Survey
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
HVAC Guide Specifications Commercial Water-to-Water Heat Pump Unit with Puron® Refrigerant (R-410A) Size Range: 3 to 30 Tons, Nominal Carrier Model Number: 50PSW Part 1 — General 1.01 SYSTEM DESCRIPTION A. Heat pump units designed to operate with 20 to 110 F entering water temperature range. Units shall consist of high-efficiency scroll compressors and shall have dual independent refrigeration circuits. B. Units shall be individually packaged with wooden skid covered with protective corner posts and plastic stretch wrapping for maximum protection. 1.02 QUALITY ASSURANCE A. Basic unit shall be rated in accordance with ISO/ ASHRAE Standards and ETL listed. B. Units shall have insulation and adhesive which meet NFPA 90A requirements for flame spread and smoke generation, and assembled units shall be ETL listed to UL standard 1995. C. Units shall be factory tested under normal operating conditions at nominal water flow rates to assure proper operation of all components and safety devices. D. Units shall have ARI/ISO and ETL, US and Canada labels. Part 2 — Product 2.01 EQUIPMENT A. General: 1. Factory-tested and assembled single-piece water source heat pump units shall be factory wired, charged with HFC-410A, contain refrigerant-to-water heat exchanger, 4-way reversing valve, compressor, metering device, and all internal controls and safety devices. 2. Extended Range: a. Unit shall operate at entering water temperature of 20 to 110 F. b. Extended range adds closed cell isolation to internal water lines and provides insulation on suction side refrigeration tubing including refrigerant-to-water heat exchangers. B. Unit Cabinet: 1. Unit shall be constructed of heavy gage, powder-painted, galvanized sheet metal with removable service panels (3). 2. Unit shall have separate entrances for high and low-voltage electrical supplies. 3. Supply and return water connections shall be copper FPT fittings, terminating out the top of the unit to facilitate heading on multiple units side-by-side. 4. All interior surfaces shall be lined with 1/2-in. thick, 13/4 lb per cu ft density acoustic type fiberglass insulation. All fiberglass shall be coated and all edges shall be tucked under flanges. C. Compressors: Unit shall have heat pump duty, scroll compressors with internal and external isolation. D. Heat Exchangers: 1. Refrigerant-to-water heat exchanger shall be steel/copper tube-in-tube type rated for coaxial 625 psig refrigerant, 450 psig water-side pressures. Heat exchanger shall be powder coated for extra protection. 2. Optional steel/cupronickel refrigerant-to-water heat exchanger shall be used for open loop applications, or where water quality cannot be maintained as specified by manufacturer. E. Refrigerant Components: 1. Refrigeration circuit components shall include liquid line service valve, suction line service valve, reversing valve, a full charge of compressor oil, and a holding charge of refrigerant. 2. Thermostatic expansion valves shall be provided for refrigerant metering. Reversing valve shall be 4-way solenoid activated that defaults to heating. F. Solid-State Controls: Two light-emitting diodes (LEDs) shall be externally mounted to indicate compressor ON status and unit fault modes. G. Controls and Safeties: 1. Safety devices on all units shall include low-pressure sensor, high-pressure switch and low water temperature sensor. 2. Standard Complete C electronic control system(s) shall be a solid-state control system. Units utilizing electro-mechanical control systems shall not be acceptable. The control system microprocessor board shall be specifically designed to protect against building electrical system noise contamination, EMI and RFI interference. The control system shall interface with a heat pump type thermostat. The control system shall have the following features: a. Anti-short cycle time delay on compressor operation. b. Random start on power-up. c. Low voltage protection. d. High voltage protection. e. Unit shutdown on high or low refrigerant pressures. f. Unit shutdown on low water temperature. g. Option to reset unit at thermostat or disconnect. h. Automatic intelligent reset. Unit shall automatically restart 5 minutes after shutdown if the fault has cleared. Should a fault occur 3 times sequentially, then lockout will occur. i. Ability to defeat time delays for servicing. j. Light-emitting diode (LED) to indicate high pressure, low pressure, improper voltage, source freeze protection, load freeze protection, condensate overflow, and control voltage status. k. The low-pressure switch shall not be monitored for the first 120 seconds after a compressor start command to prevent nuisance safety trips. l. 24-v output to cycle a motorized water valve with compressor contactor. m. Unit Performance Sentinel (UPS). The UPS warns when the heat pump is running inefficiently. n. Source water coil low temperature sensing (selectable for water or antifreeze). o. Load water coil low temperature sensing. The Complete C control system also provides the upgraded 75 va control transformer with load side short circuit and overload protection via a built-in circuit breaker. 3. Optional Deluxe D electronic control shall have all the features of the Complete C control, with the following additional features: a. A removable thermostat connector. b. Random start on return from night setback. c. Minimized reversing value operation for extended life and quiet operation. d. Night setback control from low temperature thermostat, with 2-hour override initiated by a momentary signal from the thermostat. e. Dry contact night setback output for digital night setback thermostats. f. Ability to work with heat/cool (Y, W) or heat pump (Y, O) thermostats. g. Ability to work with heat pump thermostats using O or B reversing valve control. h. Single grounded wire to initiate night setback or emergency shutdown. i. Boilerless system control can switch automatically to electric heat at low loop water temperature. j. Control board shall allow up to 3 units to be operated from one thermostat without any auxiliary controls. k. A relay to operate an external damper. The control to be such that the damper will not open until 30 minutes after the unit comes back from Unoccupied mode. l. Fan speed selection at thermostat. m. A relay to restart a central pump or control a 24-v motorized water valve. n. Intelligent fan speed selection based upon thermostat demand and/or dehumidistat signal. This option also provides the upgraded 75 va control transformer with load side short circuit and overload protection via a built-in circuit breaker. 4. Carrier PremierLink™ Controller: This control will function with CCN (Carrier Comfort Network®) and ComfortVIEW™ software. It shall also be compatible with ComfortLink™ controllers. It shall be ASHRAE 62-99 compliant and Internet ready. It shall accept a CO2 sensor in the conditioned space and be demand control ventilation (DCV) ready. The communication rate must be 38.4K or faster. It shall include an integrated economizer controller. 5. LonWorks* Interface System: Units shall have all features of chosen control panel (either Complete C or Deluxe D) and the control board shall be supplied with a LonWorks interface board, which is LONMark* certified. This will permit all units to be daisy chained via a 2-wire twisted pair shielded cable. The following points must be available at a central or remote computer location: a. source leaving water temperature. b. load leaving water temperature. c. command of space temperature set point. d. cooling status. e. heating status. f. low temperature sensor alarm. g. low pressure sensor alarm. h. high pressure switch alarm. i. condensate sensor alarm. j. high/low voltage alarm k. unoccupied/occupied command. l. cooling command. m. heating command. n. fault reset command. o. itemized fault code revealing reason for specific shutdown fault (any one of 7). This option also provides the upgraded 75 va control transformer with load side short circuit and overload protection via a built-in circuit breaker. *Registered trademark of Echelon Corporation. H. Electrical: 1. A control box shall be located within the unit compressor compartment and shall contain a 75 va transformer, 24 volt activated, 2 or 3 pole compressor contactor, terminal block for thermostat wiring and solid-state controller for complete unit operation. Electro-mechanical operation WILL NOT be accepted. 2. Units shall be name-plated for use with timedelay fuses or HACR circuit breakers. 3. Unit controls shall be 24 volt and provide heating or cooling as required by the remote thermostat. I. Special Features: 1. Optional sound attenuation (mute) package consists of attenuation material applied to unit base pan and removable panels plus refrigerant muffler. Unit sizes 180 and 360 include sound blanket on both compressors to reduce noise. 2. Thermostat Controls: Accessory thermostat controls include: a. Programmable, multi-stage thermostat with 7-day clock, holiday scheduling, large backlit display and remote sensor capability. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. b. Programmable 7-day light-activated thermostat offers occupied comfort settings with lights on, unoccupied energy savings with lights off. c. Programmable 7-day flush-mount thermostat offers locking cover plate with tamper proof screws, flush to wall mount, dual point with adjustable deadband, O or B terminal, and optional remote sensor. d. Programmable 5-day thermostat offers 2-stage heat, 2-stage cool, auto changeover, 5-minute built-in compressor protection, locking cover included. e. Non-programmable thermostat with 2 heat stages, 2 cool stages, auto changeover, 5-minute built-in compressor protection, locking cover included. Fire-rated hose kits come with a fixed MPT on one end and a swivel with an adapter on the other end. Hose kits can be either stainless steel or galvanized. Ball valves (brass body) are for shutoff and balancing water flow. Valves are available with memory, memory stop, and pressure temperature ports. Y Strainers (bronze body) are “Y” type configuration with a brass cap and a stainless steel strainer screen. Maximum operating pressure rating of strainers is 450 psig. Solenoid valves (brass body) provide slow operation for quiet system application. Hose kit assemblies include a ported ball valve with pressure temperature (P/T) plug ports, flexible stainless steel hose with swivel and nipple. Return hose includes a ball valve, preset measure flow (gpm) with two P/T ports, flexible stainless steel hose with a swivel and nipple. Hot water generator coil and high temperature switch shall generate hot water within the unit. PremierLink™ accessories include air temperature sensors, CO2 sensors, communicating room sensors, and linkage thermostats. An Aquazone™ system control panel as specified in 50RLP Product Data (52500040) is available. A remote sensor for wall or duct mounted applications is available. A loop controller with six stages (2 stages for heating and 4 stages for heat rejection) is available.