Download MiniSub 44KV Manual - English

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Mercury-arc valve wikipedia , lookup

Transformer wikipedia , lookup

Three-phase electric power wikipedia , lookup

Power engineering wikipedia , lookup

Opto-isolator wikipedia , lookup

History of electric power transmission wikipedia , lookup

Buck converter wikipedia , lookup

Ground (electricity) wikipedia , lookup

Portable appliance testing wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Transformer types wikipedia , lookup

Fuse (electrical) wikipedia , lookup

Voltage optimisation wikipedia , lookup

Electrical substation wikipedia , lookup

Earthing system wikipedia , lookup

Stray voltage wikipedia , lookup

Surge protector wikipedia , lookup

Electrical wiring in the United Kingdom wikipedia , lookup

Alternating current wikipedia , lookup

Mains electricity wikipedia , lookup

Transcript
MiniSub
44kV UNIT SUBSTATION
INSTALLATION AND OPERATION MANUAL
Issue 2015
Revision0
Installation and Operation Manual
ii
Installation and Operation Manual
TABLE OF CONTENTS
1.0
2.0
3.0
4.0
INTRODUCTION
1.1 General …………………………………………
1.2 Sealed tank MiniSub ……………………….
1.3 Safety practices ……………...………………...
1.4 WARNINGS - Voltage hazards ……………….
5
5
5
7
SHIPPING AND RECEIVING
2.1 Shipping ……………………………………….
2.2 Receiving ………………………………………
8
8
HANDLING AND STORAGE
3.1 Handling ……………………………………….
3.2 Storage …………………………………………
10
10
INSTALLATION
4.1 External inspection …………………………….
4.2 Location and Mounting ……………………….
4.3 Electrical Connections …………………………
4.3.1 Grounding ……………………………
4.3.2 Low Voltage Connections ……………
4.3.3 High Voltage Connections …………...
4.4 Testing………………………………………….
11
11
11
12
12
12
12
5.0
OPERATION AND MAINTENANCE
5.1 Operation ………………………………………..
13
5.2 Maintenance …………………………………….
13
5.2.1 Before Energization …………………..
14
5.2.2 Table of maintenance …………………
14
5.3 Insulating fluid and Gas………………………….
16
5.3.1 Mineral Oil …………………………..
16
5.3.2 Envirotemp FR3® Fluid ……………
17
5.3.3 Oil Analysis …………………………..
17
5.3.3.1 Typical Properties …………….
17
5.3.3.2 Gases dissolved in Insulating …
Fluid ………………………….
17
5.4 Fuse replacement procedure……………………………..19
6.0
COMPONENTS AND ACCESSORIES
6.1 Bushings ………………………………………..
6.2 Radiator(s) ……………………………………...
6.2.1 Installation of Removable Radiators ……
6.3 Gaskets …………………………………………
6.3.1 Replacing gaskets in the field ………...
6.4 Liquid Thermometer ……………………………
6.5 Off Load Tap Changer ………………………….
6.6 Dual Voltage Switch ……………………………
iii
19
19
19
20
20
20
20
21
Installation and Operation Manual
6.7 Pressure Relief Valve ……………………………
6.8 Liquid Level Gauge ………………………………
6.9 Bay-O-Net fuse …………………………………
6.9.1 Isolation Link …………………………
6.9.2 Current Sensing Fuse Link ……………
6.9.3 Dual Sensing Fuse Link ……………….
6.10 Lightning arrestors ……………………………..
6.11 Key interlock ……………………………………
6.12 Utility Metering…………………………………
6.13 Current Transformers……………………………
21
21
22
23
23
23
23
24
24
24
7.0
REPLACEMENT PARTS ……………………………..
25
8.0
TERMS OF SALE AND WARRANTY
26
iv
Installation and Operation Manual
1.0 INTRODUCTION
1.1 General
This manual contains information on receiving, handling, installation, operation,
and maintenance of liquid-filled MiniSub. Every MiniSub will have its own
specific and individual combination of accessories. These accessories are detailed
in the MiniSub drawings attached to this manual.
The information, recommendations, descriptions and safety procedures contained herein
are based on the company’s experience and should not be considered to be all inclusive or
covering all contingencies. This manual is not a substitute for adequate training in the safe
working procedures of MiniSubs and switches. If further information is desired or required,
POWER SYSTEMS TECHNOLOGY (EEGENCO LTD). should be consulted.
KEEP THIS INSTRUCTION MANUAL ACCESSIBLE FOR THOSE RESPONSIBLE
FOR INSTALLATION, MAINTENANCE, OPERATION, AND SERVICE OF THE
MINISUB.
THE MINISUB SHOULD BE OPERATED, SERVICED, AND INSTALLED ONLY BY
COMPETENT, ADEQUATELY TRAINED ELECTRICAL PERSONNEL.
Additionally, all applicable safety procedures, regional and local safety requirements, and
safety guidelines set forth in the Electrical Code must be considered and used by those who
operate, service, and install this unit.
1.2 Sealed tank MiniSub
Sealed tank MiniSubs have the interior of the MiniSub sealed from the atmosphere. An air
space is left above the oil such that over a specified temperature range the gas pressure will
not exceed specified safe values. The oxygen in the air space is absorbed by the oil, but the
small quantity involved is of no consequence to the operation or life of the MiniSub. Once
sealed, there is no contact between the oil and the outside atmosphere. Therefore, the oil is
not subject to further oxidation during normal service.
1.3 Safety Practices
Electrical equipment can prove to be very dangerous for the unwary person. It is necessary
to follow a basic series of precautions prior to working on any equipment. Safety
considerations are highlighted in the following manner:
DANGER - This is a danger notice.
The same method is used for CAUTION NOTICES.
5
Installation and Operation Manual
These warnings are meant to highlight incorrect practices which may be dangerous and
which may cause personal injury or damage to the equipment. Any additional safety
precautions, which may apply, as part of the safety program instituted by your company,
must also of course be followed.
If you are not sure of the correct procedure to follow, refer to this instruction manual and/or
contact a person who is trained in the work you are required to perform.
BASIC SAFETY PRECAUTIONS:

Every employer has a safety program implemented at the location you are working
in. Ensure that you know what the program is, including emergency procedures in
the event of an accident.

Make sure safety equipment and tools are always close at hand. Keep a fire
extinguisher suitable for fires involving electrical equipment near the work location.
Make sure it is correctly charged and you know how to use it.

Always be alert for emergencies. If an accident should occur, quickly utilize the
safety equipment and emergency tools at hand. Before you begin any project, make
sure that at least two people know first aid procedures (CPR, Cardio-pulmonary
resuscitation training, is additionally recommended) and have the proper first aid
kits available.

Be concerned, not only for your own safety, but also for the safety of the people
around you. Insist that others follow the correct safety rules.

Make sure that all of the protective equipment required for the job is available for
all workers who require it and that it is used correctly. This equipment may include
hard-hats, breathing apparatus, eye protection, gloves, foot protection etc.

Make sure that all electrical circuits have been traced and de-energized. Verify that
all safety grounds have been correctly applied to protect personnel against the
accidental application of power to these circuits while work is being performed. DO
NOT assume that someone else has turned off the power - check for yourself.

Use padlocking facilities and key interlock systems, where available, to protect
yourself and others.

Do not work under equipment, which is raised or blocked. Do not walk under
equipment that is suspended from a crane.

Do not work on or adjust moving equipment. Do not work on or adjust mechanical
equipment unless its motive source has been de-activated - Keep your hands away.
6
Installation and Operation Manual
1.4 WARNING -Voltage hazards
The turns ratio between the windings of any MiniSub make them capable of transforming
what are normally considered to be harmless voltages to dangerous and even lethal levels.
Electric welders, continuity checking instruments and insulation testing apparatus are
examples of sources of so called harmless voltages. Even if these are direct current (DC)
devices, they are capable of producing voltages high enough to be hazardous to human life
when their circuits are connected or interrupted.
Other situations, which may present hazardous conditions, include the high voltages
produced by open circuited current MiniSubs, which have current flowing in the primary
circuit.
When personnel are working on de-energized MiniSubs, winding terminals should be
suitably short circuited and grounded according to correct safety practice to avoid current
flowing in CT. Unused current MiniSubs shall always have their secondary windings
short-circuited with a suitable size of wire to avoid the high open circuit voltages.
7
Installation and Operation Manual
2.0 SHIPPING AND RECEIVING
2.1 Shipping
The MiniSub is normally shipped completely assembled, liquid-filled and sealed for open
carrier transport. Shipping clearances determine which accessories must be removed and
shipped in separate boxes. Careful inspection of the packing list should be done to check
for possible shortages.
2.2 Receiving
We have taken normal precautions to prevent damage during shipping. However, even the
most elaborate precautions cannot prevent the possibility of a mishap during transit.
Before accepting delivery, it is recommended that the customer examine the shipment
before it is off loaded. This examination should include the following:
123456-
Check the main tank for signs of oil leakage, paint scratches or other indications of
damage.
Check timber bracing, bolt down rods or cables for signs of shifting of the
apparatus.
Check all containers or accessories for damage or tampering.
Check the operation of the off-load tap changer.
Units with motor operators or sensing controls, all cables should be properly
coiled and isolated from primary power cables.
Ensure system ground is installed to the main MiniSub ground.
8
Installation and Operation Manual
2.2 Receiving
Low Voltage Section
Remove covers and inspect the following
12-
3-
45-
:
If CTs are installed, they should be securely mounted to support bar and MiniSub.
All terminals are to be checked for security.
Metering, if installed, should be checked for correct installation in base. Check
that fuses are installed, fully inserted into holders and CT shorting switches are
out.
If breakers are installed, check mounting bracket is securely attached to frame. If
bus torque sticker is not visible check all bus work. Be sure ground CT, if
installed, is connected to the breaker. All breaker settings will be set to their
lowest values.
Cable supports: be sure all cables connected out going are properly supported and
not held only by lugs.
Replace all barriers and securely fasten.
If shortages, tampering, damage or any indication of rough handling is evident, this should
be noted on the shipping receipt or the bill of lading. Do not remove or open any of the
shipment until the transport agent has made his examination. A damage claim should be
filed with the transportation company and Power Systems Technology (EEGENCO Ltd. )
should be notified immediately.
MiniSubs are shipped with windings connected according to the customer's instructions,
which are shown on the nameplate. It is advisable for the customer to thoroughly check all
connections before placing the MiniSub in operation. Contact Power Systems Technology
(EEGENCO Ltd.) before making any connections not shown on the nameplate.
CAUTION: Under no circumstances should a damaged shipment or any part
of that shipment be unloaded from the trailer until the damage claim has
been resolved with the carrier.
9
Installation and Operation Manual
3.0 HANDLING AND STORAGE
3.1 Handling
Palletized units may be moved by a forklift truck, but special care should be taken to not
damage the cabinet compartments and the cooling radiators. These items can be easily
damaged by improper handling.
Lifting hooks are provided on all MiniSub tanks and heavy parts such as covers, radiators,
radiator banks and core and coil assemblies. Approximate total weight is listed on the
outline drawing and on the nameplate.
Lifting hooks are designed for vertical strain only and are provided for lifting the complete
MiniSub. When lifting the MiniSub, use all the hooks and use proper spreaders to obtain a
vertical lift in order to prevent horizontal strain on the tank.
Completely assembled MiniSubs can be lifted with chain slings or a lifting beam. Chain
slings should be of equal length so that the MiniSub will be lifted evenly. The cover should
always be securely and correctly fastened into place when lifting, to prevent buckling of the
tank walls. For safe lifting, we recommend a minimum lifting angle of 60°. The working
load limit of the chain is then 86.5 % of nominal rating.
Jacking may be accomplished using the jacking pads (if provided) on the MiniSub. Never
attempt to raise the MiniSub by placing jacks under any other attachments. MiniSubs may
be moved on rollers but care must be taken to distribute the stress over the entire tank base.
3.2 Storage
It is advisable to ship a new MiniSub directly to its permanent location and to follow the
prescribed installation instructions whether or not the MiniSub is put into immediate
service.
If the MiniSub must be stored, locate it upright preferably in its permanent location on the
concrete pad. If a level concrete pad is not available, then a pallet of adequate strength will
provide a suitable means of keeping the unit from direct contact with the ground. Adequate
ventilation should be maintained under the bottom of the MiniSub. The MiniSub should not
be stored in the presence of corrosive gases such as chlorine, acid fumes, etc. Periodic
inspection should ensure that proper liquid and gas level is maintained at all times. Gas
pressure must be maintained at all times to prevent possible corrosion and
degradation of insulating parts in the tank
Improper storage will void warranty. All loose materials such as cable terminators,
inserts and spare parts must be stored in a clean dry place.
10
Installation and Operation Manual
4.0 INSTALLATION
Installation should comply with the latest edition of the Electrical Code applicable and
should be performed only by adequately trained electrical personnel.
4.1 External Inspection
The oil level in the MiniSub must be at the proper level prior to applying voltage. Oil level
can be checked using the liquid level gauge. Use only the same type of fluid when re-filling
the MiniSub in the field.
THE OWNER SHOULD TAKE THE NECESSARY PRECAUTIONS THAT PCB
CONTAMINATION IS NOT INTRODUCED DURING FIELD FILLING,
OPERATION, OR MAINTENANCE OF THE MINISUB. The MiniSub was filled
with NON-PCB fluid at the factory in compliance with Federal regulations.
4.2 Location and Mounting
MiniSubs should be mounted on a strong and level foundation of sufficient strength to
support the MiniSub weight. The location should allow for adequate air circulation to avoid
overheating and allow sufficient space for future inspection and maintenance of the unit.
The MiniSub should be installed level without a tilt in any direction greater than 1½
degree. This is in order to maintain the proper fluid level for accessories installed at the
upper level of the liquid. The MiniSub cabinet (if any) should be flush against the pad at all
points. Any gaps that may exist must be plugged in order to maintain the tamper resistant
design of a padmount MiniSub.
When supplied, hold down cleats should be installed to bolt the cabinet securely to the
concrete pad.
4.3 Electrical Connections
We suggest the following sequence of connections when installing the MiniSub:
1. all ground connections
2. all low voltage connections
3. all high voltage connections – SEE 44kV INSTRUCTION 44kV CABLE
CONNECTORS
When removing the MiniSub from service the reverse of the above operations is
recommended.
11
Installation and Operation Manual
4.3.1 Grounding
A good, permanent and low resistance ground connection must be made for
adequate protection from the tank becoming momentarily energized by internalexternal faults or lightning surges. Ground the tank permanently by using the
ground pads provided near the bottom of the tank.
MiniSubs designed for use on grounded wye system must have the neutrals solidly
grounded to the common neutral of the system prior to applying voltage to the
MiniSub.
4.3.2 Low Voltage Connections
Low voltage bushings through 600 V are supplied with NEMA standard hole
spacing and drillings. Lugs (if supplied with the MiniSub) may be stacked or
mounted on either side of the bushing spade. A minimum 2.5 cm (1”) air clearance
must be maintained between phase-to-phase and phase-to-ground live parts in all
applications (30 kV BIL). Cables should be supported so as not to allow the weight
of the cable to rest only on the bushing.
4.3.3 High Voltage Connections
REFER TO INSTRUCTION 44kV CABLE CONNECTORS
Connections must be made without placing undue mechanical stress on the bushing
terminals. Conductors should be securely fastened in place and supported properly,
with allowance for expansion and contraction.
4.4 Testing
All completed installations must be field tested prior to energizing in accordance with
applicable ANSI/IEEE/NEC/CSA standards and local governing code authorities. To
ensure personnel safety and to maintain the Power Systems Technology products
warranty, an appropriate field Hi Pot test must be conducted.
12
Installation and Operation Manual
5.0 OPERATION AND MAINTENANCE
5.1 Operation
MiniSubs are designed to operate at their rated kVA as long as the ambient temperature
does not exceed 40 C (104 F) and does not exceed an average of 30 C (86 F) in any
24 hour period. Ambient temperatures below 20 C (68 F) may allow higher loading. In
addition, a standard MiniSub is designed to operate only if it is situated below 1000 m
(3300 ft) in elevation. MiniSubs designed for use over 1000 m will require larger external
electrical clearances and additional cooling capability.
MiniSubs are built and tested in accordance with the latest version of the applicable
standards and customer’s specifications. The MiniSub is only one piece of equipment in
the total electrical distribution system. Therefore, proper consideration must be given to
the protection of the MiniSub from system disturbances, such as over voltages and over
currents. Coordination of the complete distribution system must be achieved for proper
operation of the MiniSub.
5.2 Maintenance
IF BROKEN PARTS, LEAKING FLUID OR OTHER POTENTIALLY
HAZARDOUS CONDITIONS ARE OBSERVED, REMOVE THE MINISUB
FROM SERVICE.
The purpose of this section is to offer guidelines for the frequencies of inspections and
maintenance, as well as suggested tests that can be performed.
It is recommended that a logbook be maintained to record readings and observations of
each MiniSub. Remember that high voltage is present on an energized MiniSub, and
proper safety precautions must be observed whenever you are working on this equipment.
MiniSubs are very reliable, but if they should fail, they may be out of service for a long
time. Proper maintenance of MiniSubs is not difficult, and does not take a great deal of
time over the life of the unit, but it can result in significantly lower life cycle costs.
The following pages contain rules for recording and performing maintenance on
MiniSubs. Each section is separated into two parts where applicable, Basic and
Suggested. The basic section covers the minimum necessary duties to perform in order
that the MiniSub will be properly maintained. The suggested duties section covers a full
range of data gathering which may prove very useful in identifying problems that may
take years to form. The suggested section ensures that very little is left to chance
especially for critical MiniSubs.
13
Installation and Operation Manual
5.2.1 Before Energization
After the MiniSub has been received, prior to the first energization, it is
recommended that dissolved gas in oil analysis be performed. This check provides
a benchmark for all future gas in oil tests performed throughout the life of the
MiniSub. Dissolved gas in oil tests are probably the most important and powerful
method available for protecting against incipient faults - the identification of
faults when they are small and have caused little or no permanent damage, before
they can grow into major problems.
5.2.2 TABLE OF MAINTENANCE
First Days
First week
BASIC MAINTENANCE
SUGGESTED MAINTENANCE



Liquid level gauge
Temperature
Check radiators with valves ( all
sections are close to being equally
warm)
Temperature
Liquid level gauge



Voltage (primary and secondary)
Current (overloading condition)
None

Oil analysis (Compare with the results
of before energization)
Take an oil sample to test for dielectric
strength and water content

If the MiniSub is in an
inaccessible place, the basic
checks may be made once every
two or three months
Oil analysis more frequently of
the MiniSub is operating in
extremely high temperature
and/or high loads or overloads.
Monthly


First six month


14
Installation and Operation Manual
BASIC MAINTENANCE
One year






2nd, 3rd and 4th
year

Every five years







SUGGESTED MAINTENANCE
Check for continuity of the MiniSub

tank to ground
Take an oil sample, to be tested
dielectric strength, water content and
power factor
Take an oil sample, to be tested for
dissolved gas in oil and compare it to
the tests performed before energization
and at six months. It is important to
remember that over time even a healthy
transformer produces « fault » gases,
and it is the trend in gas production that
is often more important than the
absolute values.
Perform insulation power factor tests on
the MiniSub per ANSI C57.12.90
Check terminations for any sag or
movement from the original installed
position.
Check condition of conection between
the switch and MiniSub to see that the
white connector is tight around the
inserts. (This should be done only when
the unit is de-energized).
Take an oil sample, to be tested for

dielectric strength and water content
Take an oil sample, to be tested for
dissolved gas in oil and compare it to
the tests performed before energization
and at six months.
Take an oil sample, to be tested for

dielectric strength, water content and
power factor
Clean up Lightning Arrester
Check for continuity of the MiniSub
tank to ground
Take an oil sample, to be tested for
dissolved gas in oil and compare it to
the tests performed before energization
and at six months.
Perform insulation power factor tests on
the MiniSub per ANSI C57.12.
Clean, prime and paint any corroded
areas on the MiniSub
None
None
None
15
Installation and Operation Manual
5.3 Insulating Fluids and Gas
Insulating fluids and gas play a major role in all liquid-filled MiniSubs. They provide
good performance and can help maintenance people detect and predict failures. Through
the use of proven analytical techniques, a well planned maintenance program can lead to
fault detection long before it escalates into a major failure.
Fluid in the transformer portion of the MiniSub acts not only as a coolant but also
as insulation. During normal operation, the fluid withstands thermal and electrical
stresses. These slowly degrade the fluid, which then loses its insulating property.
In extreme cases this can cause MiniSub failures.
5.3.1 Mineral Oil
An oil-filled MiniSub offers the best compromise between cost and performance.
It has excellent dielectric and cooling properties, but has the inherent weakness of
having the lowest flash point. Therefore, is restricted to outdoor installations or
installed within a special vault if used indoors.
Naphthenic oils have performed exceedingly well - often for periods in excess of
20 years - in all types of oil-cooled MiniSubs.
They are formulated to resist oxidation and sludge formation in service. All
brands of insulating oils have negative gassing tendencies, which help to prevent
the formation of hydrogen gas resulting from electrical breakdowns or discharges
in the transformer. This property provides an additional safeguard against
explosions or fire resulting from the accumulation of hydrogen gas. These oils
have excellent dielectric strength and power factor characteristics.
Depending on the intended application and required service life, insulating oils
are available with different low temperature performance characteristics and
oxidation inhibitor contents. These products do not contain any polychlorinated
biphenyls (PCBs).
 CLASS A TYPE 1 is a premium uninhibited (0.08% of antioxidant)
electrical insulating oil designed to meet the critical operation requirements of
most power transformers operating at ambient temperatures below -25°C (13°F). It meets the CSA C50 and ASTM D3487 specifications for viscosity
limit of 2500 cSt max. at -40°C (-40°F).
 CLASS A TYPE 2 is a fully inhibited (0.30% of antioxidant) electrical oil
that has the same low temperature performance characteristics for a Class A
with antioxidant added.
 CLASS B TYPE 1 is a higher viscosity uninhibited electrical oil which use
widely in distribution transformers. It meets the CSA C50 and ASTM D3487
specifications for viscosity limit of 4000 cSt max. at -40°C (-40°F).
16
Installation and Operation Manual
5.3.2 Envirotemp FR3® Fluid
Envirotemp FR3® fluid is a Fire Resistant soy based Fluid dielectric coolant
formulated for use in distribution transformers where its unique electrical, thermal
and safety properties are advantageous. FR3® fluid is non-toxic and readily
biodegradable. It is compatible with standard insulating materials. Envirotemp
FR3 fluid's fire point is 360ºC, providing even greater fire safety. Envirotemp
FR3 fluid is Factory Mutual Global Approved and UL® Classified as a LessFlammable fluid, making compliance with code and insurance requirements
easier.
For indoor applications, FR3® MiniSubs provide the proven performance of
liquid-filled design. Outdoor applications where enhanced safety is recommended
include close proximity to buildings, rooftop or vault installations.
® Registered Trademark of COOPER
5.3.7 Oil Analysis
Testing the oil is an inexpensive and reliable way of assessing the operating
condition of a MiniSub.
5.3.7.1. Typical Properties
The American Society for Testing Materials (ASTM) has developed a
series of tests to determine oil quality by determining the physical,
chemical and electrical properties. The major tests are: dielectric
breakdown, neutralization number, interfacial tension (IFT), color,
moisture content, specific gravity, sediment, power factor and PCB
content.
Some of these tests are very closely related. For example, IFT and
neutralization numbers go hand in hand. IFT determines the probability of
sludging occurring in a MiniSub’s insulating system. The neutralization
number measures the acidity of the oil, which is caused by oxidation. Low
IFT numbers indicate a probability of sludge formation and high acidity
indicates oil deterioration and the formation of acidic compounds, which,
in extreme cases, will also form sludge. Dielectric strength and water
content follow the same pattern. To be a good insulator, oil must retain
high dielectric strength. Dissolved water can lower the insulating
properties of oil, effecting the dielectric strength and increasing the risk of
flashover.
5.3.7.2 Gases dissolved in Insulating Fluid
The detection of certain gases generated in a liquid-filled MiniSub in
service is frequently the first available indication of a malfunction that
may eventually lead to failure if not corrected. The two principal causes
of gas formation within an operating MiniSub are thermal and electrical
disturbances. Arcing, corona discharge, sparking, severe overloading and
17
Installation and Operation Manual
overheating in the insulation are the causes of gas generation. Normal
operation will also result in the formation of some gases. Generated gases
can be found dissolved in the insulation fluid. The Dissolved Gas
Analysis (DGA) produced from a sample of fluid will give a status of the
Mini-Sub condition. However, interpretation of their significance is not a
science, but an art subject to variability. Their presence and quantity are
dependent on variables such as loading conditions, location, temperature
of the vault and even the sampling procedure.
The interpretation of Gas Analysis refers to various diagnostic techniques
such as Dornenburg ratios, Rogers ratios, Duval and IEC. For more
details, please refer to the following guides:
IEEE C57.104
Guide for the Interpretation of Gases Generated in
Oil-Immersed transformer.
IEEE C57.106
Guide for Acceptance and Maintenance of Insulating
Oil in Equipment.
IEEE C57.111
Guide for Acceptance of Silicone Insulating Fluid and
Its Maintenance in transformer.
18
Installation and Operation Manual
5.4 Fuse Replacement Procedure
The fuses in the MiniSub are oil immersed Bay-O-Net® type. Access to the fuses is
blocked by a metal door, which can only be accessed by placing the correct key into the
interlock and releasing the door and allow access. To obtain the key the SF6 switch must
be in the off position (SEE SWITCH OPERATION SECTION). After proper visual
inspection of the switch to determine that all three switch blades are in the open position,
the key may be rotated in the lock and removed. The switch is now locked in the open
position.
With the door open and the 3 fuse holders exposed, the loophole in the fuse is twisted or
pulled forward to unlock the holder and allow them to be removed upward on an angle.
Care should be given not put stress against the sides of the fuse and holder while replacing.
6.0 COMPONENTS AND ACCESSORIES
6.1 Bushings
MiniSubs are equipped with molded bushing wells in the transformer and switch.
The type and design of the bushing is coordinated with the impulse level of the
MiniSub to form an integrated insulation system. MiniSubs are shipped with the
bushings mounted in place.
6.2 Radiator(s)
Each panel consists of two plates seam-welded along the edges and mounted on a header at
the top and the bottom with a maximum of 36 panels to form a radiator. Our radiators will
withstand full vacuum and are pressure tested at 12 PSIG prior to installation.
6.2.1 Installation of removable radiators (if applicable)
Radiators and valves are TIG-welded and are interchangeable. Radiators should not
be fitted until the unit is in its permanent position. Carefully check for shipping
damage. Remove transit flanges and plastic inserts and check that the drain and
bleeder plugs are secure.
Lift radiators from pallet taking care to protect the panels from possible damage.
Use the two lugs at the top for lifting and if necessary the single lug at the bottom to
stabilize the radiator (Using the two lugs will maintain balance on the radiator).
Retain the gasket shipped with the radiator for re-assembly. Tighten down on the
gaskets. Install radiator support angles and tie bars if supplied. After installation is
completed open bleeder plug and then slowly open main radiator valves and allow
oil to fill radiator before replacing bleeder plug. Top off main unit after filling
radiators.
19
Installation and Operation Manual
To remove a radiator, close the radiator valve, drain the liquid from the drain plug
and reverse the procedure described above.
6.3 Gaskets
Gaskets, which are used on liquid filled MiniSubs, are manufactured from a neoprene/cork
material, neoprene or BUNA-N.
6.3.1 Replacing gaskets in the field
On occasion, it may become necessary to replace a gasket in the field or to make up
a replacement gasket. Contact Power Systems Technology in order to ensure that
the replacement gasket material and thickness are the same as the present one.
6.4 Liquid Thermometer
This instrument has a sensing bulb, a rugged cast aluminum case housing for reading and a
control portion with up to four (optional) adjustable contacts in option.
As the temperature of the bulb increases, the liquid expands, causing an increase in
pressure, which is transmitted to the spiral bourdon tube. When the tube expands, a shaft
connected to the end of the tube rotates in proportion to the temperature being measured.
The pointer of the thermometer is connected directly to the shaft and also rotates to indicate
the correct temperature. When contacts are required, they are operated by cams mounted on
the same drive shaft as the pointer. Thus, the contact action is always consistent with
pointer movement.
Usually, the instrument is supplied with a thermal well and a quick disc disconnect cable
assembly. It is possible to remove the thermometer.
6.5 Off Load Tap Changer
The externally operated tap changer switch is designed for use in MiniSubs filled with oil,
R-Temp® or Silicone fluid. The Tap Changer is usually the only sophisticated mechanical
device in an otherwise stationary apparatus. Due to this fact, it is also responsible for the
majority of MiniSub outages and failures. Therefore it is very important to understand its
function, application and weak points.
Off load tap changers are located inside the MiniSub tank and utilize the MiniSub fluid for
dielectric strength. Most specifications ask for plus and minus 2 steps of 2.5 %, so that
switch has five positions. To reduce the operating current, the Tape Changer is normally
located on the HV side of the MiniSub. Off load tap changers are normally gang operated
by a handle outside the tank. The handle can be padlocked in any position. The indicator
plate permits easy identification of the position of the contacts.
DANGER - THE OFF LOAD TAP CHANGER MUST ONLY BE OPERATED
WITH THE MINISUB COMPLETELY DE-ENERGIZED.
20
Installation and Operation Manual
The contacts of the switch are slow moving and are only designed to select a position while
the MiniSub is de-energized. No current can be interrupted. After selecting the required tap,
the handle should be padlocked in position.
6.6 Dual Voltage Switch
The externally operated under-oil Dual Voltage switch is used to change the connection of
de-energized MiniSub windings between series and parallel to provide different common
MiniSub voltage ratios. It connects primary windings either in series for a higher winding
ratio, or in parallel for a lower winding ratio. Tri-voltage switches are also available.
DANGER - THE DUAL VOLTAGE SWITCH MUST ONLY BE OPERATED WITH
THE MINISUB COMPLETELY DE-ENERGIZED.
Externally operable switches eliminate many of the hazards associated with manual internal
tap changing. The switches are designed for use in distribution MiniSubs filled with
mineral oil, R-Temp® or Silicone fluid. Series multiple switches have a pad-lockable and a
hotstick operable handle, which provide greater leverage and positive indication of the
switch position.
6.7 Pressure Relief Valve
The pressure relief valve features a one-piece brass housing. A stainless steel spring,
factory selected to a pre-determined setting, is designed to release pressure build-up within
a sealed tank. A Viton O-ring seals the valve and a stainless steel pull ring is attached to
the valve shaft to facilitate manual pressure relief operation. These valves are designed to
operate under environmental conditions encountered on outdoor applications. The exhaust
port is protected by a "bug shield" cover, which inhibits foreign matter from entering the
valve body.
Operation:
When gas pressure in the MiniSub tank exceeds a specified limit, the valve automatically
compresses the spring, which drives the poppet, breaking the seal and venting potentially
dangerous gas pressure. With pressure reduced the valve automatically reseals itself to
prevent entry of outside air.
Operating pressure tolerance is +/- 2 PSI. The minimum flow rate is 35 scfm @ 15 PSIG.
Resealing occurs approximately 2 PSIG below operating pressure.
21
Installation and Operation Manual
6.8 Liquid Level Gauge
All MiniSubs are equipped with a magnetic type liquid level gauge, which provides visible
indication of the fluid level inside the MiniSub.
Installation:
The gauge is installed at the factory and is ready for operation. However, if a replacement
gauge is to be installed, first check the operation of the float by moving it over its entire
range. The movement of the indicating hand on the dial should correspond to the
movement of the float. Prior to installation of the gauge, the oil level must be lowered
below the mounting flange of the gauge. The gauge should be bolted rigidly to the
mounting on the MiniSub to ensure an oil tight gasket seal. The alarm contacts, when
fitted, should be checked for operation at the "Low" level point. Alarm contact leads are
connected as shown on the MiniSub wiring diagram.
Generally no maintenance is required for this device. If the gauge does become inoperative
the entire gauge should be replaced.
6.9 Bay-O-Net Fuse
The Bay-O-Net® fuse assemblies are used to protect MiniSubs and distribution systems.
They are designed for use in padmounted distribution transformers. The assemblies
combine the ease of hotstick operation with the safety of deadfront construction. In the case
on this MiniSub the fuses are key interlocked with the load break switch ahead requiring it
to be isolated before access to the fuses is permitted. UNDER NO CIRCUMSTANCES
SHOULD THE INTERLOCK SYSTEM BE DEFEATED OR THE FUSES BE
ACCESSED LIVE.
The Flapper Bay-O-Net® fuse assemblies include a flapper valve inside the housing,
which closes when the fuse holder is removed. This results in minimal oil spillage from the
MiniSub tank, which increases safety to line personnel during fuse change outs.
Current sensing, dual sensing, dual element and high ampere overload fuse links can be
used in a Bay-O-Net® fuse assembly. The assembly must be used in series with an
isolation link or current-limiting (CL) fuse to prevent the possibility of a high current fault
close-in, even after the fuse link has been replaced. Partial range CL fuses use the low
current clearing capabilities of the Bay-O-Net® fuse assembly while protecting against
high current internal faults that could cause disruptive equipment failure or upstream
system damage.
22
Installation and Operation Manual
In a two-fuse protection scheme with a current-limiting backup fuse, the secondary faults
and overload currents are cleared by the Bay-O-Net® fuse and high level faults are cleared
by the CL fuse. The two fuses are connected in series and are coordinated so that the
current-limiting fuse operates only upon internal equipment failure. If the Bay-O-Net®
fuse will not be used in series with a current-limiting fuse, an isolation link is required.
6.9.1 Isolation Link
Isolation links provide extra protection during refusing and switching operations
when used in series with a Bay-O-Net® fuse. They are not fuses and do not have an
interrupting rating. During a MiniSub failure, the isolation link will melt so that the
opened primary circuit of a faulted MiniSub cannot be re-energized by the line
crew.
6.9.2 Current Sensing Fuse Link
Current Sensing fuse link is used in Bay-O-Net® fuse assemblies to protect the
MiniSub from damaging currents and to protect distribution systems from failed
apparatus. A Bay-O-Net® fuse is ideal for use in a two-fuse protection scheme with
a CL backup fuse. The two fuses are connected in series, and are coordinated so
that the CL fuse operates only upon internal equipment failure.
6.9.3 Dual Sensing Fuse Link
Dual Sensing fuse link is used in Bay-O-Net® fuse assemblies to protect the
MiniSub from damaging currents and to protect distribution systems from failed
apparatus. Dual Sensing links sense not only secondary faults, excessive load
currents and MiniSub faults, but also MiniSub fluid temperature. They will limit
long-term MiniSub heating caused by overloads and high temperature
environments.
6.10 Lightning Arresters
Lightning arresters used in the MiniSub are elbow mounted distribution type. A separate
set of bushing wells is provided as an optional feature in the transformer tank wall for this
purpose. The arresters are connected to the MiniSub ground.
23
Installation and Operation Manual
6.11 Key Interlock (IF APPLICABLE)
An Interlock System is a series of safety devices applied in such a manner as to prevent or
allow operation of the equipment in a prearranged sequence only.
The interlock housings are made of heavy bronze. The locking bolt is 5/8” diameter
stainless steel or Everdur rod. The lock is a special 7-pin tumbler lock, simple and of a
rugged construction. The lock number is stamped on the face of the lock and also on the
key. This serial lock number, which applies to the lock and keys provided, is used as a
record for possible replacements and extension of the interlock system.
Each interlock is supplied with a single key. There is no duplicate of this key. The interlock
sequence is customized for each application.
6.12 Utility Metering
If so supplied, the Utility metering provision pan is mounted in the upper portion of the low
voltage compartment. The Current transformers are mounted directly on the phase
bushings with voltage and current leads cabled to the metering pan.
A meter socket is provided to allow the meter to be plugged in. For shipping purposes the
meter is shipped loose. Voltage leads are fused through a set of dead front fuse holders, and
the current leads are provided with shorting blocks. An optional meter reader’s door is
installed on the outside of the low voltage door with its own locking hasp.
6.13 Current Transformers (CT)
Most of the time, wiring from the current transformers to the control box is assembled at
the factory. If connections are to be made in the field use the following procedure:

Isolate all leads not in use to prevent them coming in contact with other leads or
grounded parts. Ground one side of the CT secondary unless such grounding will
interfere with the proper operation of the associated instruments. Normally a shorting
block is provided for metering applications

The secondary circuit of the current transformer must not be left open-circuited. It
must be closed either through or by a short-circuiting link provided. Remove the short
circuiting link after the burden has been connected and replace the short-circuiting link
before disconnecting the burden.

If the secondary of a current transformer is open when the primary is energized,
dangerously high voltages will exist between the secondary terminals. Though the
insulation may remain undamaged it will be necessary to demagnetize the CT before
normal operation is resumed.
24
Installation and Operation Manual
If the secondary of the current transformer has been accidentally opened when line current
was flowing in the primary a high peak voltage may have been developed in the secondary,
thus causing insulation damage. Ratio tests should be made on the installed CT if
symptoms indicate a short circuit condition in the winding.
7.0 REPLACEMENT PARTS
When ordering replacement parts or requesting information regarding an existing
MiniSub, be sure to give the kVA rating and the serial number. This information is on the
nameplate and on the supplied drawings. The list of components is on the Outline
drawing.
25
Installation and Operation Manual
8.0
WARRANTY
We warranty our products to be free from defects in material and factory workmanship.
When the product described herein is installed and used according to our instructions, the
original purchaser from us has the following warranty.
If any product of ours is found by us to be defective or not to be as ordered, and a written
claim is made to us, we will repair or replace the said product or issue credit for the same
at our option, to the original purchaser, C.I.F. factory.
This warranty terminates on the earliest of twelve months from date of installation or
eighteen months from date of shipment from our plant. There is no other representation,
warranty or condition in any respect, expressed or implied, statutory or otherwise, in
contract, tort, otherwise, other than the above, nor will we be liable in any way for
consequential damages, however caused, including damages arising out of our own
negligence or that of our servants, staff, agents or representatives.
We expressly disclaim any responsibility for expenses incurred in removing the said
defective product or installing or using any replacement product or for loss of time or use
of the said defective product, transportation costs, or any other indirect, incidental or
consequential damage or inconvenience.
This warranty does not apply if our product has been damaged due to improper
installation, alteration, abuse or misuse, accident, fire, flood or Act of God.
26