ELECTRICAL SYMBOLS LEGEND
J
SERVICE and EQUIPMENT
OUTLETS
CIRCUITRY and RACEWAYS
SINGLE RECEPTACLE (120 VOLT)
DUPLEX RECEPTACLE
CONDUIT INSTALLED (by E.C.)
TVSS
CONDUIT INSTALLED (by others)
VFD
EMERGENCY RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
CONDUIT STUB UP
TRANSIENT VOLTAGE SURGE SUPPRESSION
VARIABLE FREQUENCY DRIVE
T
TRANSFORMER
CONDUIT STUB DOWN
DISCONNECT SWITCH (fuse size shown)
HOME RUN (with circuit numbers)
MAGNETIC STARTER (BY x/C U.O.N.)
SURFACE FLOOR BOX
END OF CONDUIT RUN
COMB. STARTER (BY x/C U.O.N.)
SPECIAL EQUIPMENT RECEPTACLE
END OF CONDUIT RUN, CAP AND STAKE
TELEPHONE OUTLET
"CONDUIT RUN CONTINUES" INDICATION
PANELBOARD, SURFACE MOUNTED
PANELBOARD, FLUSH MOUNTED
F
FLUSH FLOOR BOX
S
1,3
DATA OUTLET
OR
FLEXIBLE PIGTAILS/CONNECTIONS
WEATHERHEAD
TELEPHONE / DATA OUTLET
WM
WIREMOLD AS SPECIFIED
UTILITY METER, AS REQUIRED
PM
PLUGMOLD AS SPECIFIED
BD
BUS DUCT
PP POWER POLE
JUNCTION BOX
UFD
WALL JUNCTION BOX
J
PULL (JUNCTION) BOX
J
UNDERFLOOR JUNCTION BOX
MECHANICAL
CEILING MOUNTED WIFI
SINGLE PHASE MOTOR
TT
TELEPHONE TERMINAL BOARD
TRANSFER SWITCH
TS
ENCLOSED CIRCUIT BREAKER
CAPACITOR
RESISTANCE HEATER, KW SHOWN
PIPE TRACE HEATER
CONTROL
ELECTRIC UNIT HEATER
WH
ELECTRIC WATER HEATER
T
THERMOSTAT
H
HUMIDISTAT
DESIGNATIONS
THERMAL OVERLOAD SWITCH
X
DEMOLITION NOTE
X
PLAN NOTE
X
ADDENDUM NOTE
A
AC
ACUAFF
AHJ
AHUAIC
AS
ATS
AMPS
ABOVE COUNTER
AIR CONDITIONING UNIT
ABOVE FINISHED FLOOR
AUTHORITY HAVING JURISDICTION
AIR HANDLING UNIT
AMPS INTERUPTING CAPACITY
ABOVE SHELF
AUTOMATIC TRANSFER SWITCH
BBC
BLDG
BOILER
BELOW COUNTER
BUILDING
CHLRCND (C)
CKT
CKT BKR
CTCUCUH-
CHILLER
CONDUIT
CIRCUIT
CIRCUIT BREAKER
COOLING TOWER
CONDENSING UNIT
CABINET UNIT HEATER
DFUDISC
DWG
DWH-
DUCT FURNACE
DISCONNECT
DRAWING
DOMESTIC WATER HEATER
EBBEC
EFEM
EMT
EWC
EXIST (E)
ELECTRIC BASEBOARD
ELECTRICAL CONTRACTOR
EXHAUST FAN
EMERGENCY
ELECTRICAL METALLIC TUBING
ELECTRIC WATER COOLER
EXISTING
FLA
FLEX
FLR
FLUOR
FSES
F/S
FU-
FULL LOAD AMPS
FLEXIBLE CONDUIT
FLOOR
FLUORESCENT
FOOD SERVICE EQUIP. SUPPLIER
FIRE/SMOKE
FURNACE
WIREWAY
WW
THREE PHASE MOTOR
SINGLE-POLE SWITCH
THREE-WAY SWITCH
FOUR-WAY SWITCH
MANUAL MOTOR SWITCH
KEY SWITCH
TIME SWITCH
DIMMER SWITCH
GENERATOR, KW SHOWN
G
GROUND CONNECTION PER N.E.C.
SWITCHES
SWITCH WITH PILOT LIGHT
CURRENT TRANSFORMERS
CT
UNDERFLOOR DUCT
J
D
ABBREVIATIONS LEGEND
3
PUSHBUTTON STATION (number of
buttons indicated)
P
PPB
PNL
PRVPVC
PWR
GC
GFI
GND
GENERAL CONTRACTOR
GROUND FAULT INTERUPTER
GROUND
HHID
HOA
HP
HR
HVAC
HUMIDIFIER
HIGH INTENSITY DISCHARGE
HAND-OFF-AUTO SELECTOR SWITCH
HORSEPOWER
RECEPT
HOUR
RGC
HEATING/VENTILATING/AIR CONDITIONING
RTU-
IG
IMC
ISOLATED GROUND
INTERMEDIATE METAL CONDUIT
JB
JUNCTION BOX
LC
LT
LTG
LT FLEX
POLE
PUMP
PULL BOX
PANEL
POWER ROOF VENTILATOR
POLY VINYL CLORIDE
POWER
RECEPTACLE
RIGID GALVANIZED STEEL CONDUIT
ROOF TOP UNIT
SFSPEC
SW
SWBD
SUPPLY FAN
SPECIFICATIONS
SWITCH
SWITCHBOARD
LIGHT CONTROL
LIGHT
LIGHTING
LIQUID TIGHT FLEXIBLE METAL CONDUIT
TCC
TR
TS
TYP
TEMPERATURE CONTROL CONTRACTOR
TAMPER PROOF RECEPTACLE
TAMPER PROOF SWITCH
TYPICAL
MAX
MC
MCC
MIN
MLO
MT
MTD
MTG
MUAU-
MAXIMUM
MECHANICAL CONTRACTOR
MOTOR CONTROL CENTER
MINIMUM
MAIN LUG ONLY
MOUNT
MOUNTED
MOUNTING
MAKE-UP AIR UNIT
UF
UHUL
UNO
UNDER FLOOR
UNIT HEATER
UNDERWRITERS' LABORATORIES, INC.
UNLESS NOTED OTHERWISE
V
VL
VOLTS
VERIFY LOCATION WITH OWNER
NC
NIC
NL
NO
NTS
NORMALLY CLOSED
NOT IN CONTRACT
NIGHT LIGHT
NORMALLY OPEN
NOT TO SCALE
W
W/
W/O
WP
WATTS
WITH
WITHOUT
WEATHER PROOF
XFMR
TRANSFORMER
GENERAL ELECTRICAL NOTES
1.
ALL WALL AND FLOOR PENETRATIONS ARE TO BE SEALED TO
MAINTAIN ORIGINAL RATING.
2.
ALL CONDUITS TO BE FIELD ROUTED ALONG EXISTING PIPING AND
STRUCTURAL STEEL.
3.
THE DIVISION 26 CONTRACTORS SHALL VISIT THE PROJECT AND
DETERMINE THE EXACT EXTENT OF THE DEMOLITION WORK
REQUIRED BEFORE BIDDING THE PROJECT.
4.
REMOVE ALL EXISTING OBSOLETE EXPOSED CONDUIT, WIRE AND
UNUSED EQUIPMENT WHERE WORK IS BEING DONE EXCEPT ITEMS
NOTED OTHERWISE.
5.
WHERE BUILDING SURFACES ARE DAMAGED BY THE REMOVAL OF
OLD WORK, SURFACES SHALL BE PATCHED TO MATCH ADJACENT.
6.
EXISTING WORK WHICH IS PRESENTLY CONCEALED AND WHICH WILL
REMAIN CONCEALED AND DOES NOT INTERFERE WITH ANY NEW
WORK OF ANY TRADE NEED NOT BE REMOVED. HOWEVER, ALL
CONDUIT SHALL BE CAPPED BELOW FINISH SURFACE AND THEN
PATCHED TO MATCH, OR AS NOTED.
7.
EXISTING OPENINGS, WHICH ARE TO BE REUSED, SHALL BE
MODIFIED OR ENLARGED TO SUIT THE NEW SYSTEMS AS REQUIRED.
PROVIDE ALL REQUIRED CUTTING AND PATCHING.
8.
IF ASBESTOS IS PRESENT, IT WILL BE REMOVED OR RENDERED
HARMLESS UNDER SEPARATE CONTRACT BY THE OWNER.
ELECTRICAL KEY NOTES
DISCONNECT FROM EXISTING PANEL. WIRE EXISTING EQUIPMENT OR
DEVICE TO NEW EMERGENCY PANEL AS INDICATED ON THE PANEL
SCHEDULES.
DISCONNECT AND REMOVE EXISTING RACK MOUNTED UPS'S. REMOVE
ASSOCIATED CONDUIT AND WIRE. RELOCATE EXISTING CIRCUITS TO
NEW PLUG STRIPS.
10KVA UNINTERRUPTABLE POWER SUPPLY (UPS) TOTAL OF (2)
PROVIDE RACK-MOUNTABLE, UNINTERRUPTABLE POWER SUPPLY (UPS).
UPS SHALL BE 10KVA RATED, HIGH EFFICIENCY, DOUBLE CONVERSION,
CONTINUOUS DUTY, ON-LINE TYPE. INPUT VOLTAGE OF 208VAC, 60HZ,
1-PHASE, 3-WIRE PLUS GROUND. OUTPUT VOLTAGE OF 208VAC, 60HZ,
1-PHASE, 3-WIRE PLUS GROUND. 65KAIC RATED. INTEGRATED
MAINTENANCE BYPASS SWITCH, BACKLIT LCD CONTROL PANEL.
INCLUDE WEB CARD AND ALARM RELAY BOARD FOR REMOTE
MONITORING, INDOOR RATED IP-20 ENCLOSURE. ENERSYS SEALED
CELL BATTERIES. 5-MINUTE RUN TIME. SELF DIAGNOSTICS. SEPARATE
POWER DISTRIBUTION BOX TYPE PD2-HDWR-MBS.
LIEBERT EXM UPS MODEL GXT4-10000-RT-208.
INCLUDE SYSTEM START-UP SERVICES, USER TRAINING AND
TWO-YEAR, ON-SITE WARRANTY SERVICE FOR PARTS & LABOR.
9.
UPS
"A"
EXIST.
FIRE PUMP
CONTROLLER
UPS
"B"
(4) #3
(1) #8 GND
(1) 1 1/4" CND
THE DIVISION 26 CONTRACTOR SHALL BE RESPONSIBLE FOR
PATCHING THE EXISTING WALLS TO MATCH THE ADJACENT
SURFACES BEHIND ALL SURFACE MOUNTED EQUIPMENT.
(4) #3/0
(1) #4 GND
(1) 2" CND
10. CONTRACTOR SHALL FIELD VERIFY ALL EQUIPMENT VOLTAGES AND
LOADS PRIOR TO INSTALLING SERVICE TO EQUIPMENT.
11. DRAWINGS ARE BASED ON EXISTING RECORD DOCUMENT AND
CASUAL FIELD OBSERVATION. REPORT ANY DISCREPANCIES TO
ENGINEER FOR CLARIFICATION.
(3) #12
(1) #12 GND
(1) 1" CND
BATTERY CIRCUIT
BLOCK HEATER CIRCUIT
(4) #3/0
(1) #4 GND
(1) 2" CND
TO LOCAL
PANEL
REMOTE ANNUNCIATOR
(LOCATED AT SECURITY DESK)
NEW
ATS
400A
WIRE ELEVATOR CONTROLS TO ONLY OPERATE ONE AT A TIME DURING
GENERATOR OPERATIONS.
PROVIDE PDU/PLUGSTRIP. PROVIDE RECEPTACLE AT TOP OF RACK TO
FEED PDU, L6-30P RECEPTACLE. CONTRACTOR SHALL PROVIDE RACK
MOUNTING BRACKET TO SUPPORT PDU LOCATED ON EXTERNAL BACK
OF RACK. MOUNT RECEPTACLE AT BOTTOM OF RACK. ROUTE CABLING
AT PERIMETER OF RACK. PROVIDE EMERSON #MPH2-NBV_L5-20P_18A
POWER STRIPS.
BELDON 9460
(2) #12
(1) 3/4" CND
(4) 300 KCMIL
(1) #2 GND
(1) 2 1/2" CND
150KW/180KVA
GENERATOR
(4) 500 KCMIL
(1) #2/0 GND
(1) 3 1/2" CND
START CIRCUIT
NEW
CONCRETE PAD BY EC
EXIST.
BUS DUCT
PROVIDE (25) BLUE PATCH CORDS AND (25) RED PATCH CORDS FOR
OWNER SERVERS. COORDINATE LENGTH AND PLUG CONFIGURE WITH
OWNER.
EXIST.
P1 PH
PROVIDE WEB CARD AND CONNECTION FROM EQUIPMENT TO MAIN
SERVER RACK FOR MONITORING.
(3) #6
(1) #8 GND
(1) 1" CND
EXIST.
P2 PH
EXIST.
PANEL
"EBPP01"
EXIST.
CHILLER
EXIST.
PANELS "BA",
"GA", "2A", "3A"
FROM
UTILITY
EXIST. 208V
XMFR
FROM
UTILITY
H458
TVSS
DISCONNECT AND REMOVE EXISTING ATS. REFEED PANEL "EBCP01" TO
NEW PANEL EM.
DISCONNECT AND REMOVE EXISTING GENERATOR AND ASSOCIATED
CONDUIT AND WIRE.
DISCONNECT AND REMOVE EXISTING SURFACE WIREMOLD AND WIRE.
DEMO EXISTING GAS PIPING FROM EXISTING GENERATOR BACK TO GAS
METER.
ROUTE NEW GAS PIPING FROM EXISTING GAS METER TO NEW
GENERATOR AS SHOWN. GAS PIPING TO COME OUT OF EXISTING
BUILDING WALL AND THEN DROP DOWN TO BELOW GRADE. PIPING TO
BE ROUTED BELOW GRADE TO GENERATOR AND THEN COME UP OUT
OF THE GROUND. PROVIDE GAS SHUT OFF VALVE AND DIRT LEG ABOVE
GRADE AT THE GENERATOR. GAS PIPING TO BE STEEL PIPE WITH
MALLEABLE-IRON FITTINGS AND THREADED JOINTS OR WROUGHT
STEEL FITTINGS WITH WELDED JOINTS. PIPING INSTALLATION TO BE
PER THE INTERNATIONAL FUEL GAS CODE. PRIME AND PAINT ALL
ABOVE GRADE GAS PIPING YELLOW.
CONTRACTOR TO COORDINATE UPGRADING NATURAL GAS METER WITH
UTILITY PROVIDER. NEW METER NEEDS TO HAVE A OPERATING FUEL
PRESSURE BETWEEN 7-INCH - 11-INCH TO RUN NEW GENERATOR.
MAIN
EXIST.
UTILITY
TRANSFORMER
NEW PANEL - "EMPD01"
EXIST.
UTILITY
SWITCHBOARD
1
REVISED RISER DIAGRAM
SCALE: NTS
H205
ELECTRICAL KEY NOTES
15'
12"
13'
12"
DISCONNECT AND REMOVE EXISTING RACK MOUNTED UPS'S. REMOVE
ASSOCIATED CONDUIT AND WIRE. RELOCATE EXISTING CIRCUITS TO
NEW PLUG STRIPS.
GENERATOR
5'
UNION
GAS COCK
1" BY 1"
CHAMFER
(BOTH SIDES)
G
GENERATOR
DIRT LEG
12" DEEP
CONCRETE PAD
WITH REBAR
1
DISCONNECT FROM EXISTING PANEL. WIRE EXISTING EQUIPMENT OR
DEVICE TO NEW EMERGENCY PANEL AS INDICATED ON THE PANEL
SCHEDULES.
GRADE
GENERATOR PAD DETAIL
SCALE:NTS
10KVA UNINTERRUPTABLE POWER SUPPLY (UPS) TOTAL OF (2)
PROVIDE RACK-MOUNTABLE, UNINTERRUPTABLE POWER SUPPLY (UPS).
UPS SHALL BE 10KVA RATED, HIGH EFFICIENCY, DOUBLE CONVERSION,
CONTINUOUS DUTY, ON-LINE TYPE. INPUT VOLTAGE OF 208VAC, 60HZ,
1-PHASE, 3-WIRE PLUS GROUND. OUTPUT VOLTAGE OF 208VAC, 60HZ,
1-PHASE, 3-WIRE PLUS GROUND. 65KAIC RATED. INTEGRATED
MAINTENANCE BYPASS SWITCH, BACKLIT LCD CONTROL PANEL.
INCLUDE WEB CARD AND ALARM RELAY BOARD FOR REMOTE
MONITORING, INDOOR RATED IP-20 ENCLOSURE. ENERSYS SEALED
CELL BATTERIES. 5-MINUTE RUN TIME. SELF DIAGNOSTICS. SEPARATE
POWER DISTRIBUTION BOX TYPE PD2-HDWR-MBS.
LIEBERT EXM UPS MODEL GXT4-10000-RT-208.
INCLUDE SYSTEM START-UP SERVICES, USER TRAINING AND
TWO-YEAR, ON-SITE WARRANTY SERVICE FOR PARTS & LABOR.
WIRE ELEVATOR CONTROLS TO ONLY OPERATE ONE AT A TIME DURING
GENERATOR OPERATIONS.
PROVIDE PDU/PLUGSTRIP. PROVIDE RECEPTACLE AT TOP OF RACK TO
FEED PDU, L6-30P RECEPTACLE. CONTRACTOR SHALL PROVIDE RACK
MOUNTING BRACKET TO SUPPORT PDU LOCATED ON EXTERNAL BACK
OF RACK. MOUNT RECEPTACLE AT BOTTOM OF RACK. ROUTE CABLING
AT PERIMETER OF RACK. PROVIDE EMERSON #MPH2-NBV_L5-20P_18A
POWER STRIPS.
PROVIDE (25) BLUE PATCH CORDS AND (25) RED PATCH CORDS FOR
OWNER SERVERS. COORDINATE LENGTH AND PLUG CONFIGURE WITH
OWNER.
PROVIDE WEB CARD AND CONNECTION FROM EQUIPMENT TO MAIN
SERVER RACK FOR MONITORING.
DISCONNECT AND REMOVE EXISTING ATS. REFEED PANEL "EBCP01" TO
NEW PANEL EM.
DISCONNECT AND REMOVE EXISTING GENERATOR AND ASSOCIATED
CONDUIT AND WIRE.
DISCONNECT AND REMOVE EXISTING SURFACE WIREMOLD AND WIRE.
DEMO EXISTING GAS PIPING FROM EXISTING GENERATOR BACK TO GAS
METER.
ROUTE NEW GAS PIPING FROM EXISTING GAS METER TO NEW
GENERATOR AS SHOWN. GAS PIPING TO COME OUT OF EXISTING
BUILDING WALL AND THEN DROP DOWN TO BELOW GRADE. PIPING TO
BE ROUTED BELOW GRADE TO GENERATOR AND THEN COME UP OUT
OF THE GROUND. PROVIDE GAS SHUT OFF VALVE AND DIRT LEG ABOVE
GRADE AT THE GENERATOR. GAS PIPING TO BE STEEL PIPE WITH
MALLEABLE-IRON FITTINGS AND THREADED JOINTS OR WROUGHT
STEEL FITTINGS WITH WELDED JOINTS. PIPING INSTALLATION TO BE
PER THE INTERNATIONAL FUEL GAS CODE. PRIME AND PAINT ALL
ABOVE GRADE GAS PIPING YELLOW.
CONTRACTOR TO COORDINATE UPGRADING NATURAL GAS METER WITH
UTILITY PROVIDER. NEW METER NEEDS TO HAVE A OPERATING FUEL
PRESSURE BETWEEN 7-INCH - 11-INCH TO RUN NEW GENERATOR.
APPROXIMATE LOCATION OF
SECURITY DESK ON FIRST FLOOR
REMOVE AND REPLACE
CONCRETE SIDEWALK OR
DIRECTIONAL BORE.
GENERATOR ANNUNCIATOR
NATURAL GAS LINE
E-STOP
GAS SHUT OF
PAD BY EC
N
ELECTRICAL KEY NOTES
DISCONNECT FROM EXISTING PANEL. WIRE EXISTING EQUIPMENT OR
DEVICE TO NEW EMERGENCY PANEL AS INDICATED ON THE PANEL
SCHEDULES.
EXIST.
EXHAUST FAN
DISCONNECT AND REMOVE EXISTING RACK MOUNTED UPS'S. REMOVE
ASSOCIATED CONDUIT AND WIRE. RELOCATE EXISTING CIRCUITS TO
NEW PLUG STRIPS.
EX
EXIST.
PT/CT
EXIST.
"H458"
ELEVATOR
#1
EXIST.
BUS DUCT
APPROXIMATE LOCATION
ON FIRST FLOOR
EXIST.
300KVA
480-208V
EXIST.
SMOKE DETECTION
EXIST.
PANEL "EMPD01"
NEW
ATS
EXIST.
PANEL "EBCP01"
EXIST.
UTILITY METER
EXIST.
PANEL "ESDP01"
ELEVATOR
#4
EXIST.
FIRE PUMP
COMPRESSOR
NEW
PANEL "EM"
NEW
PANEL "EM"
ATS EX
FM 200
EXIST.
ELEV. CAB LTG
EXIST.
ELEVATOR #4
EXIST.
"H205"
EXIST.
LIGHTING CONTROL
EXIST.
PANEL "EBCP02"
EXIST.
PANEL "ESPP01"
WIRE ELEVATOR CONTROLS TO ONLY OPERATE ONE AT A TIME DURING
GENERATOR OPERATIONS.
PROVIDE PDU/PLUGSTRIP. PROVIDE RECEPTACLE AT TOP OF RACK TO
FEED PDU, L6-30P RECEPTACLE. CONTRACTOR SHALL PROVIDE RACK
MOUNTING BRACKET TO SUPPORT PDU LOCATED ON EXTERNAL BACK
OF RACK. MOUNT RECEPTACLE AT BOTTOM OF RACK. ROUTE CABLING
AT PERIMETER OF RACK. PROVIDE EMERSON #MPH2-NBV_L5-20P_18A
POWER STRIPS.
PROVIDE (25) BLUE PATCH CORDS AND (25) RED PATCH CORDS FOR
OWNER SERVERS. COORDINATE LENGTH AND PLUG CONFIGURE WITH
OWNER.
PROVIDE WEB CARD AND CONNECTION FROM EQUIPMENT TO MAIN
SERVER RACK FOR MONITORING.
EXIST.
ELEVATOR #4
ELEVATOR
#3
10KVA UNINTERRUPTABLE POWER SUPPLY (UPS) TOTAL OF (2)
PROVIDE RACK-MOUNTABLE, UNINTERRUPTABLE POWER SUPPLY (UPS).
UPS SHALL BE 10KVA RATED, HIGH EFFICIENCY, DOUBLE CONVERSION,
CONTINUOUS DUTY, ON-LINE TYPE. INPUT VOLTAGE OF 208VAC, 60HZ,
1-PHASE, 3-WIRE PLUS GROUND. OUTPUT VOLTAGE OF 208VAC, 60HZ,
1-PHASE, 3-WIRE PLUS GROUND. 65KAIC RATED. INTEGRATED
MAINTENANCE BYPASS SWITCH, BACKLIT LCD CONTROL PANEL.
INCLUDE WEB CARD AND ALARM RELAY BOARD FOR REMOTE
MONITORING, INDOOR RATED IP-20 ENCLOSURE. ENERSYS SEALED
CELL BATTERIES. 5-MINUTE RUN TIME. SELF DIAGNOSTICS. SEPARATE
POWER DISTRIBUTION BOX TYPE PD2-HDWR-MBS.
LIEBERT EXM UPS MODEL GXT4-10000-RT-208.
INCLUDE SYSTEM START-UP SERVICES, USER TRAINING AND
TWO-YEAR, ON-SITE WARRANTY SERVICE FOR PARTS & LABOR.
DISCONNECT AND REMOVE EXISTING ATS. REFEED PANEL "EBCP01" TO
NEW PANEL EM.
EXIST.
T.C.C HEADEND
EXIST.
PANEL "EBPP01"
EXIST.
SUMP PUMP
DISCONNECT AND REMOVE EXISTING GENERATOR AND ASSOCIATED
CONDUIT AND WIRE.
EXIST.
SEWAGE PUMP
DISCONNECT AND REMOVE EXISTING SURFACE WIREMOLD AND WIRE.
DEMO EXISTING GAS PIPING FROM EXISTING GENERATOR BACK TO GAS
METER.
EXIST.
HWR PUMP
GENERATOR
EXIST.
T.C.C HEADEND
EXIST.
FIRE PUMP
EXIST.
TAC
EXIST.
AIR COMPRESSOR
EXIST.
JOCKEY PUMP
EXIST.
FIRE PUMP CONTROL
N
EXIST.
NATURAL GAS METER
EXIST.
NATURAL GAS LINE
M
3"
TO GENERATOR
EXIST.
TCC
N
ROUTE NEW GAS PIPING FROM EXISTING GAS METER TO NEW
GENERATOR AS SHOWN. GAS PIPING TO COME OUT OF EXISTING
BUILDING WALL AND THEN DROP DOWN TO BELOW GRADE. PIPING TO
BE ROUTED BELOW GRADE TO GENERATOR AND THEN COME UP OUT
OF THE GROUND. PROVIDE GAS SHUT OFF VALVE AND DIRT LEG ABOVE
GRADE AT THE GENERATOR. GAS PIPING TO BE STEEL PIPE WITH
MALLEABLE-IRON FITTINGS AND THREADED JOINTS OR WROUGHT
STEEL FITTINGS WITH WELDED JOINTS. PIPING INSTALLATION TO BE
PER THE INTERNATIONAL FUEL GAS CODE. PRIME AND PAINT ALL
ABOVE GRADE GAS PIPING YELLOW.
NATURAL GAS LINE
CONTRACTOR TO COORDINATE UPGRADING NATURAL GAS METER WITH
UTILITY PROVIDER. NEW METER NEEDS TO HAVE A OPERATING FUEL
PRESSURE BETWEEN 7-INCH - 11-INCH TO RUN NEW GENERATOR.
ELECTRICAL KEY NOTES
DISCONNECT FROM EXISTING PANEL. WIRE EXISTING EQUIPMENT OR
DEVICE TO NEW EMERGENCY PANEL AS INDICATED ON THE PANEL
SCHEDULES.
DISCONNECT AND REMOVE EXISTING RACK MOUNTED UPS'S. REMOVE
ASSOCIATED CONDUIT AND WIRE. RELOCATE EXISTING CIRCUITS TO
NEW PLUG STRIPS.
10KVA UNINTERRUPTABLE POWER SUPPLY (UPS) TOTAL OF (2)
PROVIDE RACK-MOUNTABLE, UNINTERRUPTABLE POWER SUPPLY (UPS).
UPS SHALL BE 10KVA RATED, HIGH EFFICIENCY, DOUBLE CONVERSION,
CONTINUOUS DUTY, ON-LINE TYPE. INPUT VOLTAGE OF 208VAC, 60HZ,
1-PHASE, 3-WIRE PLUS GROUND. OUTPUT VOLTAGE OF 208VAC, 60HZ,
1-PHASE, 3-WIRE PLUS GROUND. 65KAIC RATED. INTEGRATED
MAINTENANCE BYPASS SWITCH, BACKLIT LCD CONTROL PANEL.
INCLUDE WEB CARD AND ALARM RELAY BOARD FOR REMOTE
MONITORING, INDOOR RATED IP-20 ENCLOSURE. ENERSYS SEALED
CELL BATTERIES. 5-MINUTE RUN TIME. SELF DIAGNOSTICS. SEPARATE
POWER DISTRIBUTION BOX TYPE PD2-HDWR-MBS.
LIEBERT EXM UPS MODEL GXT4-10000-RT-208.
INCLUDE SYSTEM START-UP SERVICES, USER TRAINING AND
TWO-YEAR, ON-SITE WARRANTY SERVICE FOR PARTS & LABOR.
WIRE ELEVATOR CONTROLS TO ONLY OPERATE ONE AT A TIME DURING
GENERATOR OPERATIONS.
PROVIDE PDU/PLUGSTRIP. PROVIDE RECEPTACLE AT TOP OF RACK TO
FEED PDU, L6-30P RECEPTACLE. CONTRACTOR SHALL PROVIDE RACK
MOUNTING BRACKET TO SUPPORT PDU LOCATED ON EXTERNAL BACK
OF RACK. MOUNT RECEPTACLE AT BOTTOM OF RACK. ROUTE CABLING
AT PERIMETER OF RACK. PROVIDE EMERSON #MPH2-NBV_L5-20P_18A
POWER STRIPS.
PROVIDE (25) BLUE PATCH CORDS AND (25) RED PATCH CORDS FOR
OWNER SERVERS. COORDINATE LENGTH AND PLUG CONFIGURE WITH
OWNER.
PROVIDE WEB CARD AND CONNECTION FROM EQUIPMENT TO MAIN
SERVER RACK FOR MONITORING.
DISCONNECT AND REMOVE EXISTING ATS. REFEED PANEL "EBCP01" TO
NEW PANEL EM.
DISCONNECT AND REMOVE EXISTING GENERATOR AND ASSOCIATED
CONDUIT AND WIRE.
DISCONNECT AND REMOVE EXISTING SURFACE WIREMOLD AND WIRE.
DEMO EXISTING GAS PIPING FROM EXISTING GENERATOR BACK TO GAS
METER.
ROUTE NEW GAS PIPING FROM EXISTING GAS METER TO NEW
GENERATOR AS SHOWN. GAS PIPING TO COME OUT OF EXISTING
BUILDING WALL AND THEN DROP DOWN TO BELOW GRADE. PIPING TO
BE ROUTED BELOW GRADE TO GENERATOR AND THEN COME UP OUT
OF THE GROUND. PROVIDE GAS SHUT OFF VALVE AND DIRT LEG ABOVE
GRADE AT THE GENERATOR. GAS PIPING TO BE STEEL PIPE WITH
MALLEABLE-IRON FITTINGS AND THREADED JOINTS OR WROUGHT
STEEL FITTINGS WITH WELDED JOINTS. PIPING INSTALLATION TO BE
PER THE INTERNATIONAL FUEL GAS CODE. PRIME AND PAINT ALL
ABOVE GRADE GAS PIPING YELLOW.
EXIST.
A/C UNIT
DATA RACKS
N
1
EXISTING DATA RACKS
SCALE:NTS
CONTRACTOR TO COORDINATE UPGRADING NATURAL GAS METER WITH
UTILITY PROVIDER. NEW METER NEEDS TO HAVE A OPERATING FUEL
PRESSURE BETWEEN 7-INCH - 11-INCH TO RUN NEW GENERATOR.
ELECTRICAL KEY NOTES
DISCONNECT FROM EXISTING PANEL. WIRE EXISTING EQUIPMENT OR
DEVICE TO NEW EMERGENCY PANEL AS INDICATED ON THE PANEL
SCHEDULES.
DISCONNECT AND REMOVE EXISTING RACK MOUNTED UPS'S. REMOVE
ASSOCIATED CONDUIT AND WIRE. RELOCATE EXISTING CIRCUITS TO
NEW PLUG STRIPS.
EXIST.
MACHINE/MOTOR
EXIST.
CONTROLLER
10KVA UNINTERRUPTABLE POWER SUPPLY (UPS) TOTAL OF (2)
PROVIDE RACK-MOUNTABLE, UNINTERRUPTABLE POWER SUPPLY (UPS).
UPS SHALL BE 10KVA RATED, HIGH EFFICIENCY, DOUBLE CONVERSION,
CONTINUOUS DUTY, ON-LINE TYPE. INPUT VOLTAGE OF 208VAC, 60HZ,
1-PHASE, 3-WIRE PLUS GROUND. OUTPUT VOLTAGE OF 208VAC, 60HZ,
1-PHASE, 3-WIRE PLUS GROUND. 65KAIC RATED. INTEGRATED
MAINTENANCE BYPASS SWITCH, BACKLIT LCD CONTROL PANEL.
INCLUDE WEB CARD AND ALARM RELAY BOARD FOR REMOTE
MONITORING, INDOOR RATED IP-20 ENCLOSURE. ENERSYS SEALED
CELL BATTERIES. 5-MINUTE RUN TIME. SELF DIAGNOSTICS. SEPARATE
POWER DISTRIBUTION BOX TYPE PD2-HDWR-MBS.
LIEBERT EXM UPS MODEL GXT4-10000-RT-208.
INCLUDE SYSTEM START-UP SERVICES, USER TRAINING AND
TWO-YEAR, ON-SITE WARRANTY SERVICE FOR PARTS & LABOR.
EXIST.
CONTROL PANEL
EXIST.
TCC
EXIST.
PNL "P2"
EXIST.
ELEVATOR #1
CHW-1
EXIST.
PNL "P1"
EXIST.
ELEVATOR #1
EXIST.
CONTROLLER
EXIST.
ELEVATOR #3
WIRE ELEVATOR CONTROLS TO ONLY OPERATE ONE AT A TIME DURING
GENERATOR OPERATIONS.
PROVIDE PDU/PLUGSTRIP. PROVIDE RECEPTACLE AT TOP OF RACK TO
FEED PDU, L6-30P RECEPTACLE. CONTRACTOR SHALL PROVIDE RACK
MOUNTING BRACKET TO SUPPORT PDU LOCATED ON EXTERNAL BACK
OF RACK. MOUNT RECEPTACLE AT BOTTOM OF RACK. ROUTE CABLING
AT PERIMETER OF RACK. PROVIDE EMERSON #MPH2-NBV_L5-20P_18A
POWER STRIPS.
PROVIDE (25) BLUE PATCH CORDS AND (25) RED PATCH CORDS FOR
OWNER SERVERS. COORDINATE LENGTH AND PLUG CONFIGURE WITH
OWNER.
EXIST.
MACHINE/MOTOR
CHW-2
PROVIDE WEB CARD AND CONNECTION FROM EQUIPMENT TO MAIN
SERVER RACK FOR MONITORING.
DISCONNECT AND REMOVE EXISTING ATS. REFEED PANEL "EBCP01" TO
NEW PANEL EM.
DISCONNECT AND REMOVE EXISTING GENERATOR AND ASSOCIATED
CONDUIT AND WIRE.
DISCONNECT AND REMOVE EXISTING SURFACE WIREMOLD AND WIRE.
DEMO EXISTING GAS PIPING FROM EXISTING GENERATOR BACK TO GAS
METER.
ROUTE NEW GAS PIPING FROM EXISTING GAS METER TO NEW
GENERATOR AS SHOWN. GAS PIPING TO COME OUT OF EXISTING
BUILDING WALL AND THEN DROP DOWN TO BELOW GRADE. PIPING TO
BE ROUTED BELOW GRADE TO GENERATOR AND THEN COME UP OUT
OF THE GROUND. PROVIDE GAS SHUT OFF VALVE AND DIRT LEG ABOVE
GRADE AT THE GENERATOR. GAS PIPING TO BE STEEL PIPE WITH
MALLEABLE-IRON FITTINGS AND THREADED JOINTS OR WROUGHT
STEEL FITTINGS WITH WELDED JOINTS. PIPING INSTALLATION TO BE
PER THE INTERNATIONAL FUEL GAS CODE. PRIME AND PAINT ALL
ABOVE GRADE GAS PIPING YELLOW.
CONTRACTOR TO COORDINATE UPGRADING NATURAL GAS METER WITH
UTILITY PROVIDER. NEW METER NEEDS TO HAVE A OPERATING FUEL
PRESSURE BETWEEN 7-INCH - 11-INCH TO RUN NEW GENERATOR.
N