EXISTING CONDITIONS STUDY
NEWTON FALLS COMMUNITY CENTER
52 East Quarry Street
Newton Falls, Ohio 44444
OWNER:
The City of Newton Falls
ARCHITECT:
the workshop arch + design, llc
25 east boardman street; suite 537
youngstown, ohio 44503
ELECTRICAL
ENGINEER:
denise holt; aia, acha, ncarb, edac, leed ap
STRUCTURAL
ENGINEER:
Baker Bednar Snyder & Associates Inc
628 Niles-Cortland Road; Suite 201
Warren, Ohio 44484
Josh D. Thomas; PE
MECHANICAL
ENGINEER:
J.M. Verostko, Inc.
1216 Ameritech Boulevard
Youngstown, Ohio 44509
Peter Verostko; PE, LEED AP BD+C
CJL Engineering
1044 North Meridian Road; Suite B
Youngstown, Ohio 44509
Eric Bella; PE
GENERAL
CONTRACTOR:
DeSalvo Construction Company, Inc.
1491 West Liberty Street
Hubbard, Ohio 44425
Joseph K. DeSalvo; CHC
ENVIRONMENTAL Diamond Environmental
TESTING:
3624 State Route 303
Ravenna, Ohio 44266
Keith R. Bickel; CHMM, REP, CAHES
PURPOSE OF THIS STUDY:
Document the existing conditions of the existing City of Newton Falls Community Center
located at 52 East Quarry Street
and provide recommendations for improvements to the facility.
BUILDING CODE
2011 Ohio Building Code (OBC)
The existing facility is an A-3 Assembly Occupancy.
The existing facility is non-compliant with allowable building area per the construction type (5B).
The existing facility does not have adequate plumbing facilities for the calculated occupancy of the building.
LIFE SAFETY CODE
2012 NFPA 101 Life Safety Code
Chapter 13, Existing Assembly Occupancies was reviewed.
Kitchen needs reviewed for compliance with NFPA 96.
ACCESSIBILTY GUIDELINES
2010 ADA Standards for Accessible Design
The existing facility is non-compliant in regards to the toilet rooms, door hardware, building signage, and parking.
2011 OHIO MECHANICAL CODE (OMC)
2011 OHIO PLUMBING CODE (OPC)
2015 INTERNATIONAL ELECTRIC CODE
NFPA 13; STANDARDS FOR THE INSTALLATION OF
SPRINKLER SYSTEMS
2014 NFPA 70; NATIONAL ELECTRIC CODE
2013 NFPA 72; NATIONAL FIRE ALARM AND SIGNALING CODE
NFPA 96; STANDARD FOR VENTILATION CONTROL AND FIRE
PROTECTION OF COMMERCIAL COOKING OPERATIONS
WEST – BASEBALL FIELDS
EAST – DETENTION POND
ACCESS DRIVE AND PARKING
SITE
SOUTH - PLAYGROUND


ACCESS
East Quarry Street accessed from West River Road or South Center Street
PROPERTY
 owned by the City of Newton Falls
baseball fields to the west; detention pond to the east; playground to the south
ACCESS DRIVE
 access drive wraps around the building with access on each side from East Quarry Street
 access drive is in poor condition
PARKING
 the number of parking spaces is inadequate for the facility
 ADA compliant parking needs reviewed
SITE

BUILDING USE
 originally constructed as a USO facility
dedicated as the Newton Falls Community Center on January 18, 1942
BUILDING CONSTRUCTION
 building was constructed presumably to the code standard for that time period
 today there are more stringent building code requirements
 some portions of the building comply with today’s requirements, other portions do not
 with rehabilitation, this structure will continue to function, however, the longevity is difficult to predict
BUILDING HISTORY
DETERIORATION OF FOUNDATION
ROOF STRUCTURE
LATERAL DISPLACEMENT OF FOUNDATION
FLOOR STRUCTURE
STRUCTURE
DETERIORATION OF FOUNDATION
FLOOR SLOPING IN AUDITORIUM
AREA OF
“BOWED” WALL
STRUCTURE


FOUNDATION
 the foundation walls show signs of deterioration
the foundation along the west wall of the auditorium is displaced
ROOF STRUCTURE
the roof of the main portion of the building is pitched wood trusses on wood bearing walls (over original flat roof)
and appears to be sound and intact
 the auditorium roof is a heavy timber, rigid frame system which appears to be original to the building
shows no major signs of problems or deterioration
FLOOR STRUCTURE
 the floor structure is comprised of wood joists spanning between perpendicular masonry walls
 the floor structure in the front of the building appears to be in good condition with little sign of damage or deterioration
 the floor appears to be level with the exception of the southeast corner of the auditorium
WALL STRUCTURE
 the walls of the main portion of the building appear to be wood framed bearing walls
 the auditorium appears to be a wood framed curtain wall spanning between heavy timber frames
 there is an area of wall along the west side of the auditorium that is displacing outward
STRUCTURE
ROOF – FRONT ELEVATION
ROOF – SIDE ELEVATION
SIDING – DAMAGED CORNERS
SIDING – PENETRATIONS
ROOF – REAR ELEVATION
SIDING – DAMAGE
BUILDING ENVELOPE
EXTERIOR DAMAGE AND WEAR OF WINDOWS
INTERIOR DAMAGE AND WEAR OF WINDOWS
BUILDING ENVELOPE


FOUNDATION
 the foundation walls show signs of deterioration
openings in foundation walls have been boarded up due to animals getting in
EXTERIOR WALLS
vinyl siding is damaged in numerous locations and appears to have met it’s life expectancy
 abandoned doors and windows were sided over in place
 exterior walls appear not to be properly insulated
 there have been problems with black mold on the exterior walls in the past
WINDOWS
 windows appear to have met their life expectancy
 there is an air infiltration problem
ROOF
 the existing asphalt shingle roof appears to have met it’s life expectancy
BUILDING ENVELOPE
EXTERIOR DOORS
 front doors appear to be in fair condition but need serviced
 other man doors are in fair to poor condition
RAMP
 wood ramp is constructed over the original concrete stairs and does not meet current codes


SERVICE ENTRANCE
 ramp is deteriorating
ramp and railings do not meet current codes
OTHER ENTRANCES / FIRE EXITS
there are fire exits on the east and west sides of the building that do not meet current codes
ABANDONED ACCESS
 there appears to be a set of STAIRS (external to the building) that accessed the basement
BUILDING ACCESS
WATER STAINS ON MASONRY
WATER STAINS ON MASONRY
SUBMERGED MECHANICAL EQUIPMENT
SUBMERGED ELECTRICAL EQUIPMENT
IRON OXIDE DEPOSITS
BASEMENT
DAMAGED CEILING – EVIDENCE OF ASBESTOS
CRAWLSPACE – UNDERSIDE OF FLOOR STRUCTURE
BASEMENT
PARTIAL BASEMENT
 houses mechanical and electrical equipment as well as a sump pump
 ceiling is damaged in areas and shows signs of asbestos
WATER INFILTRATION
 known flooding problems (to a height of almost 5’-0” in some areas)
 iron oxide deposits from a pipe entering the building

CRAWL SPACE
exposed dirt floor with exposed wood floor trusses above
BASEMENT
UNFINISHED, UNUSABLE SPACE
WATER DAMAGE AT CEILING
WATER DAMAGE IN TOILET ROOMS
INTERIOR ENVIRONMENT
LOBBY
AUDITORIUM
WEST ACTIVITY ROOM
TOILET ROOM
EAST ACTIVITY ROOM
KITCHEN
INTERIOR ENVIRONMENT
INTERIOR WALLS
 interior walls appear to be wood stud throughout
 unfinished areas
WATER INFILTRATION
 water damage found in numerous locations on walls and ceilings
 known problems of rotted

FINISHES
finishes are worn and need replaced throughout
FUNCTION OF SPACES
 the lobby is oversized and unused a large portion of the time
 the two front activity rooms function well, the third is not used due to flooding and odors
 the auditorium functions well with exception to the stage which is unused
 the toilet rooms are undersized, do not meet current codes, and are in fair to poor condition
 the kitchen is not functional and does not meet current codes
 an old, enclosed porch is unconditioned and unused
INTERIOR ENVIRONMENT
EXISTING FURNACES AND CONDENSING UNITS (ADMINISTRATIVE)
EXISTING FURNACES AND CONDENSING UNITS (AUDITORIUM)
MECHANICAL SYSTEMS
EXHAUST DUCTWORK AND HOOD (KITCHEN)
ABANDONED MECHANICAL EQUIPMENT
MECHANICAL SYSTEMS
HVAC SYSTEMS
 the main portion of the building is served by four (4) gas fired furnaces with remote condensing units which
are nearing the end of their useful life expectancy
 the auditorium is served by two (2) air handlers with gas fired duct heaters and Dx cooling which
were replaced about five (5) years ago and are in good operational condition
EXHAUST HOOD
 the existing kitchen exhaust hood is a type II hood which does not meet current codes
 there is no ansul system installed

ABANDONED EQUIPMENT
an abandoned steam boiler is located in the basement
MECHANICAL SYSTEMS
GAS LINE (KITCHEN)
HOT WATER TANK (KITCHEN)
STAINLESS STEEL SINKS
HOT WATER TANK AND MOP SINK (HOUSEKEEPING)
PLUMBING SYSTEMS
WOMEN’S TOILET ROOM
MEN’S TOILET ROOM
PLUMBING SYSTEMS
HOT WATER TANKS
 one (1) hot water tank is located in the kitchen and serves the space
 one (1) smaller hot water tank is located in the housekeeping closet and serves the remainder of the building
 tempering valves do not appear to be installed (code requirement)
PIPING
 piping is in poor condition
 known problems with sanitary backup in the kitchen
SANITARY
 kitchen does not have a grease trap or food interceptor
 known problems with sanitary backup in the kitchen
GAS
 missing shunt trip gas shut off which isolates the gas supply to the range (code requirement)
PLUMBING SYSTEMS
CURRENT CONDITIONS
 currently there is no automatic fire protection system
CODE REQUIREMENT
 an automatic fire protection system (in compliance with NFPA 13) is required
FIRE PROTECTION SYSTEM
ELECTRICAL SERVICE
 single 600-amp, 208Y/120V, 3-phase, 4-wire overhead electrical service
 run to overhead mast and extends to a single 600-amp distribution panel with a 600-amp main circuit breaker
 the main distribution panel feeds the HVAC equipment and branch circuit panel boards inside
 service entrance conductors are installed in a single conduit in lieu of (2) parallel conduits
ELECTRICAL SERVICE
ELECTRICAL SERVICE
Due to the existing conditions of the electrical
equipment and the overwhelming evidence of flooding
within the basement,
a serious and potentially life threatening electrocution
hazard may be created should occupants enter the
basement upon signs of flooding.
It is strongly recommended that no building occupant
(staff or the public) enter the basement upon signs of
flooding until the water infiltration issue can be rectified
and the electrical equipment has been deemed safe.
ELECTRICAL DISTRIBUTION SYSTEM
ELECTRICAL PANELS AND LUGS (BASEMENT)
ELECTRICAL DISTRIBUTION SYSTEM
BASEMENT ELECTRICAL EQUIPMENT
 equipment is in poor physical condition and appears to be original to the building
 signs of significant water damage
 covers are missing and live or energized parts are clearly exposed
 (2) conductors terminate in a single lug to feed the additional equipment (appear to be a violation of NFPA 70 and NEC)
FIRST FLOOR PANEL BOARD
 panel board is in decent physical condition
 no available spaces for future expansion and are loaded near capacity
RECEPTACLES
 120V convenience receptacles throughout and appear to be original to the building
 most receptacles are in satisfactory condition and working order
 some receptacles show signs or arcing or tracking on the faceplate (wiring is possibly faulty)
 known sporadic “spark” or “flash” at some receptacles which could potentially be a fire hazard
ELECTRICAL DISTRIBUTION SYSTEM
FIRE ALARM SYSTEM
 building currently has a non-addressable, analog type Simplex 4001 system
 system is currently not functional
 existing system does not meet the Ohio Building Code, International Fire Code, or NFPA 72
 speaker type notification devices are required
 system is not currently being monitored as required by a UL Certified Central Station
FIRE ALARM PANEL
FIRE ALARM SYSTEM
EXTERIOR LIGHTING
 wall packs appear to work
 exterior fixtures operate via a photocell (unable to verify if functioning properly)
INTERIOR LIGHTING
 most fixtures appear to have been replaced with new LED fixtures
 light levels appear to be low in some areas
 exit signs appear to be in good condition and working order

EMERGENCY LIGHTING
wall mounted battery packs appear to be in satisfactory condition and original to the building
 certain fixtures were not fully operational
 no exterior emergency lighting is installed (code requirement)
LIGHTING
SECURITY CAMERAS
 there are currently no security systems for the building
CARD ACCES
 there is currently no card access system for the building
SECURITY SYSTEMS
ASBESTOS
 asbestos containing materials were identified
LEAD
 lead containing materials were identified
MOLD
 mold testing not performed at this time
ENVIRONMENTAL TESTING
ADDITIONAL RECOMMENDED INVESTIGATIONS
 site evaluation and civil review
 investigation of foundation walls for deficiencies
 investigation of displaced foundation (west wall of auditorium)
 investigation of foundation settlement (southeast corner of auditorium)
 investigation of the displacement of the west wall of the auditorium
 investigation of first floor trusses and substrate (crawlspace)
 investigation of wood exposed to open soil (crawlspace)
 scope drain lines for deterioration and potential issues with the drainage system
 verify lighting levels throughout the facility
ADDITIONAL RECOMMENDED TESTING
 mold testing
ADDITIONAL INVESTIGATIONS
and TESTING
SITE RECOMMENDATIONS
 re-pave and/or replace access drive and parking lot
 provide required ADA compliant parking and associated signage
STRUCTURE RECOMMENDATIONS
 address foundation masonry deterioration
 perform any required remedial work as a result of additional recommended investigations
EXTERIOR ENVELOPE RECOMMENDATIONS
 replace asphalt shingle roof
 replace vinyl siding
 properly insulate exterior walls
 remove and infill abandoned doors and windows
 replace man doors
 replace exterior windows
 remove abandoned stair well
 repair and waterproof exterior basement wall
 reroute pipe in basement outside
 address access points for animals to get under the building
RECOMMENDATIONS
INTERIOR ENVIRONMENT RECOMMENDATIONS
 see Diamond Environmental reports for recommendations relative to asbestos and lead testing
 repair and waterproof exterior basement walls
 repair damaged ceiling membranes in basement
 finish unconditioned porch area used for storage
 remove stage
 rework kitchen to meet the Owners needs
 replace finishes throughout
 rework toilet rooms to meet code requirements
 provide adequate fire extinguishers
 install ADA compliant door hardware
 install ADA compliant signage
MECHANICAL SYSTEMS RECOMMENDATIONS
 replace existing kitchen hood with a type I hood and ansul protection system
 provide air to unconditioned porch
 verify if furnaces serving the administrative portions of the building need replaced
 remove abandoned equipment from basement
RECOMMENDATIONS
PLUMBING SYSTEMS RECOMMENDATIONS
 install grease trap and food interceptor in the kitchen
 install tempering valves on all of the hot water supply systems
 verify all plumbing fixtures are operable
 provide all required insulation on plumbing fixtures for ADA compliance
 install required water fountains
 scope and clean out all pipes; replace damaged
FIRE PROTECTION SYSTEMS RECOMMENDATIONS
 install automatic fire protection system throughout (dry)
 system shall be installed in the basement, first floor, attic, and crawl spaces as required
 install ansul protection system at new kitchen hood
ELECTRICAL SYSTEMS RECOMMENDATIONS
 upgrade electrical service
 replace basement electrical equipment
 replace panel boards
 replace and/or rewire receptacles as required
 replace fire alarm system
 replace light fixtures as required
 install security cameras
 install card access system for after hour use
RECOMMENDATIONS
PROBABLE COSTS
PRELIMINARY STUDY for a
NEW COMMUNITY CENTER
52 East Quarry Street
Newton Falls, Ohio 44444
SITE
POTENTIAL FLOOR PLAN
MAIN ENTRY
AUDITORIUM ENTRY
POTENTIAL EXTERIOR ELEVATIONS
PROBABLE COSTS