Download 1. General presentation - OPS Schneider Electric

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Electrical ballast wikipedia , lookup

Power engineering wikipedia , lookup

Electrical substation wikipedia , lookup

Ohm's law wikipedia , lookup

Opto-isolator wikipedia , lookup

History of electric power transmission wikipedia , lookup

Spark-gap transmitter wikipedia , lookup

Oscilloscope history wikipedia , lookup

Metadyne wikipedia , lookup

Surge protector wikipedia , lookup

Stray voltage wikipedia , lookup

Three-phase electric power wikipedia , lookup

Distribution management system wikipedia , lookup

Voltage optimisation wikipedia , lookup

Rectifier wikipedia , lookup

Alternating current wikipedia , lookup

Buck converter wikipedia , lookup

Capacitor discharge ignition wikipedia , lookup

Niobium capacitor wikipedia , lookup

Capacitor plague wikipedia , lookup

Aluminum electrolytic capacitor wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Mains electricity wikipedia , lookup

Capacitor wikipedia , lookup

Transcript
Specification for Tender
582778924
S
General Specification for MV Capacitor
Units
General presentation of PROPIVAR capacitors
Standards
Technical characteristics
Electrical characteristics
Technology
Operating conditions
Options and accessories
Factory tests
Documents supplied in case of an order
Last update : 2017-05-12
-1-
Specification for Tender
582778924
Table of contents:
1. General presentation …………..……………………………………………………….........
p. 3
2. Standards……………………………………………………………………………………..
p. 3
3. Technical characteristic ……………………………………………..…………………........
p. 3
3.1 Installation…………………………………………………………………………….….......
p. 3
3.2 Ambient temperature…………………………………………………………………............
p. 3
4. Electrical characteristics………………………………………………….……………........
p. 4
4.1 Acceptable overcurrent and overvoltage……………………………………..........................
p. 4
4.2 Design voltage, design power and marking……………………………………………….....
p. 4
5. Technology …………………………………………………………………….....................
p. 5
6. Operating conditions …………………………………………………………………….......
p. 5
6.1 Protection against internal faults ………………………………………………………….....
p. 5
6.2 Inrush current limiting device…………………………………………………………….......
p. 6
7. Options and accessories …………………………………………………………………......
p. 6
8. Factory tests ……………………………………………………………………………….....
p. 6
9. Documents ……………………………………........................................................................
p. 6
Last update : 2017-05-12
-2-
Specification for Tender
582778924
1. General presentation
Rectiphase produces medium voltage capacitor units called "PROPIVAR". These units are used in MV
capacitor banks to built power factor correction systems, and/or harmonic filtering solutions.
Available models
PROPIVAR range includes three types of capacitors:
- Three-phase capacitor units,
- Single-phase capacitor units, with internal fuses,
- Single-phase capacitor units, without internal fuses,
Three-phase capacitor
Single-phase capacitor
2. Standards
PROPIVAR capacitor units are designed, manufactured and tested according to relevant IEV
recommendations:
- IEC 60871-1 & 2
- BS 1650
- VDE 0560
- C22-2 N° 190-M1985
Capacitor units fitted with internal fuses also comply with the following standards:
- NF C 54-102
- IEC 60871-4
3. Technical characteristic
3.1 Installation
PROPIVAR capacitor units are designed to be used indoor or outdoor. They can be installed inside cubicles
or in open racks.
3.2 Ambient temperature
Our capacitor units are designed to operate permanently in ambient temperature conditions from -25 to
+55°C (D class temperature category).
Last update : 2017-05-12
-3-
Specification for Tender
582778924
4. Electrical characteristics
Available ranges
PROPIVAR capacitor units exist for rated voltage up to 36kV.
According to network service voltage, the following insulation levels are proposed :
Network
nominal voltage
(kV)
4,16 kV
6,6 kV
11 kV
15 kV
22 kV
33 kV
Capacitor design
voltage (Vdim)
Three-phase
Single-phase
4600 V
7100 V
12000 V
/
/
/
/
3810 V
6350 V
8660 V
12700 V
9530 V
Insulation level
(kV)
Power freq.
Impulse voltage
voltage withstand withstand (kV
(kV rms)
peak)
7,2
7,2
12
17,5
24
36
20
20
28
38
50
70
60
60
75
95
125
170
The tolerance on the rated power of the capacitor unit is: -5/+10%,
Capacitance variation according to temperature is: -3,5.10-4/°C.
The use of insulated racks and connection in series of several capacitor units allow the construction of
capacitor banks up to 400kV.
4.1 Acceptable overcurrent and overvoltage
PROPIVAR capacitor units are designed for:
- 1,10 x Un overvoltage - 12 hours per day,
- 1,15 x Un power frequency overvoltage - 30 minutes per day,
- Permanent overcurrent : 1,3 x In.
Three-phase and single-phase PROPIVAR capacitor units can be used on both 50 or 60Hz electrical
networks.
4.2 Design voltage, design power and marking
According to IEC 60871 recommendations, capacitor units nameplates shall indicate the maximum power
and voltage for which it is designed.
As a consequence, our capacitor units nameplates show these design power and design voltage values (Qdim
and Vdim). Operating values can be equal or lower than these values (Qn and Vn).
The documents supplied with our medium voltage products (price lists, order forms, catalogues, …) provide
reactive power values for the most common network voltages. If the required voltage does not appear in the
tables, it is possible to make a calculation using the formulae:
Qn = (Vn/Vdim)² x Qdim
Last update : 2017-05-12
-4-
Specification for Tender
582778924
5. Technology
PROPIVAR capacitor units use "all film" technology: each capacitor element is made of two aluminium
foils and several polypropylen films. These elements are connected in series-parallel groups to make the
active part of the capacitor.
This active part goes in a metallic case which is filled with a dielectric liquid (JARYLEC or SAS 40) (*) and
hermetically closed. The metallic case finishing includes : sand blasting, zinc coating (80µm) and vinylique
paint. It is suitable for any outdoor type ambient conditions.
Two fixing brackets allow vertical or horizontal mounting of the capacitor units. A oblong hole is available
in each bracket to permit fixing of the unit (to be used with M10 screws).
Two (for single-phase units) or three (for three-phase units) epoxy resin bushings are used for the electrical
connexion of the capacitor. (M16 screws).
(*) JARYLEC and SAS 40 are PCB free and Chlorine free liquids.
As far as technically possible, "internal fuse" technology is used for our single-phase capacitor units.
In case of internal fault, the fuse of the defective element blows and disconnect it from the others. According
to electrical characteristics and internal arrangement, a quantity of melted fuses is allowed during normal
operation. This technology increase the service continuity and improve reliability of the capacitor bank.
"Double star" is the compulsory connexion diagram for this technology.
According to IEC 60871 requirements and other major international standards, PROPIVAR capacitor units
also include discharge resistors. The resistance value is such as the residual voltage is lower than 75V within
10 minutes after disconnection of the bank from the power supply.
Dielectric materials, internal resistors and internal fuses generate losses. The total amount for one capacitor
unit depends on its electrical characteristics but can be estimated as below:
- 0,16 W/kvar for PROPIVAR capacitor units with internal fuses,
- 0,12 W/kvar for PROPIVAR capacitor units without internal fuses.
6. Operating conditions
6.1 Protection against internal faults:
PROPIVAR capacitor units have to be protected according to Rectiphase recommendations and
sepcification.
Three-phase capacitor units must be protected with HRC fuses.
Current rating of the fuses must take into account the possible peak inrush current due to capacitor
switching.
It should be at least 1,8 x In.
Single-phase capacitor units have to be double star connected. An unbalance protection device, using
unbalance CT and overcurrent relay, shall be used.
Unbalance protection settings (current and time delay thresholds) have to be checked and approved by
Rectiphase.
Last update : 2017-05-12
-5-
Specification for Tender
582778924
6.2 Inrush current limiting device
PROPIVAR capacitor units are designed to be able to withstand 100 x In transient overcurrents but
switching capacitor banks can sometime lead to higher values.
Inrush current limiting reactors is the device which has to be used to remain within acceptable limits.
Warning: Specifically designed and type tested switchgear has to used for capacitor bank operation and
protection.
(Technical characteristics and specific type test reports from switchgear suppliers have to be supplied)
7. Options and accessories
Two options are available for PROPIVAR capacitor units:
Connector (clamp) for one conductor (for one bushing)
Connector (clamp) for two conductors (for one
bushing)
8. Factory tests
Each PROPIVAR capacitor unit manufactured by Rectiphase must pass routine testing before delivery. The
factory routine tests are performed according to IEC relevant recommendations and include the following:
- capacitance measurement,
- loss angle measurement (tg ),
- sealing test,
- internal discharge resistor value checking,
- voltage test between terminals,
- voltage test between terminals and container,
9. Documents
The following documents are part of Rectiphase supply:
- three sets of routine test certificates (french / english),
- one instruction manual (french / english / spanish).