Download rt41LURES IN THREE-PHASE STATOR WINDINGS

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Mercury-arc valve wikipedia , lookup

Electrical ballast wikipedia , lookup

Current source wikipedia , lookup

Ohm's law wikipedia , lookup

Thermal runaway wikipedia , lookup

Electrification wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Commutator (electric) wikipedia , lookup

Electric power system wikipedia , lookup

Ground (electricity) wikipedia , lookup

Power inverter wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Islanding wikipedia , lookup

Brushless DC electric motor wikipedia , lookup

Power MOSFET wikipedia , lookup

Rectifier wikipedia , lookup

Electric motor wikipedia , lookup

Electrical substation wikipedia , lookup

Power engineering wikipedia , lookup

Voltage regulator wikipedia , lookup

History of electric power transmission wikipedia , lookup

Brushed DC electric motor wikipedia , lookup

Buck converter wikipedia , lookup

Opto-isolator wikipedia , lookup

Distribution management system wikipedia , lookup

Power electronics wikipedia , lookup

Transformer wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Transformer types wikipedia , lookup

Rectiverter wikipedia , lookup

Electric machine wikipedia , lookup

AC motor wikipedia , lookup

Stray voltage wikipedia , lookup

Voltage optimisation wikipedia , lookup

Alternating current wikipedia , lookup

Coil winding technology wikipedia , lookup

Surge protector wikipedia , lookup

Mains electricity wikipedia , lookup

Induction motor wikipedia , lookup

Three-phase electric power wikipedia , lookup

Stepper motor wikipedia , lookup

Transcript
rt41LURES IN THREE-PHASE
STATOR WINDINGS
MAGNETO ELECTRIC
SINCE 1946
1150 EGLINTON AVE. EAST
MISSISSAUGA, ONTARIO L4W2M6
TELEPHONE (905) 625-9450
FAX (905) 625-4540
WEBSITE www.magnetoele.com
E MAIL [email protected]
UJrll-Ol·UJnl
paJJ04S 6U!PU!M
(pa~uuo~ -v)
pa5B4d- a16U!S 6U!PU!M
aset~d-Ol-asB4d
paJJ04S 6U!PU!M
(paJ:>aUUO~ - A)
pa5B4d-ai6U!S 6U!PU!M
rJlVJS 1SVHJ·11HH1 Nl S1H01/V:I
WINDINGS
Winding with Shorted Coil
Winding Grounded
in the Slot
Winding Grounded
at Edge of Slot
Shorted Connection
Phase Damage Due to
Unbalanced Voltage
Winding Damaged
Due to Overload
Damage Caused
by Locked Rotor
Winding Damaged
by Voltage Surge
I
he life of a three-phase stator
winding can be shortened
dramatically when the motor is
exposed to unfavorable operating
conditions- electrical , mechanical
or environmental. The winding
failures illustrated in this brochure are
typical of what can happen in such
circumstances. They are shown here
to help in identifying the causes of
failure , so that, where possible,
preventive measures may be taken .
new stator winding is pictured
above for purposes of comparison
with the winding failures shown in
Photos 1 - 12. Descriptions of the
causes of failure are provided on the
back cover.
TYPICAL CAUSES OF WINDING FAILURES IN THREE-PHASE STATORS
Photo
Number
1&2 A single-phased winding
unbalanced loads on the
power source, a poor
connection at the motor
terminal, or a high resistance
contact (weak spring) .
NOTE: A one-percent voltage
unbalance may result in a sixto ten-percent current
unbalance.
failure is the result of an open
in one phase of the power
supply to the motor. The open
is usually caused by a blown
fuse, an open contactor, a
broken power line or bad
connections.
3,4,5, These photos illustrate
6,7
insulation failures that typically
&8
are caused by contaminants,
10
Thermal deterioration of the
insulation in all phases of the
stator winding typically is
caused by load demands
exceeding the rating of the
motor.
NOTE: Under-voltage and
over-voltage (exceeding
NEMA standards) will result in
the same type of insulation
deterioration.
abrasion , vibration or voltage
surge.
9
Thermal deterioration of
insulation in one phase of the
stator winding can result from
unequal voltage between
phases. Unequal voltages
usually are caused by
)
11
Severe thermal deterioration of
the insulation in all phases of
the motor normally is caused
by very high currents in the
stator winding due to a locked
rotor condition. It may also
occur as a result of excessive
starts or reversals.
12
Insulation failures like this
usually are caused by voltage
surges. Voltage surges are
often the result of switching
power circuits, lightning
strikes, capacitor discharges
and solid-state power devices.
:
Prepared by: Engineering Committee
Electrical Apparatus Service Association, Inc.
1331 Baur Boulevard
St. Louis, Missouri 63132
(314} 993-2220
Copyright 1985