Download static bypass switch unb40.0

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Stray voltage wikipedia , lookup

Electrical substation wikipedia , lookup

Utility frequency wikipedia , lookup

Current source wikipedia , lookup

Electromagnetic compatibility wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Rectifier wikipedia , lookup

Control system wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Alternating current wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Voltage optimisation wikipedia , lookup

Two-port network wikipedia , lookup

Voltage regulator wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Schmitt trigger wikipedia , lookup

Islanding wikipedia , lookup

Power inverter wikipedia , lookup

Buck converter wikipedia , lookup

Mains electricity wikipedia , lookup

Solar micro-inverter wikipedia , lookup

Opto-isolator wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Transcript
STATIC BYPASS SWITCH
UNB40.0
In: 2 x 230VAC
Out: 230VAC (40.0kVA)
· 19‘‘, 4U
· „Hot plug-in” design
· Wide synchronization range
· Optimized mains synchronization
· Alphanumeric LCD display for
measurement values and system
parameters
· Complete system monitoring via
CAN-Bus
· Temperature-controlled fan cooling
The UNB range of static bypass switches features
the latest micro controller technology for monitoring, synchronization and communication combined
with a flexible 19”-compatible rack mounting.
These modular units are designed for systems
consisting of UNV- or PWS-type inverters. Parallel
connection up to 40.0kVA is possible to increase
the output power or system reliability by (n+1)redundancy.
The micro processor-controlled synchronization
unit guarantees mains synchronicity of single or
paralleled inverters. The availability of all inverters in the system is continuously checked and
monitored.
All monitoring functions and system parameters
are indicated and can be adjusted by an alphanumeric display and control keys on the front panel.
All system parameters can be read out by PC software together with the central monitoring unit
UPC3 (optional).
Static bypass switch for AC power supplies in all areas
of industry, telecommunication, power generation and
power distribution.
Type Range
UNB40.0-24
UNB40.0-48
UNB40.0-60
UNB40.0-110
UNB40.0-220
Article code
600-400-411.00
600-400-511.00
600-400-611.00
600-400-711.00
600-400-811.00
Nominal input voltage - Source 1 + 2
220/230/240VAC, programmable
Input voltage tolerance
± 20%
Input frequency range
47-53 resp. 57-63Hz, programmable
Overall efficiency
≥ 99%
Nominal battery voltage
24VDC
48VDC
60VDC
108VDC
216VDC
2A gL
2A gL
1A gL
1A gL
Redundant circuitry supply-fusing (external)
2A gL
Nominal output voltage
220/230/240VAC, programmable
Switching thresholds
± 5% … ± 20%, programmable
Nominal switching capacity
40.0kVA
Overload capability
1000% for 10 ms
Output frequency
acc. to the input frequency
Transfer time
≤ 4 ms
Input fusing
External with 200A, character gL
LED indications
Operation (green), Source 1 OK (green), Source 2 OK (green), Load on Mains (green), Load on Inverter
(green), Synchronization (green), Alarm (red)
Monitoring functions
Source 1 and source 2 with load transfer, synchronization, overtemperature, fan failure
Alphanumeric display
LCD (4x16 characters), background lighted
Signal contacts
Relay “common alarm”
Microprocessor control
Programmable monitoring functions for all system parameters; adjustment via control keys and LCD
display at the front
Communication
CAN-Bus interface for communication with inverters of type UNV and central monitoring unit UPC3
Ambient temperature
Operation: -20°C to +55°C, storage: -40°C to +85°C
Climatic conditions
according to IEC 721-3-3 class 3K3/3Z1/3B1/3C2/3S2/3M2
Dust
< 1mg/m3
Max. installation altitude
≤ 1500m
Audible noise
< 45dB (A) at 1m distance
Type of construction
19“, 4U
Dimensions (W/H/D)
483/177/460mm
Weight
approx. 16.9kg
Cooling
Temperature-controlled fan cooling (front to rear) with fan monitoring
Type of enclosure / Protection class
IP20 (front panel) / 1 acc. to EN 60950 (electr.)
Surface
Front panel: powder coating RAL 7035, black imprint; constructive parts: anodized
Connections
Rear side: AC inputs/output, DC input and signalization;
Front side: 2 x CAN bus (RJ11); 1 x Sub-Min-D (not used)
CE conformity
yes
Compliance to safety standards
EN 60950-1; VDE 0100 part 410; VDE 0110; EN 50178; EN 60146
Compliance to EMC standards
EN 55011/EN 55022 class “B“; EN 61000-4 part 2-5
Article
Article Code
Mounting set
880-MEC-MKT.03
DS_UNB40.0_2007_E_R03 - Subject to change without notice - Eltek Valere Industrial GmbH