Download Panel Linking - Microsoft Word document

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Telecommunications relay service wikipedia , lookup

Panel switch wikipedia , lookup

Transcript
PANEL LINKING
470 ohm
Fire relay
n/o
+ zone 1
non latch
or
_ rem evac
4k3 eol
Panel 1
Panel 2
470 ohm
Zone 1
+
Non latch
or
Rem evac _
4k3 eol
Fire relay
n/o
Linking Panels
To link two panels together, two pairs of wires are required.
On panel 1 connect the first pair of wires to the fire relay with the end of line resistor
and triggering resistor network as shown. The other end of this pair of wires is
connected to a non latching zone or rem evac input on panel 2.
When panel 1 goes into fire, the fire relay contacts change to n/c triggering panel 2
into fire. When panel 1 is silenced panel 2 will also silence as the input is non
latching.
On panel 2 connect the second pair of wires to the fire relay with the end of line
resistor and triggering resistor network as shown. The other end of this pair of wires is
connected to a non latching zone or rem evac input on panel 1.
When panel 2 goes into fire, the fire relay contacts change to n/c triggering panel 1
into fire. When panel 2 is silenced panel 1 will also silence as the input is non
latching.
SUGGESTED WAY OF CONNECTING RESISTORS ON THE FIRE RELAY
CONTACTS
COMMON FIRE RELAY
CONTACT
470 ohm
RESISTOR
Zone 1
+
Non latch
or
Rem evac
-
N/C FIRE RELAY
CONTACT
4K3
EOL
N/O FIRE RELAY
CONTACT