Download The Importance of the Neutral Connection in 3-Phase

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Mercury-arc valve wikipedia , lookup

Stepper motor wikipedia , lookup

Ground loop (electricity) wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Islanding wikipedia , lookup

Electrical ballast wikipedia , lookup

History of electric power transmission wikipedia , lookup

Ohm's law wikipedia , lookup

Schmitt trigger wikipedia , lookup

Rectifier wikipedia , lookup

Single-wire earth return wikipedia , lookup

Electrical substation wikipedia , lookup

Current source wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Power electronics wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Triode wikipedia , lookup

Power MOSFET wikipedia , lookup

Voltage regulator wikipedia , lookup

Ground (electricity) wikipedia , lookup

Buck converter wikipedia , lookup

Opto-isolator wikipedia , lookup

Electrical wiring in the United Kingdom wikipedia , lookup

Voltage optimisation wikipedia , lookup

Alternating current wikipedia , lookup

Stray voltage wikipedia , lookup

Earthing system wikipedia , lookup

Mains electricity wikipedia , lookup

Three-phase electric power wikipedia , lookup

Surge protector wikipedia , lookup

Transcript
The Importance of the Neutral Connection in 3-Phase
Surge Diverters
A surge diverter is a shunt, or parallel connected device, designed to conduct harmful
surge energy away from equipment which might otherwise be damaged. A typical
surge diverter contains metal oxide varistors (MOVs) and gas discharge tubes (GDTs)
– at normal mains voltages, these components appear as a virtual open circuit and do
nothing. When a surge is encountered on the line, the MOVs and GDTs go into a
conductive state, dissipating the energy supplied by the surge.
Figure 1: Representative surge diverter schematic
Figure 1 shows a representative schematic of a 3-phase surge diverter. Between each
line and neutral there is a metal oxide varistor, between neutral and earth there is a gas
discharge tube. Transverse mode protection is provided by the MOVs; common mode
is provided by the addition of the GDT.
Under normal installation conditions, the diverter is virtually transparent to the overall
system. MOVs feature some leakage current at mains voltages but it is negligible (10100µA), whilst the GDT is totally benign until its break over voltage is reached
(typically 350Vpk). In a properly installed MEN distribution system there should be
negligible voltage between neutral and earth.
Novaris Pty Ltd
72 Browns Road, Kingston, TAS. 7050 AUSTRALIA
Tel: + 613 6229 7233
FAX: + 613 6229 9245
URL: www.novaris.com.au
Email: [email protected]
Section #: SK10
Revision: 1
Date:
16/04/04 Page:
1 of 3
Figure 2: Normally connected surge diverter
Figure 2 shows the state of the surge diverter circuit during normal operation. Neutral
and earth are bonded at the MEN link thus are, for all intents and purposes, at the
same voltage reference. The MOVs are connected in a star configuration, with the
phase-neutral voltage on each line dropped across the MOV.
At the rated operating voltage, MOVs exhibit a small leakage current (in the vicinity
of 100uA). Most MOVs are produced with tolerances of +/- 20%, which means that
the leakage current through each MOV at any given voltage may vary by as much as
this.
So long as the star point of the three phases is tied to a stable reference (i.e. ground,
via the MEN link) the voltage seen between each phase and the star point will be the
same as that of the supply. If however, the neutral connection is removed from the
diverter, the star point will no longer be referenced to ground and will tend to float
towards the potential of the phase with the greatest load. As the potential of one phase
is approached, the potential between the other phases and the star point increases
proportionally, until a point of equilibrium is reached.
Novaris Pty Ltd
72 Browns Road, Kingston, TAS. 7050 AUSTRALIA
Tel: + 613 6229 7233
FAX: + 613 6229 9245
URL: www.novaris.com.au
Email: [email protected]
Section #: SK10
Revision: 1
Date:
16/04/04 Page:
2 of 3
Figure 3: Surge diverter without neutral connection
The voltage dropped across a MOV needs only to increase by a small amount before
heating effects will cause it to self-destruct. In the case of a 275V MOV, which are
standard in surge diverters for Australia, 320V is more than enough to cause rapid
heating and breakdown of the element. In a star connected surge diverter without a
neutral reference, it is common for the voltage across two of the phases to reach this
level as the star point drifts towards the remaining phase.
Examination by Novaris of surge diverters which have failed after being operated
without a neutral reference has confirmed this phenomena. In most instances, the
MOV elements of two phases have exhibited signs of overheating and failure, whilst
the remaining phase is undamaged.
During installation of a surge diverter, the correct connection of all conductors is
critical to the correct operation of the device. Not only does the ability of the diverter
to provide surge protection depend on the availability of a neutral reference; the
diverter itself is likely to fail even in its passive state.