* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Download Shunt reactive power compensation
Pulse-width modulation wikipedia , lookup
Power inverter wikipedia , lookup
Variable-frequency drive wikipedia , lookup
Standby power wikipedia , lookup
Three-phase electric power wikipedia , lookup
Buck converter wikipedia , lookup
Audio power wikipedia , lookup
Power over Ethernet wikipedia , lookup
Power electronics wikipedia , lookup
Electrical substation wikipedia , lookup
Voltage optimisation wikipedia , lookup
Wireless power transfer wikipedia , lookup
Power factor wikipedia , lookup
Switched-mode power supply wikipedia , lookup
Mains electricity wikipedia , lookup
Electric power system wikipedia , lookup
History of electric power transmission wikipedia , lookup
Alternating current wikipedia , lookup
Unit-4 Lecture 30 Shunt reactive power compensation Since most loads are inductive and consume lagging reactive power, the compensation required is usually supplied by leading reactive power. Shunt compensation of reactive power can be employed either at load level, substation level, or at transmission level. most cases compensation is capacitive. The most common form of leading reactive power compensation is by connecting shunt capacitors to the line. voltage at the substation bus and at the load bus varies. Since the load power factor is always lagging, a shunt connected capacitor bank at the substation can raise voltage when the load is high. The shunt capacitor banks can be permanently connected to the bus (fixed capacitor bank) or can be switched as needed. Switching can be based on time, if load variation is predictable, or can be based on voltage, power factor, or line current. Generation and absorption of reactive power Synchronous generators - synchronous machines can be made to generate or absorb reactive power depending upon the excitation (a form of generator control) applied. The ability to supply reactive power is determined by the short circuit ratio. Synchronous compensators - certain smaller generators, once run up to speed and synchronized to the system, can be declutched from their turbine and provide reactive power without producing real power. capacitive and inductive compensators - these are devices that can be connected to the system to adjust voltage levels. Dept. of EEE, NIT-Raichur Page 1 Unit-4 Lecture 30 A capacitive compensator produces an electric field thereby generating reactive power An inductive compensator produces a magnetic field to absorb reactive power. Compensation devices are available as either capacitive or inductive alone or as a hybrid to provide both generation and absorption of reactive power. Overhead lines and underground cables, when operating at the normal system voltage, both produce strong electric fields and so generate reactive power. When current flows through a line or cable it produces a magnetic field which absorbs reactive power. A lightly loaded overhead line is a net generator of reactive power while a heavily loaded line is a net absorber of reactive power. In the case of cables designed for use at 275 or 400kv the reactive power generated by the electric field is always greater than the reactive power absorbed by the magnetic field and so cables arealways net generators of reactive power. Transformers always absorb reactive power. Dept. of EEE, NIT-Raichur Page 2