THE EUROPEAN REGIONAL DEVELOPMENT FUND AND THE MINISTRY OF INDUSTRY AND TRADE OF CZECH REPUBLIC SUPPORT INVESTMENT IN YOUR FUTURE RIS P01 insulation status relay Technical specifications: Rated supply voltage Rated current Insulation resistance at 230 (127) V Equipment Return Insulation resistance at 42 (36) V Equipment Return Temperature range Relative humidity Case Dimensions Weight 42VAC +20%, -30% 50Hz 0.05A 15kW >20kW 4,5kW >6.5kW 0°C to +80°C 85% w/o cond. IP20 94 x 46 x 126mm 0.2kg Application: The RIS P01 insulation status relay is used for the permanent monitoring of insulation status of auxiliary AC 50Hz networks (networks 36V, 42V or 127V, 230V). RIS P01 is designed for installation in flameproof “d” enclosures or in safe areas (e.g. on the surface). Description: All monitoring circuits are designed as nonflammable circuits. The RIS P01 integrates the two separate blocks, with each block operating fully autonomously. One block is used for monitoring the insulation level of 36V and 42V auxiliary networks and the second block is then used to monitor the insulation level of auxiliary networks 127V, 230V. The RIS P01 does not need a choke to function. The RIS P01 also includes: LED indicators (located on the front of the module) are used to indicate operating status. A 21-pin connector for connecting more downstream circuits. Coding holes located in the base module. Potential-free output relay with retainer, electrical or mechanical reset possible. The catalogue has only those selected important parameters for your final decision. For project designs always ask for the user’s guide for this product and any engineering consultation about possible uses. ISO 9001 : 2009 ZAM-SERVIS s.r.o. Křišťanova 1116/14 702 00 Ostrava - Přívoz tel.: +420 596 135 422, email: [email protected], www.zam.cz V140116 These data sheets are not an offer within the meaning of Czech Republic Law No. 89/2012.