* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Download Breakers, Relays, and Disconnects
Control system wikipedia , lookup
Electric power system wikipedia , lookup
Flexible electronics wikipedia , lookup
Switched-mode power supply wikipedia , lookup
Buck converter wikipedia , lookup
Fault tolerance wikipedia , lookup
Alternating current wikipedia , lookup
Mains electricity wikipedia , lookup
Ground (electricity) wikipedia , lookup
Variable-frequency drive wikipedia , lookup
Surge protector wikipedia , lookup
Power engineering wikipedia , lookup
Integrated circuit wikipedia , lookup
Ignition system wikipedia , lookup
Distribution management system wikipedia , lookup
Protective relay wikipedia , lookup
Rectiverter wikipedia , lookup
Earthing system wikipedia , lookup
Electrical substation wikipedia , lookup
Residual-current device wikipedia , lookup
Operator Generic Fundamentals Components – Breakers, Relays, and Disconnects © Copyright 2016 – Rev 2 Operator Generic Fundamentals 2 Terminal Learning Objectives At the completion of this training session, the trainee will demonstrate mastery of this topic by passing a written exam with a grade of ≥ 80% on the following areas: 1. Explain the purpose, safety precautions, and operation of electrical circuit interrupting and circuit switching devices. 2. Explain the construction, operation, and indications for electrical circuit breakers. 3. Describe the conditions that must be met prior to paralleling two generators, including effects of not meeting these conditions. © Copyright 2016 – Rev 2 TLOs Operator Generic Fundamentals 3 Circuit Protection TLO 1 – Explain the purpose, safety precautions, and operation of electrical circuit interrupting and circuit switching devices. 1.1 Explain the principles of circuit protection and their application, including selective tripping. 1.2 Describe the protection provided by each of the following: fuses, protective relays, circuit breakers, and overload devices. 1.3 Describe the function of the following types of switches: disconnect switch, automatic transfer switch and manual transfer switch. 1.4 Describe the personnel safety and equipment protection precautions associated with circuit interrupting devices and relays. 1.5 Interpret symbols for breakers, relays, and disconnects in a simple one-line diagram, and explain operation of the control circuit. 1.6 Explain the purpose and function of normal and power seeking automatic transfer switches. 1.7 Describe the functions, operation, and protective features of motor controllers. © Copyright 2016 – Rev 2 TLO 1 Operator Generic Fundamentals 4 Circuit Protection ELO 1.1 – Explain the principles of circuit protection and their application, including selective tripping. • Designed to de-energize circuit to protect equipment and circuit from electrical faults • Uses various types of fault sensors – Overcurrent, undervoltage, underfrequency, etc. • Uses various types of circuit interrupting devices – Fuses, breakers, etc. • Designed to maximize system reliability – Avoid unnecessary trips – Isolate only portion of circuit necessary, continuing service to remainder © Copyright 2016 – Rev 2 ELO 1.1 Operator Generic Fundamentals 5 Selective Tripping • Protective device closest to fault operates to remove fault from system – Maintaining largest possible portion of system energized • In example below, fuses open circuit at 50 amps to Load 1 • Output breaker for generator set to trip at 500 amps – Ensures power to Load 2 2 75A Fuses 1 Figure: Selective Tripping © Copyright 2016 – Rev 2 ELO 1.1 Operator Generic Fundamentals 6 Circuit Protection Example Power Plant Electrical System • Isolates faults to prevent damage • Maintains as much of the system energized as possible, maximizes plant reliability • Functions as selective tripping Four Condensate Booster Pumps • Motor Control Center (MCC) 1 supplies two pumps through individual breakers • Motor Control Center (MCC) 2 supplies two pumps through individual breakers • Ability to isolate faults at individual pump or power supply levels © Copyright 2016 – Rev 2 ELO 1.1 Operator Generic Fundamentals 7 Circuit Protection Example Fault on Individual Pump Motor • Isolate the pump to prevent damage • Maintain three pumps available and the plant online • Maintain full electrical system availability Fault at Power Supply Level • Isolate the power supply at the MCC • Maintain other MCC available • Maintain two pumps available and possibly the plant online © Copyright 2016 – Rev 2 ELO 1.1 Operator Generic Fundamentals 8 Circuit Interrupting Devices ELO 1.2 – Describe the protection provided by each of the following: fuses, protective relays, circuit breakers, and overload devices. Fuses • Device containing fusible link that protects electrical circuit from overcurrent condition only – Fusible link directly heated and destroyed by excessive current passing through it • Element sized so heat generated by normal current flow does not melt element • Overcurrent or short-circuit current flows through fuse – Fusible link melts to open circuit (blown fuse) – May be time-delayed – Vital to replace safety-related fuses with correct type © Copyright 2016 – Rev 2 ELO 1.2 Operator Generic Fundamentals 9 Types of Fuses Plug Fuse • Consists of zinc or alloy strip – Fusible element enclosed in porcelain or Pyrex™ housing – Screw base • Normally used on circuits rated at 125V or less to ground Figure: Typical Fuses © Copyright 2016 – Rev 2 ELO 1.2 Operator Generic Fundamentals 10 Types of Fuses Cartridge Fuse • Constructed with zinc or alloy fusible element – Enclosed in cylindrical tube – Element ends attached to metallic contact piece at ends of tube • Normally used on circuits rated between 250 volts and 600 volts • Maximum continuous currentcarrying capacity of 600 amps Figure: Typical Fuses © Copyright 2016 – Rev 2 ELO 1.2 Operator Generic Fundamentals 11 Circuit Breaker Protective Relays Relays • Varied types of protective relays detect fault conditions – Send signals to trip one or more circuit breakers to isolate the fault – Protect equipment from damage and personnel from injury • Different parameters are monitored to – Provide prompt response to a fault condition – Also avoid unnecessary system interruptions © Copyright 2016 – Rev 2 ELO 1.2 Operator Generic Fundamentals 12 Circuit Breaker Protective Relays Overload Relay Devices (also known as overcurrent) • Breakers usually provided with three overcurrent tripping devices – Provides breaker with long-time, short-time, and instantaneous tripping capabilities • Long-time delay trip (also known as 51) – Device reacts to light overloads and trips breaker after a time delay – Trips breaker on overload condition slightly higher than normal full load o Example: gradual bearing failure © Copyright 2016 – Rev 2 ELO 1.2 Operator Generic Fundamentals 13 Circuit Breaker Protective Relays Overload Relay Devices • Short-time delay trip (also known as 51) – Device reacts to slightly higher current and trips breaker in a shorter period of time – Allows for motor starting currents without tripping breaker unless current level has not decayed within certain time frame after motor start o Example: Locked/seized rotor • Instantaneous trip (also known as 50) – Device reacts quickly to trip breaker due to high currents o Example: Short-circuit © Copyright 2016 – Rev 2 ELO 1.2 Operator Generic Fundamentals 14 Circuit Breaker Protective Relays Undervoltage Relay (also known as 27) • Used in large power systems with many induction motors • Induction motors draw more current when voltage drops • Challenges entire power system • Isolating the cause of undervoltage protects the system Underfrequency Relay (also known as 81) • Trips breaker when frequency drops below a preset value • Protects loads on a system that cannot tolerate a significant change in frequency © Copyright 2016 – Rev 2 ELO 1.2 Operator Generic Fundamentals 15 Circuit Breaker Protective Relays Lockout (also known as 86) • Fault should be isolated by breaker actuation – Appears as if fault cleared, could allow breaker to reclose on fault • Lockout relays prevent automatic reclosure • Ensures the system is not re-energized before the fault is isolated © Copyright 2016 – Rev 2 ELO 1.2 Operator Generic Fundamentals 16 Circuit Breaker Protective Relays Reverse-Power Relay (also known as 32) • Senses a change in normal direction of current, indicating an abnormal condition – A change in direction of power flow through breaker – Power flowing into source versus power flowing out of source • Usually used to protect electrical generator from damage – Due to motoring – Trips generator output breaker © Copyright 2016 – Rev 2 ELO 1.2 Operator Generic Fundamentals 17 Circuit Interrupting Devices Thermal Overloads • Heat sensitive element and an overload heater connected in series with motor load circuit • When motor current is excessive and sustained – Heat from heater causes heat sensitive element to open the motor breaker or motor line contacts Figure: Three-Phase Magnetic Controller With Thermal Overloads © Copyright 2016 – Rev 2 ELO 1.2 Operator Generic Fundamentals 18 Circuit Interrupting Devices • Molded case breakers with larger current ratings also have magnetic trip element to supplement thermal trip element • Magnetic unit utilizes magnetic force surrounding conductor to operate circuit breaker tripping linkage • After activation, must manually reset an overload device to resume motor operation • Can reset magnetic overload devices immediately © Copyright 2016 – Rev 2 ELO 1.2 Operator Generic Fundamentals 19 Resetting Overload Devices • An activated overload device must be reset for motor operation – NOTE: Thermal overloads must cool before they can be reset – Manual Reset o Located in controller enclosure which contains overload device o Usually has a hand-operated rod, lever, or button that returns device tripping mechanism to its original position and resets interlocks – Automatic Reset o Usually uses a spring or gravity operated device to reset overload device without operator action o Only after condition causing overload has cleared – Electrical Reset o Actuated by an electromagnet controlled by a push button o Used when desired to reset an overload device remotely © Copyright 2016 – Rev 2 ELO 1.2 Operator Generic Fundamentals 20 Circuit Interrupting Devices Knowledge Check – NRC Exam Bank Which one of the following breaker trip signals will trip the associated motor breaker if a motor bearing seizes while the motor is running? A. Undervoltage B. Underfrequency C. Time-delayed overcurrent D. Instantaneous overcurrent Correct answer is C. © Copyright 2016 – Rev 2 ELO 1.2 Operator Generic Fundamentals 21 Transfer and Disconnect Switches ELO 1.3 – Describe the function of the following types of switches: disconnect switch, automatic transfer switch, and manual transfer switch. • Provide flexibility within an electrical distribution system • Used to change lineup of system or power source for loads within system • Provide direct visual indication that a circuit is broken – High-voltage disconnects used in switchyard operation © Copyright 2016 – Rev 2 ELO 1.3 Operator Generic Fundamentals 22 Disconnect Switches • Two-position switches used for isolation of power supplies from one or more loads or motor control centers • May be used in pairs to transfer power supplies from one source to another Figure: Typical Disconnect Switch © Copyright 2016 – Rev 2 ELO 1.3 Operator Generic Fundamentals 23 Disconnect Switch Design & Operation • Disconnects differ from breakers – Operated manually – Not designed to be opened under load • Design does not include arc chutes or any other means to extinguish arc drawn when disconnect opened – Cannot be opened under load • When energizing circuit with disconnect switch: – Close disconnect switch first, then close breaker • When de-energizing circuit with disconnect switch: – Open breaker first, then open disconnect © Copyright 2016 – Rev 2 ELO 1.3 Operator Generic Fundamentals 24 Disconnect Switch Design & Operation • Disconnects may contain fuses, which provide overcurrent protection for loads supplied by disconnect – If not equipped with fuses, provide isolation for circuit only – Separate fuses or breakers would be required elsewhere in circuit to provide protection for loads © Copyright 2016 – Rev 2 ELO 1.3 Operator Generic Fundamentals 25 Disconnect Switch Design & Operation • Safety Switches – Low voltage (less than or equal to 600VAC) switches that are enclosed – May be locked in OFF – Used in isolation points for electrical maintenance • Special precautions required operating disconnects to protect personnel from potential arcs – Leather gloves and safety glass should be worn – Operator should stand to side of disconnect and look away during operation o Protects operator's eyes and face from arc that may occur during switch operation © Copyright 2016 – Rev 2 ELO 1.3 Operator Generic Fundamentals 26 Disconnect Switch Design & Operation • Before disconnect can be opened, all electrical loads fed by disconnect must be verified off, or not operating • Opening disconnect under load can result in damage to disconnect and injury to personnel © Copyright 2016 – Rev 2 ELO 1.3 Operator Generic Fundamentals 27 Transfer Switches • Used to make and break electrical circuits in order to provide smooth power transfer from one source of power to another Manual Transfer Switch • Similar to disconnect switches – Except, have three positions to allow power supply for an electrical component to be transferred from one source to another • Manual transfer switches may contain internal fuse protection © Copyright 2016 – Rev 2 ELO 1.3 Operator Generic Fundamentals 28 Transfer and Disconnect Switches Knowledge Check What is an advantage of using high-voltage disconnect switches instead of breakers to isolate main power transformers? A. Disconnect switches can be operated either locally or remotely. B. Disconnect switches provide direct visual indication that the circuit is broken. C. Disconnect switches are cheaper and provide the same automatic protection as a breaker. D. Disconnect switches are capable of interrupting a higher current flow with less heating than a breaker. Correct answer is B. © Copyright 2016 – Rev 2 ELO 1.3 Operator Generic Fundamentals 29 Transfer and Disconnect Switches Knowledge Check A 480 volt AC motor control center supplies a load through a breaker and a manual disconnect. Which one of the following sequences will provide the greatest level of personnel safety when de-energizing the load for maintenance and when re-energizing the load after the maintenance? A. Open breaker first (de-energizing); shut disconnect first (reenergizing) B. Open disconnect first (de-energizing); shut breaker first (reenergizing) C. Open breaker first (de-energizing); shut breaker first (reenergizing) D. Open disconnect first (de-energizing); shut disconnect first (reenergizing) Correct answer is A. © Copyright 2016 – Rev 2 ELO 1.3 Operator Generic Fundamentals 30 Safety and Equipment Protection ELO 1.4 – Describe the personnel safety and equipment protection procedures and precautions associated with circuit interrupting devices and relays. Personnel should always observe electrical safety precautions and PPE requirements: • Do not open a disconnect switch under load • Disconnects should not be used to start and stop equipment • Follow all precautions for working on energized equipment when checking voltages on breakers, relays, and switches with test equipment © Copyright 2016 – Rev 2 ELO 1.4 Operator Generic Fundamentals 31 Safety and Equipment Protection • Do not remove or replace any fuse under load • Never replace a fuse with one that has a different voltage or current rating than that of the intended circuit • Perform the following before racking out circuit breakers: – Ensure circuit breaker is open – Ensure control power is removed when applicable – Tag or lockout applicable electrical sources – Utilize Personal Protective Equipment as specified for the voltage and current involved • Always strip loads prior to reenergizing a dead bus © Copyright 2016 – Rev 2 ELO 1.4 Operator Generic Fundamentals 32 Precautions The following electrical safety precautions are good work practices: • Have a person stand by to deenergize the equipment in the event of an emergency • Stand on insulating rubber material to increase the electrical resistance of the body to ground • Cover exposed energized circuits with insulating material to prevent inadvertent contact • Use insulated tools to prevent inadvertent contact with adjacent equipment © Copyright 2016 – Rev 2 ELO 1.4 Operator Generic Fundamentals 33 Safety and Equipment Protection Knowledge Check Which one of the following is an unsafe practice if performed when working on or near energized electrical equipment? A. Use insulated tools to prevent inadvertent contact with adjacent equipment. B. Cover exposed energized circuits with insulating material to prevent inadvertent contact. C. Attach a metal strap from your body to a nearby neutral ground to ensure that you are grounded. D. Have a person standing by with the ability to remove you from the equipment in the event of an emergency. Correct answer is C. © Copyright 2016 – Rev 2 ELO 1.4 Operator Generic Fundamentals 34 Electrical Drawings ELO 1.5 – Interpret symbols for breakers, relays, and disconnects in a simple one-line diagram, and explain the operation of the control circuit. • Common symbols include contacts, fuses, breakers, indicating lights, trip coil, and closing coil Fuse Indicating Lights Closing Coil, Trip Coil Breaker Open Contact © Copyright 2016 – Rev 2 Overloads ELO 1.5 Closed Contact Operator Generic Fundamentals 35 Electrical Drawings Common Symbols • Overloads, relays, switches, rectifier bridge, and transformer Relays Switch Transformer Switches Closed Switch Open Switch © Copyright 2016 – Rev 2 ELO 1.5 Operator Generic Fundamentals 36 Electrical Drawings • Usually a legend on first sheet of drawing series • Different suppliers have differences in their conventions, so operator should review drawing legend when in doubt • "a" contacts are open when the relay controlling it is de-energized, and closed when it is energized • “b" contacts are closed when the relay controlling it is de-energized, and open when it is energized • Drawing representation shows contacts in their de-energized state © Copyright 2016 – Rev 2 ELO 1.5 Operator Generic Fundamentals 37 Circuit Breaker Control • To operate circuit breakers from remote location – Electrical control circuit must be incorporated – Control power supplied by AC source rectified to DC o Some vital power sources use DC as control power Figure: Breaker Control Circuit © Copyright 2016 – Rev 2 ELO 1.5 Operator Generic Fundamentals 38 Circuit Breaker Control Major Components: • Rectifier unit • Closing relay • Closing coil • Tripping coil • Auxiliary contacts • Circuit breaker control switch Figure: Breaker Control Circuit © Copyright 2016 – Rev 2 ELO 1.5 Operator Generic Fundamentals 39 Circuit Breaker Control • Control circuit can be designed with protective features: – Overcurrent – Underfrequency – Undervoltage • Fault conditions cause associated contact to close – Energize tripping coil – Trip circuit breaker Figure: Breaker Control Circuit © Copyright 2016 – Rev 2 ELO 1.5 Operator Generic Fundamentals 40 Closing a Remotely Operated Circuit Breaker • To close circuit breaker control switch, turn to CLOSE position – Provides path to energize closing relay (CR) • Energized closing relay shuts an auxiliary contact – Energizes closing coil (CC) – Closing coil shuts circuit breaker Figure: Breaker Control Circuit © Copyright 2016 – Rev 2 ELO 1.5 Operator Generic Fundamentals 41 Closing a Remotely Operated Circuit Breaker • Once breaker is shut – It is latched in the closed position – "b" contact associated with the closing replay opens deenergizing o Closing relay o Closing coil (anti-pumping feature) Figure: Breaker Control Circuit © Copyright 2016 – Rev 2 ELO 1.5 Operator Generic Fundamentals 42 Closing a Remotely Operated Circuit Breaker • When breaker closes – "a" contact closes – Enables trip circuit • Circuit breaker control switch returns to neutral position when released Figure: Breaker Control Circuit © Copyright 2016 – Rev 2 ELO 1.5 Operator Generic Fundamentals 43 Opening a Remotely Operated Circuit Breaker • Control switch turned to TRIP position • Provides path to energize trip coil (TC) • Releases latching mechanism – Circuit breaker will open – "a" contact will open – deenergized tripping coil • "b" contact will close – Sets up next remote closure • Control switch may be released © Copyright 2016 – Rev 2 Figure: Breaker Control Circuit ELO 1.5 Operator Generic Fundamentals 44 Opening a Remotely Operated Circuit Breaker • Circuit breaker is equipped with – Underfrequency trip – Undervoltage trip • Both/Either energize the breaker's trip coil opening breaker © Copyright 2016 – Rev 2 ELO 1.5 Operator Generic Fundamentals 45 Analyzing Valve Control Circuits Valve Fully Open ELO 1.5 • Valve open limit switch contact is shut • A1 relay energized A1(a) contact shut; red, open lamp energized • Valve shut limit switch open • A2 relay deenergized and A2(b) contact is shut Figure: Valve Fully Open Circuit • Both A1(b) and A2(a) contacts open; green shut light out © Copyright 2016 – Rev 2 ELO 1.5 Operator Generic Fundamentals 46 Analyzing Valve Control Circuit Valve in Intermediate Position ELO 1.5 • Both valve open and valve closed limit switches open • Both relays deenergized; (b) contacts closed, (a) contacts open • Both lamps energized Figure: Valve Intermediate Position © Copyright 2016 – Rev 2 Operator Generic Fundamentals 47 Analyzing Valve Control Circuits Valve Closed • Valve shut limit switch contact closed • A2 relay energized; A2(a) contact closed, green shut lamp energized • Valve open limit switch is open; A1 relay deenergized, A1 (b) contact is shut Figure: Valve Closed Circuit • Both A2(b) and A1(a) contacts open; red open light out © Copyright 2016 – Rev 2 ELO 1.5 Operator Generic Fundamentals 48 Electrical Drawings Example 1 Opening and Closing the Valve • As you can see, energizing K1 relay opens valve, deenergizing K1 relay closes valve Figure: Valve Control Circuit © Copyright 2016 – Rev 2 ELO 1.5 Operator Generic Fundamentals 49 Electrical Drawings Example 1 • To manually open the valve – Push PB2 – Energizes K3 contact, which in turn energizes K1 relay • There is no other means to open valve through control circuit • After valve is opened, K1 relay has a seal-in K1 contact which maintains power to K1 relay and keeps valve open Figure: Valve Control Circuit © Copyright 2016 – Rev 2 ELO 1.5 Operator Generic Fundamentals 50 Electrical Drawings Example 1 • To close the valve – Push PB1 – Interrupts power to K1 relay – Causes the K1 seal-in contact to open when K1 relay is deenergized – Valve closes and stays closed Figure: Valve Control Circuit © Copyright 2016 – Rev 2 ELO 1.5 Operator Generic Fundamentals 51 Electrical Drawings Example 1 Valve response to loss of control power • K1 relay must remain energized for valve to stay open – If control circuit loses power, effect is the same as pushing PB1; power to K1 relay is interrupted and valve closes – K1 seal in contact opens; when power is restored, valve stays closed Figure: Valve Control Circuit © Copyright 2016 – Rev 2 ELO 1.5 Operator Generic Fundamentals 52 Electrical Drawings Example 1 Alarm Light Function • As you can see from the drawing, the alarm lights when K2 time delay relay picks up and closes K2 contact – Occurs after K2 relay has been energized for a 10-second period – If deenergized before time delay completes, they reset to zero Figure: Valve Control Circuit © Copyright 2016 – Rev 2 ELO 1.5 Operator Generic Fundamentals 53 Electrical Drawings Example 1 • K2 time delay relay is energized if the following sequence occurs: – PB2 is pushed to open valve o energizes K3 relay o closes K3 contact, energizing K1 relay and closing K1 seal in contact • Power supplied to K2 time delay relay only if LS1 (limit switch) is made up, which occurs when valve is fully closed Figure: Valve Control Circuit © Copyright 2016 – Rev 2 ELO 1.5 Operator Generic Fundamentals 54 Electrical Drawings Example 1 • Circumstances required for alarm to light are: – Button is pushed to open the valve and 10 seconds later, with an open signal still applied, valve is fully closed • If valve is partially or fully open, LS1 will be open and alarm will not sound • If operator depresses PB1 to close the valve, K1 relay will deenergize and its seal in contact will open, alarm will not sound Figure: Valve Control Circuit © Copyright 2016 – Rev 2 ELO 1.5 Operator Generic Fundamentals 55 Electrical Drawings Example 2 • Simple Motor Control Circuit • Control power is taken from termination L1 • Returns at termination L2 • Requires START pushbutton to be depressed • Energizes MAIN coil • Closes maintaining contacts • Starting resistors in circuit – Until Time Delay coil energizes Figure: Control Power Circuit © Copyright 2016 – Rev 2 ELO 1.5 Operator Generic Fundamentals 56 Electrical Drawings Example 2 • Time Delay energizes Accelerating Coil • Closes contacts to bypass resistors – Motor up to speed and starting current drops off • When motor stopped with STOP coil (or overload) – MAIN coil deenergizes – Time Delay coil deenergizes – Accelerating coil deenergizes – Starting resistors ready for next motor start Figure: Control Power Circuit © Copyright 2016 – Rev 2 ELO 1.5 Operator Generic Fundamentals 57 Electrical Drawings Knowledge Check - NRC Question Refer to the drawing of a typical valve control circuit. What is the purpose of depressing the S1 pushbutton? A. To de-energize the K3 relay after the initiating condition has cleared. B. To prevent energizing the K3 relay when the initiating condition occurs. C. To manually energize the K3 relay in the absence of the initiating condition. D. To maintain the K3 relay energized after the initiating condition has cleared. © Copyright 2016 – Rev 2 ELO 1.5 Correct answer is A. Operator Generic Fundamentals 58 Electrical Drawings Knowledge Check – NRC Question Refer to the drawing of a valve control circuit below. Note that limit switch (LS) contacts are shown open regardless of valve position, but relay contacts are shown open/closed according to the standard convention for control circuit drawings. © Copyright 2016 – Rev 2 ELO 1.5 Operator Generic Fundamentals 59 Electrical Drawings Knowledge Check (continued) Which one of the following describes the purpose of the alarm? A. Alert the operator when the valve motor circuit has been energized for 10 seconds after pushbutton PB2 is depressed. B. Alert the operator when the valve has not moved off its closed seat within 10 seconds of depressing pushbutton PB2. C. Alert the operator that the valve is opening by sounding the alarm for 10 seconds after PB2 is depressed. D. Alert the operator if the valve has not reached full open within 10 seconds of depressing pushbutton PB2. Correct answer is B. © Copyright 2016 – Rev 2 ELO 1.5 Operator Generic Fundamentals 60 Automatic Transfer Switches ELO 1.6 – Explain the purpose and function of normal and power seeking automatic transfer switches. • Used in electrical distribution systems to – quickly disconnect a deenergized electrical load from one power supply – and connect it to a backup power supply such as an emergency diesel generator • Ensure source of power available to essential electrical loads at all times © Copyright 2016 – Rev 2 ELO 1.6 Operator Generic Fundamentals 61 Automatic Transfer Switches • Grouped into two categories based on operation – Power-seeking o Auto to alternate power supply o Manual back to normal supply – Normal-seeking o Auto to alternate power supply o Auto back to normal power supply © Copyright 2016 – Rev 2 ELO 1.6 Operator Generic Fundamentals 62 Automatic Transfer Switches • Many normal-seeking ATSs equipped with time delay – prevents them from shifting back to normal source of power until it has been restored for a pre-set period of time (e.g. five seconds) – Ensures ATS will not shift its electrical loads back to an unreliable source of power when normal source restored • Power-seeking ATSs do not make a distinction between power sources – It will stay connected to new source of power until that source of power is lost, or – until the ATS is manually shifted back to original source of power © Copyright 2016 – Rev 2 ELO 1.6 Operator Generic Fundamentals 63 Motor Controllers ELO 1.7 – Describe the functions, operation, and protective features of motor controllers. • Range from a simple toggle switch to a complex system using solenoids, relays, and timers • Basic function to control and protect the operation of a motor includes – Starting and stopping motor – Protecting motor from overcurrent, undervoltage, and overheating conditions that would cause motor damage • Two basic categories of motor controllers – Manual controller – Magnetic controller © Copyright 2016 – Rev 2 ELO 1.7 Operator Generic Fundamentals 64 Manual Motor Controllers • Operated by hand • Provided with thermal and direct acting overload units – Protect motor from overload conditions • ON-OFF switch with overload conditions • Could be push buttons © Copyright 2016 – Rev 2 ELO 1.7 Operator Generic Fundamentals 65 Manual Motor Controllers • Used on small loads such as – Machine tools – Fans/blowers – Pumps – Compressors • Simple design and operation • Provide quiet operation © Copyright 2016 – Rev 2 ELO 1.7 Operator Generic Fundamentals 66 Magnetic Motor Controller • Master switch frequently operated automatically – Float switch – Pressure switch – Thermostat • Manually operated master switches for these types of controllers include – Push buttons – Drum switches Figure: Three-Phase Magnetic Controller With Thermal Overloads – Knife switches © Copyright 2016 – Rev 2 ELO 1.7 Operator Generic Fundamentals 67 Magnetic Motor Contactor • Operated by electromagnet • Electromagnet and movable iron armature on which movable and stationary contacts are mounted • When no current flowing through electromagnetic coil – armature held away by spring • When coil energized Figure: Magnetic Contactor Assembly – electromagnet attracts armature and closes electrical contacts © Copyright 2016 – Rev 2 ELO 1.7 Operator Generic Fundamentals 68 Motor Controller Types and Operation • Three major types of AC across-the-line controllers: – Low-voltage protection (LVP) – Low-voltage release (LVR) – Low-voltage release effect (LVRE) © Copyright 2016 – Rev 2 ELO 1.7 Operator Generic Fundamentals 69 Low Voltage Protection • Main purpose is to – Deenergize motor during low voltage – Prevent restarting automatically upon return of normal voltage Figure: Low-Voltage Protection Controller © Copyright 2016 – Rev 2 ELO 1.7 Operator Generic Fundamentals 70 Low-Voltage Protection Controller • When START button pushed – Contactor M coil is energized – Closing M and Ma contacts • When START button released – M “a” contact remains closed, completing circuit Figure: Low-Voltage Protection Controller © Copyright 2016 – Rev 2 ELO 1.7 Operator Generic Fundamentals 71 Low-Voltage Protection Controller • When low voltage condition occurs – M coil will drop out at some pre-determined value of voltage – Usually 70-80% of rated voltage – M and Ma contacts open • To restart motor, START button must be pushed © Copyright 2016 – Rev 2 Figure: Low-Voltage Protection Controller ELO 1.7 Operator Generic Fundamentals 72 Low-Voltage Protection Controller • Depressing STOP button deenergizes M coil – Opens M and Ma contacts – Stops motor Figure: Low-Voltage Protection Controller © Copyright 2016 – Rev 2 ELO 1.7 Operator Generic Fundamentals 73 Low-Voltage Release Controller • General purpose – Deenergize motor in low voltage condition – Restart motor when normal voltage is restored • Used primarily on small and/or critical loads – Cooling water pumps required for safety related equipment © Copyright 2016 – Rev 2 Figure: Low-Voltage Release Controller ELO 1.7 Operator Generic Fundamentals 74 Low-Voltage Release Controller • Placing START switch in run – Energizes M coil – Closing M contacts – Starting motor • When low-voltage condition occurs – M coil drops out – Opening M contacts Figure: Low-Voltage Release Controller – Deenergizing motor © Copyright 2016 – Rev 2 ELO 1.7 Operator Generic Fundamentals 75 Low-Voltage Release Controller • When normal voltage restored – M coil is reenergized – Closing M contacts – Restarting motor Figure: Low-Voltage Release Controller © Copyright 2016 – Rev 2 ELO 1.7 Operator Generic Fundamentals 76 Low-Voltage Release Effect • Maintains motor circuit at all times • Manual controller found mostly on small loads that must start automatically upon restoration of voltage • May contain overloads • If overloads are used, they are placed in lines to load Figure: Low-Voltage Release Effect Controller © Copyright 2016 – Rev 2 ELO 1.7 Operator Generic Fundamentals 77 Knowledge Check Knowledge Check Refer to the drawing of a typical valve control circuit for a 480 VAC motor-operated valve below. The valve is currently open with the contact configuration as shown. If the S1 pushbutton is depressed, the valve will ____________ and when the S1 pushbutton is subsequently released, the valve will ____________. A. remain open; close B. remain open; remain open C. close; open D. close; remain closed Correct answer is D. © Copyright 2016 – Rev 2 ELO 1.7 Operator Generic Fundamentals 78 Circuit Breakers TLO 2 – Explain the construction, operation, and indications for electrical circuit breakers. 2.1 Explain the construction and functions of circuit breakers, the different types of circuit breakers and their applications, and the protective features incorporated into circuit breakers. 2.2 Describe the following associated with racking out circuit breakers: purpose for racking out circuit breakers, effect of racking out breakers on control and indicating circuits, removal of control power on breaker operation. 2.3 Describe the indications provided for each of the following: local circuit breaker position indications, control room circuit breaker status indications, circuit breaker and protective relay trip indications. 2.4 Describe the effects of losing circuit breaker control power (to include circuit breaker indicator lights and the ability to open and close a circuit breaker remotely). © Copyright 2016 – Rev 2 TLO 2 Operator Generic Fundamentals 79 Circuit Breakers ELO 2.1 – Explain the construction, functions, and operation of circuit breakers, the different types of circuit breakers and their applications, and the protective features incorporated into circuit breakers. • Circuit breakers used to – Isolate circuits – Circuit protection in the event of faults – Switching during normal operation • Circuit breakers do not sense faults – Relays or overload devices that sense faults often contained in same cabinet as circuit breaker they signal to trip © Copyright 2016 – Rev 2 ELO 2.1 Operator Generic Fundamentals 80 Circuit Breakers Breaker Classifications • High voltage: above 15,000 volts • Intermediate or medium voltage: 600-15,000 volts • Low voltage: less than 600 volts © Copyright 2016 – Rev 2 ELO 2.1 Operator Generic Fundamentals 81 Circuit Breakers Low-Voltage Air Circuit Breaker • For circuits rated at 600 volts or lower • Applications: – Molded case breakers – Small motor control center (MCC) breakers Figure: Molded Case Circuit Breaker © Copyright 2016 – Rev 2 ELO 2.1 Operator Generic Fundamentals 82 Circuit Breakers Molded Case Breaker Operation • Turning ON or OFF position will connect or disconnect a circuit • All breakers, except very small ones, have a linkage that allows for a quick make (quick break) contact action • If circuit breaker opens under fault condition, handle goes to "trip-free" position Figure: Cutaway View of Molded Case Circuit Breaker © Copyright 2016 – Rev 2 ELO 2.1 Operator Generic Fundamentals 83 Circuit Breakers Automatic Tripping • Circuit breaker automatically trips when current through it exceeds a pre-determined value • In lower current ratings, thermal tripping devices provide the means of automatic tripping Figure: Cutaway View of Molded Case Circuit Breaker © Copyright 2016 – Rev 2 ELO 2.1 Operator Generic Fundamentals 84 Thermal Tripping Elements • Consists of bimetallic element calibrated so normal current heat does not cause deflection • High current will cause element to deflect and trip linkage that holds circuit breaker shut – Short circuit – Overload • Circuit breaker opened by spring action Figure: Thermal Tripping Element © Copyright 2016 – Rev 2 ELO 2.1 Operator Generic Fundamentals 85 Thermal Tripping Elements • Bimetallic element is responsive to heat produced by current flowing through it • Inverse-time characteristic – If an extremely high current is developed, circuit breaker will be tripped very rapidly – For moderate overload currents, it will operate more slowly Figure: Thermal Tripping Element © Copyright 2016 – Rev 2 ELO 2.1 Operator Generic Fundamentals 86 Magnetic Tripping Elements Arc Chutes • When the separable contacts of an air circuit breaker open, an arc develops between contacts • Different designs and arrangements of contacts and their surrounding chambers • Most common design places moving contacts inside an arc chute – Construction allows this arc chute to magnetically draw arc formed as contacts open © Copyright 2016 – Rev 2 ELO 2.1 Operator Generic Fundamentals 87 Large Air Circuit Breaker • Large distribution systems require much larger air circuit breakers • Breakers have current ratings as high as 4,000 amps, and interrupting ratings as high as 150,000 amps • Requires stronger mechanism to “make” and “break” contact Figure: Large Air Breaker Front © Copyright 2016 – Rev 2 ELO 2.1 Operator Generic Fundamentals 88 Large Air Circuit Breaker Operation • Closing device, stored energy mechanism • Uses large compressed coil springs • Springs compressed – Manually – Small charging motor Figure: Large Air Circuit Breaker © Copyright 2016 – Rev 2 ELO 2.1 Operator Generic Fundamentals 89 Large Air Circuit Breaker • Closing breakers compresses tripping spring • Tripping spring and trip latch trip open breaker • Trip latch operation – Manually – Remotely by trip coil • Electrically-operated circuit breakers used when – Operated at frequent intervals – Remote operation required © Copyright 2016 – Rev 2 ELO 2.1 Figure: Large Air Circuit Breaker Operator Generic Fundamentals 90 Large Air Circuit Breaker • When electrically operated breaker tripped – Closing spring recharged by spring charging motor – Makes breaker ready for next closing operation Figure: Large Air Circuit Breaker © Copyright 2016 – Rev 2 ELO 2.1 Operator Generic Fundamentals 91 Large Air Circuit Breaker • Closing springs are compressed by pulling downward on large operating handle on front of breaker • Closing springs may also be charged by an electric motor – Motor powered from breaker control power – Will charge springs after breaker closing attempt – If control power lost, can charge motor manually using a lever or hand crank Figure: Large Air Breaker Front © Copyright 2016 – Rev 2 ELO 2.1 Operator Generic Fundamentals 92 High-Voltage Breaker Classifications • Circuits with voltage ratings higher than 600 volts use high-voltage circuit breakers (including breakers rated at intermediate voltage) • Standard voltage ratings are from 4,160 to 765,000 volts with threephase interrupting ratings of 50,000 to 50,000,000 kVA – Early design of high-voltage circuit breakers were oil circuit breakers – Newer designs are magnetic or compressed air © Copyright 2016 – Rev 2 ELO 2.1 Operator Generic Fundamentals 93 High-Voltage Breaker Classifications Magnetic Air Circuit Breakers • Rated up to 750,000 kVA at 13,800 volts, interrupts air with aid of magnetic blowout coils • When contacts separate during a fault condition (see figure), magnets draw arc out horizontally and transfer it to a set of arcing contacts • Blowout coil provides a magnetic field to draw arc upward into arc chutes • Arc accelerates upward into arc chute where it is elongated and divided into many small segments © Copyright 2016 – Rev 2 Figure: Magnetic Air Circuit Breaker ELO 2.1 Operator Generic Fundamentals 94 High-Voltage Breaker Classifications Compressed Air Circuit Breakers • Uses compressed air stream directed toward separable contacts to interrupt arc • Air-blast circuit breakers developed for extra high-voltage applications Figure: Compressed Air Arc Chute © Copyright 2016 – Rev 2 ELO 2.1 Operator Generic Fundamentals 95 High-Voltage Breaker Classifications Oil Circuit Breakers • Have contacts immersed in oil, arc cooled and quenched • Oil tanks in oil circuit breakers are sealed • Electrical connections between contacts and external circuits through porcelain bushings Figure: Oil Circuit Breaker © Copyright 2016 – Rev 2 ELO 2.1 Operator Generic Fundamentals 96 GE Magne-Blast Breaker • GE Magne-Blast breaker is a medium-voltage breaker (see figure) with wide use in power plant switchgear application • Early designs were an air circuit breaker, with a solenoid operated mechanism • Latest designs outfitted with vacuum type contacts Figure: GE Magne-Blast Breaker © Copyright 2016 – Rev 2 ELO 2.1 Operator Generic Fundamentals 97 GE Magne-Blast Breaker • Chassis contains primary contact assembly and bushings, interlocks, and ground strap • Primary contact assembly is the main current carrying part of the breaker • Assembly consists of all barriers, arc chutes, and air puffer system • Some breaker designs include a manual bar to charge closing springs locally at breaker © Copyright 2016 – Rev 2 Figure: GE Magne-Blast Breaker ELO 2.1 Operator Generic Fundamentals 98 Charging Motor • Normally, charging motor charges closing spring(s) • Located below operating mechanism on front left side and connected to a drive fitting and levers to ratchet wheel • Spring discharge interlock – Discharges the closing springs when the breaker is rolled in or out of switchgear cubicle © Copyright 2016 – Rev 2 ELO 2.1 Operator Generic Fundamentals 99 Local Circuit Breaker Operation • Some circuit breakers are designed for local rather than remote operation • Locally operated breakers may be designed to be opened and closed electrically or manually Figure: Circuit Breaker © Copyright 2016 – Rev 2 ELO 2.1 Operator Generic Fundamentals 100 Local Circuit Breaker Operation • Electrically operated – Provided with a local breaker control switch – Uses breaker control power to electrically operate circuit breaker – Normally located in associated switchgear © Copyright 2016 – Rev 2 ELO 2.1 Operator Generic Fundamentals 101 Local Circuit Breaker Operation • Control switch has three positions – TRIP, breaker opens – Midposition, normal "at rest" position – CLOSE, breaker closes if interlocks met Figure: Breaker Control Switch © Copyright 2016 – Rev 2 ELO 2.1 Operator Generic Fundamentals 102 Local Circuit Breaker Operation • Logic circuitry checks breaker interlocks are satisfied before allowing closing • Loss of control power breaker fails as is • Breaker control switch may have a PULL OUT (Pull-To-Lock) position that prevents automatic closing – Standard with this type of control switch and does not imply breaker has automatic closing features © Copyright 2016 – Rev 2 ELO 2.1 Operator Generic Fundamentals 103 Local Circuit Breaker Operation • Electrically operated breakers may also have two different position indicators – Circuit breaker position indicating flags o Red flag indicates breaker was last positioned closed o Green flag indicates breaker was last positioned open o “Flag mismatch” if breaker positions differently from switch – Amber or white light – Circuit breaker position indicating lights o Illuminated red indicates closed o Illuminated green indicates open © Copyright 2016 – Rev 2 ELO 2.1 Operator Generic Fundamentals 104 Local Circuit Breaker Operation Manually Operated Breakers • Some MCC or load center circuit breakers do not have capability of being operated electrically • Manually operated through use of a "TRIP" and a "CLOSE" push button • Do not have: – Circuit breaker control switches – Position indicating lights – Logic circuits to check for interlocks • Must be operated per procedure © Copyright 2016 – Rev 2 ELO 2.1 Operator Generic Fundamentals 105 Local-Remote Transfer Switch • Some components provided with REMOTE/LOCAL transfer switch – DG output breaker – Remote Shutdown Panel components • When REMOTE selected: – control power available for trips and breaker can be operated remotely from control room • When LOCAL selected: – control power available for trips, but breaker can only be operated locally © Copyright 2016 – Rev 2 ELO 2.1 Operator Generic Fundamentals 106 Circuit Breaker Protective Relays • Circuit breaker control circuit can be designed so that any one of a number of protective features may be incorporated • If conditions exists while circuit breaker is closed – Relay will close its associated contact – Energize breaker tripping coil – Circuit breaker trips open • Various protective relays presented earlier (for example) – Undervoltage, underfrequency, reverse power – Long-term, short-term, or instantaneous overcurrent © Copyright 2016 – Rev 2 ELO 2.1 Operator Generic Fundamentals 107 Circuit Breakers Knowledge Check – NRC Question A typical 120 VAC manual circuit breaker has tripped due to overload. To close this circuit breaker, the breaker handle must be moved from the... A. OFF position directly to the ON position; trip latch reset is not required. B. midposition directly to the ON position; trip latch reset is not required. C. OFF position to the midposition to reset the trip latch, and then to the ON position. D. midposition to the OFF position to reset the trip latch, and then to the ON position. Correct answer is D. © Copyright 2016 – Rev 2 ELO 2.1 Operator Generic Fundamentals 108 Circuit Breakers Knowledge Check – NRC Question How is typical breaker operation affected when the associated breaker control power transfer switch is placed in the LOCAL position? A. Control power will be available to provide protective trips, and the breaker can be electrically operated only from the control room. B. Control power will be removed from both the open and close circuits, and the breaker can be electrically operated only from the control room. C. Control power will be available to provide protective trips, and the breaker can be electrically operated only from the breaker cabinet. D. Control power will be removed from both the open and close circuits, and the breaker can be electrically operated only from the breaker cabinet. Correct answer is C. © Copyright 2016 – Rev 2 ELO 2.1 Operator Generic Fundamentals 109 Racking Circuit Breakers ELO 2.2 – Describe the following associated with racking out circuit breakers: purpose for racking out circuit breakers, effect of racking out breakers on control and indicating circuits, and removal of control power on breaker operation. • Breakers may be racked to three positions – Connect (racked in): normal position, breaker supplies power to load – Test: breaker will not connect to load, but control power is supplied to breaker – Disconnect (racked out): deenergizes the load for maintenance (control power must be removed to completely deenergize) © Copyright 2016 – Rev 2 ELO 2.2 Operator Generic Fundamentals 110 Large ACB Racking Operation • To completely deenergize an electrical component and its associated control and indication circuits – breaker should be racked out with control power fuses removed • There are many types of ACB circuit breakers – Method of rackout will be specific to type of breaker © Copyright 2016 – Rev 2 ELO 2.2 Operator Generic Fundamentals 111 Large ACB Racking Operation • Draw out circuit breakers disconnected by moving breakers physically away from bus • Accomplished with racking wrench Figure: Draw out Breaker © Copyright 2016 – Rev 2 ELO 2.2 Operator Generic Fundamentals 112 Large ACB Racking Operation • Breaker moves from – CONNECT position to – TEST position to – DISCONNECT position • Some plants have breaker racking tools that rack the breaker with the operator at a distance • Interlock prevents circuit breaker operation at any point during racking operation © Copyright 2016 – Rev 2 Figure: Breaker Racking Tool ELO 2.2 Operator Generic Fundamentals 113 Large ACB Racking Operation • Remote rackout device minimizes danger associated with potential arc blast as breaker is racked out • Ensure plant procedures and required PPE are used during breaker racking operation • Accidents when racking breakers can be fatal! Figure: Racking Arc Blast © Copyright 2016 – Rev 2 ELO 2.2 Operator Generic Fundamentals 114 Large ACB Racking Operation • CONNECT position allows energizing/ deenergizing load • TEST position allows operation of breaker with control power while not connecting load to bus • DISCONNECT allows removal of breaker from switchgear Figure: Breaker Racked Out © Copyright 2016 – Rev 2 ELO 2.2 Operator Generic Fundamentals 115 Large ACB Racking Operation • To perform a verification of breaker position and operability, following must be ensured: – Indication on floor of circuit breaker housing corresponds to markings on the circuit breaker – Racking release lever is fully in CONNECT position (extreme counterclockwise position) – Closing spring motor toggle switch is in ON position and closing spring is charged (or fuses installed) – Control power breaker is closed and/or control power fuses in place (not blown), ensuring power is available © Copyright 2016 – Rev 2 ELO 2.2 Operator Generic Fundamentals 116 Racking Circuit Breakers Knowledge Check To completely deenergize an electrical component and its associated control and indication circuits, the component breaker should be… A. open with the control switch in Pull-To-Lock. B. open with the control switch tagged in the open position. C. racked out and tagged in racked-out position. D. racked out with control power fuses removed. Correct answer is D. © Copyright 2016 – Rev 2 ELO 2.2 Operator Generic Fundamentals 117 Circuit Breaker Position Verification ELO 2.3 – Describe the indications provided for each of the following: local circuit breaker position indications, control room circuit breaker status indications, and circuit breaker and protective relay trip indications. • Circuit breaker status can be determined by a number of means – Breaker's OPEN/CLOSE mechanical indicators – Breaker position indication lights (control power) – Load-side voltage/current – Physical breaker position • All can be used to positively determine breaker position © Copyright 2016 – Rev 2 ELO 2.3 Operator Generic Fundamentals 118 Circuit Breaker Position Verification • Control indications include: – Red (energized/closed) indicating light – Green (deenergized/open) indicating light – Amber (mismatch) indicating light o On some breakers – Breaker control switch position – Load ammeter © Copyright 2016 – Rev 2 ELO 2.3 Operator Generic Fundamentals 119 Circuit Breaker Position and Control Switch Mismatch • Amber “mismatch” light indication – When light is ON o Physical breaker position (open or closed) does not match current control switch position – Provides additional control room indication of potential problem © Copyright 2016 – Rev 2 ELO 2.3 Operator Generic Fundamentals 120 Circuit Breaker Trip Flags • Automatic circuit breaker trip may be determined by local device protection flag indication • Once protective trip occurs, the trip coil energizes and the circuit breaker opens – Indicated by local mechanical flag • If any protective devices are actuated – local mechanical trip flags must be manually reset once the condition clears o However, relay reset not required to close breaker – Unless it trips an 86 lockout device © Copyright 2016 – Rev 2 ELO 2.3 Operator Generic Fundamentals 121 Circuit Breaker Position Verification • Use all available indications to determine circuit breaker condition • Best indications are those solely dependent on breaker position – Load side voltmeter readings – Local OPEN/CLOSE mechanical flags • Protective devices (relays) not good indicators – Breaker may indicate tripped by a protective trip mechanical flag but may actually be closed – Circuit breaker could actually be closed but the trip flag may still indicate tripped because protective device was not reset (manually) from previous trip © Copyright 2016 – Rev 2 ELO 2.3 Operator Generic Fundamentals 122 Circuit Breaker Position Verification • Circuit breaker position indicating lights are not necessarily a good indicator of actual breaker position – Without breaker control power, breaker may indicate open (red light is not illuminated) when actually closed – Indicating bulbs may also be burned out • Load side ammeter readings cannot be counted on to give an accurate indication of breaker position – Unless breaker directly Starts/Stops a motor © Copyright 2016 – Rev 2 ELO 2.3 Operator Generic Fundamentals 123 Circuit Breaker Position Verification Knowledge Check Breaker local overcurrent trip flag indicators, when actuated, indicate that… A. a breaker trip will occur unless current is reduced. B. a breaker overcurrent condition is responsible for a breaker trip. C. an overcurrent condition has cleared and the breaker can be closed. D. the associated breaker has failed to trip open during an overcurrent condition. Correct answer is B. © Copyright 2016 – Rev 2 ELO 2.3 Operator Generic Fundamentals 124 Circuit Breaker Position Verification Knowledge Check While remotely investigating the condition of a normally-open 480 VAC motor control center (MCC) feeder breaker, an operator observes the following indications: • Green breaker position indicating light is out. • Red breaker position indicating light is lit. • MCC voltmeter indicates 480 VAC. • MCC ammeter indicates zero amperes. Based on these indications, the operator should report that the feeder breaker is __________ and racked __________. A. open; in B. closed; in C. open; to the TEST position D. closed; to the TEST position Correct answer is B. © Copyright 2016 – Rev 2 ELO 2.3 Operator Generic Fundamentals 125 Circuit Breaker Position Verification Knowledge Check While remotely investigating the condition of a typical normally-open motor control center (MCC) feeder breaker, an operator observes the following indications: • Green breaker position indicating light is lit. • Red breaker position indicating light is out. • MCC voltmeter indicates zero volts. • MCC ammeter indicates zero amperes. Based on these indications, the operator can accurately report that the breaker is open and racked to __________ position. A. the OUT B. the IN C. the TEST D. an unknown Correct answer is D. © Copyright 2016 – Rev 2 ELO 2.3 Operator Generic Fundamentals 126 Circuit Breaker Control Power ELO 2.4 – Describe the effects of losing circuit breaker control power on breaker operation and indications. • To operate breakers using a control switch, remotely or locally, a control circuit must be provided • Control power is usually taken from line contacts, rectified, and provided to the control circuit through fuses © Copyright 2016 – Rev 2 ELO 2.4 Operator Generic Fundamentals 127 Circuit Breaker Control Power • Rectifier unit • Closing relay • Closing coil • Trip coil • Auxiliary contacts • Breaker control switch Figure: Breaker Control Circuit © Copyright 2016 – Rev 2 ELO 2.4 Operator Generic Fundamentals 128 Circuit Breaker Control Power • Protective features can be added to trip circuit breaker • Control circuit shown has protective features that will close contacts to energize trip coil – Underfrequency – Undervoltage Figure: Breaker Control Circuit © Copyright 2016 – Rev 2 ELO 2.4 Operator Generic Fundamentals 129 Closing Breaker • Control switch to close – Energizes closing relay – Energizes closing coil – Closes breaker – Closes "a" contact to enable the trip coil • No automatic closures Figure: Breaker Control Circuit © Copyright 2016 – Rev 2 ELO 2.4 Operator Generic Fundamentals 130 Opening Breaker • Control switch to "trip" – Trip coil releases latch, allowing breaker to open – "a" contact opens, deenergizing trip coil – "b" contact closes, enabling closing relay • Automatic opening features – Underfrequency – Undervoltage – When relays actuate, contact energize trip coil © Copyright 2016 – Rev 2 Figure: Breaker Control Circuit ELO 2.4 Operator Generic Fundamentals 131 Loss of Control Power • Effects of losing circuit breaker control power – Lose local and remote breaker indication lights – Lose remote breaker control (open/close) – Lose capability to trip open automatically from a protection trip device or electrical fault – Lose ability for breaker closing spring to electrically recharge after local closing of breaker (charging motor not energized) – Can still OPEN breaker locally/manually © Copyright 2016 – Rev 2 ELO 2.4 Operator Generic Fundamentals 132 Circuit Breaker Control Power Knowledge Check Loss of breaker control power will cause... A. breaker line voltage to indicate zero regardless of actual breaker position. B. the remote breaker position to indicate open regardless of actual breaker position. C. inability to operate the breaker locally and remotely. D. failure of the closing spring to charge following local closing of the breaker. Correct answer is D. © Copyright 2016 – Rev 2 ELO 2.4 Operator Generic Fundamentals 133 Circuit Breaker Control Power Knowledge Check When a typical 4,160 volt breaker is racked to the TEST position, control power is __________ the breaker; and the breaker is __________ the load. A. removed from; isolated from B. removed from; connected to C. available to; isolated from D. available to; connected to Correct answer is C. © Copyright 2016 – Rev 2 ELO 2.4 Operator Generic Fundamentals 134 Paralleling AC Sources TLO 3 – Describe the conditions that must be met prior to paralleling two generators including effects of not meeting these conditions. 3.1 Describe the conditions required to properly parallel two AC power sources, including voltage, frequency, and phase. 3.2 Describe the effects of paralleling two AC sources under the following conditions: current out of phase, frequencies not matched, high voltage differential, and low current or too much load. © Copyright 2016 – Rev 2 TLO 3 Operator Generic Fundamentals 135 Paralleling AC Sources – Conditions ELO 3.1 – Describe the conditions required to properly parallel two AC power sources, including voltage, frequency, and phase. Three conditions must be met prior to paralleling or synchronizing AC sources. • Terminal voltages almost equal – Minimize VAR loading • Frequency of incoming machine slightly higher than grid – Synchroscope rotating slowly in the FAST (clockwise) direction – Ensures incoming machine picks up some load instead of becoming a load (motorizing) • Output voltages in phase – Minimize current surge through breaker © Copyright 2016 – Rev 2 ELO 3.1 Operator Generic Fundamentals 136 Paralleling AC Sources • During paralleling operations, voltages of the generators to be paralleled are shown on voltmeters • Frequency matching is accomplished through the use of output frequency meters • A synchroscope is a device that senses two frequencies – indicates phase differences between generators – allows phase matching of two generators • Once breaker closed, synchroscope locks in at 12 o’clock • Most plants have “sync check relays” – Doesn’t allow breaker closure out of phase © Copyright 2016 – Rev 2 ELO 3.1 Operator Generic Fundamentals 137 Abnormal Conditions During Paralleling Operations ELO 3.2 – Describe the effects of paralleling two AC sources under the following conditions: current out of phase, frequencies not matched, high voltage differential, and low current or too much load.. • Recall that three conditions must be met prior to paralleling or synchronizing AC sources – Following these three minimize current through breaker being paralleled o Minimum VAR loading o Minimum real load picked up o Minimum current from phase differences © Copyright 2016 – Rev 2 ELO 3.2 Operator Generic Fundamentals 138 Paralleling Terminal Voltages • Voltages of running and incoming should be matched – Some plants allow incoming voltage to be slightly higher • Voltage indication might be “stepped down” to 120 volts on meters • Once generator loaded, voltage setting can be changed to carry desired VAR loading – Usually raise voltage in morning to pick up anticipated VARs out – Usually lower voltage in evening to lower anticipated VARs out © Copyright 2016 – Rev 2 ELO 3.2 Operator Generic Fundamentals 139 Paralleling Frequencies • Frequency of incoming machine slightly higher – Ensures some load picked up by incoming generator – Operator usually goes to RAISE on speed control to pick up additional load • Frequency of incoming machine slightly lower – Synchroscope rotating in SLOW (counterclockwise) direction o Known as "motoring or reverse powering“ – Breaker could stay closed if speed control immediately taken to RAISE to pick up load • If frequencies matched – Synchroscope stays motionless at given clock position o Could be in-phase or out-of-phase © Copyright 2016 – Rev 2 ELO 3.2 Operator Generic Fundamentals 140 Paralleling Output Voltages in Phase • Incoming (generator) and running (grid) “in-phase” as synchroscope passes through 12 o’clock • When breaker closed, generator gets “locked” in phase with grid – Synchroscope goes to 12 o’clock and stays there • If breaker closed “out-of-phase”, current surge could damage breaker or generator • Sync check relays might allow closure – Between 11 and 1 o’clock – Basically between +30 degrees and -30 degrees phase differential – Therefore, anything > 30 degrees could be damaging © Copyright 2016 – Rev 2 ELO 3.2 Operator Generic Fundamentals 141 Powering a Deenergized Bus • Closing the output breaker of a three-phase generator onto a deenergized bus can produce an overcurrent condition on the generator – Occurs if the bus was not first unloaded – Due to instantaneous flow of starting current for all loads running when power was lost • If DG provided sole power to a vital bus – Bus usually “load shed” first (all breakers open) – DG comes up to speed – DG output breaker closes – Sequencer loads bus in timed sequence o Allows starting currents to diminish before starting next load © Copyright 2016 – Rev 2 ELO 3.2 Operator Generic Fundamentals 142 Paralleling Operations Knowledge Check A main generator is about to be connected to an infinite power grid. Generator voltage is equal to grid voltage and the synchroscope is rotating slowly in the counterclockwise direction. The generator breaker is closed just prior to the synchroscope pointer reaching the 12 o'clock position. Which one of the following is most likely to occur after the breaker is closed? A. The breaker will remain closed and the generator will supply only MW to the grid. B. The breaker will remain closed and the generator will supply both MW and MVAR to the grid. C. The breaker will open due to overcurrent. D. The breaker will open due to reverse power. Correct answer is D. © Copyright 2016 – Rev 2 ELO 3.2 Operator Generic Fundamentals 143 Paralleling Operations Knowledge Check If a main generator output breaker is closed when the generator output voltage is 5 degrees out of phase with the power grid voltage, the main generator will experience a __________ stress; if the breaker remains closed and no additional operator action is taken, the main generator voltage will __________ with the grid voltage. A. B. C. D. minor; remain out of phase minor; become locked into phase potentially damaging; remain out of phase potentially damaging; become locked into phase Correct answer is B. © Copyright 2016 – Rev 2 ELO 3.2 Operator Generic Fundamentals 144 NRC KA to ELO Tie KA # KA Statement Purpose of racking out breakers (de-energize components and associated control and K1.01 indication circuits) RO SRO 2.6 2.8 2.2 K1.02 Local indication that breaker is open, closed or tripped Loss of power supply circuit breaker indicator lights and capability in remotely open and K1.03 close Operation of various push buttons, switches and handles and the resulting action on K1.04 breakers 2.8 2.9 2.3 2.9 3.1 2.4 2.9 3.0 2.1 K1.05 Function of thermal overload protection device 2.3 2.4 1.2 K1.06 Interpretation of symbols for breakers, relays and disconnects in a one-line diagram Safety procedures and precautions associated with breakers, including MCC bus K1.07 breakers, high, medium and low voltage breakers, relays and disconnects Effects of closing breakers with current out of phase, different frequencies, high voltage K1.08 differential, low current, or too much load Effect of racking out breakers on control and indicating circuits and removal of control K1.09 power on breaker operation 2.3 2.6 1.5 3.0 3.3 1.4 3.3 3.5 3.2 2.8 3.1 2.3, 2.4 K1.10 Function, control, and precautions associated with disconnects 2.7 3.1 1.3 K1.11 Control room indication of a breaker status 3.1 3.3 2.3 K1.12 Trip indicators for circuit breakers and protective relays 2.9 2.9 1.2, 2.3 © Copyright 2016 – Rev 2 ELO Operator Generic Fundamentals