Survey
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Standby power wikipedia , lookup
Integrating ADC wikipedia , lookup
Valve RF amplifier wikipedia , lookup
Audio power wikipedia , lookup
Power MOSFET wikipedia , lookup
Surge protector wikipedia , lookup
Index of electronics articles wikipedia , lookup
Radio transmitter design wikipedia , lookup
Rectiverter wikipedia , lookup
A NOVEL ON SUPPRESSION OF NEGATIVE SEQUENCE CURRENTS IN HIGH SPEED ELECTRIC RAILWAY BY USING POWER QUALITY COMPENSATOR. 1 .Sravani.p, 2. Kiran kumar.p 1 M.Tech Student of JNTUA,EEE Dept,Kuppam Engineering college,Chittor,A.P, India 2 Asst.prof, EEE Dept, JNTU,Anantapur,Kuppam Engineering College,Chittor, AP-India, Abstract- In order to suppress negative sequence currents harmonics for full bridge circuit of four quadrant converter in high speed electric railway, a method is proposed i.e., pulse width modulation. The four-quadrant converter of EMUs is single-phase full bridge circuit, which enables two-direction flow of electrical energy, and to ensure that the power factor of the net side to approximate. Each unit of the EMUs adopts parallel two level by the two groups of fourquadrant converters through the transformer winding, through which can further reduce the harmonic currents of the grid side. By switching devices appropriately through turn-on and turn-off control, the frequency of the converter input voltage us can be the same with that of the grid voltage. Four-quadrant converter can achieve unity power factor in traction and braking conditions. In regenerative braking condition, as to achieve the purpose of a stable DC voltage and unity power factor ,the phase between U and I should be 180 degrees. when the fourquadrant converter is running at the form of parallel two-level, the harmonic characteristics is similar with the double-time switch frequency. As a result, interlaced PWM converters can reduce the harmonic grid current with the same switching losses in the same frequency. Keywords-single phase full bridge circuit, crh5 emu’s ,railway static power conditioner, negative sequence currents, electric railway. I. INTRODUCTION In railways negative sequence currents become a signifificant problem , to solve this problem a power quality compensator is proposed. Which is constituted by RPC, two thyristor controlled reactors, two thyristor controlled filters. Normal filters are not reduces the negative sequence currents it only suppress the harmonics. CRH5 EMUs are produced by the Changchun Railway Vehicles Factory. The maximum operating speed of crh5 emu’s is up to 250km/h and they are running from Harbin to Beijing. CRH5 EMUs adopt 8 grouping, and may even be linked to run the two groups. EMUs have two proportionately independent main traction systems, one is constructed of three EMUs units and a trailer, the remaining is constructed of two units EMUs and two trailers.EMUs can withstand upto very low temperature. The bogies of crh5 emu’s made of Alstom Pendilino i.e., it has lite weight bogies. Harmonic Filters may be used to less intense, and in some cases eliminate power system harmonics. Non-linear loads like rectifiers, converters, home electronic appliances, and electric arc furnaces giving rise to extra losses i.e., harmonics in power equipment like tr motors, capacitors and transformers. They can also cause other serious problems, when obstructing with control systems and electronic devices. Placing filters near the harmonic sources and it can effectively decrease harmonics. Conventional filters are used for large, easily identifiable sources of harmonics, and designed to meet the demands of the actual applications. They are the most cost efficient in the view of eliminating harmonics. These filters contains capacitor banks with suitable tuning reactors and damping resistors. Active filters based on power electronic converters for small and medium size loads with high switching frequency, it may be a more aesthetically pleasing solution. Regulation of the power factor to increase the transmission capability and reduce transmission losses. Shunt capacitors are primarily used to improve the power factor in transmission and distribution networks, resulting in reduced network losses, improved voltage regulation and capable capacity use effectively. Figure shows a plot of terminal voltage versus line loading for a system that has a shunt capacitor installed at the load bus. Improved transmission voltage regulation can be obtained during heave power transfer conditions when the system consumes a large amount of reactive power that must be replaced by compensation. At the line surge impedance loading level, the shunt capacitor will reduce the line losses by more than 35%. In distribution and in industrial systems, it is common to use shunt capacitors to compensate for the highly inductive loads, thus acquiring decreased launch system losses and network voltage drop. II. STRUCTURE OF SYSTEM MMM Fig.2 shows the four-quadrant converter equivalent circuit. By switching devices appropriately through turn-on and turn-off control, the frequency of the converter input voltage us can be the same with that of the grid voltage Here, s1 u is the fundamental component of AC voltage, 11 i is the current fundamental component of 1 i,ω is the frequency of the grid voltage. The following formula is relative to the fundamental phase ⃗ N=𝑈 ⃗ S1 +RS⃗𝐼11 +jѠLS𝐼11 𝑈 ……………………………(1) Four-quadrant converter can achieve unity power factor in traction and braking conditions. As a result, U and I is in the same phase in traction condition. From formula (1) we can see the phase diagram in Figure 3 (a) U lags behind U. In regenerative braking condition, as to achieve the purpose of a stable DC voltage and unity power factor ,the phase between U and I should be 180 degrees, which is shown in Figure 3 (b) U lags behind U We can see that as long as properly control the amplitude and phase of 1 S U , it will be able to control the amplitude and phase of I Here, s1 u is the fundamental component of AC voltage, 11 i is the current fundamental component of 1 i,ω is the frequency of the grid voltage. The following formula is relative to the fundamental phase ⃗ N=𝑈 ⃗ S1 +RS⃗𝐼11 +jѠLS𝐼11 𝑈 ……………………………(1) Four-quadrant converter can achieve unity power factor in traction and braking conditions. As a result, U and I is in the same phase in traction condition. From formula (1) we can see the phase diagram in Figure 3 (a) U lags behind U. In regenerative braking condition, as to achieve the purpose of a stable DC voltage and unity power factor ,the phase between U and I should be 180 degrees, which is shown in Figure 3 (b) U lags behind U We can see that as long as properly control the amplitude and phase of 1 S U , it will be able to control the amplitude and phase of I III. SIMULATION RESULTS Before using the second loop filter see the negative sequence currents in the below waveform Fig(1): voltage and current waveforms at inverter side After using the second loop filter see the waveforms without negative sequence currents are shown below Fig.voltage and current waveforms at load side IV CONCLUSION This article studies the mathematical model and simulation of four-quadrant converter of CRH5 EMUs, specially studies the current distribution under the steady condition. Compared with the original “Shaoshan” series locomotives, EMUs use PWM rectifier, thus the power factor is close to 1 and the low harmonic content is obviously decreased, but the high-order harmonic content is slightly increased. In this paper, the preparation of the electric locomotives and EMUs simulation software, data interface can be called for other software to further analyze the spread law of the harmonic grid current in traction and the probability distribution of harmonic currents and so on. The effectiveness of the converter operation is verified for the harmonic supervision and cancellation when transient or time varying harmonics exhibit in power systems. The unique features of converter analysis, such as frequency identification without prior knowledge of frequency and the ability to identify damping factors, are useful to power system quality study. Further studies can be carried out for power quality study. Just as converter analysis was used with harmonic selective active filters, converter analysis may be applied to other measures to improve power quality. REFERENCES [1] Lu Fang, An Luo, Senior Member, IEEE, Xianyong Xu, Houhui Fang, “A Novel Power Quality Compensator for Negative sequence and Harmonic Currents in High-speed Electric Railway”, pp. 596-600, Nov. 2011 [2] Xiangzheng Xu, Baichao Chen, “Study on Control State and Development of Power Quality for Railway Traction Power Supply System,” Circuits, Communications and Systems, 2009. PACCS '09. Pacific-Asia Conference on 16-17, pp. 310-313, May 2009. [3] An Luo, Shuai Z.,Wenji Zhu, et al. “Development of Hybrid Active Power Filter Based on the Adaptive Fuzzy Dividing Frequency-Control Method,” IEEE Trans. Power Delivery, Vol.24, pp.424-432, Jan. 2009. Zhang Chen, Huang Jidong, “Conversion between the method of measurement of electrified railway radio disturbance in our country and the method stipulated by EN standard,” Environmental Electromagnetic, 2003. CEEM 2003. Proceedings. Asia-Pacific Conference on 4-7, pp. 596-600, Nov. 2003. [4] Zhao Wei, Tu Chun-ming, Luo An, et al. “A Novel Single-phase Hybrid Active Power Filter Applied to Electrical Railway System,” Proceedings of the CSEE, Vol 28, pp.51-56, July, 2008. [5] Zhuo Sun, Xinjian Jiang, Dongqi Zhu, et al. “A novel active power quality compensator topology for electrified railway,” IEEE Trans. On Power Electronics, vol.19, pp. 1036-1042, July, 2004. J.Cben, W.Lee, M.Chen, “Using a Static Var Compensator to Balance a Distribution System,” IEEE Transactions on Industry Applications, Vol l35, pp.298-304, April, 1999. [6] Zhang Chen, Huang Jidong, “Conversion between the method of measurement of electrified railway radio disturbance in our country and the method stipulated by EN standard,” Environmental Electromagnetic, 2003. CEEM 2003. Proceedings. Asia-Pacific Conference on 4-7, pp. 596-600, Nov. 2003. [7] Mochinaga, Y., Hisamizu, Y., Takeda, M., et al. “Static power conditioner using GTO converters for AC electric railway,” Power Conversion Conference, pp. 641-646, 2002. [8] G.F.Reed, M.Takeda, and I.Iyoda, “Improved power quality solutions using advanced solid-state switching and static compensation technologies,” in proc. IEEE Power Engineering Society Winter Meeting,1999, vol.2, pp.1132-1137. [9] O.Anaya-Lara and E.Acha,” Modelling and analysis of custom power systems by PSCAD/EMTDC”, IEEE Trans. Power Del., vol.17, no. 1,pp. 266-272, Jan.2002. [10] H.H.Zeineldin, E.F.El-Saadany,” Analysis of Harmonic Distortion and negative sequence “ IEEE Trans. On power Electronics,vol.16, pp138-207,Dec.2000 [11] Yu-Kang Lo, et.All., “Design In-Direct PI Controller and Adjust the Error Signal and fed back to the system.” IEEE Trans.Power Tech, vol.18, pp 266-272. [12]Shine-Tzong Ho, et.all., [13] . kanetkar.V.R.Dubey.G.K., “series equivalence/ Mochinaga, Y., Hisamizu, Y., Takeda, M., et al. “Static power conditioner using GTO converters for AC electric operation of current controlled boost-type single phase voltage source converters for bidirectional power flow, “power Electronics, IEEE Transactions on Vol.12,pp. 278-286,March 1997.