Download TB2014-002 e3 Transorb Installation Instructions.indd

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Resistive opto-isolator wikipedia , lookup

History of electric power transmission wikipedia , lookup

Current source wikipedia , lookup

Rectifier wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Voltage regulator wikipedia , lookup

P–n diode wikipedia , lookup

Alternating current wikipedia , lookup

Opto-isolator wikipedia , lookup

Stray voltage wikipedia , lookup

Buck converter wikipedia , lookup

Rectiverter wikipedia , lookup

Voltage optimisation wikipedia , lookup

Relay wikipedia , lookup

Mains electricity wikipedia , lookup

Protective relay wikipedia , lookup

Surge protector wikipedia , lookup

Transcript
USA & Canada (800) 421-1587 & (800) 392-0123
(760) 438-7000 - Toll Free FAX (800) 468-1340
www.linearcorp.com
TECHNICAL BULLETIN
TB2014-002
ISSUE DATE 3/21/2014
e3 Door Lock Relay Transorb Installation Instructions
What’s a Transorb?
A transient voltage suppression diode (commonly known as a
“transorb”) is an electronic component used to protect sensitive
electronics from voltage spikes induced by another source. A transorb
will shunt excessive current when the voltage across the transorb
exceeds a certain level. Transorbs do not require “resetting” and will
return to an open state when the transient voltage spike is over.
Why Transorbs for the e3 System?
Linear’s e3 Access Control platform products are typically connected
to electromechanical or magnetic door strikes that control building
access to users. These types of door locks create a magnetic field
when energized to perform the physical locking or unlocking of the
door. When the lock is de-energized, a strong voltage spike may result
when the lock’s magnetic field collapses. Installing transorbs across
the e3 relay terminals protects the system from these unwanted and
potentially damaging transient voltage spikes.
Fail Safe DC Door Strike (without power, door strike is unlocked)
Transorb Installation
Transorbs should be installed across all e3 door lock relay contacts, in
parallel with the lock wiring. This applies to both AC and DC locks.
Four (4) transorbs are included with each e3 system. DO NOT discard
these important devices.
Install a transorb to the door lock relay connector in the same terminal
positions as the lock wiring. The Type SA48C transorbs supplied
are bi-directional (no polarity) and can be installed across the relay
terminals wired in either direction.
Even with a transorb installed across the relay terminals at the panel,
still be sure to install the appropriate protection device (a diode or MOV)
on the other end of the cable at the location of the door lock.
See the installation examples for wiring details. They show both the
transorb across the e3 relay terminals and the diode or MOV across
the door lock.
Fail Secure DC Door Strike (without power, door strike is locked)
Relay
Terminals
e3 Circuit Board Door Relay Terminal Locations
Copyright © 2014 Linear LLC
Fail Secure AC Door Strike (without power, door strike is locked)
P2083 X1