Download Edison Power Distribution Blocks

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Audio power wikipedia , lookup

Solar micro-inverter wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Electric power system wikipedia , lookup

Power over Ethernet wikipedia , lookup

History of electric power transmission wikipedia , lookup

Single-wire earth return wikipedia , lookup

Telecommunications engineering wikipedia , lookup

Electrification wikipedia , lookup

Electrical substation wikipedia , lookup

Amtrak's 25 Hz traction power system wikipedia , lookup

Power engineering wikipedia , lookup

Mains electricity wikipedia , lookup

Alternating current wikipedia , lookup

Wire wrap wikipedia , lookup

Electrical wiring wikipedia , lookup

National Electrical Code wikipedia , lookup

Transcript
Prices as of April 27, 2016. Check Web site for most current prices.
Edison Power Distribution Blocks
Short-Circuit Current Rated Power
Distribution Blocks
We offer distinctly different styles of short-circuit current rated
Power Distribution Blocks and Terminal Blocks to match different application needs.
1) Enclosed style or Open style
2) UL1953 Listed power distribution blocks or UL1059 Recognized
terminal blocks, that have different minimum spacing requirements.
The table below can assist in the selection of the correct series
for your application requirements.
Why are these important?
Assembly short-circuit current ratings (SCCRs) are now required in the 2005 NEC® and UL508A Listed industrial control panels.
Marking the SCCR on:
Industrial Control Panels (NEC® 409.110)
Industrial Machinery Electrical Panels (NEC® 670.3(A))
HVAC equipment (NEC® 440.4(B)
The above sections are now required by the National Electrical Code. Power Distribution Blocks or Terminal Blocks not
marked with an SCCR are typically one of the weakest links
and may limit an assembly to no more than 10 kA SCCR per
Table SB4.1 UL508A. The EPDB series and HPB series Power
Distribution Blocks have increased spacing required where
used in feeder circuits in equipment listed to UL508A. The PB
series UL1059 Terminal Blocks must be evaluated for proper
spacing. Also, for building wiring systems, the EPDB series and
HPB series power distribution blocks can be used to meet the
2005 NEC® requirements in section 376.56(B) for power distribution blocks in wireways.
Edison Power Distribution Blocks Selection Guide*
Series
UL
High Spacing***
† Enclosed SCCR**
1” Air
2” Surface
UL 1953 Listed
EPDB Power Distribution
HPB
PB
Blocks
UL 1953 Listed
Power Distribution
Blocks
UL 1059 Recognized Terminal
Blocks
Industrial Control
Panels
UL 508A
Branch Circuit
Industrial Control HVAC
Wireways
Panels
UL
1995
NEC®
376.56(B)
UL 508A
(Requires
UL 1953)
Feeder Circuit
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No****
Yes
Yes
Yes
Yes
Yes
Yes (with optional cover)
No****
Yes
No*****
Yes
No*****
Yes
No
† IP-20 finger-safe under specific conditions.
*Refer to specific UL standards and NEC sections for a complete application guide.
**When protected by proper fuse class with maximum ampere rating specified or smaller.
This does not apply to PB40, PB51 and PB71 series.
***See Minimum Space Requirements for Equipment table below.
****Optional covers are available. They are not IP-20 rated, but do provide additional protection against direct contact with Live Parts.
*****Exception: Yes, if single pole units installed with proper spacings.
Minimum Space Requirements for Equipment
UL Standard
Spacing Between
Spacing Between Live Parts
Live Parts of
and Grounded Parts or
Opposite Polarity
Enclosures, Through Air and
Through
Over Surface
Over Surface @ 600V
Air @
600V
1”
@ 600V
508A Feeder Circuits, Table 10.2
2”
1”
508A Branch Circuits, Table
3/8”
1/2”
1/2”
10.1
UL 1995 HVAC
3/8”
1/2”
1/2”
Note: Refer to specific UL standards for complete spacing details.
Book 3 (14.3)
eTB-92
Terminal Blocks
1 - 8 0 0 - 633 - 0 4 0 5
Prices as of April 27, 2016. Check Web site for most current prices.
EPDB Series Edison Finger-Safe
Power Distribution Blocks
Finger-safe
distribution blocks
Features
Use Finger-safe Power Distribution
Blocks to manage your power distribution needs, from splitting primary power
circuits into a variety of branch circuits to
providing a fixed junction tap-off point.
The modular design allows the end user
to select and configure the number of
poles required by each application.
These blocks are engineered to allow
copper conductors and maintain an
SCCR rating of 200kA. These features
make these blocks the perfect solution
to today’s power circuit wiring requirements.
Company
Information
Terminal Blocks
Power
Distribution
Blocks
Ratings
•Fully enclosed block for touch-safe
isolation of live parts
• IP20 rating under specific conditions
•Integrated DIN-rail or direct panel
mounting. (Panel mount only for EPDB306
and EPDB702)
•Captive termination screws cannot be
lost
•Used in UL508A panels for both feeder
and branch circuit applications
•Suitable for both factory and field wiring
•Tin-plated aluminum connectors suitable
for copper conductors
•Ampere ratings from 175 Amps to 760
• 600 VAC or VDC
•Short Circuit Current Rating (SCCR) 200kA
with proper fusing
• Flammability: UL 94V0
Agency Approvals
• UL 1953 Listed - File E256146, Guide
QPQS
• CSA Certified - Class 6228-01, File 700490
• CE component IEC 60947-7-1
• IEC-60529, IP20 (Finger-Safe)
See table for specific conditions.
Part Number
EPDB101
EPDB104
EPDB301
Finger-safe
(EPDB)
EPDB306
EPDB512
Accessory
EPDB702
DN-EB35*
Amps
Multi-wire
Connectors
Sensor Cables
and Connectors
M12 Junction
Blocks
Panel Interface
Connectors
Cable Ties
Description
Wire
SCCR Rtg Pcs/Pkg Wt.
Price
175 max 1 pole distribution block, 1 in/1 out
200 kA
1
3.4 oz.
$10.50
175 max 1 pole distribution block, 1 in/4 out
200 kA
1
4.2 oz.
$15.50
310 max 1 pole distribution block, 1 in/1 out
200 kA
1
8.1 oz.
$25.00
380 max 1 pole distribution block, 1 in/6 out
1 pole distribution block,
570 max
2 in/12 out
760 max 1 pole distribution block, 2 in/2 out
200 kA
1
9.1 oz.
$35.50
200 kA
1
12.5 oz. $41.00
200 kA
1
16.4 oz. $64.00
–
50
1.87 lb.
–
ZIPLink
Connection
System
Wiring Duct
Finger-safe Power Distribution Blocks Selection Table
Series
Wiring
Accessories
End bracket
Bulk
Multi-conductor
Cables
Wire
Management
Products
Power Supplies
$39.50
DC Converters
*Note: DIN-rail anchors are required on block or blocks. Anchors must be used to
prevent damage to the plastic housing when tightening terminals.
Transformers
and Filters
Circuit Protection
Tools
Test
Equipment
Finger-safe Power Distribution Block General Specifications
Wire Type
Voltage
Operating Temperature
Storage Temperature
Mounting
Enclosures
75°C*, Cu
Enclosure
Climate Control
600 VAC or VDC maximum (UL 1953), 690 VAC/VDC (IEC)
-10°C to 60°C (14°F to 140°F)
Safety: Electrical
Components
-20°C to 60°C (-4°F to 140°F)
35mm DIN rail (DN-R35S1) or surface mount.
Safety: Protective
Wear
*Note: Amp Rating is based on NEC table 310.16 for 75°C copper wire.
Terms and
Conditions
Book 3 (14.3)
w w w. a u t o m a t i o n d i r e c t . c o m / t e r m i n a l - b l o c k s
Terminal Blocks
eTB-93
Prices as of April 27, 2016. Check Web site for most current prices.
EPDB Series Edison Finger-Safe Power
Distribution Blocks Specifications
Edison Finger-Safe Power Distribution Blocks Wire and Torque Range Specifications
Part
Number
EPDB101
EPDB104
Line
Load
Torque Trim Length Hex
Lb-in (Nm) in (mm) Key
CU Wire Range
2/0 to 8 AWG, 70 to 10 mm2
110 [12.4]
2/0 to 8 AWG, 70 to 10 mm2
0.850 [21.6]
120 [13.6]
3/16”
0.750 [19.0]
CU Wire Range
Torque
Lb-in (Nm)
Trim Length
in (mm)
Hex
Key
2/0 to 8 AWG, 70 to 10 mm2
110 [12.4]
0.970 [24.6]
3/16”
4 to 12 AWG, 25 to 16 mm2
35 [4.0]
8 AWG, 10 mm2
25 [2.8]
3/16”
10 to 14 AWG, 6 to 2.5 mm2
EPDB301 350 kcmil to 6 AWG, 185 to 16 mm2 275 [31.1]
1.350 [34.3]
5/16” 350 Kcmil to 6 AWG, 185 to 16 mm2
EPDB306 500 kcmil to 6 AWG, 240 to 16 mm2 500 [56.5]
1.250 [31.8]
EPDB512 300 kcmil to 4 AWG, 150 to 25mm2 275 [31.1]
EPDB702 500 kcmil to 6 AWG, 240 to 16 mm
2
500 [56.5]
3/8”
1.15 [29.2] top
row
1.400 [35.6]
bottom row
1/4”
1.250 [31.8]
3/8”
20 [2.3]
275 [31.1]
2 to 3 AWG, 35 mm
50 [5.7]
4 to 6 AWG, 25 to 16 mm2
45 [5.1]
8 AWG, 10 mm2
40 [4.5]
10 to 14 AWG, 6 to 2.5 mm2
35 [4.0)]
4 to 6 AWG, 25 to 16 mm2
35 [4.0]
8 AWG, 10 mm2
25 [2.8]
2
0.550 [14.0] top row,
0.850 [21.6] bottom row 1/8”
10 to 14 AWG, 6 to 2.5 mm2
20 [2.3]
500 kcmil to 6 AWG, 240 to 16 mm2
500 [56.5]
1.250 [31.8]
5/16”
0.590 [15.0] top row
1/8”
1.200 [30.5] bottom row
0.550 [14.0] top row,
1.00 [25.4] middle row, 1/8”
1.220 [31.0] bottom row
1.250 [31.8]
3/8”
Short-Circuit Current Rating Data
Line
Load
Maximum Fuse Class and Amps***
Part
Number
Openings Wire Range openings Wire Range Class Class T
Class RK1
Class RK5 SCCR
(All Single Capacity* per Pole (copper only) per Pole (copper only) J(JDL) (A3T/A6T) (LENRK/LESRK) (ECNR/ECSR) Rating
Pole)
EPDB101
175A
1
2/0 to 8 AWG
70 to 10 mm2
1
EPDB104
175A
1
2/0 to 8 AWG
70 to 10 mm2
4
EPDB301
310A
1
350 kcmil to 6 AWG
185 to 16 mm2
1
1
500 kcmil to 6 AWG
240 to 16 mm2
EPDB306
380A
6
300 kcmil
150 mm2)
EPBD512
EPDB702
570A
760A
2
2
300 kcmil to 4 AWG
150 to 12 mm2
500 kcmil
240 mm2
500 kcmil to 6
AWG
240 to 16 mm2
12
2
2/0 to 8 AWG
70 to 10 mm2
200
200
100
60
200 kA
4 to 6 AWG
25 to 16 mm2
200
200
100
60
200 kA
4 to 14 AWG
25 to 2.5 mm2
175
200
175
200
100
100
60
60
100 kA
50 kA
350 kcmil to 6 AWG
150 to 16 mm2
400
400
200
100
200 kA
2 to 6 AWG
35 to 16 mm2
400
400
200
100
200 kA
2 to 14 AWG
35 to 2.5 mm2
200
175
200
175
100
100
30
30
50 kA
100 kA
4 to 8 AWG
25 to 10 mm2
600
600
400
200
200 kA
4 AWG
25 mm2
600
600
400
200
50 kA
4 to 14 AWG
25 to 2.5 mm2
200
200
100
30
50 kA
500 kcmil
240 mm2
600
600
800**
800**
600
600
400
600
200 kA
100 kA
500 kcmil to 6
AWG
240 to 16 mm2
600
600
400
200
100 kA
*Amp ratings are based on NEC® Table 310.16 for 75°C copper wire and UL508A Table 28.1.
**Class L 800A or less fuses are suitable for this particular SCCR case.
***Class G 60A or less, or Class CC 30A or less fuses are suitable for all SCCRs in this table.
Book 3 (14.3)
eTB-94
Terminal Blocks
1 - 8 0 0 - 633 - 0 4 0 5
Prices as of April 27, 2016. Check Web site for most current prices.
EPDB Series Edison Finger-Safe Power
Distribution Blocks Dimensions
Company
Information
Terminal Blocks
Power
Distribution
Blocks
Edison Finger-Safe Power Distribution Blocks Dimensions (in[mm])
Part Number
EPDB101
EPDB104
EPDB301
EPDB306
EPDB512
EPDB702
Width
A
Length
B
Height
C
D
E
F
G
H
1.03 [26.2]
3.55 [90.2]
2.15 [54.6]
3.37 [85.6]
2.90 [73.7]
0.2 [5.1]
0.2 [5.1]
N/A
1.03 [26.2]
3.55 [90.2]
2.15 [54.6]
3.37 [85.6]
2.90 [73.7]
0.2 [5.1]
0.2 [5.1]
N/A
1.54 [39.1]
4.62 [117.3]
2.87 [72.9]
4.44 [112.8]
3.78 [96.0]
0.2 [5.1]
0.24 [6.1]
N/A
1.54 [39.1]
4.62 [117.3]
2.87 [72.9]
4.44 [112.8]
3.78 [96.0]
0.2 [5.1]
0.24 [6.1]
N/A
1.86 [47.2]
4.65 [118.1]
2.95 [74.9]
4.47 [113.5]
3.81 [96.8]
0.2 [5.1]
0.24 [6.1]
N/A
2.56 [65.0]
4.65 [118.1]
3.17 [80.5]
4.47 [113.5]
3.81 [96.8]
0.2 [5.1]
0.24 [6.1]
1.81 [46.0]
Wiring
Accessories
ZIPLink
Connection
System
Multi-wire
Connectors
Sensor Cables
and Connectors
M12 Junction
Blocks
Panel Interface
Connectors
EPDB104
EPDB101
Wiring Duct
Cable Ties
Wire
Bulk
Multi-conductor
Cables
Wire
Management
Products
Power Supplies
DC Converters
EPDB306
EPDB301
Transformers
and Filters
Circuit Protection
Tools
Test
Equipment
Enclosures
Enclosure
Climate Control
Safety: Electrical
Components
EPDB702
Safety: Protective
Wear
EPDB512
Terms and
Conditions
Part Number
Minimum Enclosure Size in(mm)*
EPDB101
16 x 16 x 6.75 [406.4 x 406.4 x 171.45]
EPDB104
16 x 16 x 6.75 [406.4 x 406.4 x 171.45]
EPDB301
36 x 30 x 12.63 [914.4 x 762 x 320.80
EPDB306
24 x 20 x 6.75 [609.6 x 508 x 171.45]
EPDB512
24 x 20 x 6.75 [609.6 x 508 x 171.45]
EPDB702
36 x 30 x 12.63 [914.4 x 762 x 320.80]
*Note: Terminal block SCCR determined based on testing in minimum-size enclosure
Wire Connector Hole Diameter
Part Number Line in (mm) Load in (mm)
EPDB101
0.450 [11.43] 0.450 [11.43]
EPDB104
0.450 [11.43] 0.246 [6.25]
EPDB301
0.720 [18.29] 0.720 [18.29]
EPDB306
0.870 [22.10] 0.314 [7.98]
EPDB512
0.687 [17.45] 0.265 [6.73]
EPDB702
0.875 [22.23] 0.875 [22.23]
Book 3 (14.3)
w w w. a u t o m a t i o n d i r e c t . c o m / t e r m i n a l - b l o c k s
Terminal Blocks
eTB-95
Prices as of April 27, 2016. Check Web site for most current prices.
EPDB Series Edison Finger-Safe Power
Distribution Blocks IP-20 Finger-safe
Status Requirements
Specific Conditions to Achieve IP-20 Finger-Safe Status for EPDB Series
Line
IP-20
Installed Wire Conductor Screw
Openings Opening
Part
Number
Trim Length
in [mm]
EPDB101
0.850 [21.6]
2/0 to 8 AWG
70 to 10mm²
EPDB104
0.750 [19.0]
2/0 to 8 AWG
70 to 10mm²
EPDB301
1.350 [34.3]
EPDB306
EPDB512
EPDB702
1.250 [31.8]
1.15 [29.2] top row,
1.400 [35.6] bottom row
1.250 [31.8]
Yes
Load
Trim Length
in [mm]
IP-20
Installed Wire Conductor Screw
Openings Opening
2/0 to 8 AWG
70 to 10mm²
Yes
Yes
4 to 14 AWG
25 to 2.5mm²
Yes
Yes
screws fully opened
no wire in hole
N/A
No
Yes
N/A
350 Kcmil to 2/0 AWG
185 to 70mm²
Yes
Yes
Yes
1/0 to 6 AWG
50 to16mm²
No
Yes
Yes
2 to 14 AWG
35 to 2.5mm²
Yes
Yes
screws fully opened
N/A
Yes
no wire in hole
No
N/A
4 to 14 AWG
25 to 2.5mm²
Yes
Yes
screws fully opened
no wire in hole
N/A
Yes
Yes
N/A
500 to 350 Kcmil
240 to 185mm²
Yes
Yes
300 Kcmil to 6 AWG
150 to 16mm²
No
Yes
screws fully opened
no wire in hole
N/A
No
No
N/A
Yes
0.970 [24.6]
Yes
Yes
0.550 [14.0] top row,
0.850 [21.6] bottom row
350 Kcmil to 2/0 AWG
185 to 70mm²
Yes
Yes
1/0 to 6 AWG
50 to 16mm²
No
500 to 250 Kcmil
240 to 150mm²
Yes
4/0 to 6 AWG
120 to 16mm²
No
Yes
N/A
N/A
N/A
300 Kcmil to 4/0 AWG
150 to 120mm²
Yes
Yes
1.250 [31.8]
3/0 to 4 AWG
95 to 25mm²
No
Yes
screws fully opened
no wire in hole
N/A
No
No
N/A
500 to 350 Kcmil
240 to 185mm²
Yes
Yes
300 Kcmil to 6 AWG
150 to 16mm²
No
Yes
screws fully opened
no wire in hole
N/A
No
No
N/A
0.590 [15.0] top row,
1.200 [30.5] bottom row
0.550 [14.0] top row
1.00 [25.4] middle row
1.220 [31.0] bottom row
1.250 [31.8]
Book 3 (14.3)
eTB-96
Terminal Blocks
1 - 8 0 0 - 633 - 0 4 0 5