1.1 AC input
Two kinds of AC rated input voltage, the requirements of input voltage, current and frequency
see table 1 (when testing, use NOMAL ±1% input voltage), when MINI input voltage and peak
load, the power starts up.
Table 1 :AC input Line Requirements
AC Input
Voltage
Frequency
Min
Normal
Max
Unit
90
110
130
VAC rms
180
220
260
VAC rms
50
---
60
Hz
1.1.1
Input Overcurrent Protection,The power supply shall incorporate primary fusing for input
overcurrent protection ,Fuses should be slow-blow type or equivalent to prevent nuisance trips.
1.1.2
Inrush Current Limiting
100A Max. At 25℃ Cold Start
1.2
DC Output
Voltage
+3.3V
+5V
+12V
-12V
+5Vsb
MAX. Load⑴
7A
7A
7A
0.3A
2.0A
Low Load
0.30A
1.0A
0.50A
0.01A
0.1A
Peak Load⑵
10A
10A
14A
Regulation⑷
±5%
±5%
±5%
±10%
±5%
Ripple
80mV
80mV
150mV
150mV
80mV
Noise⑶
120mV
120mV
240mV
240mV
100mV
Note:
⑴ The continuous max. DC output power shall not exceed 150W, +3.3V and +5V combined
continuous output power 60W max.
⑵ +12V peak surge current 12sec. Max.
⑶ A 0.1uF and 10uF tantalum capacitors should be put across output terminals during ripple &
noise test. The oscilloscope bandwidth is set at 20 MHz and co-axial probe will be used to
measure it.
⑷ The cross-load regulation in defined in the matrix below.(Unit: A)
Item
1
2
Load
+3.3V
+5V
+12V
-12V
+5Vsb
High
2.0A
4.0A
2.0A
0.5A
0.8A
Low
0.30A
1.0A
0.50A
0A
0.05A
High
10A
2A
2A
0.3A
2.0A
Low
2.8A
4.4A
2.0A
0.1A
0.1A
1.3
Protection
If the power supply is latch into shutdown stage (when OPP,OVP or short protection is
working), the power supply shall return to normal operation only after the fault has been
removed and remote signal must reset for a minimum of 1 seconds. Then, it will turn on again.
The +5Vsb must be capable of being shorted indefinitely, but when the short is removed, the
power supply shall recover automatically or by cycling the PS-ON#.
1.3.1
OVER POWER PROTECTION
The power supply will be shutdown and latch off when total power over 110%~150% of rated
DC output.
Notes:5VSB will be auto-recovery when the fault removed.
1.3.2
OVER VOLTAGE PROTECTION
Output
Min
Nom.
Max.
Unit
+12VDC
13.4
14.5
15.6
Volts
+5VDC
5.74
6.3
7.0
Volts
+3.3VDC
3.7
4.0
4.3
Volts
1.3.3
SHORT CIRCUIT PROTECTION
All output to GND.
1.4 Time Sequence
1.4.1
Power On Time
500ms Max. at 100% Load.
1.4.2
PWR_OK(Power Good)
100mS-500mS at 100% Load.
1.4.3
Power Good Delay Time
1 mS Min. at 70% Load.
1.4.4
Hold-up Time
14 mS Min. at 70% Load.
1.5 Remote On/Off Control.
PS-ON# is active-low, TTL-compatible signal that allows a motherboard to remotely control the
power supply in conjunction with features such as soft on/off, wake-on-LAN, or wake-onmodem. When PS-ON# is pulled to TTL low, the power supply should turn on the four main DC
output rails:+12VDC,+5VDC,+3.3VDC,-12VDC. When PS_ON# is pulled to TTL high or open
circuited, the DC output rails should not deliver current and should be held at zero potential
with respect to ground. PS_ON# has no effect on the +5VSB output, which is always enabled
whenever the AC power is present.
Vil,Input Low Voltage
Min.
Max.
0.0V
0.8V
Iil,Input Low Current,Vin=0.4V
Vih,Input
200Ua
High Voltage,
Vih,Open Circuit,Iin=0
-1.6 mA
Iin=- 2.0V
5.25V
1.6 +5Vsb
+5VSB is a “standby” supply output that is active whenever the AC power is present. It
provides a power source for circuits that must remain operational when the four main DC
output rails are in a disabled state. Example uses include soft power control, wake-on-LAN,
wake-on-modem, intrusion detection, or suspend stage activities. +5VSB is required for the
implementation of PS_ON#.
The +5VSB output should be capable of delivering a minimum of 2000 mA at +5V +/- 5% to
external circuits. Overcurrent protection is required on the +5VSB output regardless of the
output current ration. This ensures the power supply will not be damaged if external circuits
draw more current than the supply can provide.
1.7 HI-POT
1000VAC 3S 10mA Min.
Input-GND:
1.8 Earth Continuous test
100mΩ Max. at 25A.
1.9 Leakage Current Each Line To GND
3.5 mA Max. At 264VAC 50HZ
2.0 Environment
2.1 Temperature
Operating ambient
+10℃ - +50℃
(At full load, with a maximum rate of change of 5℃/10minutes,but no more than 10℃/hr.)
Nonoperating ambient
-40℃ to +70℃
(Maximum rate of change of 20℃/hr.)
2.2 Humidity
Operating
To 85% relative humidity(noncondensing)
Nonoperating
To 95% relative humidity(noncondensing)
Note:95% RH is achieved with a dry bulb temperature of 55℃ and a wet bulb temperature of
54℃.
2.3 Altitude
Operating
To 10000ft
Nonoperating To 50000ft
2.4 Mechanical Shock
Nonoperating 50g, trapezoidal input; velocity change 170 in/s.
Three drops on each of six faces are applied to each sample.
3.0 CHASSIS MECHANICAL DIMENSION AND WIRE LENGTH
184mm*60mm*50mm