warranty can be
granted. However, an accurate exhaust analysis and accurate description of the system is necessary.
Without a sufficient gas cleaning system, no guarantee for the pollutant conversion of the catalyst will be
given for sewage gas, landfill gas and biogas.
10.2.2
Exhaust silencers
The task of an exhaust silencer is to dampen the exhaust noise produced when the engine is operating to a
level commensurate with the respective surrounding environment. The silencers used take the form of
reflection, absorption or combination type silencers. Reflection silencers achieve their maximum effect in the
lower 125-500 Hz frequency range, whilst absorption silencers are most effective in the 250-1000 Hz range.
In the case of combination silencers, the first part is designed as a reflection silencer and the second as an
absorption silencer. The combination silencer unites the characteristics of both silencer types and so
achieves a significant silencing effect over a broad frequency range.
In cases in which the required level of silencing cannot be achieved with a combination silencer, additional
absorption silencers must be fitted after the combination silencer. An expansion joint must be installed
between the silencers to insulate against structure-borne noise.
See also Chapter 4.3, Noise issues.
The exhaust silencers go through heat expansion at operating temperature. Fixed and loose supports must
be provided accordingly during planning.
3
Source: Air Sonic
Chapter_10 - Exhaust system.docx
02999408
Page 15 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
10.2.3
Exhaust heat exchanger
Exhaust heat exchangers are used to recover the heat from the exhaust. These exhaust heat exchangers
are built in accordance with the European pressure vessel guideline (PED 97/23/EC). The testing procedures
4
5
are based on national regulations, for example the TRD and AD leaflets of the manufacturing country.
In CHP systems, the exhaust heat exchangers are usually made of stainless steel (1.4571). For natural gas
applications, the exhaust temperature at the heat exchanger outlet is normally 120°C. To prevent corrosion,
it must be ensured that the exhaust gas does not fall below the dew point.
In all systems where the exhaust heat exchangers are mounted higher than the engine, a continuous
condensate drain / separator generally has to be installed. This will prevent water from finding its way into
the engine via the exhaust pipe in the case of a water breakthrough in the exhaust heat exchanger.
In the case of systems which are operated on landfill gas or sewage gas, the increased content of sulfur,
chloride, hydrochloric acid and hydrofluoric acid in the exhaust must be borne in mind when selecting
materials. These components have a highly corrosive effect and can even damage stainless steel exhaust
heat exchangers.
If there is a risk of increased concentration of chlorine or other halogenated components in the burning gas,
exhaust tubes made of thick low alloyed boiler steel are preferable to stainless steel tubes due to danger of
local pitting and stress corrosion. This steel is less sensitive against this type of corrosion. In order to avoid
wide-spread corrosion, it is absolutely necessary to prevent condensation of the above mentioned acids and
water out of the exhaust gas. In this case, the exhaust temperature should be > 180 °C.
For systems with sulfur in the combustion gas and with an oxidation catalyst pre-connected to the exhaust
heat exchanger, a fine desulfurization of the combustion gas must be carried out. In the oxidation catalyst,
sulfur dioxide in the exhaust gas is oxidized to form sulfur trioxide. When cooling the exhaust gas in the
connected exhaust heat exchanger, sulfur trioxide reacts with water and forms concentrated sulfuric acid.
Concentrated sulfuric acid has a highly corrosive reaction and can quickly cause destruction to the exhaust
heat exchanger. Furthermore, operating faults may be caused by an increased exhaust backpressure, which
has been created by sulfurous deposits. Effective protection for this system design can only be guaranteed
with a fine desulfurization of the combustion gas.
The water qualities in respect to the heating requirements must be complied with (Technical Circular for
coolant).
In large heating circuits, complying with the minimum requirements for the water quality may pose a problem.
In this case, the installation of a small closed decoupling circuit between exhaust heat exchanger and
heating circuit is urgently recommended. In the technical circular for cooling water, a chloride content smaller
than 20 mg/l is required for the coolant in the heating circuit. For increased chloride ion content and
increased flow temperatures in the heating circuit, the stainless steel pipes usually used in the exhaust heat
exchangers are subject to stress corrosion cracking, which can lead to the exhaust heat exchanger being
damaged. Therefore, providing there are no contrary requirements on the exhaust side, an exhaust heat
4
5
TRD = Technische Regeln für Dampfkessel = Technical Directions for Steam Boilers
AD = Arbeitsgemeinschaft Druckbehälter = Pressure Vessels Working Party
Chapter_10 - Exhaust system.docx
02999408
Page 16 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
exchanger with water-bearing components (pipes, pipe plate and casing) made of normal steel should be
envisaged
for
decoupling
of
the
exhaust
heat
exchanger
in
the
heating
circuit
and
water
temperatures >110 °C.
(Also see Chapter 6.7, The heating circuit & 6.8, Coolant in the heating circuit)
The exhaust heat exchangers go through heat expansion at operating temperature. Fixed and loose
supports must be provided accordingly during planning.
Chapter_10 - Exhaust system.docx
02999408
Page 17 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
10.2.4
Exhaust components in biogas systems
The following items must be considered when selecting exhaust systems for biogas systems:
•
For biogas systems with a maximum permissible sulfur content (total) of < 2.2 g/m³n or a
H2S content of < 0.15 % volume in the biogas, the exhaust gases should not be cooled
below 180 °C. The limit values must be kept permanently. In this case an oxidation catalyst
must not be used.
•
To cool down an exhaust to 120 °C, in addition to our "Minimum characteristics of
combustion gases in gas engines", the sulfur content of the biogas has to be limited to < 0.1
g/m³n or the H2S content to < 70 ppm.
•
When using oxidation catalysts, a fine desulfurization of the combustion gas must be carried
out. This must always completely remove the H2S (validation limit of the field measuring
instrumentation, but maximum 5 ppm H2S). This can be implemented technically with an
activated carbon adsorber with doped/impregnated active carbon.
•
In biogas systems, the exhaust silencers are to be preferably mounted ahead of the exhaust
heat exchanger, as the risk of acid condensation is lower at higher exhaust temperatures.
•
Furthermore, a continuous condensate drain has to be installed. The condensate drain has
to be checked at regular intervals during operation and must be protected against freezing in
the winter.
•
The exhaust side of the heat exchanger must be cleaned regularly
•
All components carrying exhaust gas must be insulated due to the risk of condensation; this
is imperative outdoors, too.
10.2.5
Exhaust flaps
For most applications, the layout of the exhaust system is individual for each engine. In these systems,
exhaust flaps are used for by-passing exhaust components. With multi-engine installations where engines
must be connected to one common exhaust system, exhaust flaps must be provided for the disconnection of
the individual engine from the common exhaust system. This is, for example, the case if the exhaust gas of
several engines is combined for the operation of a common absorption chiller.
Exhaust flaps are not completely tight in the fully closed position, there is always a small amount of leakage
flow.
The requirements concerning the tightness of exhaust flaps have to be considered with the individual
application demands (e.g. TRD 604 Bl. 2).
Chapter_10 - Exhaust system.docx
02999408
Page 18 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
10.2.5.1 By-passing of components in the exhaust system
For by-passing exhaust components such as, for example, exhaust heat exchangers and/or steam boilers,
exhaust flaps are used. The flaps' drive is via an electric motor or pneumatic actuator. They simply have an
open/close function and no control function. Preferably, flap combinations are used, i.e. there is only one
drive mounted on one of the flaps whereas the other flap drive is via a reverse-acting mechanical link.
10.2.5.2 Multi-engine installations with common exhaust pipe
For multi-engine systems with a common exhaust pipe, exhaust gas must be prevented from uncontrolled
backflow to the engines currently not in operation. Uncontrolled backflow of exhaust gas will cause corrosion
in this engine. There are different possibilities for avoiding backflow of exhaust gas by a respective
arrangement of exhaust flaps. They are described in the following.
Exhaust flap arrangement with separate exhaust pipe
With this system, an exhaust flap is arranged behind the engine. Using a bypass flap combination, the
exhaust gas is either led to the common exhaust manifold or to the open air via a separate exhaust pipe (see
also Figure 10.4). When the engine is not in operation, the exhaust flap behind the engine (flap 1) and the
flap in the pipe branch to the common exhaust manifold (flap 2) are closed, whereas the flap in the pipe
branch to the open air (flap 3) is open. In the common exhaust manifold, there will be an overpressure when
the other engines are running and, in consequence, there will be a slight leakage flow via flap 2 into the
space between. As the leakage flow is comparably small regarding the large free cross section to the open
air (flap 3 open), the leakage gas will go to the open air and the engine will be protected by closed flap 1.
Before starting the engine, the exhaust flap 1 behind the engine will be opened; in the first instance, the
exhaust flow is via flap 3 to the open air. After the running up phase of the engine, the exhaust can lead to
the common exhaust pipe via operation of the exhaust by-pass flap combination. The exhaust flow via flap 3
to the open air is closed and, simultaneously, the path to the exhaust manifold is opened.
This arrangement has the following advantages:
•
Each engine can be operated individually, i.e. it is independent on the conditions in the
common system.
•
The engine can be started without exhaust backpressure.
•
With electricity-led operation, the exhaust heat can be adjusted to the active demand by
switching the by-pass to the open air.
This arrangement is highly recommended with several engines connected to one common exhaust system.
Chapter_10 - Exhaust system.docx
02999408
Page 19 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 10.4
Common exhaust system with by-pass to the open air
Bypass ins Freie
5
4
Sammelleitung
2
2
33
11
Motor
1
Exhaust flap 1
2
Exhaust flap 2
3
Exhaust flap 3
4
Bypass to open air
5
Exhaust manifold
Motor
Exhaust flap arrangement with air lock
With this system, there are two exhaust flaps arranged one after another in the exhaust pipe to the common
exhaust manifold. The flaps can be opened and closed via an actuator. The sealing air line is connected in
the space in-between both flaps. The supply of sealing air is via blower with successive flap (see also Figure
10.5).
When the engine is not running, both flaps (flap 1 and 2) are closed and sealing air is blown into the space
between the flaps. The pressure of the locking air must be higher than the maximum pressure in the exhaust
manifold and the volume flow of the sealing air must be greater than the leaking rate of the exhaust flaps.
There is no possibility of exhaust backflow to the non-running engine.
Before starting the engine, both exhaust flaps must be opened, flap 3 after the blower will be closed and the
sealing air blower will be switched off. The engine has to start at the increased exhaust pressure level
existing in the exhaust manifold. The engine has to start at the increased exhaust pressure level existing in
the exhaust manifold.
Advantage: No additional exhaust pipe to the open air is necessary.
Chapter_10 - Exhaust system.docx
02999408
Page 20 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 10.5
Common exhaust system with air lock
4
Sammelleitung
2
2
33
1
1
Motor
1
Exhaust flap 1
2
Exhaust flap 2
3
Air flap
4
Exhaust manifold
Motor
Exhaust flap arrangement with intermediate venting
With this system, too, there are two exhaust flaps arranged one after another in the exhaust pipe to the
common exhaust manifold. The flaps can be opened and closed via an actuator. The sealing air line is
connected in the space in-between both flaps. The leakage gas in the space between the flaps is extracted
by the extracting fan and routed to the open air (see also Figure 10.6).
When the engine is not running, both flaps (flap 1 and 2) are closed and a slight negative pressure is
maintained in the space between the exhaust flaps. The leakage gas flowing via the exhaust flaps is routed
to the open air via the extractor fan. Leakage gas flowing into the engine when not running is avoided.
Before starting the engine, both exhaust flaps must be opened, flap 3 before the blower will be closed and
the extractor will be switched off. The engine has to start at the increased exhaust pressure level existing in
the exhaust manifold. The engine has to start at the increased exhaust pressure level existing in the exhaust
manifold.
Disadvantage: A separate pipe to the open air must be provided, but the cross section is comparably small in
relation to a full-sized exhaust pipe as per Fig. 10.4 above.
Chapter_10 - Exhaust system.docx
02999408
Page 21 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 10.6
Common exhaust system with intermediate venting
4
Sammelleitung
2
2
3
3
1
1
Motor
1
Exhaust flap 1
2
Exhaust flap 2
3
Air flap
4
Exhaust manifold
10.2.6
Motor
Laying exhaust pipes
Because of the relatively high exhaust temperatures, heat expansion is quite considerable (approx. 1-1.5
mm/m and 100 °C).
To avoid unacceptably high stresses in the exhaust pipes, expansion joints must be fitted at suitable
locations to compensate for the heat expansion in the pipes and components. Depending on how the
exhaust line is laid, the supports should be fixed and moveable. They must not be fixed on the exhaust
turbocharger or the engine. The first fixed point must be located directly after the expansion joint at the
turbocharger outlet. In particular, components integrated in the exhaust system such as heat exchangers,
catalytic converters, silencers, etc. must be protected against stresses arising from the expansion of the
exhaust pipe by fitting expansion joints on the inlet and outlet sides. The exhaust expansion joints must be
installed in accordance with the manufacturer's directions (permissible axial and lateral offset must be
complied with). Because of the high operating temperatures, the exhaust system is permanently provided
with insulation.When installing pipes outside, a contact protection is only sufficient for exhaust pipes after
exhaust heat exchangers.
Chapter_10 - Exhaust system.docx
02999408
Page 22 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
10.2.7
Additional hints for the design of exhaust heat exchangers and silencers
10.2.7.1 Lifting lugs
For better handling of the components during installation, lifting lugs should be provided.
10.2.7.2 Structure-borne noise
When affixing the unit, it is important to note that where appropriate, sound-technology aspects also play a
role here. In this case, it must be ensured that minimal sound is transmitted to other components. For this
reason, vibration dampers are installed in the feet or the mounting. This applies equally to standing as well
as suspended versions. As the piping and the catalyst housing are insulated for temperature reasons, no
further sound insulation of these components is necessary in the majority of units.
10.2.7.3 Installation
When installing catalyst housings, exhaust heat exchangers and silencers, careful handling is essential to
ensure that protruding parts such as probes, feet, etc will not be damaged.
This inevitably leads to damage to the housing and components. Mounting feet are only for taking the design
load. The client is requested to find out about the installation situation, preferably when placing the order. If a
housing has sliding supports which are not directly fixed to concrete or steel frames but mounted to a sliding
plate, it must be ensured that a lubricant is used between foot and sliding plate. Periodic checks should be
conducted to ensure that enough lubricant is always present during operation.
10.2.7.4 Cleaning of exhaust heat exchangers
When installing the exhaust heat exchangers, enough free space must be considered for cleaning purposes.
Chapter_10 - Exhaust system.docx
02999408
Page 23 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
10.2.8
Exhaust stacks
Especially in the vicinity of residential areas, it is necessary to avoid impermissible engine exhaust
emissions. Stacks are used to transport the exhaust gas up to a high level in the atmosphere.
The exhaust stacks must be insulated to avoid condensation in the exhaust system. The speed of the
exhaust gas in the stack should be between 15-20 m/s. Above 20 m/s, there is a risk of resonance vibrations
in the gas column. A high outlet speed leads to a dynamic increase in effective stack height and improves
the dispersal of the gases, but it also increases the flow noise.
The draught effect of the stack, which is dependent on stack height, lessens the backpressure in the exhaust
system. However, installing deflector hoods at the mouth of the stack can partially or even entirely offset the
stack draught, with the result that, in a worst-case scenario, the backpressure of the stack must also be
regarded.
Exhaust stacks must be equipped with permanent drainage and weather-induced contamination (e.g. rain,
snow) must be excluded.
All components must be provided with a permanent drainage facility at their lowest point. Condensate
disposal must be clarified on a case-by-case basis and, where necessary, it must be directed to a
neutralization facility.
Chapter_10 - Exhaust system.docx
02999408
Page 24 / 24
VD-S 2014-06 EN
Caterpillar confidential: none
Power plants layout
Chapter 11
Compressed air system
06-2014
Caterpillar Energy Solutions GmbH Carl-Benz-Straße 1 D-68167 Mannheim Phone: +49(0)621 384-0 Fax: +49(0)621 384-8612
Caterpillar confidential: none
Contents
11.
Compressed air system .............................................................................................................. 3
11.1
Compressed air system components ............................................................................................ 5
11.1.1
Compressors ................................................................................................................................. 5
11.1.2
Compressed air bottles ................................................................................................................. 5
11.1.3
Compressed air pipes ................................................................................................................... 5
11.2
Low-pressure air system ............................................................................................................... 6
11.3
Safety Note.................................................................................................................................... 6
11.4
Compressed air quality ................................................................................................................. 6
Chapter_11 - Compressed air system.docx
02999408
Page 2 / 6
VD-S 2014-06 EN
Caterpillar confidential: none
11.
Compressed air system
Some engine models are started with compressed air. In this case, the engine is started with a compressed
air starter which acts on a flywheel gear rim. Table 11.1 shows the starting systems employed for the various
series.
Table 11.1
Engine type
Compressed air
starter via gear rim
Electric starter

TCG 2016
TCG 2020(K)

TCG 2032

Chapter_11 - Compressed air system.docx
02999408
 (Standard
Page 3 / 6
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 11.1 shows a starting air system for an engine with a compressed air starter.
1
Compressor
2
Oil separator
3
Pressure gauge
4
Non-return valve
5
Compressed air bottle
6
Condensation deflector
7
High-pressure shut-off valve
8
Dirt trap
9
Pressure regulator
10
Safety valve
11
Starting valve
12
Starter
13
Control valve
14
Pressure switch / Compressor ON / OFF
15
Pressure switch / Alarm min. pressure
Chapter_11 - Compressed air system.docx
02999408
Page 4 / 6
VD-S 2014-06 EN
Caterpillar confidential: none
The compressor (1) fills the compressed air bottle (5), which is equipped with a water separator (6) via the
non/return valve (4) and the oil separator (2). The filling pressure of the bottle can be read from the pressure
gauge (3). The high-pressure shut-off valve (7) and the dirt trap (8) provide the starter valve (11) with
compressed air. When the engine starts, the starter valve is opened by the control valve (13) and the starter
(12) is pressurized with compressed air. The engine starts.
11.1
Compressed air system components
11.1.1
Compressors
Redundant diesel or electric compressors are provided with the appropriate equipment for pressure released
starting. Compression generally takes place in two stages with intermediate cooling, the final pressure is 30
bar.
The design must be matched to the total volume of the compressed air bottles connected to the system.
11.1.2
Compressed air bottles
The compressed air bottles are implemented as either vertically or horizontally installed vessels. The volume
of the bottles is dependent on the type and number of engines connected and the required number of starts
to be achieved without refilling the air bottles.
Compressed air containers must be drained regularly. Vertical vessels can be drained via the valve head,
horizontal vessels must be installed with a slope towards the base of the vessel, so that they can be properly
drained through the base. Generally automatic drainage facilities must be provided. These must always be
arranged beneath the vessel; the line from the vessel to the drain must always be laid with a continuous
slope.
11.1.3
Compressed air pipes
An oil and water separator must be installed in the filling pipe between the compressor and the compressed
air bottle if this is not provided on the compressor.
The starting pipe between the compressed air bottle (head of vessel) and the main starter valve must be as
short as possible and must include the minimum number of elbows. Dependent on how the pipes are laid, an
automatic drain facility must be fitted at the lowest points.
It is recommended that a dirt trap with drain-off valve be installed in the starter line. When fitting the dirt trap,
pay attention to the orientation (sieve always to be removed from below) and the direction of flow. The dirt
trap is a component of the start system for gensets with a compressed air starter.
In the case of multi-engine systems, a ring circuit may increase the starting availability of the system.
Welding deposits and any other contamination must be avoided in the compressed air pipe.
The starting air pipes must always be stainless steel pipes (see also chapter 20.2)!
Chapter_11 - Compressed air system.docx
02999408
Page 5 / 6
VD-S 2014-06 EN
Caterpillar confidential: none
11.2
Low-pressure air system
In the case of series TCG 2032, the pneumatic shut-off valves in the gas control line are supplied as
standard with compressed air at max. 10 bar via a connection to the starter group. The low-pressure
connection is not required if gas control lines are used with solenoid valves.
11.3
Safety Note
When carrying out work on the engine, it is essential to shut off the compressed air supply to the engine to
prevent the engine from being started unintentionally.
11.4
Compressed air quality
The compressed air must be free from dust and oil. The compressors and air filters must be designed
accordingly.
Chapter_11 - Compressed air system.docx
02999408
Page 6 / 6
VD-S 2014-06 EN
Caterpillar confidential: none
Power plants layout
Chapter 12
Measuring, monitoring and
limiting devices
06-2014
Caterpillar Energy Solutions GmbH Carl-Benz-Straße 1 D-68167 Mannheim Phone: +49(0)621 384-0 Fax: +49(0)621 384-8612
Caterpillar confidential: none
Contents
12.
Measuring, monitoring and limiting devices ............................................................................ 3
12.1
Monitoring as per DIN EN 12828 .................................................................................................. 3
12.2
Monitoring as per TRD 604 ........................................................................................................... 3
12.3
Temperaturemeasurement............................................................................................................ 4
12.3.1
Installation note for temperature sensors ...................................................................................... 4
12.4
Differential pressure monitoring .................................................................................................... 5
12.5
Exhaust backpressuremonitoring .................................................................................................. 5
Chapter_12 - Measuring, monitoring and limiting devices.docx
02999408
Page 2 / 6
VD-S 2014-06 EN
Caterpillar confidential: none
12.
Measuring, monitoring and limiting devices
These are used to protect and control the CHP set, as well as to fulfil the safety requirements for heat
generators.
Declarations of conformity and CE markings are necessary for the measuring, monitoring and limiting
devices -pursuant to the Low Voltage Directive 2006/95/EC and the Electromagnetic Compatibility Directive
2004/108/EC.
The instructions for operation and use and the manufacturer's maintenance instructions must be taken into
account when installing the measuring, monitoring and limiting devices.
When installing, it is essential to take account of the following:
12.1
•
permissible ambient temperature
•
permissible operating medium
•
permissible medium temperature
•
permissible operating pressure
•
permissible installation site
•
permissible flow speed
•
requisite minimum immersion depth
•
Choice of cables as described in chapter 17 (shielded sensor connection line)
Monitoring as per DIN EN 12828
In order to limit temperature, pressure, flow and low water level, the devices must fulfil the following
requirements:
•
Temperature sensors and limiters must be tested according to DIN EN 14597 (limiters with
reactivation lock)
•
Pressure limiters must be component-tested to VdTÜV Notice "Pressure 100/1“ with
reactivation lock
12.2
•
Flow limiters must be component-tested to VdTÜV Notice "Flow 100“
•
Water level limiters must be component-tested to VdTÜV Notice "Water level 100/2“
Monitoring as per TRD 604
In order to limit temperature, pressure and low water level, devices of a particular design must be used.
Flow limiters must comply with VdTÜV Notice "Flow 100".
Chapter_12 - Measuring, monitoring and limiting devices.docx
02999408
Page 3 / 6
VD-S 2014-06 EN
Caterpillar confidential: none
12.3
Temperaturemeasurement
Temperatures are detected with the aid of resistance thermometers in the water circuits and thermocouples
in the exhaust. The temperature-dependent changes in resistance and thermoelectric voltage are converted
via transmitters in the sensor head into a standardized 4 – 20 mA signal.
12.3.1
Installation note for temperature sensors
Fast measuring of dynamical temperature changes is an absolute requirement for a good control system.
The installation position has a great influence on the response times and measuring errors.
Figure 12.1 shows good and bad examples for installation in tubes. The length of the immersion sleeves has
to be designed so that the sensor measures the temperature in the core of the flow. The sensor has to be
connected to the immersion sleeve thermally by a conductive medium. Temperature-proof oils and heatconductive pastes are suitable for this. Insulating air gaps between the immersion sleeve and sensor should
be avoided in all cases.
Fig. 12.1 Installation of the temperature sensor
bad
good
(Sensor not in the core of the flow)
(Sensor in the core of the flow)
1
2
4
2
3
1
PT100 Sensor
2
4-20 mA transmitter
3
Immersion sleeve with air gap
4
Gap filled with conductive medium
Chapter_12 - Measuring, monitoring and limiting devices.docx
02999408
1
Page 4 / 6
VD-S 2014-06 EN
Caterpillar confidential: none
12.4
Differential pressure monitoring
Differential pressure switches are used to monitor differential pressures.
12.5
Exhaust backpressuremonitoring
A special design of gas pressure monitor in the sense of VdTÜV Notice "Pressure 100/1“ is used to monitor
the exhaust backpressure. The measuring line must always slope upwards towards the sensor.
Chapter_12 - Measuring, monitoring and limiting devices.docx
02999408
Page 5 / 6
VD-S 2014-06 EN
Caterpillar confidential: none
Chapter_12 - Measuring, monitoring and limiting devices.docx
02999408
Page 6 / 6
VD-S 2014-06 EN
Caterpillar confidential: none
Power plants layout
Chapter 13
Requirements for CHP systems
in accordance with the medium-voltage directive
June 2008 version
with 4th amendment in January 2013)
06-2014
Caterpillar Energy Solutions GmbH Carl-Benz-Straße 1 D-68167 Mannheim Phone: +49(0)621 384-0 Fax: +49(0)621 384-8612
Caterpillar confidential: none
Contents
13.
Requirements in accordance with the medium-voltage directive ....................................................... 3
13.1
Medium-voltage directive, 2008 version with 4th amendment ........................................................... 3
13.2
Static voltage stability ......................................................................................................................... 3
13.3
Dynamic network support ................................................................................................................... 3
13.4
Requirements for the CHP system ..................................................................................................... 4
13.5
Certification of the gensets (from January 2014) ............................................................................... 5
13.6
Simulations and measurements ......................................................................................................... 5
13.7
Assignment of generators for network connection conditions ........................................................... 7
13.8
International network connection conditions ...................................................................................... 7
Chapter_13 - Medium-voltage directive.docx
02999408
Page 2 / 8
VD-S 2014-06 EN
Caterpillar confidential: none
13.
Requirements in accordance with the medium-voltage directive
Among other things, the medium-voltage directive regulates the behavior of power generators in the
medium-voltage network under defined operating conditions. Prior to 2008, there was a requirement to
immediately disconnect from the network in the event of a fault when using CHP systems. Special protection
devices such as the vector surge relay were developed and implemented for a fast disconnection. In network
technology, CHP systems were treated as so-called "negative consumers". Only the consumer load was
reduced when a CHP system failed.
13.1
Medium-voltage directive, 2008 version with 4th amendment
As a result of the progressing decentralization of power generation with photovoltaic, wind, water and CHP
systems, these systems are becoming more and more significant within the supply network. In line with this,
the connection conditions of power generators in the medium-voltage network have been revised in the
following directive:
Generating plants connected to the medium-voltage network
Directive for generating plants' connection to and parallel operation with the medium-voltage network
June 2008 version with the 4th amendment as of 2013-01-01
According to this new directive, CHP systems must also engage in the static and dynamic network support
alongside the photovoltaic, wind and water systems.
13.2
Static voltage stability
Static voltage stability is the voltage stability in the medium-voltage network for the normal operating state.
For this, slow voltage changes in the distribution network are kept in acceptable boundaries.
13.3
Dynamic network support
Dynamic network support is voltage stability when the voltage drops in the medium-voltage network. This
prevents large feeder lines from disconnecting and the network from collapsing.
Chapter_13 - Medium-voltage directive.docx
02999408
Page 3 / 8
VD-S 2014-06 EN
Caterpillar confidential: none
13.4
Requirements for the CHP system
With the technical conditions for the static and dynamic network support described above, the requirements
for the CHP unit (engine and generator) and for the operating mode of the system have been changed.
Before now, CHP systems were designed for maximum efficiency and maximum power at cosφ=1. With the
new medium-voltage directive, other requirements have to be taken into account:
•
increased voltage and frequency range
•
reduced power over the frequency
•
external power demand
•
variable cosφ
•
dynamic network support
For dynamic network support, the CHP system must be able to remain above the characteristic line in the
network as specified in Fig. 15.1 in the event of a voltage drop and be able to ride through the following
voltage characteristic line in the event of an FRT (Fault Ride Through).
Borderline of voltage profile
Minimum value of
voltage range
Time in ms
Event of network disturbance
Fig 15.1: Borderline for the voltage profile at the network connection point (in the event of an FRT)
The CHP system may only be disconnected from the network when the voltage at the network connection
point falls below the limiting curve. If the voltage at the connection point falls below 30% of the nominal
voltage, the CHP system can be disconnected from the network. If the voltage drops below 70%, the system
may only be disconnected after 150ms.
The dynamic network support lays down technically high requirements for the CHP system. The genset
control and the components (e.g. moment of inertia of the generator) must be adapted for safe operation in
the event of an FRT.
Chapter_13 - Medium-voltage directive.docx
02999408
Page 4 / 8
VD-S 2014-06 EN
Caterpillar confidential: none
13.5
Certification of the gensets
The appropriateness of the gensets for operation in the medium-voltage network must be validated and
confirmed with a certificate by an accredited certification institute in accordance with EN45011.
For the PGU (Power Generating Unit), the certifier issues a PGU certificate and there is a component
certificate from the relevant manufacturer for the protection device.
For the complete system PGS (Power Generating System), the certifier issues a PGS certificate.
13.6
Simulations and measurements
Simulations were performed for the gensets for the event of an FRT using a model. The generators for
achieving dynamic network support have been designed based on these simulations.
The following tests were carried out on the real network. The network voltage was lowered to the
corresponding value and the behavior of the genset was measured using a test container.
As the measurement and the simulation for this example both show, the genset supports the voltage to
approximately 55% of the nominal voltage in the event of a voltage decrease to 30% for 150msec at the
network connection point. For this, the generator voltage is approx. 67% of the nominal value (image 2). The
generator current increases to 4.7xln (image 3). Image 4 and 5 show the speed fluctuations and the rotor
angle.
Chapter_13 - Medium-voltage directive.docx
02999408
Page 5 / 8
VD-S 2014-06 EN
Caterpillar confidential: none
Image 2. Voltage at the network connection point
and at the generator
Image 3. Generator current
Image 4. Genset speed
Image 5. Generator rotor
Chapter_13 - Medium-voltage directive.docx
02999408
Page 6 / 8
VD-S 2014-06 EN
Caterpillar confidential: none
13.7
Assignment of generators for network connection conditions
To fulfil the network connection conditions, the generators have been reassigned for the individual engine
types. With the exception of the genset TCG 2016 V08 C, generators with a higher mass moment of inertia
have been established.
Genset
Generator
Mass moment of inertia for
generator [kgm²]
TCG 2016 V08 C
Marelli MJB 355 MB4
13.12
TCG 2016 V12 C
Marelli MJB 400 LC4
26
TCG 2016 V16 C
Marelli MJB 450 MB4
33.8
TCG 2020 V12K1
Marelli MJB 450 LB4
33.8
TCG 2020 V12 / V12K
Marelli MJB 500 MB4
50
TCG 2020 V16 / V16K
Marelli MJB 500 LA4
59
TCG 2020 V20
Marelli MJB 560 LB4
96.5
Table 17.1 Assignment of the generators
13.8
International network connection conditions
Along with the medium-voltage directive applicable in Germany, there are country-specific regulations which
specify the framework conditions for the parallel operation with the network in other countries, both inside
and outside of the EU. More and more countries are revising these regulations in consideration of the
decentral supply with renewable energy.
Regulations in Europe were prepared by the European Network of Transmission System Operators for
Electricity ENTSO-E. The framework conditions for the country-specific directives/regulations are defined in
the Requirements for Network Connection Applicable to all Generators requirement. Once it is adopted, this
regulation must be considered in the country-specific directives.
Furthermore, a standard for the network connection conditions applicable in Europe is being prepared by
CENELEC (European Committee for Electrotechnical Standardization). This standard will subsequently
be -published as a DIN EN regulation.
Since the regulations in many countries are currently being revised or redeveloped, it must be checked for
each genset/system whether the conditions are complied with.
Chapter_13 - Medium-voltage directive.docx
02999408
Page 7 / 8
VD-S 2014-06 EN
Caterpillar confidential: none
Chapter_13 - Medium-voltage directive.docx
02999408
Page 8 / 8
VD-S 2014-06 EN
Caterpillar confidential: none
Power plants layout
Chapter 14
Electrical switchgear systems
06-2014
Caterpillar Energy Solutions GmbH Carl-Benz-Straße 1 D-68167 Mannheim Phone: +49(0)621 384-0 Fax: +49(0)621 384-8612
Caterpillar confidential: none
Contents
14.
Electrical switchgear systems ................................................................................................... 3
14.1
TEM System for gas engines ........................................................................................................ 3
14.1.1
TEM-EVO System ......................................................................................................................... 3
14.1.2
Layout ............................................................................................................................................ 4
14.1.3
Operating log and histories ........................................................................................................... 4
14.1.4
Diagnosis and service functions.................................................................................................... 4
14.1.5
Technical data ............................................................................................................................... 5
14.1.6
Installation notes for the I/O controller .......................................................................................... 6
14.2
Advantages for the user ................................................................................................................ 7
14.3
Auxiliary drives control and supply – Auxiliary drive panel "HAS" ................................................ 7
14.4
Power part – Generator power field "GLF" ................................................................................... 7
14.5
Central control - Central system control "ZAS" ............................................................................. 8
Chapter_14 - Electrical switchgear systems.docx
02999408
Page 2 / 8
VD-S 2014-06 EN
Caterpillar confidential: none
14.
Electrical switchgear systems
When equipping and installing switchgear systems, in addition to the acknowledged rules of engineering,
particular attention should be paid to the following regulations: low voltage directive 2006/95/EC, EMC
directive 2004/108/EC, VDE 0116, VDE 0660 Part 500 and BGV A2. When working in control- / switch
cabinets with electrical components, as well as handling electrostatically sensitive components (e.g. circuit
boards), the service bulletin including the specially set out DIN EN 61340 – 5 – 1 and DIN EN 61340-5-2, has
to be observed. The switchgear systems must be designed for ambient temperatures of 0 °C to 40 °C and for
a relative humidity of 5-70 %. The switch cabinet internal temperature must not exceed 45 °C.
An exception to this is the TEM-control cabinets. Here, the internal temperature of the cabinet may rise to
50 °C.
If necessary, the lost heat of the control devices has to be dissipated by means of thermostatic controlled
fans in order to avoid an excess of the permissible internal temperatures. An air-conditioning device in the
switchgear or switch cabinet room should be provided when the ambient temperature is higher. Direct
sunlight contact on the cabinets is to be avoided by means of an appropriate arrangement.
14.1
TEM System for gas engines
The TEM System is the brains of the entire gas engine module, including engine management, control and
monitoring of the gas engine, and optionally also the emergency cooling, heating circuit control and
monitoring. It is a user interface for operating and observing the system, it regulates and optimizes the
combustion of gas in the cylinders, and it controls and monitors the engine/genset with all its auxiliary
equipment. Through its monitoring functions, it protects the genset against impermissible boundary
conditions and guarantees long service life. Thanks to the integrated regulatory functions, it ensures
optimum, reproducible engine status values in all operating conditions.
The integral short- and long-term history stores the relevant measurement values on retentive data storage
media and provides a transparent view of its own procedures.
14.1.1
TEM-EVO System
With the TEM-EVO System, the functions described in Chapter 14.1 are integrated in modular form.
In addition, by choosing from a wide range of options, the TEM-EVO System can be adapted to suit specific
applications (e.g. anti-knocking regulation (AKR), engine room ventilation, control and regulation of the table
coolers in the heating circuit, engine circuit, emergency cooling circuit and mixture cooling circuit as well as
parameterizable measured values, counter values and control circuits, CH4-value led operation etc.). The
result is a simple-to-operate system with high operational reliability and optimized economic efficiency.
Chapter_14 - Electrical switchgear systems.docx
02999408
Page 3 / 8
VD-S 2014-06 EN
Caterpillar confidential: none
14.1.2
Layout
The TEM-EVO System comprises 3 components:
•
Genset control cabinet (AGS) complete with connected cables to the genset; contains the
genset control and the TÜV-tested safety chain. The length of cable between the gas engine
and the TEM cabinet is 8 m (optionally 15 m).
•
I/O-Controller for installation in auxiliary drives cabinet (HAS, max. 250 m distance from the
genset control cabinet; cabling to comprise shielded 3-core bus line)
•
Operating computer (max. 100 m distance from genset cabinet; cabling to comprise shielded
3-core line) for installation in the auxiliary drives cabinet or external control cabinet.
This layout minimizes the time it takes for cabling in the system.
The genset control cabinet is mounted in immediate proximity to the genset. Together with the factory-tested
engine cabling, the cables fitted and tested on the genset control cabinet and connected to the genset (with
plug connections on the genset end) ensure smooth commissioning and a high level of operational reliability.
Signals relating to the power part are exchanged with the TEM-EVO System directly at the auxiliary unit
panel cabinet via the I/O-Controller. Data is transmitted to the genset control via a fail-safe CAN bus
connection.
The operating computer can be located on the system as desired, in the auxiliary unit panel if required or in
the control room. The max. distance from the TEM cabinet is 100 m.
14.1.3
Operating log and histories
The recording functions of the electronic operating log kept by the TEM-EVO System take the place of a
manual log. All operating messages and operationally relevant switching actions are recorded with a precise
time stamp (date/time), as are all parameter changes.
As a whole, the TEM-EVO System can monitor and distinguish between over 600 different events. This
makes it possible to provide fast and detailed analyses of genset operating modes, including TEM-EVOcontrolled auxiliary functions.
The history function records up to 84 measured values. Up to 20 measured value curves can be jointly
illustrated in one graph. The user is himself able to assemble the measured value curves.
TEM-EVO records histories at three speed stages:
•
Working cycle history: records actual values in each working cycle
(1 working cycle = 2 crankshaft revolutions)
14.1.4
•
6 min. history: records current values at one second intervals
•
40 h-history: records 6 min. measured values.
Diagnosis and service functions
Chapter_14 - Electrical switchgear systems.docx
02999408
Page 4 / 8
VD-S 2014-06 EN
Caterpillar confidential: none
In addition to the history and operating log, the basic TEM-EVO system also includes further diagnosis and
service functions which make a valuable contribution to the early detection of abnormalities and allow system
operation to be optimized. Fault situations are thus more quickly eliminated and also commissioning
becomes significantly simpler and faster. This contributes decisively towards the overall economic efficiency
of the gas engine set.
The following service and diagnostic functions are available
•
Auxiliary genset test mode
•
Digital speed governor
•
Electronic ignition system
•
Parameterization
•
Oil replacement
•
Electronic operating hours counter
•
Selection of language and printer
•
System setup (software versions, serial numbers, color settings, screen saver, etc.)
•
Other diagnosis/service masks for some options (e.g. anti-knocking regulation, dual gas
operation)
The service and diagnosis masks, like all other masks, can also be accessed by analog modem via the
normal telephone network, IP modem via the internet, or radio modem for remote data transfer (option). In
this way, remote diagnosis and remote repair can be provided with very short response times via Customer
Service or the operator's own on-call staff.
14.1.5
Technical data
•
Genset control cabinet: standard dimensions: 1200x800x300 mm (HxWxD); protection type:
IP 54, operating temperatures: 5-50°C, cables enter from below.
•
I/O- Controller: dimensions: 114.5x112 mm (DxH); length dependent on number of options;
protection type: IP 20, operating temperatures: 5-45°C
•
Operating computer: dimensions: 311x483x101 mm (HxWxD) including front plate;
installation depth 95 mm; cutout for mounting 282 x 454 mm (HxW) front-side protection
type: IP 65, operating temperatures: 5-40°C
Chapter_14 - Electrical switchgear systems.docx
02999408
Page 5 / 8
VD-S 2014-06 EN
Caterpillar confidential: none
14.1.6
Installation notes for the I/O controller
The I/O-controller must be installed in a horizontal 35-mm top-hat rail (EN 50022) in a switch cabinet. It
should be installed vertically (Figure 1), so that sufficient airing is guaranteed. The distance between two
cable ducts should be 200 mm (at least 160 mm). Along with the IO module, space is provided for possible
retrofitting of other IO modules. This space may not be blocked by other components when installing the
controller in the switch cabinet.
Fig. 1 : I/O Controller
2
1
1
Top-hat rail
2
top
Chapter_14 - Electrical switchgear systems.docx
02999408
Page 6 / 8
VD-S 2014-06 EN
Caterpillar confidential: none
14.2
Advantages for the user
TEM-EVO offers the user the following advantages:
•
Compact structure and integration of numerous additional peripheral functions such as heat
recovery, etc.
•
High engine efficiency by controlled operation at optimum operating point.
•
Permanently low exhaust emissions.
•
High level of system reliability thanks to automatic plausibility checks.
•
Rapid elimination of faults thanks to the display of measured values and warning and fault
messages.
•
Fast, cost-effective service thanks to extended diagnosis options backed up by short and
long-term histories.
•
Effective remote operation and remote diagnosis via the central control room or other
external computer by telephone or radio modem (option).
•
14.3
Additional remote diagnosis options from the Service via telephone modem (option).
Auxiliary drives control and supply – Auxiliary drive panel "HAS"
In addition to the TEM System, a typical system includes a cabinet for each genset for auxiliary drives,
synchronization and generator protection, as well as the appropriate charging equipment.
Auxiliary drives include all power supplies for pumps, control valves, flap valves, fans, etc.
The synchronization function ensures synchronous connection to the network by precision balancing. Control
of engine speed is balanced to the power frequency under consideration of voltage and phase relation.
Generator protection covers all necessary and recommended monitoring facilities for generators as per ISO
8528 - 4.
The battery charging devices charge the batteries during normal operation in accordance with the constant
voltage/constant current curves.
14.4
Power part – Generator power field "GLF"
The power part includes the generator circuit breaker and the corresponding transformers to protect the
generator. The current and voltage transformers are likewise located in the power part.
With small systems, it is possible to accommodate both power part and auxiliary drive cabinet in one cabinet.
With larger or medium-voltage systems, the power parts are installed in a separate switchgear room.
Chapter_14 - Electrical switchgear systems.docx
02999408
Page 7 / 8
VD-S 2014-06 EN
Caterpillar confidential: none
14.5
Central control - Central system control "ZAS"
The central control undertakes all common control and monitoring functions which need to be taken into
account with multi-engine systems.
Functions of the central control for the individual gensets:
•
Selection and deselection
•
Specifying genset output
•
Specifying operating mode
•
System-parallel, isolated or back-up operation
Possible additional functions of the central control:
•
Controlling the different operating modes
•
Gas type selection
•
Network failure monitoring
•
Controlling and monitoring the lubricating oil supply and used oil disposal (lubricating oil
service tank, used oil tank)
•
Controlling and supplying central pumps
•
Controlling and supplying central emergency cooling facilities
•
Monitoring and controlling a heat storage tank
•
Gas tank level-dependent operation
•
Controlling and supplying the ventilation system
•
Controlling and supplying the gas warning system
•
Controlling and supplying fire protection facilities, etc.
In addition, a manual operating level must also be provided to allow local control of the system in the event of
a failure of the process management system.
Chapter_14 - Electrical switchgear systems.docx
02999408
Page 8 / 8
VD-S 2014-06 EN
Caterpillar confidential: none
Power plants layout
Chapter 15
Isolated operation mode
06-2014
Caterpillar Energy Solutions GmbH Carl-Benz-Straße 1 D-68167 Mannheim Phone: +49(0)621 384-0 Fax: +49(0)621 384-8612
Caterpillar confidential: none
Contents
15.
Isolated operation mode with gas engines .............................................................................. 3
15.1
General description of isolated operation mode ........................................................................... 3
15.2
Isolated operation after a changeover from mains parallel operation ........................................... 4
15.3
Isolated operation without a public network .................................................................................. 6
15.4
Back-up power operation according to DIN VDE 0100-710 / DIN VDE 0100-560 / DIN EN
50172/ DIN VDE 0100-718 ........................................................................................................... 8
15.5
Active load distribution in isolated operation ................................................................................. 8
15.6
Starting of large consumers .......................................................................................................... 8
15.7
Black start...................................................................................................................................... 9
15.8
Earthing system............................................................................................................................. 9
15.9
Emissions ...................................................................................................................................... 9
15.10
Summary ..................................................................................................................................... 10
Chapter_15 - Isolated operation mode.docx
02999408
Page 2 / 10
VD-S 2014-06 EN
Caterpillar confidential: none
15.
Isolated operation mode with gas engines
15.1
General description of isolated operation mode
On the electrical side, there are different possibilities for operating gas engines. In the majority of cases, the
engines run parallel to the public network. The network is to be seen as a large system with very high inertia
which will not drop or increase the level of voltage or frequency depending on the local load of the individual
consumers. Gas engines are designed to operate parallel to the network as described with optimized
efficiency. But, in some cases, the customer has no or no continuous public network available. For this
reason, isolated operation mode is available as an additional feature.
In isolated operation mode, it is not possible to control the power of the gas genset via the TEM system.
Thus, the power controller will be deactivated and the genset will be operated by speed control to maintain a
constant frequency. In isolated operation mode, the TEM system on its own can have no effect on the load of
the engine. For this reason, the boundary conditions such as inlet air temperature and engine cooling water
inlet must be followed. Therefore, the load switching to any gas genset - and especially for the highly
turbocharged gas gensets (TCG2016, TCG 2020, TCG2032) - and the load shedding must be controlled by
the customer's load management system. For this case, maximum permissible load steps for each gas
genset were defined (see also Chapter 16, Load Steps).
For isolated operation mode with gas gensets, the whole system concept must be planned in detail from the
beginning of the design process. Therefore, the system single line diagram and the knowledge of the
customer's consumers (real starting power and start-up characteristic), especially for the large consumers
like pumps and large fans, are important in order to achieve a good project status. Another important fact is
to analyze the earthing concept for the whole system. In order to reach an effective integrated concept,
coordination during project planning is offered to the customers.
Two possibilities of isolated operation are classified:
•
Isolated operation after a changeover from mains parallel operation
•
Isolated operation without a public network
Chapter_15 - Isolated operation mode.docx
02999408
Page 3 / 10
VD-S 2014-06 EN
Caterpillar confidential: none
15.2
Isolated operation after a changeover from mains parallel operation
In normal operation, the gas gensets run parallel to the public network. Each genset is controlled by the
power controller of the TEM system. The frequency and voltage level will be held by the public network.
In the case of a network failure, the network circuit breaker will be opened immediately. The gas gensets will
supply the consumers of the customer system without interruption.
The single line diagram (Fig 15.1) shows a typical layout for an emergency power supply. The gas engine
auxiliary drives are supplied by an auxiliary transformer.
If there is a network failure, the network circuit breaker is opened and the gas genset will supply the
consumers to the plant. Normally, the transition from mains parallel to isolated operation causes rapid load
changing. If this load changing exceeds the relevant load steps, the turbocharger of the gas engine will start
to pump and, in extreme cases, the gas engine will be switched off. A total power outage of the complete
system may follow.
To solve this problem, various solutions are available which will be coordinated according to the
requirements of the whole system during project planning. It is important to analyze the behavior of the gas
engines together with the consumers to create an adequate concept.
Chapter_15 - Isolated operation mode.docx
02999408
Page 4 / 10
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 15.1 Isolated operation after a changeover from mains parallel operation
Chapter_15 - Isolated operation mode.docx
02999408
Page 5 / 10
VD-S 2014-06 EN
Caterpillar confidential: none
15.3
Isolated operation without a public network
In isolated operation, it is important to analyze the start procedure and the load switching as well as the load
shedding. In some cases, it is necessary to provide an emergency diesel or a UPS as auxiliary supply for
prelubrication and after-cooling of the engine (see also Chapter 15.7, Black start).
The single line diagram (Fig.15.2) shows a typical layout for isolated operation mode. An emergency diesel is
connected to the 400 V panel. The diesel starts at first and supplies the auxiliary panels. Then the first gas
genset starts and supplies the customer's consumers and the auxiliaries as well via the auxiliary transformer.
Now the diesel can be stopped.
If the operator wants to stop the whole system, all gas gensets except one are stopped subsequently and the
stopped gas engines are cooled down. The diesel genset is now started and synchronized with the auxiliary
busbar. After this, the breaker of the auxiliary transformer can be opened and the last gas genset can be
stopped and cooled down. It is very important that the heat at the turbocharger is discharged after switching
off each gas genset in order to protect it from overheating. When the after-cooling period has expired, the
TEM will stop the genset auxiliary drives and the diesel genset can be stopped as well.
Chapter_15 - Isolated operation mode.docx
02999408
Page 6 / 10
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 15.2 Isolated operation without a public network
Chapter_15 - Isolated operation mode.docx
02999408
Page 7 / 10
VD-S 2014-06 EN
Caterpillar confidential: none
15.4
Back-up power operation according to DIN VDE 0100-710 / DIN VDE 0100-560 / DIN EN
50172/ DIN VDE 0100-718
For some special applications, it is necessary to supply power to important consumers for emergency
reasons within 15 seconds. In order to realize this kind of emergency power supply, the function and load
must be clearly defined in the project planning phase. The power available from the genset within 15
seconds corresponds to the first load step as per the load table (see also chapter 16). For this application,
the gas engine must be able to black start. This condition can only be fulfilled by single-engine systems of
the series TCG 2016 C and TCG 2020 V12 and TCG 2020 V16. The TCG 2020 V20 is not suitable for backup power operation because its startup up time is too long.
In isolated operation mode with more than one gas genset, the first genset will supply the back-up power.
The other gas gensets will start once the power supply of the first engine is stable. The auxiliary drive power
for the other gas gensets will be supplied by the first one. The other engines will be synchronized to the first
one. In some special cases, it is possible to start more than one gas genset to cover a higher amount of
back-up supply as well. The available back-up power will be calculated according to the first load step
multiplied by the number of running gensets. This is a very special application of the gas gensets and must
be planned in detail.
15.5
Active load distribution in isolated operation
If more than one gas genset is running parallel in isolated operation, the load must be distributed between
these gensets. Therefore, an active load balancer is integrated in the overall control system. The system
provides the following features: common frequency control for all synchronized gas gensets and optimized
signals to increase or decrease the power of each genset in order to avoid load oscillations between the
gensets.
15.6
Starting of large consumers
Some consumers such as pumps or fans have an effective starting power, which is a multiple of the nominal
power. In the case of a high effective starting power, it is necessary to use special starting procedures, for
example, star / delta starting or soft starting. If there are consumers with a heavy starting torque, it is
sometimes necessary to use load banks to start these large consumers. For this reason, it is necessary to
check the customer system consumers and to coordinate the load switching during project planning.
Chapter_15 - Isolated operation mode.docx
02999408
Page 8 / 10
VD-S 2014-06 EN
Caterpillar confidential: none
15.7
Black start
If a gas genset is "black-started", it starts without auxiliary drive power for prelubrication and cooling water
pumps. The gas genset is started directly after the TEM demand contact has been closed. The cooling water
pumps start as soon as the auxiliary drive power supply is available. Furthermore, the gas genset will be
started without prior leak monitoring of the gas control line.
The black start is an emergency function of the gas gensets and should be used only for emergency
situations. Due to the high wear of the gas engine, this function should not be used more than three times a
year.
The following gas engines are able to black-start:
•
TCG 2016 V08 C / V12 C / V16 C
•
TCG 2020 V12 / V16 / V20
•
TCG 2020 V12K / V16K
The black-start is purely a function for isolated operation and is not possible in mains parallel operation.
The TCG 2032 V12/V16 is not able to black-start. Because of the necessary prelubrication for this series
before the engine starts, a power supply for the auxiliary drives is required, for example using an emergency
diesel or UPS.
15.8
Earthing system
The earthing system for the system design must also be considered in good time; it must be studied
according to the customer single line diagram of the whole system. Due to the complexity of some systems,
the earthing concept must be adapted to the individual requirements. The genset manufacturer offers its
customers coordination during project planning in order to develop an effective integrated concept.
15.9
Emissions
During isolated operation, the TEM system regulates the exhaust gas emissions automatically. The typical
value is 500 mg NOx/Nm³ (in relation to 5% O2, dry) or higher and can be parameterized by the
commissioning staff. The higher enrichment of fuel / air ratio provides a better load changing behavior of the
gas engine, but leads to a higher NOx level. If the emissions value must be smaller than 500mg/Nm³ in
isolated operation, the fuel / air ratio has to be leaner. In this case, the load step table (see also Chapter 21)
must be readjusted. The step levels must be decreased and, as a result, the number of step levels from idle
to full load will increase.
Chapter_15 - Isolated operation mode.docx
02999408
Page 9 / 10
VD-S 2014-06 EN
Caterpillar confidential: none
15.10
Summary
To design a fault-free isolated operation, it is important to analyze the whole system and the customer's
requirements during project planning. For this reason, it is necessary to check the following customer
documents according to the requirements of the gas engine (for example load steps):
•
Single line diagram of the whole system
•
Actual starting power and starting conditions of large consumers
•
Operating mode of the system
Chapter_15 - Isolated operation mode.docx
02999408
Page 10 / 10
VD-S 2014-06 EN
Caterpillar confidential: none
Power plants layout
Chapter 16
Load steps
06-2014
Caterpillar Energy Solutions GmbH Carl-Benz-Straße 1 D-68167 Mannheim Phone: +49(0)621 384-0 Fax: +49(0)621 384-8612
Caterpillar confidential: none
Contents
16.
Load steps
16.1
Conditions for the load steps......................................................................................................... 3
16.2
Variables influencing the load steps ............................................................................................. 3
16.3
Load steps in tables ...................................................................................................................... 4
16.4
Load steps as diagrams ................................................................................................................ 4
Chapter_16 - Load steps.docx
02999408
3
Page 2 / 10
VD-S 2014-06 EN
Caterpillar confidential: none
16.
Load steps
In the following tables and diagrams, the capability of load acceptance and load shedding is shown for the
different engine types. The capability of load acceptance depends on the engine type itself and the active
engine load.
16.1
Conditions for the load steps
Generally, the load steps specified for the different engine series are only valid with the following
operating conditions:
•
Exhaust emission 500 mg NOx (stationary)
•
Natural gas operation
•
Warm engine
•
ISO conditions
•
Line from the zero-pressure controller of the gas control line to the gas mixer valve max. 1.5
m long
•
Minimum gas pressure before the zero-pressure control line 100 mbar (note for system
design)
The load steps change in the case of deviating conditions.
When connecting electric drives (pumps, compressors), it is necessary to consider the switching power in
addition to the nominal power of the drive.
16.2
Variables influencing the load steps
The following operating parameters influence the height of the load steps:
•
air filter, clean / contaminated
•
increased exhaust counter-pressure
•
fuel heat value
•
engine wear
•
installation height
•
air inlet temperature
•
NOx emissions requirements
Chapter_16 - Load steps.docx
02999408
Page 3 / 10
VD-S 2014-06 EN
Caterpillar confidential: none
16.3
Load steps in tables
The first column in the table shows how the engine can be loaded stepwise from zero load up to 100% load.
The second column shows the recovery time necessary between the individual load steps. The indicated
recovery times are in accordance with DIN ISO 8528 Part 5. The third column shows the speed drop the
engine will have when the load is applied. These given load steps must also be observed when relieving load
from the engine.
Load shedding from any load to 0% is generally allowed.
Example: The engine type TCG 2016 C can be loaded with 25% in the first load step. In the second load
step, this figure is 17% and, in the third load step, 13%. The last load step is 7% (from 93% load to 100%
load). The engine needs 15 seconds to recover between the load steps.
16.4
Load steps as diagrams
In the diagrams, the permitted load acceptance of the engines is given as curves. On the x axis, you have
the active load of the engines and the y axis shows the possible load acceptance related to the active engine
load. If we refer to the same example as mentioned above (TCG 2016 C), the diagram shows a sloping
curve in the engine load range between 0% and 55%. In this load range, the permitted load application
decreases from 25% to 10% if the engine output is increased. In the load range from 55% to 75%, the
permitted load application is 10%. Above 75% to 100%, the permitted load application continues to
decrease. Upon reaching 100% load, no additional load application is possible.
Chapter_16 - Load steps.docx
02999408
Page 4 / 10
VD-S 2014-06 EN
Caterpillar confidential: none
Load steps for TCG 2016 C
Conditions
Moment of inertia of generator
Air intake temperature
30 °C
TCG 2016 V08
≥ 13.1 kgm2
Intercooler inlet
Natural gas
40 °C
TCG 2016 V12
≥ 19.9 kgm2
temperature
Biogas
40 °C
TCG 2016 V16
≥ 26.0 kgm2
PN [%]
t f,in [s]
n [%]
0 - 25
15
13
25 - 42
42 - 55
15
15
55 - 65
15
11
10
10
65 - 75
12
9
75 - 85
12
9
85 - 93
10
6
93 - 100
8
6
TCG 2016 C
30
LS [%]
25
20
15
10
5
0
0
10
20
30
40
50
60
70
80
90
100
PN [%]
PN
Active load
LS
Load step
Chapter_16 - Load steps.docx
02999408
tf,in
n
Recovery time
Speed drop
Page 5 / 10
VD-S 2014-06 EN
Caterpillar confidential: none
Load steps for TCG 2020
Conditions
Moment of inertia of generator
Air intake temperature
30 °C
TCG 2020 V12
≥ 44.6 kgm2
Intercooler inlet
Natural gas
40 °C
TCG 2020 V16
≥ 57.0 kgm2
temperature
Biogas
50 °C
TCG 2020 V20
≥ 95.0 kgm2
PN [%]
t f,in [s]
n [%]
PN [%]
t f,in [s]
n [%]
0 - 20
15
11
55 - 60
15
7
20 - 30
15
10
60 - 65
15
7
30 - 40
15
9
65 - 70
12
7
40 - 45
15
9
70 - 80
12
7
45 - 50
15
8
80 - 90
12
7
50 - 55
15
7
90 - 100
12
7
TCG 2020
25
LS [%]
20
15
10
5
0
0
10
20
30
40
50
60
70
80
90
100
PN [%]
PN
Active load
LS
Load step
Chapter_16 - Load steps.docx
02999408
tf,in
n
Recovery time
Speed drop
Page 6 / 10
VD-S 2014-06 EN
Caterpillar confidential: none
Load steps for TCG 2020 K
Conditions
Moment of inertia of generator
Air intake temperature
Intercooler inlet
Natural gas
30 °C
TCG 2020 V12K
≥ 44.6 kgm2
40 °C
TCG 2020 V16K
≥ 57.0 kgm2
temperature
PN [%]
t f,in [s]
n [%]
0 -27
15
10
27 - 45
15
9
45 - 60
15
8
60 - 70
15
8
70 - 80
80 - 90
15
15
5
4
90 - 100
15
4
TCG 2020 K
30
LS [%]
25
20
15
10
5
0
0
10
20
30
40
50
60
70
80
90
100
PA [%]
PN
Active load
LS
Load step
Chapter_16 - Load steps.docx
02999408
tf,in
n
Recovery time
Speed drop
Page 7 / 10
VD-S 2014-06 EN
Caterpillar confidential: none
Load steps for TCG 2032 V12 (50 Hz) , TCG 2032 V16 (50Hz, 60 Hz)
Conditions
Moment of inertia of generator
Air intake temperature
Intercooler inlet
Natural gas
25 °C
TCG 2032 V12
≥ 550 kgm2
40 °C
TCG 2032 V16
≥ 710 kgm2
temperature
PN [%]
t f,in [s]
n [%]
0 -16
10
8
16 - 29
10
8
29 - 39
10
8
39 - 48
10
8
48- 59
10
59 - 71
10
8
8
71 - 82
10
8
82 - 91
10
8
91 - 100
10
8
TCG 2032 V12 (50 Hz) , TCG 2032 V16 (50Hz, 60 Hz)
18
16
LS [%]
14
12
10
8
6
4
2
0
0
10
20
30
40
50
60
70
80
90
100
PN[%]
PN
Active load
LS
Load step
Chapter_16 - Load steps.docx
02999408
tf,in
n
Recovery time
Speed drop
Page 8 / 10
VD-S 2014-06 EN
Caterpillar confidential: none
Load steps for TCG 2032 V12 (60 Hz)
Conditions
Moment of inertia of generator
Air intake temperature
25 °C
Intercooler inlet
Natural gas
≥ 520 kgm2
TCG 2032 V12
40 °C
temperature
PN [%]
t f,in [s]
n [%]
PN [%]
t f,in [s]
n [%]
0 -9
15
5
60 - 66
15
5
9 - 18
15
5
66 - 72
15
5
18 - 27
15
5
72 - 79
15
5
27 - 34
15
5
79 - 86
15
5
34 - 40
15
5
86 - 93
15
5
40 - 45
15
5
93 - 100
15
5
45 - 50
15
5
50 - 55
15
5
55 - 60
15
8
LS [%]
TCG 2032 V12 (60 Hz)
10
9
8
7
6
5
4
3
2
1
0
0
10
20
30
40
50
60
70
80
90
100
PN [%]
PN
Active load
LS
Load step
Chapter_16 - Load steps.docx
02999408
tf,in
n
Recovery time
Speed drop
Page 9 / 10
VD-S 2014-06 EN
Caterpillar confidential: none
Chapter_16 - Load steps.docx
02999408
Page 10 / 10
VD-S 2014-06 EN
Caterpillar confidential: none
Power plants layout
Chapter 17
Cabling
06-2014
Caterpillar Energy Solutions GmbH Carl-Benz-Straße 1 D-68167 Mannheim Phone: +49(0)621 384-0 Fax: +49(0)621 384-8612
Caterpillar confidential: none
Contents
17.
Cabling ......................................................................................................................................... 3
17.1
Safety requirements for the safe use of cables and lines ............................................................. 8
17.1.1
Fundamental requirements ........................................................................................................... 8
17.1.2
General Requirements .................................................................................................................. 8
17.1.3
Cable design for normal operation ................................................................................................ 8
17.1.4
Operating mode ............................................................................................................................ 9
17.1.5
Ambient Conditions ....................................................................................................................... 9
17.1.6
Conditions and requirements for permanently laid lines ............................................................... 9
17.1.7
Requirements for flexible lines .................................................................................................... 10
17.2
Boundary conditions for the safe use of cables and lines ........................................................... 10
17.2.1
Operating conditions ................................................................................................................... 10
17.2.2
Voltage ........................................................................................................................................ 11
17.2.3
Current carrying capacity ............................................................................................................ 11
17.2.4
Thermal Influences ...................................................................................................................... 12
17.2.5
Mechanical influences ................................................................................................................. 12
17.2.5.1
Tensile load ·········································································································· 12
17.2.5.2
Bending stresses ··································································································· 12
17.2.5.3
Pressure load ······································································································· 12
17.2.5.4
Torsional stresses ·································································································· 13
17.2.6
Room types ................................................................................................................................. 13
17.2.7
Types of use and stresses .......................................................................................................... 13
17.2.8
Subdivision of stresses ............................................................................................................... 14
17.2.8.1
Use in interior rooms ······························································································ 14
17.2.8.2
Permanent open-air use ·························································································· 14
17.3
Measurement to safeguard EMC ................................................................................................ 14
17.3.1
EMC instructions for use of frequency converters ...................................................................... 15
17.3.2
Cable ducts ................................................................................................................................. 15
17.3.3
Cable fittings................................................................................................................................ 16
17.4
Examples for cable arrangements .............................................................................................. 16
Chapter_17 - Cabling.docx
02999408
Page 2 / 28
VD-S 2014-06 EN
Caterpillar confidential: none
17.
Cabling
The cabling for a CHP system comprises power cables, supply lines for auxiliary drives, control cables and
signal lines. Power cables, supply lines for auxiliary drives, control cables and signal lines must be laid
separately.
It is essential to use flexible, oil-resistant, fine-wire control lines (e.g. H05VV5-F). Signal transmission lines
must also be shielded (shielding to be composed of tinned copper braid with a minimum of 85 % coverage
such as H05VVC4V5-K, not aluminum foil).
For the supply lines to the auxiliary drives, flexible, oil-resistant, fine-wire engine connection lines must be
laid (e.g. H05VV5-F).
Cables for outside installation need to be suitable for installation in open air (weatherproof, UV-resistant, e.g
ÖLFLEX Robust 215C).
The supply lines for frequency controlled drives need additional shielding (e.g. TOPFLEX EMV-UV2YSLCYK-J). For frequency controlled drives, the total length of 100m for the pipeline must not be exceeded.
2
For the generator power cables, multi-wire power cables (25 mm upwards) made of copper must be used
(e.g. NSGAFÖU for low voltage and N2XSY for medium voltage). Single-core power cables must be installed
as per Figures 17.1a and 17.1b. The cables arriving at the generator should be secured either below or
above the level of the terminal box at an adequate distance from the center line of the generator in order to
prevent an excessively tight radius at the entry point through the wall of the terminal box and to allow for
movement of the genset on its vibration dampers without resulting in excessive mechanical strain on the
cable.
As protection against overload and short circuit, the lines must be fitted with line protection switches as per
DIN VDE 0641 and/or DIN EN 60898; circuit breakers as per DIN EN 60947-2 / IEC 947-4 must be provided
for the engines. The layout of the cabling should always be based on the currently applicable version of DIN
VDE 0100. The cables must be routed through appropriate installation ducts and cable support systems. The
cables must be laid in such a way as to prevent damage to the cable sheathing. This is of particular
importance where cables are laid on a cable support system, i.e. adequate edge protection must be
provided. As a matter of principle, cables must be fixed / secured in such a manner as to prevent tension on
the terminals (strain relief).
When laying cables, attention must be paid to measures designed to safeguard electromagnetic
compatibility. ( see Chapter 17.3 ).
Cable glands with integral strain relief must be used. The size must be selected to suit the external diameters
of the cables.
Chapter_17 - Cabling.docx
02999408
Page 3 / 28
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 17.1a:
Single-core cables, adjacent to each other with a gap of one cable diameter between. (installation in air)
Fig. 17.1b:
Single-core cables in the three phase system, installation as triangle. (installation in air)
When choosing and laying lines, the following points must be considered:
•
Avoid possible mechanical or electrical interference between neighboring circuits.
•
Consider the heat given off by lines and the chemical/physical effects of the line materials on
adjacent materials such as e.g. structural or decorative materials, insulating conduits,
fastenings.
•
The heating effect of the current on the materials used for conductors, couplings and
connections has to be considered as well.
•
Short-circuit-proof routing
To ensure a short-circuit-proof routing, the cables must be wound with five wraps of cable
bundling tape every 0.5 meters. The cables or cable bundles should be fastened to the cable
ladders or cable trays with cable clips every 1.5 to 2 meters.
•
Protective earth conductor
The protective earth conductor (PE) is connected to the generator housing, at the holes
provided for this on the generator feet and routed on the PE in the switchgear. The line is
routed parallel to the power cables.
Chapter_17 - Cabling.docx
02999408
Page 4 / 28
VD-S 2014-06 EN
Caterpillar confidential: none
The recommendation for the cross section of this line for low voltage is:
TCG 2016: 240 mm²
TCG 2020: 300 mm²
A design according to VDE 0100 results in lower cross sections. The cross sections
indicated apply for copper conductors.
•
Protective equipotential bonding
The protective equipotential bonding is necessary in order to keep the contact voltage below
the limit of 50 V.
All metallic objects must be provided with a protective equipotential bonding.
The generator housing is connected to the base frame via a copper band (70 mm²). The
base frame, engine etc. are connected to the main equipotential bonding with a copper line
(min. 70 mm²).
A compilation of corresponding Standards and VDE Regulations is contained in Table 17.1.
Chapter_17 - Cabling.docx
02999408
Page 5 / 28
VD-S 2014-06 EN
Caterpillar confidential: none
Table 17.1
Extract from the respective standards:
Power systems
DIN VDE 0100
Conditions for the erection of power installations with rated voltages below
1000 V
DIN VDE 0100 Part 100
General requirements, scope
DIN VDE 0100 Part 410
Protective measures and protection against electric shock
DIN VDE 0100 Part 430
Protection of cables and lines against overcurrent
Supplement 1 to part 430
Recommended values for current carrying capacity
DIN VDE 0100 Part 482
Choice of protective measures, protection against fire
DIN
VDE
520/Part 530
0100
Part Erection of electric operating cables, lines and busbars
Erection of electrical operating material – switch and control devices
DIN VDE 0100 Part 559
Lights and lighting equipment
DIN VDE 0100 Part 720
Industrial premises which are hazardous to fire
DIN VDE 0100 Part 726 to Hoists
Part 738
DIN VDE 0101
Erection of power installations with rated voltages above 1 kV
DIN VDE 0105
Operation of power installations
DIN VDE 0107
Electrical installations in hospitals and locations for medical use outside
hospitals
DIN VDE 0108 Part 1 to Erection and operation of power installations and safety
Part 100
power supply in communal facilities, stores and shops and exhibition rooms,
multi-story buildings, restaurants, closed parking
lots and working or business premises
DIN VDE 0165
Erection of electrical equipment in hazardous areas
DIN VDE 0166
Electrical installations and apparatus thereof for use in atmospheres potentialy
endangered by explosive material
DIN VDE 0170/0171
Electrical apparatus for potentially explosive atmospheres
DIN VDE 0185
Lightning protection systems, protection of structures against lightning
DIN VDE 0207 Part 1 to Insulating and sheathing compounds for cables and insulated lines
Part 24
DIN VDE 0245 Part 1
Lines for electrical and electronic equipment in power installations
DIN VDE 0245 Part 101 to PVC-insulated control lines
Part 202
DIN VDE 0250 Part 1 to Insulated power lines
Part 819
DIN VDE 0253
Isolated heating lines
Energy conductors
Chapter_17 - Cabling.docx
02999408
Page 6 / 28
VD-S 2014-06 EN
Caterpillar confidential: none
DIN VDE 0262
XLPE (cross linked PE) insulated and PVC sheathed installations cable up to
0.6/1 kV
DIN VDE 0265
Cables with plastic-insulated lead-sheath installations cable
DIN VDE 0267
Halogen-free cables with improved characteristics in the case of fire; rated
voltage from 6 to 30 kV
DIN VDE 0271
PVC-insulated cables and sheathed power cables for rated voltages up to and
including 3.6 / 6 (7.2) kV
DIN VDE 0276 Part 603
Power cables with rated voltages of 0.6 / 1 kV
DIN VDE 0276 Part 604
Power cables with rated voltages of 0.6 / 1 kV with special fire performance for
use in power stations
DIN
VDE
604/605
0276
Part Additional test methods
DIN VDE 0276 Part 620
Distribution cables with rated voltages of 3.6 kV to 20.8/36 kV
DIN VDE 0276 Part 1000
Current carrying capacity, general; conversion factors
DIN VDE 0276 Part 1001
Tests on cables laid with rated voltages of 6/10 kV up to 18/30 kV
DIN VDE 0281 Part 1 to PVC insulated power line
Part 404
DIN VDE 0282 Part 1 to Rubber-insulated electrical power lines: heat-resistant rubber and silicon single
Part 808
core, halogen free single core, welding cable; rubber-insulated elevator control
line, rubber hoses
DIN VDE 0284
Mineral insulated lines of up to 750 V
DIN VDE 0289 Part 1 to Definitions for power cables and insulated power lines.
Part 101
DIN VDE 0292
Code designation for harmonized cables and lines for power installations
DIN VDE 0293
Core identification for power cables and insulated power lines of up to 1000 V
DIN VDE 0295
Conductors for cables and insulated lines for power installations
DIN VDE 0298 Part 1 to Application of cables and insulated lines in power installations, recommended
Part 300
current load ratings
Chapter_17 - Cabling.docx
02999408
Page 7 / 28
VD-S 2014-06 EN
Caterpillar confidential: none
Testing, measurements
DIN VDE 0472 Part 1 to Testing of cables and insulated lines
Part 818
DIN VDE 0473 to Part 811
Insulating and sheathing materials of electric cables and lines, common test
methods
DIN VDE 0482 to Part 268
Measurement of smoke density of cables and lines
Telecommunication, switchboard and Installation cables
DIN VDE 0811
Ribbon cables with round conductors, with a pitch of 1.27 mm
DIN VDE 0812
Equipment wires and stranded equipment wires with PVC insulation sleeves
DIN VDE 0839
Electromagnetic Compatibility
DIN VDE 0881
Equipment wires and stranded equipment wires with extended temperature
range
DIN VDE 0891 Part 1 to Special directions and guiding principles of cables and insulated lines
Part 10
DIN VDE 0899 Part 1 to Special specifications for optical fibres, single cores, indoor and outdoor cables
Part 5
17.1
Safety requirements for the safe use of cables and lines
17.1.1
Fundamental requirements
When used in the manner intended, cables and lines should be regarded as safe; they present no
unacceptable risk to life or property. Unless otherwise specified, insulated cables and lines must be used
only to conduct and distribute electrical energy.
17.1.2
General Requirements
The lines selected must be adequate to accommodate the voltages and currents which may occur in all
anticipated operating conditions in the operating equipment, system or components thereof in which they are
used. They must be so structured, laid, protected, deployed and maintained as to, as far as possible, avoid
any hazards.
17.1.3
Cable design for normal operation
The conductor cross-section must be selected to ensure that, at the current load specified for the conductor,
the permissible operating temperature is not exceeded at any time or at any point. The heating or the current
carrying capacity of a cable or line is dependent on its structure, material characteristics and operating
conditions.
Chapter_17 - Cabling.docx
02999408
Page 8 / 28
VD-S 2014-06 EN
Caterpillar confidential: none
The additional heating effect of heating ducts, solar radiation, etc. on bundled cables or lines should be
considered and avoided. Where covers are used, it is important to ensure uninterrupted air circulation.
17.1.4
Operating mode
The mode of operation defines the time characteristic of the current. Continuous operation represents
constant current operation, the duration of which is at least sufficient for the operating equipment to reach
thermal steady-state, but is not otherwise limited in time. The design values for cables and lines are based
on continuous operation, whereby the permissible operating temperature of the conductor is reached.
17.1.5
Ambient Conditions
Ambient conditions are marked by, among other things, the ambient temperature, heat loss and heat
radiation. The ambient temperature is the temperature of the ambient air when the cable or line concerned is
not under load. The reference temperature is + 30 °C.
The operating conditions for cables and lines may vary both in the case of heat loss, for example in closed
rooms, underfloor cable ducts, etc., and under the influence of radiated heat, e.g. the effects of the sun.
17.1.6
Conditions and requirements for permanently laid lines
Among others, the requirements for lines which are to be permanently laid are as follows:
•
Lines must not come into contact with nor be laid in immediate proximity to hot surfaces,
unless they are suitable for the purpose.
•
Lines must not be laid directly in the soil.
•
Lines must be secured in an appropriate manner. When selecting the distance between
fixings, the weight of the line must be considered.
•
The line must not be damaged by the mechanical means of fixing employed.
•
Lines which have been in use for some time can be damaged if changes are made to the
manner in which they are laid. This is due to the natural effect of aging on the physical
characteristics of the materials used for insulating sleeves and sheathing. This process is
accelerated by higher temperatures.
Chapter_17 - Cabling.docx
02999408
Page 9 / 28
VD-S 2014-06 EN
Caterpillar confidential: none
17.1.7
Requirements for flexible lines
•
The length of connecting lines must be selected so as to be certain that the short-circuit
protection devices will respond.
•
The lines should not be subjected to excessive stresses due to strain, pressure, friction,
twisting or kinking.
•
Strain relief devices and connections must not be damaged.
•
The lines must not be laid beneath covers or other operating equipment. There is a risk that
they may suffer damage due to excessive heat build-up or mechanical damage due to being
walked on.
•
The lines must not come into contact with nor be laid in the immediate proximity of hot
surfaces.
•
The minimum bending radii must be observed.
17.2
Boundary conditions for the safe use of cables and lines
17.2.1
Operating conditions
The lines selected must be suitable for the operating conditions and the respective protection class of the
equipment concerned.
The operating conditions include, among others:
•
Voltage
•
Current
•
Protective precautions
•
Bundling of lines
•
Type of laying
•
Accessibility
The lines selected have to be suitable to withstand all external influences which may arise.
These external influences include, among others:
•
Ambient temperature
•
Rain
•
Water vapor, or accumulated water
•
Presence of corrosive, pollutant or other chemical substances
•
Mechanical stresses (e.g. sharp edges of metal structures)
•
Animals (e.g. rodents)
•
Plant life (e.g. mold fungus)
•
Radiation (e.g. sunlight)
Chapter_17 - Cabling.docx
02999408
Page 10 / 28
VD-S 2014-06 EN
Caterpillar confidential: none
Note: In this context, it should be borne in mind that color is of great importance, and that the color "black"
offers greater protection against solar radiation (high resistance to UV radiation) than other colors.
17.2.2
Voltage
The nominal voltage of a line is the voltage for which the line is designed and which is used as a definition
for electrical tests. The nominal voltage is specified in Volts using two values Uo/U where: Uo is the r.m.s.
value of the voltage between an external conductor and earth (metal sleeves of the line or surrounding
medium). U is the r.m.s. value between two external conductors of a multi-core line or a system of singlecore lines. In an a.c. voltage system, the nominal voltage of a line must at least correspond to the Uo and U
values of the system.
17.2.3
Current carrying capacity
The nominal cross-section of a conductor should be selected so that its current carrying capacity is not less
than the maximum continuous current flowing through the conductor under normal conditions. The limit
temperatures to which the current carrying capacity relates must not be exceeded either for the insulating
sleeve or sheathing of the respective line type. Among the defined conditions is also the manner in which the
line is laid. Attention should be paid here to the specified permissible current loads.
The conditions to be taken into account include, among others:
•
Ambient temperature
•
Bundling of lines
•
Type of overcurrent protection
•
Heat insulation
•
Rolled or coiled lines (should be avoided)
•
Frequency of the current (in deviation from 50 Hz)
•
Effects of harmonics.
The conductor cross-section should not be selected simply in accordance with the requisite current carrying
capacity (DIN VDE 0298-4). Rather, the requirements for protection against hazardous shock currents,
overload and short-circuit currents and voltage drop should be considered. Where lines are to be operated
for extended periods at temperatures higher than those specified, they may suffer serious damage which can
lead to premature failure or to a significant impairment of their characteristics and life threatening situations.
Chapter_17 - Cabling.docx
02999408
Page 11 / 28
VD-S 2014-06 EN
Caterpillar confidential: none
17.2.4
Thermal Influences
Lines should be selected, laid and installed so as to ensure that the anticipated release of current-induced
heat is not obstructed and there is no risk of adjacent materials catching fire. The limit temperatures for the
individual line types are specified by the manufacturer. The specified values must, under no circumstances,
be exceeded due to the interaction between internal current-induced heat and ambient conditions. The
typical temperature range for permanently laid standard cables is - 40°C to + 80°C. If higher temperatures
occur, heat-resistant cables must be used.
17.2.5
Mechanical influences
When assessing the risks of mechanical damage to the lines, consideration must be given to all mechanical
stresses which might arise:
17.2.5.1 Tensile load
The strain values specified for the cables must not be exceeded. Typical values are 50 N/mm² for
permanently installed lines and 15 N/mm² for flexible lines. In cases in which the above-mentioned values
are exceeded, it is recommended that a separate strain relief element or similar be fitted. Such strain relief
elements should be connected to the line in such a way that they do not damage the line.
17.2.5.2 Bending stresses
The internal bending radius of a line should be selected in order to avoid damage to the line. The internal
bending radii for the different types of control lines are approx. 10 x line diameter (dependent on cable type
and manufacturer) and for power cables approx. 15 x cable diameter. The minimum bending radius must in
each case be checked for the particular lines/cables used.
When stripping the insulation, care must be taken not to damage the conductors, as otherwise their bending
behavior will be seriously impaired.
The specified bending radii apply at ambient temperatures of 20°C (± 10 K). For other ambient temperatures,
account must be taken of the manufacturer's specifications.
Bends should be avoided in the immediate vicinity of external or internal fixing points.
17.2.5.3 Pressure load
Lines should not be subjected to such pressure as might damage them.
Chapter_17 - Cabling.docx
02999408
Page 12 / 28
VD-S 2014-06 EN
Caterpillar confidential: none
17.2.5.4 Torsional stresses
Flexible lines are generally not intended to support torsional stresses. Where such torsional stresses are
unavoidable, this must be clarified on a case-by-case basis with the cable manufacturer.
17.2.6
Room types
Electrical operating premises are rooms or locations used primarily for the operation of electrical equipment
and generally accessible only to trained personnel, e.g. switch rooms.
Sealed electrical operating premises are rooms or locations used exclusively for the operation of electrical
equipment and kept under lock and key. Access is permitted only to trained personnel, e.g. sealed switching
and distribution systems.
Dry rooms are rooms or locations which are generally devoid of condensation, or in which the air is not
saturated with moisture.
Damp and wet rooms are rooms or locations in which the safety and reliability of the operating equipment is
impaired by moisture, condensation, chemical or similar influences.
General notes:
To assign rooms to one of the above listed types often requires a precise knowledge of local and operational
conditions. If for example a high level of moisture occurs only at one specific point in a room, but the room
itself remains dry thanks to regular ventilation, it is not necessary to classify the whole room as a wet room.
Since in CHP systems it is impossible to exclude oil and water leaks, oil and chemical-resistant cables must
be used.
17.2.7
Types of use and stresses
Electrical lines may be divided between the following types of use:
•
Cables for use in interior rooms, e.g. CHP system room
•
Cables for use in the open air, e.g. supply line for table coolers
Chapter_17 - Cabling.docx
02999408
Page 13 / 28
VD-S 2014-06 EN
Caterpillar confidential: none
17.2.8
Subdivision of stresses
The term "stress" defines the suitability of a line for use in certain areas, on or in a piece of operating
equipment, and for certain combinations of external influences which occur in these areas.
In terms of stresses, electrical lines are divided into four categories:
•
Very low stress, e.g. computer systems
•
Low stress, e.g. air conditioning, data processing
•
Normal stress, e.g. mechanical engineering, CHP systems, system manufacturing
•
Heavy stress, e.g. mining
17.2.8.1 Use in interior rooms
The line is installed or connected to a piece of equipment which is permanently located inside a building,
namely within the "specified environment“. The building may be used for commercial, industrial or residential
purposes.
17.2.8.2 Permanent open-air use
The line is designed to resist the widely varying stresses which may occur in the "specified environment",
namely the open air (including the effects of weather).
17.3
Measurement to safeguard EMC
The line arrangement contributes to an essential part of the EMC of a system. The lines have to be graded in
four groups:
-Group I:
Very interference-susceptible (analog signals, measuring lines)
-Group II:
Interference-susceptible (digital signals, sensor cables, 24VDC-switch signals)
-Group III:
Fault source (control cables for inductive loads, unswitched power cables)
-Group IV:
-Strong fault source (output cables of frequency converters,
switched power cables)
Crossing should be avoided when arranging the cables. If there are unavoidable crossings, the lines of the
different groups have to cross at right angles.
Chapter_17 - Cabling.docx
02999408
Page 14 / 28
VD-S 2014-06 EN
Caterpillar confidential: none
17.3.1
EMC instructions for use of frequency converters
Depending on the EMC requirement (environmental class 1 or 2) and type of frequency converter, EMC
filters are required.
Attention must be paid to the cabling and EMC instructions in the operation manual.
17.3.2
Cable ducts
•
Metallic cable ducts have to be connected to the ground (earthing). They must be connected
constantly
•
Reduction of the magnetic field through distance of the cable troughs (Fig. 17.1)
•
Lines are installed in various cable ducts
•
Lines separate through metallic partition
Fig. 17.2
The recommended minimum distance between cable troughs is 0.15 m. The troughs should be electrically
connected to the vertical carriers.
In general, the power cables of generators should be laid separately. In the case of power cables, it must be
noted that the type of routing has a significant influence on the current carrying capacity of the line. The
correction factors in the standards must be observed here. The standard VDE 0298 specifies a distance of
0.3 meters between the cable trays/ladders and to the ceiling when routing cables on cable trays/ladders.
Chapter_17 - Cabling.docx
02999408
Page 15 / 28
VD-S 2014-06 EN
Caterpillar confidential: none
17.3.3
Cable fittings
In the case of particular EMC requirements, EMC-type cable fittings should be used. In general, chromed
brass fittings are used.
17.4
Examples for cable arrangements
Fig. 17.3
shows a starter cable arrangement. The cables are laid symmetrically and secured with cable clamps. This
prevents damage due to abrasion.
correct
Chapter_17 - Cabling.docx
02999408
Page 16 / 28
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 17.4
Shows a starter cable which is installed incorrectly.
Abrasion danger! Possible short-circuit danger!!
incorrect
Fig. 17.5
shows the arrangement of temperature sensor and fan motor cables.
The power supply cables are connected to the equipment in an installation system. The cables should be
connected to the equipment from below. It must be ensured that the cable entry point is properly sealed.
correct
Chapter_17 - Cabling.docx
02999408
Page 17 / 28
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 17.6
shows an incorrect cable installation. Rolling up the cables as a coil at the engine is not permitted because of
additional load of the plugs and EMC problems.
Abrasion danger! EMC problems!
incorrect
Chapter_17 - Cabling.docx
02999408
Page 18 / 28
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 17.7
shows the vertical arrangement of engine cables up to a cable trough at ceiling height. The access point into
the cable trough is fitted with the necessary edge protection and the cables are secured with cable clamps
(do not use cable ties)
The line to the gas mixer regulating valve is poorly laid and therefore constitutes a negative example. The
cable should not be fixed directly to a pipe (danger of abrasion) and it must not be rolled up in a coil
(faults, mechanical wear).
incorrect
correct
Chapter_17 - Cabling.docx
02999408
Page 19 / 28
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 17.8
This picture shows a cable, which is laid loose and directly on the engine and the generator. Cable damages
and EMC problems are the result of this.
Abrasion danger! Danger of short circuit! EMC problems!
incorrect
Fig. 17.9
shows the equipotential bonding for the cooling water pipe across the rubber expansion joint. The cable is
too long and is resting against the exhaust pipe insulation.
Abrasion danger! Impermissible heating!
incorrect
Chapter_17 - Cabling.docx
02999408
Page 20 / 28
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 17.10
The skinning of the shield is too long and not laid to the terminal with separate isolation. The wires are laid
on the terminals as long loops. This causes the risk of EMC problems and short-circuits.
EMC problems! Danger of short circuit!
incorrect
Fig. 17.11
In the following picture, the shielding is too long and not isolated. On the external black cables, the wire
terminal sleeves are missing.
Danger of short circuit!
incorrect
Chapter_17 - Cabling.docx
02999408
Page 21 / 28
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 17.12
shows an arrangement of TEM cables running to the genset. These are fed to the engine in cable troughs.
The power cables are secured after the 90° bend in order to prevent abrasion and to ensure the appropriate
strain relief.
The 90° bend in the power cables absorbs vibrations which thus do not place strain upon the cable fittings at
the connections.
correct
Fig. 17.13
shows correctly laid cables with clamps and cable ducts.
correct
Chapter_17 - Cabling.docx
02999408
Page 22 / 28
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 17.14
shows correctly laid cables with clamps and cable ducts.
correct
Fig. 17.15
shows a TEM-cabinet, which is standing directly in front of the generator’s exhaust air. This causes the TEM
cabinet to overheat. The temperature inside the cabinet is therefore too high and this is what causes the
problems.
Temperature problems!
incorrect
Chapter_17 - Cabling.docx
02999408
Page 23 / 28
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 17.16
It is impermissible to close or to cover the air ducts.
Heat accumulation!
incorrect
Fig. 17.17
The power cables should be connected to the generator professionally
Danger to life! Danger of short-circuit! Danger of fire!
incorrect
Chapter_17 - Cabling.docx
02999408
Page 24 / 28
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 17.18
The cable entrance is covered with sheet metal, so that no object can fall into the opening and cause a
short-circuit.
correct
Fig. 17.19
The requested bending radii for the generator power cables are kept and the weight oft the cables is
captured by the fix supports.
correct
Chapter_17 - Cabling.docx
02999408
Page 25 / 28
VD-S 2014-06 EN
Caterpillar confidential: none
Abb. 17.20
The requested bending radii of the generator power cables are kept, but the weight oft he cables is acting
onto the cable glands and cable clamps. This arrangement is not short-circuit proof.
incorrect
Abb. 17.21
The bending radii oft the generator power cables are to small. Several cables are rubbing at the screw nuts
oft he cable glands.
incorrect
Chapter_17 - Cabling.docx
02999408
Page 26 / 28
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 17.22
It is not permissible to lead the power cables through the control cabinets and TEM cabinet.
EMC problems!
incorrect
Chapter_17 - Cabling.docx
02999408
Page 27 / 28
VD-S 2014-06 EN
Caterpillar confidential: none
Chapter_17 - Cabling.docx
02999408
Page 28 / 28
VD-S 2014-06 EN
Caterpillar confidential: none
Power plants layout
Chapter 18
Transport and positioning of gensets
06-2014
Caterpillar Energy Solutions GmbH Carl-Benz-Straße 1 D-68167 Mannheim Phone: +49(0)621 384-0 Fax: +49(0)621 384-8612
Caterpillar confidential: none
Contents
18.
Transport and positioning of gensets ...................................................................................... 3
18.1
Preliminary notes .......................................................................................................................... 3
18.2
Loading by crane ........................................................................................................................... 3
18.2.1
Load support equipment / hoists ................................................................................................... 4
18.2.2
Maintenance of load support equipment / hoists .......................................................................... 5
18.2.3
Service limits for load support equipment / hoists......................................................................... 5
18.3
Transport on vehicles and ships ................................................................................................... 5
18.4
Reloading and unloading .............................................................................................................. 5
18.5
Storage of gensets and system components ................................................................................ 6
18.6
Positioning and placement on the foundation ............................................................................... 7
18.6.1
Preparations for positioning .......................................................................................................... 7
18.6.2
Pulling the genset onto the foundation .......................................................................................... 8
18.6.3
Placing the genset on the foundation ............................................................................................ 8
18.7
Transporting and setting up containers ....................................................................................... 11
18.7.1
Lifting the container ..................................................................................................................... 13
18.7.2
Transporting containers .............................................................................................................. 16
18.7.3
Setting up containers .................................................................................................................. 17
Chapter_18 - Transport and positioning of gensets.docx
02999408
Page 2 / 18
VD-S 2014-06 EN
Caterpillar confidential: none
18.
Transport and positioning of gensets
18.1
Preliminary notes
The transport of a genset from the factory to its final destination can be divided into the following steps:
18.2
•
Loading of the genset onto truck by stationary crane or mobile crane
•
Transport by truck to destination or to harbor for shipping
•
Reloading in harbor or when changing truck
•
Unloading at destination by mobile crane or mobile crane
•
Positioning and placement on the foundation
Loading by crane
The loading of gensets in the factory is either carried out using an indoor crane or by mobile crane. The
gensets are either equipped with load support points (bollards) which are arranged on each side of the
genset's base frame or, in special cases, with two double-T members which are arranged below the base
frame. Those double-T members are equipped with shackles for fixing the lifting devices (ropes or chains).
The position of the load support points is symmetric to the center of gravity of the genset. The genset will
take a stable horizontal hanging position when using four ropes or chains of equal length for lifting.
One end of the chains or ropes must be hooked to the crane's hook or to a cross member.
The opposite ends have to be fastened to the load support points of the genset. The fastening must be
secured against unexpected sudden loading.
For this reason, chains and ropes must only be secured using either clamps (lifting clamps) or textile slings
when fastening them onto the transport brackets of the genset.
When arranging chains or ropes for lifting a genset, it it must be ensured that the chains or ropes are only
touching the genset at the load support points, thus preventing damage to genset components due to
slanting chains or ropes. Special cross members are used for this, see image 18.1. If there are no suitable
cross members available for lifting, it is necessary to arrange special devices for spreading the chains or
ropes used for lifting.
Chapter_18 - Transport and positioning of gensets.docx
02999408
Page 3 / 18
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 18.1 Lifting a genset
18.2.1
Load support equipment / hoists
Load support equipment, hoists and fastening equipment which are used for lifting and transporting of heavy
loads are subjected to special monitoring and test procedures both when this equipment is produced and
during its operation life. The rules and regulations of the industrial health and safety ordinance and of the
accident prevention and insurance associations apply in the EU. The main items to be observed are listed in
the following.
•
Only trained persons may use the lifting and transport equipment.
•
The permissible load may not be exceeded on any equipment.
Before using any of this equipment, it has to be checked for proper condition, i.e. it must not show any
damage affecting its safety and function (for example breaks, chamfers, cracks, wear, deformations,
damages caused by exposure to heat or cold etc.).
Chapter_18 - Transport and positioning of gensets.docx
02999408
Page 4 / 18
VD-S 2014-06 EN
Caterpillar confidential: none
The equipment must not be overloaded with joints.
There must not be any knots or twists in the ropes and chains.
Ropes and chains may not be taken over sharp edges without the appropriate protective equipment; edge
protection must always be used.
Asymmetric loading of the equipment must be avoided.
Ropes and chains must be shortened correctly.
18.2.2
Maintenance of load support equipment / hoists
The load support equipment and hoists must be checked for visible damages, deformations, wear and
corrosion, cracks and breaks by an authorized expert. These checks have to be done in fixed time intervals,
but at least once a year. For the case of unacceptable failures, the respective device must be withdrawn from
further use. When carrying out maintenance, it is forbidden to make any change affecting the function and
the load capacity of the load support equipment.
18.2.3
Service limits for load support equipment / hoists
When exposed to high or low temperatures, the capacity of load support equipment and hoists must be
reduced accordingly.
18.3
Transport on vehicles and ships
When transporting gensets on trucks or on board ships, an appropriate intermediate layer between the
loading platform and the base frame must be provided. Providing anti-slip mats or blocks made of hard
rubber or wood is recommended. In addition, it is necessary to attach tensioning straps, lashing chains,
mounting links and cradles to keep the genset safe against slipping or tilting. When transporting, the genset
must be protected from the effects of weather using an appropriate transport cover. A package for carrying
overseas will be provided for marine transport.
18.4
Reloading and unloading
Gensets are normally reloaded and unloaded using mobile cranes. As far as the choice of hoists is
concerned, the same notes, rules and instructions as mentioned per item 18.2 for the loading of gensets can
be referred to.
Chapter_18 - Transport and positioning of gensets.docx
02999408
Page 5 / 18
VD-S 2014-06 EN
Caterpillar confidential: none
18.5
Storage of gensets and system components
Due to project requirements, gensets, switchgears and system components might have to be stored until
they are installed. The following points should be observed during storage:
•
the storage area must be dry and properly ventilated
•
the storage area must be heated if the temperature is likely to fall below the dew point due to
daily or seasonal change.
•
the storage area must be frost-proof
On the technical data sheets for the specific components, storage temperatures are indicated which depend
on the materials installed in the components. In particular seals made of elastomers grow brittle as a
consequence of frost and can be easily destroyed.
For switch cabinets with semiconductor electronic circuits, storage temperatures in the range from -10 to
+50 °C are indicated.
Especially during transport and also during storage in harbors or at hauler's, it is not always possible to
comply with the conditions described above. We accept no liability for damages caused by frost or
dampness.
Corrosion protection is applied to the inside and outside of the diesel and gas engines for a period of 24
months. If the engine is stored for longer than the protection allows, an additional protection treatment is
necessary. The length of protection provided is valid only if the storage conditions described above are
complied with.
Generators must be rotated every 6 months, regardless of whether they are individually stored or installed in
a genset.
System components which are installed in the open air during operation can also be stored in the open air.
These are, for example, ventilator coolers or exhaust silencers.
Chapter_18 - Transport and positioning of gensets.docx
02999408
Page 6 / 18
VD-S 2014-06 EN
Caterpillar confidential: none
18.6
Positioning and placement on the foundation
The positioning of a genset is described for a genset with an engine such as the TCG 2032 V16.
18.6.1
Preparations for positioning
In normal conditions, the genset has to be pulled onto the foundation via the access opening of the engine
room. It is recommended to provide a two-track ramp with covering steel plates and gravel below. The ramp
is arranged in the longitudinal direction of the foundation; the upper edge of the ramp is in alignment with the
top of the foundation. The free accessible length of the ramp on the outside of the engine room must be at
least the full length of the genset in order to place the complete genset on the ramp. Before placing the
genset on the ramp, steel rollers are arranged at the four corners of the base frame. See figure 18.2.
Fig. 18.2 Preparations for the positioning
1
Foundation
2
Steel plates
3
Gravel bed
4
Steel roller
Chapter_18 - Transport and positioning of gensets.docx
02999408
Page 7 / 18
VD-S 2014-06 EN
Caterpillar confidential: none
18.6.2
Pulling the genset onto the foundation
After placing the genset on the ramp, two ropes with winches will be attached to the two front corners of the
base frame. The ropes are to be fastened to the base frame using shackles. For fastening the opposite ends
of the ropes, load support points should be provided at the opposite wall, for example. With use of the
winches, the genset can then be pulled to its final position on the foundation. See also figure 18.3. When
placing the genset onto the ramp, attention should also be paid to aligning of the genset's longitudinal axis to
the longitudinal axis of the foundation.
Fig. 18.3 Pulling the genset
18.6.3
1
Winch
2
Foundation
Placing the genset on the foundation
After maneuvering the genset to its final position on the foundation, it has to placed on the foundation. At
least four hydraulic jacks have to be placed below the base frame. By using the hydraulic cylinders, the
genset can be lifted uniformly (see figure 18.4). After removing the steel rollers, the spring elements can be
bolted to the base frame. When lowering the hydraulic cylinders, the genset's weight will be taken by the
spring elements. To get equally balanced load on the spring elements, they have to be adjusted with regard
to the individual alignment specification (see figure 18.5 and 18.6).
Chapter_18 - Transport and positioning of gensets.docx
02999408
Page 8 / 18
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 18.4 Arrangement of the hoist cylinder
1
Hoist cylinder
Fig. 18.5 Arrangement of the spring elements
1
Hoist cylinder
Chapter_18 - Transport and positioning of gensets.docx
02999408
Page 9 / 18
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 18.6 Placing the genset on the foundation
1
Hoist cylinder
Chapter_18 - Transport and positioning of gensets.docx
02999408
Page 10 / 18
VD-S 2014-06 EN
Caterpillar confidential: none
18.7
Transporting and setting up containers
In the case of container systems, the genset is ready mounted and installed in the container. System
components such as exhaust silencers, exhaust heat exchangers and horizontal-type radiators are arranged
on a common frame or several separate frames made from square tubes on the container roof. These
frames are located loose on the container roof. For transporting a container system, the components located
on the roof are removed and transported next to the container as separate freight. Figure 18.7 shows the
container system ready mounted, Figures 18.8-18.10 show the division of the components into individual
batches for the transport. The system shown involves a CHP container in which the components are
mounted on separate frames on the roof.
Fig. 18.7 Container system, complete
5
6
7
3
4
8
3
10
9
2
11
1
1
Container
7
Exhaust heat exchanger
2
Inlet air components
8
Exhaust silencers
3
Water pipe
9
Frame
4
Table cooler
10
Air-conditioning unit
5
Exhaust flue
11
Strip foundation (at customer)
6
Exhaust bypass
Chapter_18 - Transport and positioning of gensets.docx
02999408
Page 11 / 18
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 18.8 Container without roof structures and air-conditioner
Fig. 18.9 Components with frame
Chapter_18 - Transport and positioning of gensets.docx
02999408
Page 12 / 18
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 18.10 These components are packed together loosely
18.7.1
Lifting the container
For loading the container for transport, in the case of potential reloading and unloading at the construction
site, the container must be lifted and moved suspended on a crane. The components inside the container, in
particular the elastically mounted genset, are secured for the transport. The genset is firmly interlocked using
several threaded rods and underlays comprising hardwood blocks between the genset base frame and
foundation rail. In addition to this, the genset is firmly strapped at the four corners of the base frame using
tensioning straps with holding lugs attached to the container structure. Components for commissioning or
other parts that are transported loosely along with the container are also secured for the transport.
Nevertheless, it must be ensured that the container is lifted as evenly and horizontally as possible during
hoisting. The container corner plates welded in the roof and in the floor of the container are used as load
support points. The rope lengths must be chosen so that the crane hook is located in the level of the
container center of gravity. The position of the container center of gravity is marked outside on the side wall
of the container. See also Figure 18.11. and 18.14.
When lifting the container by using the upper container corner plates it must be made sure that the acting
forcces are into direction vertical upwards. For this case a suitable traverse is necessary or the lifting must
be undertaken by use of two cranes.
Chapter_18 - Transport and positioning of gensets.docx
02999408
Page 13 / 18
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 18.11 Lifting the container with ropes
Lifting the container with the method as shown is not permitted.
2
2
2
1
2
Fig. 18.12 Lifting the container with traverse
Lifting the container by use of a traverse at upper container corner plates
3
2
2
1
Center of gravity marking
2
Container corner plate
3
Traverse
Chapter_18 - Transport and positioning of gensets.docx
02999408
2
2
1
Page 14 / 18
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 18.13 Lifting the container with two cranes
Lifting the container at upper container corner plates and use of two cranes
2
2
2
2
1
Fig. 18.14 Lifting the container with traverse
Lifting the container at lower container corner plates and use of traverse
3
2
2
2
2
1
1
S Center of gravity marking
2
Container corner plate
3
Traverse
Chapter_18 - Transport and positioning of gensets.docx
02999408
Page 15 / 18
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 18.13 Lifting a container with cross members
Picture will follow
18.7.2
Transporting containers
In most cases, the container and accessories are transported directly to the destination by truck. If plants are
to be shipped overseas, the containers are transported to a seaport and loaded onto the ship. The
containers are usually transported from the destination port to the installation site by truck again.
Fig. 18.14 Transporting a container with a low loader
Chapter_18 - Transport and positioning of gensets.docx
02999408
Page 16 / 18
VD-S 2014-06 EN
Caterpillar confidential: none
Depending on the specifications, it can also be the case that the containers are packed in a crate for sea
transport.
Both the container and the components mounted on the frame must be secured for transport. The container
corner plates must be used on the underside for fastening the container on the low loader. If using the upper
container corner plates as fastening points, the container will generally be damaged. Dents and damage to
the paintwork cannot be avoided.
Fig. 18.15 This fastening leads to dents and paint damage on the container
18.7.3
Setting up containers
The container is set up either on a continuous foundation plate or several strip foundations. In the case of
strip foundations, two strips are normally provided below the two longitudinal sides of the container.
Depending on the arrangement of the cable outlets in the container, suitable ducts or recesses must be
provided in the foundation or in the foundation strips. The implementation of the foundation, i.e. foundation
height, choice of concrete grade and reinforcement, must be carried out at the customer by a structural
engineer. The unevenness of the foundation should not exceed 5 mm in the longitudinal direction and 2 mm
in the transverse direction.
The following points must be checked before placing the container down on the foundation:
•
Check foundation for evenness and cleanliness
•
Check location of the recesses for cable outlets
•
Check container underside for cleanliness
Chapter_18 - Transport and positioning of gensets.docx
02999408
Page 17 / 18
VD-S 2014-06 EN
Caterpillar confidential: none
After this, the container is first placed onto the foundation.
Fig. 18.16 Setting up the container on the foundation
2
2
2
1
2
1
1
Container
2
Container corner plate
3
Foundation
2
2
3
After setting up the container, the components are mounted on the roof and connected. In addition, the
external lines must be provided for the gas, oil, heating water circuit and the electrical connection.
If any doors are stiff or jammed, the adjustment must be recalibrated at the hinges.
Chapter_18 - Transport and positioning of gensets.docx
02999408
Page 18 / 18
VD-S 2014-06 EN
Caterpillar confidential: none
Power plants layout
Chapter 19
Genset installation and alignment instructions
06-2014
Caterpillar Energy Solutions GmbH Carl-Benz-Straße 1 D-68167 Mannheim Phone: +49(0)621 384-0 Fax: +49(0)621 384-8612
Caterpillar confidential: none
Contents
19.
Genset installation and alignment instructions
19.1
Transport and positioning of gensets ............................................................................................ 3
19.2
Protecting the genset .................................................................................................................... 3
19.3
Elastic mounting ............................................................................................................................ 4
19.4
Torsionally flexible coupling .......................................................................................................... 4
19.5
Rubber expansion joints and hoses .............................................................................................. 6
19.5.1
Rubber expansion joints .............................................................................................................. 11
19.5.1.1
Storage ........................................................................................................................................ 11
19.5.1.2
Arrangement and installation ...................................................................................................... 11
19.5.1.3
Installation ................................................................................................................................... 12
19.5.1.4
Arrangement of pipe brackets ..................................................................................................... 14
19.5.1.5
Protective measures after installation ......................................................................................... 14
19.5.1.6
Underpressure loading ................................................................................................................ 14
19.5.2
Hoses .......................................................................................................................................... 14
19.5.2.1
Storage ........................................................................................................................................ 14
19.5.2.2
Arrangement and installation ...................................................................................................... 15
19.5.2.3
Installation ................................................................................................................................... 21
19.5.2.4
Pipe brackets............................................................................................................................... 21
19.5.2.5
Protective measures after installation ......................................................................................... 21
19.5.2.6
Type approval test ....................................................................................................................... 21
19.5.3
Exhaust expansion joints ............................................................................................................ 22
19.5.3.1
Storage ........................................................................................................................................ 22
19.5.3.2
Arrangement and installation ...................................................................................................... 22
19.5.3.2.1
Installation on the engine (turbocharger) .................................................................................... 24
19.5.3.2.2
Installation in the pipe section ..................................................................................................... 25
19.5.3.3
Installation ................................................................................................................................... 27
19.5.3.4
Arrangement of pipe brackets in the exhaust line ....................................................................... 31
19.5.3.5
Protective measures after installation ......................................................................................... 32
19.5.3.6
Insulation ..................................................................................................................................... 32
19.6
Notes on commissioning ............................................................................................................. 32
Chapter_19 - Genset installation and alignment instructions.docx
02999408
3
Page 2 / 32
VD-S 2014-06 EN
Caterpillar confidential: none
19.
Genset installation and alignment instructions
The object of these instructions is to ensure that the genset is correctly positioned and installed in the engine
room and to avoid possible consequential damage arising from incorrect installation.
19.1
Transport and positioning of gensets
Chapter 18, "Transport and Placement" describes what action has to be taken for placing the genset at its
final position.
19.2
Protecting the genset
After the genset has been mounted and aligned on its foundation and before piping and cabling works can
begin, the genset must be protected against dust and dirt, for example with a tarpaulin.
To protect the electronics and the bearings in the engine and generator, welding should not be carried out on
the genset!
It must also be ensured that components installed at the genset, such as transmitters, temperature sensors
or attachments such as pumps, filters, etc. are not used as "conductors" during the installation.
In order to maintain the value and reliability of the system, we draw your attention to the following
points:
•
The genset room as well as the switchgear room should as far as possible be kept free from
dust. Dust reduces the service life of the engine, shortens the lifetime of the generator and
restricts the functioning of the control system.
•
Condensation and dampness in engine rooms encourage corrosion of both the genset and the
switchgear. High-quality CHP system installations require dry, preferably heated rooms (above
5°C).
•
After the test run at the factory, the engine will receive interior corrosion protection as per our
works standard. The standard treatment lasts 24 months.
•
If the genset is to remain shut down for an extended period, the insulation resistance of the
generator must be checked before commissioning. In the event of dampness, the generator
must be dried (stationary heating or other suitable means).
•
If the genset is set up in a container, the genset must be fully emptied (risk of freezing) and
secured against movement for storage or transportation.
Chapter_19 - Genset installation and alignment instructions.docx
02999408
Page 3 / 32
VD-S 2014-06 EN
Caterpillar confidential: none
19.3
Elastic mounting
For the elastic mounting of the gensets, steel bellows are used as standard. These are equipped with a
leveling device as standard. Beneath the footplate of the bearing element is a rubber plate which can be set
directly onto the foundation. It must be ensured that the foundation surface is free of grease, lube oil, fuel or
other contaminants. The foundation surface should be level ± 2 mm and have a roughness equivalent to
standard concrete foundations. The foundation must not be tiled.
It is not necessary to screw down or dowel the spring elements with the foundation. However, the 4 bearing
elements can be screwed (doweled) at the corner points of the genset to fasten the genset to the foundation,
or, in the container installation, they can be fastened with steel stoppers.
The quantity and the arrangement of the bellows is shown in the order-specific genset drawing, as is the note
on the installation and alignment specification of the steel spring used.
For those regions most at risk of earthquakes, there are special requirements for mounting the gensets. For
those installations, the mounts must be doweled to the foundation. A recalculation of this connection must be
carried out by a structural engineer.
If a genset is installed in a container, a transportation lock must be provided between the genset's base
frame and the foundation plates in the container base. This will prevent movement of the genset on the steel
bellows. The transportation locks must be removed when commissioning the genset.
19.4
Torsionally flexible coupling
After aligning the genset on the foundation, the axial and radial runout of the coupling must be checked. This
is performed using dial gauges. The positioning of the dial gauges is illustrated in principle in Fig. 19.1. For
dimensions, alignment tolerances and screw torque settings, please refer to the order-specific genset
drawing.
The alignment is corrected by moving the generator or by placing shims beneath the foot of the generator.
Chapter_19 - Genset installation and alignment instructions.docx
02999408
Page 4 / 32
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 19.1 Positioning the dial gauges
1
Reference dimension for checking axial runout
2
Flywheel
3
Coupling
Chapter_19 - Genset installation and alignment instructions.docx
02999408
Page 5 / 32
VD-S 2014-06 EN
Caterpillar confidential: none
19.5
Rubber expansion joints and hoses
Expansion joints and hoses are used in the system to elastically decouple media bearing pipes from the
elastically mounted genset. Expansion joints and hoses are also used to insulate structure-borne noise which
would otherwise be transmitted through the pipes into the building.
Furthermore, rubber expansion joints and hoses must be provided in the external piping system in order to
compensate heat expansion. The quantity of expansion joints depends on the pipe routing itself and the heat
expansion caused by the temperature of the media inside the pipe.
Note:
Before installing expansion joints and hoses, the genset must be aligned on its foundation as per Chapter
19.2 (Elastic mounting elements). The external pipes are connected without filling the engine previously with
water and lubricating oil. After filling the water and lubricating oil, the genset only moves down an additional 1
- 2 mm on the engine side. If necessary, the height-adjustable elastic mounts can be readjusted.
Listed in Tables 19.1 and 19.2 are the flange connection dimensions and the specific values for the
expansion joints.
Chapter_19 - Genset installation and alignment instructions.docx
02999408
Page 6 / 32
VD-S 2014-06 EN
Caterpillar confidential: none
Table 19.1 Expansion joints with flanges as per DIN 2501
1
5
2
6
DN
7
PN
[mm]
ØD
ØK
[bar]
nxØd2
b
BL
Ødi
[mm]
3
8
9
ØC
W
10
cm²
11
4
12
[mm]
13
14
[°]
[kg]
32
42,4x2,6
16
150
100
4xØ18
16
125
35
28
75
74
30
10
10
25
4,4
40
48,3x2,6
16
150
110
4xØ18
16
125
35
28
75
74
30
10
10
25
4,4
50
60,3x2,9
16
165
125
4xØ18
16
125
43
40
85
86
30
10
10
25
4,5
65
76,1x2,9
16
185
145
4xØ18
16
125
64
68
104
110
30
10
10
25
4,9
80
88,9x3,2
16
200
160
8xØ18
18
150
73
108
117
137
40
10
10
20
5,9
100
114,3x3,6
16
220
180
8xØ18
18
150
88
124
136
146
40
10
10
15
7,2
125
139,7x4
16
250
210
8xØ18
18
150
115
187
164
175
40
10
10
15
9,1
150
168,3x4,5
16
285
240
8xØ22
18
150
145
245
190
198
40
10
10
12
10,9
175
193,7x5,4
16
315
270
8xØ22
18
150
167
320
215
225
40
10
10
10
15,7
200
219,1x5,9
16
340
295
8xØ22
20
175
194
425
265
260
45
15
15
8
19,8
Legend for column headers
Position
Figure
Designation
1
Flange dimensions as per DIN 2501 *1)
2
Bellow
3
Movement absorption
4
Expansion joint
5
DN
Nominal diameter
6
Pipe as per DIN 2448
7
Active bellows cross section
8
ØC
Sealing surface
9
W
Bellow diameter (without pressure)
10
Compression
11
Extension
12
lateral ±
13
angular
14
Weight
Chapter_19 - Genset installation and alignment instructions.docx
02999408
Page 7 / 32
VD-S 2014-06 EN
Caterpillar confidential: none
*1) Counter flanges as per DIN 2633-PN 16 with screws and self-locking nuts as per DIN 985, but without
any seals, to be ordered separately
For DN 200, counter flanges as per DIN 2632-PN 10
See counter flanges for Stenflex expansion joint type AS-a, complete 1214 0948 UE 0112-38
Stenflex expansion joint AS-a complete 0311 2808 UC 0999-38
Installation Notes No: 6.000.9.000.242 sheet 1-4
Pressure stages
Vacuum at installation
Temperature load up to
°C
Max. perm. operating pressure *)
bar
16
10
6
Test pressure (+20 °C)
bar
25
25
25
bar
60
60
Burst pressure
*) in case of loads produced by jerks, the max.
operating pressure should be reduced by 30% !
60
length ≤ BL
+ 50 + 100 + 110
Special measures are
necessary in this connection
and must be asked for !
1
2
1
Surfaces machined by cutting
2
Rating plate red/blue
In the case of interfered motions, these values have to be enquired from the manufacturer.
Chapter_19 - Genset installation and alignment instructions.docx
02999408
Page 8 / 32
VD-S 2014-06 EN
Caterpillar confidential: none
Table 19.2 Expansion joints with flanges to VG 85356
1
5
2
6
DN
7
PN
[mm]
ØD
ØK
[bar]
nxØd2
b
BL
Ødi
[mm]
84
6xØ11
3
8
9
ØC
W
cm²
16
125
34
28
10
11
4
12
[mm]
73
74
30
10
10
13
14
[°]
[kg]
25
4,4
40
42
25
108
50
50
25
120
96
6xØ11
16
125
43
40
85
88
30
10
10
25
4,5
65
60
25
140
116
8xØ11
16
125
63
68
104
112
30
10
10
25
4,9
80
80
25
150
126
8xØ11
18
150
75
108
117
139
40
10
10
20
5,9
100
100
25
172
148
10xØ11
18
150
95
124
136
148
40
10
10
15
7,2
125
120
10
200
176
10xØ11
18
150
120
187
165
178
40
10
10
15
9,1
150
159
10
226
202
12xØ11
18
150
145
245
190
202
40
10
10
12
10,9
Legend for column headers
Position
Figure
Designation
1
Flange dimesnions as per VG 85356 Part 1
2
Bellow
3
Movement absorption
4
Expansion joint
5
DN
Nominal diameter
6
Pipe diameter outside
7
Active bellows cross section
8
ØC
Sealing surface
9
W
Bellow diameter (without pressure)
10
Compression
11
Extension
12
lateral ±
13
angular
14
Weight
Chapter_19 - Genset installation and alignment instructions.docx
02999408
Page 9 / 32
VD-S 2014-06 EN
Caterpillar confidential: none
Pressure stages
Temperature load up to
Vacuum at installation
°C + 50 + 100 + 110
Max. perm. operating pressure *) bar 16
10
6
bar 25
25
25
Test pressure (+20 °C)
Special measures are
necessary in this connection
and must be asked for !
bar 60 60
60
Burst pressure
*) in case of loads produced by jerks, the max.
operating pressure should be reduced by 30% !
1
2
length ≤ BL
1
Surfaces machined by cutting
2
Rating plate red/blue
In the case of interfered motions, these values have to be enquired from the manufacturer.
Chapter_19 - Genset installation and alignment instructions.docx
02999408
Page 10 / 32
VD-S 2014-06 EN
Caterpillar confidential: none
To ensure correct installation, the following instructions must be observed:
19.5.1
Rubber expansion joints
Installation notes for Stenflex rubber expansion joints type AS-1
19.5.1.1 Storage
Expansion joints must be stored in a clean and dry condition, protected from all damage, and must not be
rolled using the bellows. In the case of storage and installation in the open air, they must be protected from
intense sunlight, such as through the use of a covering sheet.
19.5.1.2 Arrangement and installation
The expansion joint should be arranged in an accessible location where it can be monitored.
Before starting the installation, the gap into which the joint is to be fitted must be checked and the expansion
joint compressed to the correct installation length BL.
Before the expansion joint is installed, it must be checked in its consistency and with regard to state of the
rubber bellows, if for example a strong embrittlement, caused by the high temperature, has occurred.
Fig. 19.2
Flange with smooth sealing surface through to internal diameter
The higher the operating temperature on the expansion joint, the faster the elastic elements will age and
embrittle (in other words, harden) and the rubber bellows have a tendency to form cracks.
If a strong crack formation has occurred on the surface, the expansion joint should be replaced for safety
reasons.
Chapter_19 - Genset installation and alignment instructions.docx
02999408
Page 11 / 32
VD-S 2014-06 EN
Caterpillar confidential: none
Noting the maximum permissible amount of movement which may be accommodated (and which must not
be exceeded in operating mode), the expansion joint must be installed without torsion. The joint should
preferably be subjected to compression.
Attention should also be paid to the effect of external heat radiation. The bores in the flanges must remain in
alignment.
When using DIN welding neck flanges and VG flared flanges, no additional seals are required as the rubber
lip is sufficient. Other flange designs are not permissible owing to the risk of damage to the rubber lip.
19.5.1.3 Installation
Fig. 19.3
A = overall length =
installation length
The expansion joints are installed using normal hexagon screws and self-locking hexagon nuts as per DIN
985.
Only DIN welding neck flanges or VG flared flanges are to be used as counter flanges.
The nuts should be located on the counter flange side, installation type (1). If this is not possible, the length
of the screws should be selected so that the measurement X is not less than 15 mm, installation type (2).
(See Fig. 19.3)
Installation type (1) should be preferred.
The screws should be tightened evenly several times on a diagonally alternate basis; if necessary, they
should be retightened slightly after initial commissioning. Excessive tightening can crush the rubber lip.
To avoid tool damage to the rubber bellows, the wrench on the bellows side should be held steady whilst the
wrench on the counter flange side is turned.
In order not to destroy the rubber seal by overtightening the flanges, Table 19.3 with the tightening torques
has to be observed.
Chapter_19 - Genset installation and alignment instructions.docx
02999408
Page 12 / 32
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 19.3
Tightening torques for rubber expansion joints
Nominal
Tightening torque
width DN
[Nm]
40
10
50
10
65
10
80
10
100
10
125
15
150
15
The tightening torques listed apply to new expansion joints. The values can be exceeded by 50 % if
necessary.
After 24 hours operation, the deformation has to be compensated by retightening the screws.
The installation notes of the expansion joint supplier must be observed.
Chapter_19 - Genset installation and alignment instructions.docx
02999408
Page 13 / 32
VD-S 2014-06 EN
Caterpillar confidential: none
19.5.1.4 Arrangement of pipe brackets
When arranging expansion joints, pipe brackets/guides must be always provided before and after the joint.
For expansion joints that are only installed for the decoupling of vibrations (e.g. the joints of an elastically
mounted genset) fixing points must be provided at each side of the expansion joint.
Expansion joints installed for the compensation of heat expansions in the pipe generally have a pipe bracket
as a fixing point on one side and a pipe guide as a free-running point on the other side. Depending on the
individual installation situation, it might be feasible to provide free-running points on both sides. The distance
between the fixed or free-running point and the expansion joint should not exceed 3 x DN.
See also Chapter 20.4 Pipe brackets / supports
19.5.1.5 Protective measures after installation
After installation, expansion joints should be covered as protection against welding heat (e.g. weld spatter,
beads) and external damage. The expansion bellows must be kept clean and must not be painted.
19.5.1.6 Underpressure loading
If an expansion joint is to be subjected to underpressure (vacuum), it must under no circumstances be
stretched when it is installed. It is better to compress the joint slightly, making it more vacuum-resistant.
However, special measures will be called for here which should be asked for separately. The installation
notes of the expansion joint supplier must be observed here.
19.5.2
Hoses
Installation notes for rubber hoses
DN 8 to DN 40 (flame-proof)
19.5.2.1 Storage
Hoses must be stored in a clean and dry condition and above all protected against external damage. They
should not be dragged on the ground or over sharp edges.
Lay the hose out straight by unrolling the coil of the hose. Pulling on one end of the hose ring will bend the
hose beyond its minimum bending radius and subject it to an impermissible torsional stress.
Chapter_19 - Genset installation and alignment instructions.docx
02999408
Page 14 / 32
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 19.4
Optimum storage = "straight"
19.5.2.2 Arrangement and installation
Hoses should be arranged in an accessible location where they can be monitored.
Hoses should not come into contact with one another or with other objects during operation.
Hoses must not be bent beyond their permissible bending radius (Table 19.4). It is not permissible to
overbend or stretch the hoses.
Fig. 19.5
1
incorrect
A
Installation length too short
2
correct
B
Installation length satisfactory
Chapter_19 - Genset installation and alignment instructions.docx
02999408
Page 15 / 32
VD-S 2014-06 EN
Caterpillar confidential: none
Install hose without tension. Axial compression is not permissible. The braiding detaches itself from the hose
and pressure resistance is no longer guaranteed.
Hoses must not be bent at sharp angles or buckled, i.e. the hose must not be kinked. No movements or
bending stresses must act directly on connections (screw connections). The so-called neutral part of the
hose ends must be of adequate size.
If necessary, standard commercially available elbows, manifolds or ring-type screw connections must be
provided at the connection ends. When selecting the connecting parts, the stress from pressure temperature
and type of medium must be observed. In the event of movement, the hose must be mounted so that its axis
lies in the same plane as the direction of movement in order to prevent torsion.
The So Ms 59 F 50Z (= special brass) soldered connectors on the hose screw connections can be removed
from the connections and hard-soldered to the respective pipe ends.
After determining the gap in which to install the joint between the pipes to be connected, first solder the
connector in place on one side, then check the possible bending radius for the hose before soldering the
connector on the other side.
The permissible bending radii listed in the following Table 19.5 must be observed.
The ends of the connection pipes must be cut off precisely at right-angles to the axis of the pipe.
Chapter_19 - Genset installation and alignment instructions.docx
02999408
Page 16 / 32
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 19.6
1
Connection pipe
2
Soldered connector
3
Union nut
4
hard-soldered
5
Hose line
The minimum bending radii specified in Table 19.4 relate to rigidly laid hoses.
If the movement in the hose (where the bending radius is tight) is very often repeated (= continuous
operation), it is recommended that an attempt be made to increase the radius (if necessary, by using turning
knuckles). This will prevent the hose from kinking and extend its service life.
Chapter_19 - Genset installation and alignment instructions.docx
02999408
Page 17 / 32
VD-S 2014-06 EN
Caterpillar confidential: none
Table 19.4
1
2
DN
[mm]
10
11
12
13
L
[mm]
rmin. *1
[mm]
L2
[mm]
ØD
[mm]
t
[mm]
3
4
5
[bar]
[bar]
[°C]
7
8
6
9
8
300
75
12,5
10x1,0
5
25
10
38
70
GCNA 2277
10
300
80
16,5
14x1,5
6
25
10
38
20
500
130
21,5
25x1,5
8
25
10
50
OLNWV 2298
50
14 )
90 ( 15 )
125 ( 16 )
32
700
180
21,5
35x2,0
8
25
10
32
700
240
23,5
40x2,0
10
22
10
45
80
OLNWV 2298
20
500
130
21,5
25x1,5
8
25
10
50
32
700
180
21,5
35x2,0
8
25
10
50
8
300
115
12,5
10x1,0
5
215
170
510
1STT 2432
16,5
14x2,0
6
180
150
435
240
21,5
25x2,0
8
105
80
255
14 )
100 ( 17 )
100/125 ( 16 )
10
300
130
20
500
32
700
350
21,5
35x2,0
8
63
60
150
40
700
450
23,5
45x2,5
10
50
40
120
80 (
90 (
*1) rmin = smallest bending radius
Chapter_19 - Genset installation and alignment instructions.docx
02999408
Page 18 / 32
VD-S 2014-06 EN
Caterpillar confidential: none
Legend for column and row headers
Position
Figure
1
2
Designation
Medium
ØD
Diameter for pipe
3
Nominal pressure
4
Test pressure
5
Temperature max.
6
Hose designation
7
Normal
8
Upon acceptance
9
Short term
10
Diesel-Fuel
11
Diesel-Fuel, water and lubricating oil
12
Sea water
13
Lube oil, compressed air and water
14
Diesel-Fuel
15
Water
16
Lube oil
17
Compressed air
Chapter_19 - Genset installation and alignment instructions.docx
02999408
Page 19 / 32
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 19.6
1 2
2 1
4
3
5
1
Soldered connector
2
Union nut
3
up to DN 60 press version
from DN 70 screw version
4
Hose line
5
Ordering length L
The following graph (Fig. 19.7) shows - dependent on the bending angle of the hose - the bending factor by
which the minimum bending radius must be multiplied to determine the permissible bending radius for
continuous operation.
Fig. 19.7
A
Bending angle
B
Bending factor
Chapter_19 - Genset installation and alignment instructions.docx
02999408
Page 20 / 32
VD-S 2014-06 EN
Caterpillar confidential: none
19.5.2.3 Installation
When installing the hose, tighten the connection on one side only. To begin with, leave the connection at the
other side loosely fixed. Move the empty hose 2 or 3 times in the desired direction, to allow it to align itself
without twisting, then tighten the loose end as well. In the case of hoses with screw connections, it is
essential to use a second wrench to hold the connection (Fig. 19.8).
Fig. 19.8
Connect hose without twisting.
Use a second wrench to hold rotating threaded connections.
19.5.2.4 Pipe brackets
When arranging hose lines, fixed and free-running points (pipe guides) must always be provided before and
after the hose. The distance between the fixed or free-running point and the hose should not exceed 3 x DN.
19.5.2.5 Protective measures after installation
After installation, hose lines should be covered as protection against welding heat (e.g. welding spatter,
beads) and external damage. The hose line must be kept clean and must not be painted.
19.5.2.6 Type approval test
The hoses are flame resistant (flame-proof) and fulfil the requirements of all classification organizations.
Chapter_19 - Genset installation and alignment instructions.docx
02999408
Page 21 / 32
VD-S 2014-06 EN
Caterpillar confidential: none
19.5.3
Exhaust expansion joints
Installation instructions for axial expansion joints and
axial double expansion joints for the exhaust systems of stationary systems
19.5.3.1 Storage
Axial expansion joints must be stored in a clean and dry condition, protected from all damage, and must not
be rolled using the bellows. Always lift expansion joints for transportation.
19.5.3.2 Arrangement and installation
The expansion joint should be arranged in an accessible location where it can be monitored.
Before starting the installation, the gap into which the joint is to be installed must be checked to ensure the
correct installation length.
Noting the maximum permissible amount of movement which may be accommodated (and which must not
be exceeded in operating condition), the expansion joint must be installed so that it is not subjected to
torsion stresses either during installation or during operation due to adverse pipe tension. The joint should
preferably be subjected to compression. The ideal installation is when the expansion joints are installed free
of tension as far as possible whilst the system is in operation.
The holes in the flanges must line up, and the seal must be located centrally. It must be assured that the
pipes to be connected are also in precise alignment.
When specifying the length of the expansion joints, please note these different terms.
The overall length is the length of the expansion joints as generally supplied by the manufacturer (=
delivered length). The overall length is indicated on the rating plate of the expansion joint.
The installation length comprises the overall length with pre-tension (stretch + or compression -) according
to Fig. 19.9 and Fig. 19.10.
Chapter_19 - Genset installation and alignment instructions.docx
02999408
Page 22 / 32
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 19.9
A
Overall length
B
Extension
C
Installation length
A
Overall length
C
Installation length
D
Compression
Fig. 19.10
In cold condition, the expansion joint should be installed half pre-tensioned (either half stretched + or half
compressed -), dependent on how the expansion joint is to be used. This is recommended even if the axial
movement of the expansion joint is not to be fully utilized. For example, if total expansion is only 30 mm
whilst the expansion joint allows for 66 mm of expansion, it is better - likewise in terms of service life - to
preload the expansion joint to ± 15 mm rather than - 30 mm.
Chapter_19 - Genset installation and alignment instructions.docx
02999408
Page 23 / 32
VD-S 2014-06 EN
Caterpillar confidential: none
19.5.3.2.1
Installation on the engine (turbocharger)
An alignment is necessary when connecting the exhaust pipe on the system side to the exhaust expansion
joint on the engine side. A poor alignment of the engine-side exhaust expansion joint leads to impermissible
forces acting on the housing of the exhaust turbocharger.
To avoid the above problems, we provide installation specifications in the form of a drawing for the TCG
2032, TCG 2020 V12 and V16 with the turbocharger type TPS 52 and for the TCG 2020 V20 with the
turbocharger type TPS 48.
The drawings for the installation specifications are:
•
TCG 2020 V20 /TPS 48:
1242 0623 UB
•
TCG 2020 V12/V16 / TPS 52:
1242 0619 UB
•
TCG 2032 V16:
1228 2504 UB
It must always be ensured that there is no stress imposed on the engine, and in particular on the
turbocharger, due to heat expansion in the connecting pipework. In operation, the expansion joint should
accommodate only the vibrations in the genset on its elastic mountings (Fig. 19.11). The expansion joint
must be mounted at the turbocharger in such a way that the expansion joint returns to its overall length
(delivered length) when the exhaust pipe warms up. The following fixed point must be arranged directly after
the expansion joint.
Chapter_19 - Genset installation and alignment instructions.docx
02999408
Page 24 / 32
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 19.11 Arrangement of the fixed point after the engine in the exhaust line
1
2
5
3
4
1
Fixed point
2
Axial expansion joint
3
Turbocharger
4
Elastically mounted genset
5
Free-running point (pipe guide)
19.5.3.2.2
Installation in the pipe section
To determine heat expansion in a pipe, the following rule of thumb applies:
for mild steel approx. 1 mm heat expansion per meter of pipe and per 100 °C.
for stainless steel approx. 2 mm heat expansion per meter of pipe and per 100 °C.
That means that, for example for a 1 meter section of pipe at 500° C, the heat expansion is approx. 5 mm for
mild steel and 10 mm for stainless steel.
Normally, axial expansion joints are fitted in an exhaust pipe to accommodate the heat expansion. The
arrangement of the expansion joints will be shown on the installation plan for the respective order, whereby
the installation guidelines laid down by the manufacturer must be observed. It will generally be adequate to
continue the exhaust pipe as illustrated in Fig. 19.12.
Chapter_19 - Genset installation and alignment instructions.docx
02999408
Page 25 / 32
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 19.12 Fixed supports, loose supports and expansion joints in an exhaust line
1
Engine
2
Expansion joint after engine
3
Fixed point after engine
4
Free-running point / pipe guide
5
Expansion joint
6
Silencer
7
Fixed point
Chapter_19 - Genset installation and alignment instructions.docx
02999408
Page 26 / 32
VD-S 2014-06 EN
Caterpillar confidential: none
19.5.3.3 Installation
Check that the bellows corrugations are free from foreign bodies (dust, cement, insulation material), first
inside before installation and then outside after installation.
The expansion joints are fitted using normal hexagon screws and nuts.
Smooth flanges or flared flanges are used as counter flanges. The nuts must be fitted on the counter flange
side, see Fig. 19.13.
Fig. 19.13
A
Overall length
The screws should be tightened evenly several times on a diagonally alternate basis; if necessary, they
should be retightened slightly after initial commissioning.
To avoid tool damage to the expansion joint, the wrench on the bellows side should be held steady whilst the
wrench on the counter flange side is turned.
For dimensions and connection sizes, please refer to Fig. 19.14 and Table 19.5.
Chapter_19 - Genset installation and alignment instructions.docx
02999408
Page 27 / 32
VD-S 2014-06 EN
Caterpillar confidential: none
Fig. 19.14
A
Axial movement of bellows
B
Lateral movement of bellows
Chapter_19 - Genset installation and alignment instructions.docx
02999408
Page 28 / 32
VD-S 2014-06 EN
Caterpillar confidential: none
Table 19.5
1
2
*1)
4
7
3
DN
5
10
11
12
2δN
2λN
â
L0
8
9
6
13
14
15
16
17
18
19
l
DA
LK
B
BÖ
b
N
-
mm
mm
mm
mm
mm
Stück
M
mm
mm
mm
mm
mm
100
50
6
1,0
118
60
100
80
12
2,5
184
2x47
50
7,7
0,2
140
75
125
200
114
2,0
340
272
150
50
6,9
0,2
145
78
kg
5,4
210
125
G
170
18
147
14
4
M16
5,9
5
240
200
18
178
10
8
M16
6
6
265
225
18
202
10
8
M16
150
200
101,1
2,0
350
286
7
200
50
5,1
0,2
150
73
11
200
200
81,2
2,0
370
291
320
250
50
3,6
0,1
150
65
250
200
64,5
1,9
370
286
50
3,3
0,1
150
69
300
200
54,4
1,6
365
285
350
50
3,3
0,1
155
74
200
48,1
1,4
355
272
60
4,4
0,1
180
84
180
39,2
1,2
365
60
4,1
0,1
185
98
450
180
34,1
1,0
355
272
500
60
3,8
0,1
190
100
500
180
30,4
0,9
360
270
600
60
2,8
0,1
190
89
370
312
16
12
M16
395
22
365
16
12
M20x2
445
24
415
16
12
M20x2
28
29
495
22
465
16
16
M20x2
35
33
550
22
520
16
16
M20x2
40
36
600
22
570
16
20
M20x2
44
53
755
0,8
18
22
645
25,2
335
18
595
180
M16
279
450
600
8
21
540
400
16
14
490
400
258
17
440
350
18
14
375
300
280
705
26
670
20
20
M24x2
267
700
60
2,6
0,1
200
95
700
180
21,3
0,6
365
262
63
63
860
800
60
1,9
0,1
185
79
800
180
18,3
0,5
365
257
810
26
775
20
24
M24x2
74
77
975
920
30
880
20
24
M27x2
90
*1) Without counter flange, screws and nuts
Chapter_19 - Genset installation and alignment instructions.docx
02999408
Page 29 / 32
VD-S 2014-06 EN
Caterpillar confidential: none
The specified values apply at room temperature; in operating mode, lower values are to be expected.
At temperatures of up to 300 °C, deviations may be disregarded for practical purposes.
For correction values K∆J for higher temperatures, please refer to Table 19.6.
The total of all relative stresses must not exceed 100% of the temperature factor K∆J.
Legend for column headers
Position
Figure
Designation
1
Technical data – axial expansion joint
2
Flanges as per DIN 2501 PN 6
3
DN
4
Nominal diameter
Nominal accomodated movement over 1000 load cycles
5
L0
Overall length - unstressed
6
l
Corrugated length
7
Diameter
8
Screws
9
G
Weight
10
2δN
Axial
11
2λN
Lateral
12
â
Axial / radial
13
DA
Outside diameter
14
LK
Hole circle
15
B
Drilled holes
16
BÖ
Flared tube end
17
b
Blade thickness
18
N
Quantity
19
Thread
Chapter_19 - Genset installation and alignment instructions.docx
02999408
Page 30 / 32
VD-S 2014-06 EN
Caterpillar confidential: none
Likewise, where heat expansion and vibration coincide, the travel and amplitude elements must each be
considered separately as per the formula below:
2𝛿𝑎𝑥𝑖𝑎𝑙,𝐷𝑒𝑠𝑖𝑔𝑛
�2𝛿
𝑎𝑥𝑖𝑎𝑙,𝑁𝑜𝑚𝑖𝑛𝑎𝑙
2𝜆𝑙𝑎𝑡𝑒𝑟𝑎𝑙,𝐷𝑒𝑠𝑖𝑔𝑛
� + �2𝜆
𝑙𝑎𝑡𝑒𝑟𝑎𝑙,𝑁𝑜𝑚𝑖𝑛𝑎𝑙
𝑎� 𝐷𝑒𝑠𝑖𝑔𝑛
� + �𝑎�
𝑁𝑜𝑚𝑖𝑛𝑎𝑙
� ≤ 𝐾∆𝜗 𝑥 100%
Nominal (Nenn): Nominal value from Table 19.5
Design (Auslegung): Maximum movement in operation
An expansion joint comprising multi-wall bellows 1.4541 (X6 CrNiTi 18 9) and flared flange RST 37-2 may be
o
used at operating temperatures of up to 550 C.
The expansion joint only fully undertakes one of the indicated movements. The operating pressure may be
up to 1 bar (PN1).
The installation length (overall length + pre-tension) is dependent on the total system-side expansion.
The overall length Lo refers to the neutral position.
Tab. 19.6 Temperature influence on the available movement
1
J
°C
100
200
300
400
500
600
K∆J
--
1
0.9
0.85
0.8
0.75
0.7
Material
1.4541
19.5.3.4 Arrangement of pipe brackets in the exhaust line
When arranging expansion joints, pipe brackets must always be provided before and after the joint,
otherwise the pipe may bend out sideways. Depending on the installation situation, the pipe brackets can be
arranged as fixed and/or free-running points. The distance between the fixed or free-running point and the
expansion joint should not exceed 3 x DN of the pipe.
When doing this, it must be ensured that the fixed points are actually fixed. The elasticity of a fixed point
should not be so great as to allow the exhaust pipe to move a few millimeters before it is actually held tight.
Free-running points (pipe guides) are pipe clamps which surround the pipe but allow it to slide without
tension. To avoid high levels of friction resistance, possible contamination or obstructions must be prevented
between the pipe guide and the pipe.
Depending on the weight and size of the pipe, it may be necessary to fit extra pipe brackets.
1
Witzenmann, "Kompensatoren" p. 99, 1990
Chapter_19 - Genset installation and alignment instructions.docx
02999408
Page 31 / 32
VD-S 2014-06 EN
Caterpillar confidential: none
19.5.3.5 Protective measures after installation
After installation, expansion joints should be covered as protection against welding heat (e.g. weld spatter,
beads) and external damage. The expansion bellows must be kept clean and must not be painted.
19.5.3.6 Insulation
Because of the considerable heat radiation, it may under circumstances be advisable to insulate an
expansion joint particularly inside the engine house. For this purpose, a sliding tube or sheet-metal sleeve
should be laid around and at some short distance from the expansion joint,to prevent the insulation material
from resting directly on the expansion joint, see Fig. 19.16. Otherwise there is a risk that the insulation
material will jam between the sides of the bellows corrugations. For the insulation, it is recommended to use
asbestos-free plaited insulation strands or matting; glass wool or diatomite should not be used because of
their tendency to produce dust.
Fig. 19.16
19.6
Notes on commissioning
Before commissioning and handover to the client, the genset should be thoroughly cleaned.
The following points should be noted :
Check the adjustment of the elastic mounting elements
Check the alignment of the coupling
Check that the expansion joints have been installed as specified
No tension on cooling water expansion joints
Hoses exhibit prescribed bending radius
Specified pre-tension on exhaust expansion joint
Cables fitted with strain relief and laid with specified bending radius
Air filters free from dirt and contamination
Chapter_19 - Genset installation and alignment instructions.docx
02999408
Page 32 / 32
VD-S 2014-06 EN
Caterpillar confidential: none
Power plants layout
Chapter 20
Laying pipes
06-2014
Caterpillar Energy Solutions GmbH Carl-Benz-Straße 1 D-68167 Mannheim Phone: +49(0)621 384-0 Fax: +49(0)621 384-8612
Caterpillar confidential: none
Contents
20.
Laying pipes
3
20.1
General installation notes
3
20.2
Material for pipes
4
20.3
Notes on welding / soldering pipes
5
20.3.1
Welding steel pipes
5
20.3.2
Hard-soldering pipes
5
20.4
Releasable pipe connections
6
20.4.1
Flange connections
6
20.4.2
Screw connections with sealed thread
6
20.4.3
Screw pipe connections
6
20.5
Pipe brackets / supports
7
20.6
Insulating pipes
7
20.7
Surface treatment, coloring
7
Chapter_20 - Laying pipes.docx
02999408
Page 2 / 8
VD-S 2014-06 EN
Caterpillar confidential: none
20.
Laying pipes
20.1
General installation notes
•
After bending and welding and before laying, all pipes must be cleaned inside, i.e. they must
first be thoroughly steeped in an acid solution, then cleaned with an alkaline solution (soda
or similar) and flushed pH neutrally with hot water. Finally, the inside of the pipes must then
be treated with corrosion protection.
•
When commissioning the system, all pipes must be thoroughly cleaned inside to remove dirt,
scale and swarf, so as to ensure that no foreign bodies are allowed to enter the pumps,
valves, heat exchangers, sensor systems and the combustion engine etc. A pressure test
must be carried out.
•
Where pipe diameters do not match the connections to components (pumps, compressors,
radiators, etc.), they must be adapted by fitting reducers or reducer connectors. For the
location and size of the connections to this apparatus, please refer to the individual
component drawings.
•
When installing measuring instruments (e.g. calorimeters, gas meters, etc.), the guidelines
specified by the manufacturer must be observed. This applies in particular to the installation
location and the inlet and outlet sections.
•
In systems which are to be filled with fluids, connections for draining and filling must be
available at the lowest points. At all high points, air vents must be provided. At the low
points, taps for filling and draining with end cap and hose connection must be installed. At
the high points, bleeding taps or automatic breathers are to be attached.
•
In the case of pipes carrying gaseous media, a condensate collector with drain cocks must
be provided at the lowest points. The pipes must be laid with a slope to the condensate
collector.
•
Copper piping is however permissible for fresh oil filling lines (pipe connections to be
soldered using silver solder). As an alternative, unsheathed ERMETO steel piping may be
used (pipe connections generally assembled using special screw connections, never
welded!). After they have been laid, the fresh oil lines should be thoroughly flushed with new
oil.
•
Fresh oil lines of copper or steel may be compressed with oil-resistant fittings. Since the
sealing material is not oil-resistant, it is not permitted to use standard fittings for the sanitary
area.
Chapter_20 - Laying pipes.docx
02999408
Page 3 / 8
VD-S 2014-06 EN
Caterpillar confidential: none
20.2
Material for pipes
Table 20.1 shows an overview of materials which have to be used for the pipes by the different media:
Table 20.1:
Medium
Subdivision
Pipe material
Distillate fuel
Steel, copper
Blended fuel
Steel
Steel, galvanized steel,
between gas control line and engine steel or
Natural gas, mine gas
stainless steel; these lines must be absolutely
"clean".
Biogas, sewage gas, landfill gas,
generally stainless steel
associated gas
Engine circuit, mixture
cooling circuit, charge air
Water
circuit, heating circuit,
emergency cooling circuit,
raw water circuit
Lube oil, hot engine oil bypass
higher-grade materials may have to be used,
for example sea water in the emergency cooling
/ raw water circuit
Stainless steel
pipes,
Fresh oil filling pipes and waste oil
Steel, copper, stainless steel
pipes
Compressed air
generally steel, depending on the water quality,
Starter pipes
Stainless steel
Filling pipes
Steel
Control air pipes (low
pressure)
Steel, copper
in front of exhaust heat exchanger and interior
Operation with natural gas,
installation: heat-resistant steel (e.g. 15 Mo 3)
mine gas
behind AWT and outdoor installation: stainless
steel
Exhaust gas
Operation with biogas,
sewage gas, landfill gas,
Stainless steel (e.g. 1.4571)
associated gas
in front of catalytic converter always stainless steel 1.4571
With content of acid
Condensate
components
Rest
Chapter_20 - Laying pipes.docx
02999408
Stainless steel
Steel, copper, galvanized steel
Page 4 / 8
VD-S 2014-06 EN
Caterpillar confidential: none
When using materials other than those specified in Table 20.1, technical approval from the head office is
required.
20.3
Notes on welding / soldering pipes
Welded connections form a homogeneous part of the piping and guarantee absolute impermeability during
operation. They represent the most economical method of connecting pipes and are therefore used in
preference to other methods. The quality of the weld joint is dependent on how the pipes are fitted together,
the ends being perfectly centered and the edges properly prepared for welding.
Attention: When performing welding work in the pipe system, it is absolutely necessary to disconnect all
electrically conductive connections to the genset. Steel compensators on the genset must be dismantled.
In the case of E weldings, the electrode mass has to be placed as near as possible to the welding point in
order to ensure a good ground connection. Rubber and steel expansion joints must be covered during the
welding work to avoid damages from the welding sparks.
See also Chapter 19.2.
20.3.1
Welding steel pipes
The following points should be noted:
The roughness of the severance cuts must not exceed max. Rz 100
Permissible welding procedures as per
DIN ISO 857-1, manual arc welding, MIG or TIG
DIN EN 439, argon inert gas, at 5-7 liter/min argon to protect weld root
Weld seam preparation as per
DIN EN ISO 9692-1
Directive on assessment categories for irregularities
DIN EN ISO 5817 or
Filler metals
- Manual arc welding : Rod electrode DIN EN ISO 2560
- TIG: Solid rod
DIN EN 440, DIN EN 439, DIN EN 1668
- MIG: Wire electrode DIN EN 440, DIN EN 439, DIN EN 1668
20.3.2
Hard-soldering pipes
Brazed joints should be manufactured in accordance with our works standard H0340.
Chapter_20 - Laying pipes.docx
02999408
Page 5 / 8
VD-S 2014-06 EN
Caterpillar confidential: none
20.4
Releasable pipe connections
20.4.1
Flange connections
Flange connections are notable for their ease of assembly and are generally used for the pipe connections at
engines, pumps, heat exchangers, tanks, etc. Preference should be given to flanges which comply with DIN
2501, PN10 or PN16; for high-pressure media (e.g. compressed air), they should have a correspondingly
higher nominal pressure.
When servicing or maintaining engines or system components, it is often necessary to dismantle pipes to
improve accessibility. In such cases, it is particularly recommended that flange connections be installed at
suitable locations.
The materials used to seal between the flanges should be selected to suit the load imposed by the medium
itself as well as the pressure and temperature of the medium. In order to avoid leaks, flange connections
need to be monitored. Therefore, as far as possible, flange connections should be accessible in order to
replace the seals or retighten the screws. The facility to check the connections visually must, under all
circumstances, be guaranteed.
20.4.2
Screw connections with sealed thread
Whitworth pipe threads as per DIN EN 10226 are used exclusively for cylindrical, internal threaded
connections to mountings, fittings, etc. and for tapered external pipe threads. To increase the sealing
tightness before fitting, the threads must be packed with sealant in the form of hemp with sealing putty or
plastic sealing tape.
Plastic sealing tape should be used for lubricating oil, fuel and gas pipes.
20.4.3
Screw pipe connections
With screw pipe connections, the sealing tightness is achieved with the aid of a progressive ring which
creates a positive-fit, leak-proof pipe connection.
In such cases, exclusively precision steel pipes should be used, preferably with external diameters from 6 to
38 mm. Depending on the wall thickness and external diameter, it may be necessary to use reinforcing
sleeves.
Care must be taken in tightening the progressive ring.
Chapter_20 - Laying pipes.docx
02999408
Page 6 / 8
VD-S 2014-06 EN
Caterpillar confidential: none
20.5
Pipe brackets / supports
Pipes should be fastened to consoles or walls with clamps, round steel clips, etc. In the case of pipes
running horizontally, the mounting span must be selected according to the pipe diameter. In the case of
pipes subject to expansion because of the high temperature of the medium they carry, the mounting supports
must be implemented in fixed or free-running form to suit the conditions. Where appropriate, the possibility of
structure-borne noise should be considered.
20.6
Insulating pipes
Depending on the temperature of the medium they carry, pipes must be fitted with heat insulation to provide
contact protection. The insulation thicknesses must be selected to avoid the surface temperatures of the
insulation exceeding 60° C. Contact protection can also be achieved by other means, for example by fitting
perforated metal sheeting or wire mesh at an appropriate distance from the hot parts.
20.7
Surface treatment, coloring
It is essential that all piping, with the exception of stainless steel pipes, is painted. For this purpose, the pipes
must be thoroughly cleaned and primed to a dry film thickness of approx. 30 μm. A top coat must then be
applied, coating thickness approx. 40 μm.
Insofar as no particular colors are otherwise specified, the colors should be selected in accordance with DIN
2403. This standard lays down the requisite colors for pipes dependent on the media they carry.
Pipes provided with heat insulation should be coated in primer only.
Steel exhaust pipes must be painted with heat-resistant paint. A high-temperature-resistant zinc silicatebased paint should be used, preferably applied in 2 coats, each of 40 μm dry film thickness.
Chapter_20 - Laying pipes.docx
02999408
Page 7 / 8
VD-S 2014-06 EN
Caterpillar confidential: none
Chapter_20 - Laying pipes.docx
02999408
Page 8 / 8
VD-S 2014-06 EN
Caterpillar confidential: none
Power plants layout
Chapter 21
Health and safety at work, accident prevention,
environmental protection
06-2014
Caterpillar Energy Solutions GmbH Carl-Benz-Straße 1 D-68167 Mannheim Phone: +49(0)621 384-0 Fax: +49(0)621 384-8612
Caterpillar confidential: none
Contents
21.
Health and safety at work, accident prevention, environmental protection
21.1
Scaffolding, staging, ladders ......................................................................................................... 3
21.2
Noise protection ............................................................................................................................ 3
21.3
Fire safety, escape plan ................................................................................................................ 4
21.4
Contact protection ......................................................................................................................... 4
21.5
Emergency Stop facilities .............................................................................................................. 4
21.6
Storage and disposal of hazardous materials ............................................................................... 5
21.7
Electrical protection ....................................................................................................................... 5
21.8
Accident prevention regulations for electrical systems ................................................................. 6
21.9
Risk assessments ......................................................................................................................... 6
Chapter_21 - Safety, Prevention, Protection.docx
02999408
Page 2 / 6
3
VD-S 2014-06 EN
Caterpillar confidential: none
21.
Health and safety at work, accident prevention, environmental protection
When planning, installing and maintaining a system incorporating engine-driven gensets, the general rules
governing health and safety at work and the accident prevention must be observed.
In the EU, the German Health and Safety at Work Regulations (BetrSichV) for the safety of working
appliances and systems requiring monitoring have been applicable since October 03rd 2002.
Basic health and safety requirements in the design and construction of machines are laid down in the EU
Directive 2006/42/EC. The present aim is to draw attention to certain measures.
The safety provisions, which are a component of the gensets and/or system documentation, must be
complied with during layout, maintenance and operation of the systems.
21.1
Scaffolding, staging, ladders
•
When installing systems, it is usual for components to be installed at such heights that
scaffolding or staging is required. Scaffolds and stages must be equipped with safety
railings. If heavy components are to rest on the scaffolding, this must be adequate to bear
the load.
•
If frequently operated fittings or instruments to be read on a regular basis are installed at a
height which is not normally reachable, stationary platforms must be provided.
•
Only TÜV-approved ladders may be used.
•
When installing series TCG 2032 engines, it is essential that engine maintenance stages are
provided by the client.
21.2
Noise protection
In the engine room, when the gensets are operating, noise levels of above 100 dB(A) are reached. Over
time, these will cause persons present in the engine room to suffer hearing damage if protective measures
are not taken. Ear protection must therefore be worn in the engine room when the gensets are operating.
Warning notices requiring ear protection to be worn must be provided at the entrances to the engine room.
Chapter_21 - Safety, Prevention, Protection.docx
02999408
Page 3 / 6
VD-S 2014-06 EN
Caterpillar confidential: none
21.3
Fire safety, escape plan
•
The fuels, gaseous or liquid, used for the gensets and the engine lubricating oil can easily
ignite in the atmosphere. Uncontrolled fuel escapes must therefore be avoided or monitored.
Cleaning cloths soaked in oil or fuel must be disposed of immediately, since if these catch
fire, they can easily become the cause of a major conflagration. Depending on the safety
requirements for the design of the respective plant, stationary fire extinguishing facilities
must be provided along with appropriate alarm and triggering devices. There must be notices
identifying the location of fire extinguishing equipment such as e.g. manual fire extinguishers,
hydrants, etc.
•
The appropriate width (min. 600 mm) and height (min. 2000 mm) of escape routes must be
observed. In case of fire in the engine room, the escape routes must be identified. An
escape plan must be available. This is of particular importance where the engine room is
located within a larger building.
•
21.4
The statutory regulations are to be followed.
Contact protection
All components involving moving parts - in the engine room, this will primarily include the gensets with the
engine-driven generators, compressors and electric pumps - must be fitted with the appropriate protective
devices to prohibit direct contact with rotating parts. The protective devices may be removed for service and
maintenance work only. When carrying out such works, the starters must be isolated to prevent the engines
from being started unintentionally.
When the gensets are in operation, the media bearing lines, especially the cooling water and exhaust lines,
can reach temperatures which would cause burns to the skin in the event of direct contact. These lines must
be fitted with heat insulation or with appropriate contact protection.
21.5
Emergency Stop facilities
In addition to the emergency stop buttons at each genset, a secured emergency stop button must be located
at an easily accessible point in the engine room, preferably in the vicinity of the escape door, to shut down
the system in the event of a hazard.
Chapter_21 - Safety, Prevention, Protection.docx
02999408
Page 4 / 6
VD-S 2014-06 EN
Caterpillar confidential: none
21.6
Storage and disposal of hazardous materials
Fuels, lubricating oils, cooling water treatment agents, battery acid, cleaning agents, etc, constitute
hazardous materials, which should be stored in large containers, barrels or other vessels in the engine room
or in an adjacent room. The storage locations for such materials must be so designed that even if a container
is damaged, the substances cannot enter the waste water system.
21.7
Electrical protection
The VDE regulation VDE 0100 defines measures to protect against hazardous contact voltages.
It distinguishes between:
•
Protection against direct contact
Live parts of electrical operating equipment - parts carrying a voltage - must either be
insulated in their entirety or protected against direct contact by virtue of their design, location
or arrangement, or by way of special regulations.
•
Protection in the event of indirect contact
Even in the case of operating equipment which was fine at the time of manufacture,
insulation defects may occur due to aging or wear, as a result of which touchable, conductive
parts may carry high contact voltages (50 V and above).
Work should only be carried out on potentially live electrical installations whilst these are isolated from the
voltage supply.
In order to render the equipment voltage-free and secure, there are 5 safety rules to be followed:
•
Disconnect
•
Secure against reconnection
•
Check that equipment is voltage-free
•
Earth and short-circuit
•
Cover or cordon off adjacent parts which are electrically live
The responsible supervisor must not approve the workplace for works to commence until all 5 safety rules
have been complied with.
Once work has been completed, the safety measures must be lifted.
The order to switch the equipment on must not be given until the system has been released at all workplaces
and all switch points have reported that they are ready to connect.
Chapter_21 - Safety, Prevention, Protection.docx
02999408
Page 5 / 6
VD-S 2014-06 EN
Caterpillar confidential: none
21.8
Accident prevention regulations for electrical systems
The accident prevention regulations must be observed!
Especially the "General Regulations“ BGV A1 and "Electrical systems and operating equipment“ VBG4. For
the installation of power systems, please refer to VDE 0100 (up to 1 kV) or VDE 0101 (over 1 kV); for
operation, DIN EN 50191 or VDE 0105 applies.
Note:
Electrical systems and power installations may be installed and operated by trained personnel only.
Personnel must be specially trained in order to commission medium-voltage generators.
21.9
Risk assessments
Risk assessments have been carried out and documented for all gensets. The possibilities of a hazard
during installation, starting, operation and maintenance of the gensets are outlined and evaluated in the risk
assessments. The measures to be undertaken for limiting the hazard are also described.
Chapter_21 - Safety, Prevention, Protection.docx
02999408
Page 6 / 6
VD-S 2014-06 EN