Download Four Wire System Farm Wiring Review

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

CMOS wikipedia , lookup

Test probe wikipedia , lookup

Telecommunications engineering wikipedia , lookup

Operational amplifier wikipedia , lookup

Josephson voltage standard wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Schmitt trigger wikipedia , lookup

Power electronics wikipedia , lookup

Automatic test equipment wikipedia , lookup

Power MOSFET wikipedia , lookup

Current mirror wikipedia , lookup

Voltage regulator wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Ohm's law wikipedia , lookup

Valve RF amplifier wikipedia , lookup

NEMA connector wikipedia , lookup

Surge protector wikipedia , lookup

Multimeter wikipedia , lookup

Opto-isolator wikipedia , lookup

Rectiverter wikipedia , lookup

Transcript
Midwest Rural Energy Council Workshop on
Advanced Topics in Stray Voltage
Investigation. March 2, 2016 in La Crosse, WI
Farm Wiring
Four Wire System Review
Mark Cook
Mark Cook Consulting
Cambridge WI
608.220.4854
[email protected]
1
Herd size 25 year trend
170
150
130
cows
110
90
70
50
Trend in cow contact voltage from all sources 25 year span, 79%
1.2
1
0.8
Volts
0.6
0.4
0.2
0
Trend in Vpnref at the transformer
3
2.5
2
Volts
1.5
1
0.5
0
Trend in Vsnref
1.5
1.4
1.3
1.2
Volts
1.1
1
0.9
0.8
Farm rewiring pgm.
Fact:



Neutral-to-Earth Voltage exits on all electrical
systems
Neutral-to-Earth Voltage that reaches the
animal environment is called Stray Voltage
Fact: Voltage drop to one building will affect
other buildings and the utility.
7
This is the view you see........


We must look with a different
perspective...
We must see the neutral circuit as
sources, resistances, connections and
grounds.....
Re-assemble the schematic into a more
functional form.


The primary system and the secondary system
on the left......
And the cow contact on the right.
This is the farm
we are testing
How effective is on-farm mitigation?
No asfound
EPP
AsFound
EPP
No asFound
4-wire
AsFound
4-wire
Average
Icc
0.87 mA.
0.20 mA.
0.78 mA
0.39 mA.
N=
7254
939
6511
994
If both EPP and 4-wire were found, the average Icc was 0.19
mA. (N=360), If both were absent, the average Icc was 0.82
mA. (N= 5857).
Purpose: Four Wire Systems
1.
The safest, least cost
solution to the number
one cause of stray
voltage
4-wire System Panelboard
Bond
screw
removed
Neutral bus
Equipment
grounding
bus
To ground rod
To water
pipe
17
Four-wire vs three-wire feeders

Supplying a subpanel in the same building



NEC requires the ground and neutrals to be
maintained separate.
The grounded wire (the neutral) must be
insulated and labeled white.
For agricultural buildings under Art. 547 there
must be a copper grounding conductor and if
underground, the equipment grounding
conductor must be insulated or covered
18
Separation of equipment grounding and
neutrals
4-wire system
Meter
Pole
Main
Bond
screw
removed
Separate
equipment
grounding bus
19
250-32(b)(2)(2)
Supply to a separate building
Building 1
Building 2
Main
Metal Water Pipe
Telephone, Gas lines
20
Advantages of four-wire



Reduces on farm source voltages at cow
contact
Eliminates 120 volt imbalance load problems
Reduces secondary neutral current returning
through the earth
21
Disadvantages of four-wire



A four-wire service is almost never wired
correctly and to CODE.
A four-wire service only corrects the on farm
service or feeder being four-wired.
Improper installation can cause voltages on
equipment to increase.
22
ANY interconnection between
equipment grounds and
neutral can put a significant
voltage where it can reach
the animals or cause damage.
Three Wire System
Three
wire
system
•Vp=0.181
•Vs=1.818
Vps = 2
Rsn = 0.2
Rf = 5.0
Rpn = 0.5
Ic = ?
Vp
3/1/2016
Vs
24
Four-Wire System
Vps = 2
•Vp=0.0
•Vs=2
Rsn = 0.2
Rf = 5.0
Rpn = 0.5
Ic = ?
Vsg
Vp
3/1/2016
Vs
25
Warning


Separating the primary and secondary
neutrals will shift the location of NEV from
secondary neutral voltage drop at every
service, feeder and branch circuit.
Vp is never just Vp
Example of teeter/totter effect:
1.51v.
1.71v.
0.29v.
Pri.
Sec.
Isolated
0.09v.
Sec.
Pri.
Non-isolated
Happens on every
Circuit!
Think about this:

What happens when you have
interconnections?

Open neutral?


Unbalanced load current will flow through the
interconnection. Interconnections are unintentional
and not able to handle the job of a main bonding
jumper. Fire?
Phase fault?
29
Testing Four-Wire Systems
v1
Neutral bus
Reference
ground
v2
Equipment
grounding
bus
There will normally be enough NEV on v1 from the primary or other
buildings to use for test.
30
Testing 4-Wire (5-Wire)
Systems for Interconnections
31
Do not:

Use a ohm meter to test for interconnections.




Ohm meter current is to small to swamp out
noise on the system.
Circuit is to large.
Signal to noise ratio is unpredictable.
Meter not intended for this use.
32
Do not:

Use a car battery to test for AC power system
resistances or interconnections.




Current is to small to swamp out noise on the
system.
Circuit is to large.
Signal to noise ratio is unpredictable.
Polarity problems occur.
33
Do:

Use a digital volt meter to test for farm
wiring grounded and grounding system
interconnections.



NEV is the source of interest so use it.
Input Impedance is very high.
Meter operates in the desired frequency range.
34
Testing Four-wire Systems




1. Remove all loads from the service
equipment.
2. Connect two meters, each one to the
neutral bar ( v1&v2).
3. On one meter connect the second lead to
a remote reference rod (v1).
4. On the second meter connect the second
lead to the grounding bar (v2).
Testing Four-wire Systems

Evaluate the separation of the grounded
(neutral) and Grounding (fourth-wire)
conductors by the following analyses:
Four-wire System Test

A. If v1 is much greater than v2 there is an
unwanted interconnection between the
neutral and grounding wires. v2 will be near
zero if grounded and grounding conductors
are connected.
Four-wire System Test



B. Remove one outgoing grounding wire at a
time until v1 and v2 read essentially the
same.
C. Find and separate the identified
grounding wire/neutral interconnection.
D. Continue to remove other grounding wires
one at a time from the grounding buss to
verify test results.
Final comments:







Understand that every farm wiring system creates NEV.
Never assume that the four-wire system is installed
correctly.
Vp is a combination of many sources.
Vps must be monitored to understand the source voltage on
the farm.
Secondary neutral voltage drop testing must be conducted
properly.
Primary changes alter source voltages on the farm.
Eliminate interconnection.
42
QUESTIONS ?
QUESTIONS ?
QUESTIONS ?
QUESTIONS ?
QUESTIONS ?
QUESTIONS ?
QUESTIONS ?
•Not a proper four-wire