Download Raychem MC 2-hour fire-rated, polymer insulated, power cable

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Ground loop (electricity) wikipedia , lookup

Alternating current wikipedia , lookup

Stray voltage wikipedia , lookup

Power over Ethernet wikipedia , lookup

Aluminium-conductor steel-reinforced cable wikipedia , lookup

Thermal runaway wikipedia , lookup

Ground (electricity) wikipedia , lookup

Printed circuit board wikipedia , lookup

Flexible electronics wikipedia , lookup

Telecommunications engineering wikipedia , lookup

Skin effect wikipedia , lookup

Overhead power line wikipedia , lookup

Thermal copper pillar bump wikipedia , lookup

Electrical connector wikipedia , lookup

Loading coil wikipedia , lookup

Copper conductor wikipedia , lookup

Coaxial cable wikipedia , lookup

Electrical wiring wikipedia , lookup

National Electrical Code wikipedia , lookup

Transcript
MC
2-hour fire-rated, polymer insulated,
power cable
Flexible polymer insulated fire-rated
cable for protection of critical life safety
circuits.
Raychem® MC power cable is listed by UL as
2-hour fire-rated when installed in accordance
with Tyco Thermal Controls installation
procedures and system listings. This cable
meets the requirements of an “Electrical
Circuit Protective System” as referred to in
Articles 695 and 700 of the National Electrical Code (NEC). The details of this system
appear in Electrical Circuit Protective System
(FHIT), System No. 17 of the UL Fire Resistance Directory.
Raychem MC is:
• UL Listed, NEC Type MC in accordance
with UL 1569
• UL Listed for CT (cable tray) use
• For use in wet locations to 90°C
• 2-hour fire rated per UL 2196
• Armored with copper sheath that
exceeds the NEC requirement for
equipment grounding conductor
• Simple to terminate with commercially
available brass MC connectors
Raychem MC is ideal for:
• High-rise buildings – emergency feeders for fire pumps, elevators, smoke
extraction and pressurization fans, etc.
• Historic buildings to assure preservation
of fire fighting systems.
• Tunnels and subways for smoke extraction fans, fire pumps, emergency lighting,
and other power circuits.
• Airports, stadiums, hotels, banks, etc.
For additional information, contact your
Tyco Thermal Controls representative or
call Tyco Thermal Controls at
(800) 545-6258.
Cable construction
Continuously welded and
corrugated copper armor
Continuously welded and
corrugated copper armor
Silicone rubber inner jacket
Silicone rubber insulation
Annealed copper conductor
Silicone rubber insulation
Annealed copper conductor
Cable Construction
Conductor
Annealed copper, Class “B” strand, designed to ensure tensile strength under fire conditions
Insulation
Thermoset, low smoke zero halogen silicone rubber
Insulation voltage rating
600 V
Circuit identification
Conductor insulation printed “1-ONE”, “2-TWO”, 3-THREE”, and so on per ICEA Method 4
Inner jacket
Thermoset, low smoke zero halogen silicone rubber
Armor
Continuously welded and corrugated copper
Outer jacket (optional)
Flame retardant polyvinyl chloride (PVC) or low smoke zero halogen (LSZH) polyolefin
Configuration
Single or multiconductor
Cable identification
Cable armor or optional outer jacket is printed with cable identification.
H57775
12/05
(800) 545-6258
www.tycothermal.com
Tyco Thermal Controls
1 of 2
MC
Cable Specifications (nominal)
Product
code
Size
Number of
conductors
(AWG/kcmil)
Insulation
thickness
Inner jacket
thickness
Inner jacket
diameter
Armor
thickness
Armor
diameter
Weight
(in)
(in)
(in)
(mils)
(in)
lbs/kft
MC-03010
10
3
0.06
0.05
0.61
25
0.94
550
MC-031X0
1/0
3
0.09
0.05
1.29
25
1.67
2080
MC-032X0
2/0
3
0.09
0.05
1.39
25
1.80
2450
MC-033X0
3/0
3
0.09
0.05
1.45
25
1.92
2850
MC-034X0
4/0
3
0.09
0.05
1.62
25
2.04
3430
MC-01250
250
1
0.105
0.05
0.89
25
1.22
1470
MC-01350
350
1
0.105
0.05
1.00
25
1.35
1840
MC-01500
500
1
0.105
0.05
1.12
25
1.48
2400
Notes:
• For other configurations and minimum order quantities, contact Tyco Thermal Controls at (800) 545-6258.
• Installation per UL Electrical Circuit protective System (FHIT) – System No. 17, and the National Electrical Code (NFPA 70).
• Multiconductor cable ampacity is based on Table 310.16 of the National Electrical Code. Single conductor ampacity should be in accordance
with NEC 330.80.
Approvals
LISTED
UL Classified, 2-hour fire-resistive cable,
tested to UL 2196
2 of 2
Tyco Thermal Controls
www.tycothermal.com
(800) 545-6258
H57775
12/05