Download RIS P01 insulation status relay - ZAM

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Electrical substation wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Voltage optimisation wikipedia , lookup

Electronic engineering wikipedia , lookup

Relay wikipedia , lookup

Stray voltage wikipedia , lookup

Mains electricity wikipedia , lookup

Telecommunications engineering wikipedia , lookup

Flexible electronics wikipedia , lookup

Protective relay wikipedia , lookup

Earthing system wikipedia , lookup

Portable appliance testing wikipedia , lookup

Opto-isolator wikipedia , lookup

Two-port network wikipedia , lookup

National Electrical Code wikipedia , lookup

Transcript
THE EUROPEAN REGIONAL DEVELOPMENT FUND
AND THE MINISTRY OF INDUSTRY AND TRADE OF
CZECH REPUBLIC SUPPORT INVESTMENT IN YOUR FUTURE
RIS P01 insulation status relay
Technical specifications:
Rated supply voltage
Rated current
Insulation resistance at 230 (127) V
Equipment
Return
Insulation resistance at 42 (36) V
Equipment
Return
Temperature range
Relative humidity
Case
Dimensions
Weight
42VAC +20%,
-30% 50Hz
0.05A
15kW
>20kW
4,5kW
>6.5kW
0°C to +80°C
85% w/o cond.
IP20
94 x 46 x 126mm
0.2kg
Application:
The RIS P01 insulation status relay is used for the
permanent monitoring of insulation status of auxiliary AC
50Hz networks (networks 36V, 42V or 127V, 230V).
RIS P01 is designed for installation in flameproof “d”
enclosures or in safe areas (e.g. on the surface).
Description:
All monitoring circuits are designed as nonflammable
circuits. The RIS P01 integrates the two separate blocks,
with each block operating fully autonomously. One block is
used for monitoring the insulation level of 36V and 42V
auxiliary networks and the second block is then used to
monitor the insulation level of auxiliary networks 127V,
230V.
The RIS P01 does not need a choke to function.
The RIS P01 also includes:
LED indicators (located on the front of the module) are used
to indicate operating status.
A 21-pin connector for connecting more downstream
circuits.
Coding holes located in the base module.
Potential-free output relay with retainer, electrical or
mechanical reset possible.
The catalogue has only those selected important parameters for your final decision. For project designs
always ask for the user’s guide for this product and any engineering consultation about possible uses.
ISO 9001 : 2009
ZAM-SERVIS s.r.o. Křišťanova 1116/14 702 00 Ostrava - Přívoz
tel.: +420 596 135 422, email: [email protected], www.zam.cz
V140116
These data sheets are not an offer within the meaning of Czech Republic Law No. 89/2012.