Download - Yokogawa

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Immunity-aware programming wikipedia , lookup

Decibel wikipedia , lookup

Power factor wikipedia , lookup

Nominal impedance wikipedia , lookup

Heterodyne wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Wireless power transfer wikipedia , lookup

Phone connector (audio) wikipedia , lookup

Three-phase electric power wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Islanding wikipedia , lookup

Power inverter wikipedia , lookup

Rectifier wikipedia , lookup

Electric power system wikipedia , lookup

Power over Ethernet wikipedia , lookup

History of electric power transmission wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Utility frequency wikipedia , lookup

Voltage optimisation wikipedia , lookup

Electrification wikipedia , lookup

Audio power wikipedia , lookup

Power engineering wikipedia , lookup

Amtrak's 25 Hz traction power system wikipedia , lookup

Buck converter wikipedia , lookup

Opto-isolator wikipedia , lookup

Power electronics wikipedia , lookup

Power supply wikipedia , lookup

Alternating current wikipedia , lookup

AC adapter wikipedia , lookup

Mains electricity wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Transcript
High-sensitivity
Current Probe
701917 DC to 50 MHz
701918 DC to 120 MHz
Low noise compact current probe for measuring low level currents
from 1 mA to 5 A. Best suited for design and verification applications
requiring high-sensitivity at low currents.
High-sensitivity (10x more sensitive than previous models)
In comparison with existing models (701928/701929/701932/701933), the
701917/701918 has 10 times higher sensitivity (Output rate: 1 V/A).
By using these probes, low current of about 1 mA can clearly be
observed.
Slim and light weight sensor head
The sensor head is smaller than existing models, making it easy to
use in narrow spaces.
Automatic zero-adjustment and demagnetization
Zero-adjustment can be done by simply pushing the button on the
termination box. Demagnetization can also be done by holding down
the DEMAG button for a quicker setup.
Supports DL/DLM/SL series
Adopted BNC connector as the output terminal. The power can be provided from the
probe power option on a DL/DLM/SL series instrument by the probe power supply.
Application
•LED driver, controller, power supply verification
•Evaluation of the embedded power supply
•Measurement of the power consumption of
a low voltage device (FPGA)
•Evaluation of the embedded component for
household appliances and car electronics.
High-Speed Data Acquisition Unit
LF 701917-01EN
701917
701918
Bandwidth*1
DC to 50 MHz
(−3 dB) (See Fig. 1)
DC to 120 MHz
(−3 dB) (See Fig. 1)
Rise time*1
7.0 ns or less
2.9 ns or less
Maximum continuous input range
10
Gain [dB]
Items
Gain [dB]
Specifications
0
10
0
−10
−10
−20
−20
5 Arms (See Fig. 2, for derating by frequency)
−30
−30
Maximum peak current
7.5 Apeak, non-continuous
−40
Output voltage rate*1
1 V/A
Amplitude accuracy*1 *2
±1% of reading ±1 mV typical,
±3.0% of reading ±1 mV
Noise*1
60 μArms typical, 75 μArms maximum (with a
30 MHz bandwidth measuring instrument)
Input impedance
See typical characteristics on Fig. 3
Temperature coefficient for
sensitivity*1 *3
Within ±2% of reading (input: 50 Hz, 5 Arms,
after Auto-zero adjustment, without a range
of 23±5˚C)
1
10
100
1k
1
10
100
1k
10k
100k
±12 V ±0.5 V
10M 100M 1G
701918
6
5
4
3
2
1
0
100
6
5
4
3
2
1
TA = 23˚C, Sine wave
1k
10k
100k
TA = 23˚C, Sine wave
1M
10M
100M
0
100
1G
Frequency [Hz]
1k
10k
100k
1M
10M
100M
1G
Frequency [Hz]
701918
701917
Operating temperature and humidity 0 to +40˚C, 80% RH or less (no condensation)
Fig. 2: Typical derating by frequency
Storage temperature and humidity −10 to +50˚C, 80% RH or less (no condensation)
Effect of external magnetic fields*4 20 mA or less
1M
Frequency [Hz]
Maximum input current [A]
Rated supply voltage
Maximum input current [A]
3.2 VA (within maximum input range)
External dimensions
Sensor side: 155 (W) × 18 (H) × 26 (D) mm
Termination side: 29 (W) × 83 (H) × 40 (D) mm
Weight
Approximately 250 g
1
Input impedance [Ω]
Sensor cable: 1.5 m, Power cable: 1.0 m
Input impedance [Ω]
5 mA or less
5 mm
Cable lengths
0.1
0.01
User’s manual, carrying case
0.001
100
Safety EN61010-2-032
EMC
−40
Fig.1: Typical frequency characteristic
Maximum rated power
Standards Compliance
10M 100M 1G
701917
10 ns typical
Accessories
1M
Frequency [Hz]
Propagation delay
Diameter of measurable conductor
10k 100k
1k
10k
100k
1M
10M
100M
1G
1
0.1
0.01
0.001
100
1k
10k
100k
1M
Frequency [Hz]
Models
100M
1G
Frequency [Hz]
701917
EN61326-1
*1: Accuracy: 23±3°C, thirty minutes after turning ON the power. When used with a digital
oscilloscope having an input impedance of 1 MΩ±1%.
*2: DC or 45 to 66 Hz. *3: This value is added to the amplitude accuracy.
*4: in a DC or 60 Hz, 400 A/m magnetic field.
10M
701918
Fig. 3: Typical input impedance
Related products
701934 Probe Power Supply
Model
Product
Description
701917
Current probe*
5 Arms, DC to 50 MHz, High-sensitivity
701918
Current probe*
5 Arms, DC to 120 MHz, High-sensitivity
*For power supplying, Probe power option for DL/DLM/SL series or Probe power supply are
necessary. There is a spatial restriction when connecting to the ScopeCorder modules.
Dimensions
29
Sensor cable length: 1500 mm
18
Top
83
Power Supply cable
length: 1000 mm
40
17
A power supply for current probes, FET probes, and differential probes. Probes
work with both DL probe power connectors and the 701934 probe power
supply. Supplies power for up to four probes, including large current probes.
Supports both AC100 V and 200 V power supply requirements.
• Number of power supply connectors: 4
• Output voltage: ±12 V±0.5 V
• Rated output current: +12 V: 2.5 A (the total value of four outputs)
−12 V: 2.5 A (the total value of four outputs)
• Operating temperature and humidity range:
0 to 40°C, 80% RH or less (no condensation)
• Storage temperature and humidity range:
−10 to 50°C, 80% RH or less (no condensation)
• Rated supply voltage: AC100 to 240 V (50/60 Hz)
• Maximum rated power: 190 VA
• External dimensions: Approx. 80 (W) × 119 (H) × 200 (D) mm
• Weight: Approx. 1.2 kg
Notice: 701934 does not support 701928 and 701929.
Side
NOTICE
26
Diameter of measurable
conductor: 5 mm
155
Unit: mm
● Before operating the product, read the user's manual thoroughly for proper and
safe operation.
YMI-KS-MI-SE01
YOKOGAWA METERS & INSTRUMENTS CORPORATION
Global Sales Dept. /Phone: +81-422-52-6237 Facsimile: +81-422-52-6462
E-mail: [email protected]
YOKOGAWA CORPORATION OF AMERICA
YOKOGAWA EUROPE B.V.
YOKOGAWA SHANGHAI TRADING CO., LTD.
YOKOGAWA ELECTRIC KOREA CO., LTD.
YOKOGAWA ENGINEERING ASIA PTE. LTD.
YOKOGAWA INDIA LTD.
YOKOGAWA ELECTRIC CIS LTD.
YOKOGAWA AMERICA DO SUL LTDA.
YOKOGAWA AUSTRALIA PTY. LTD.
YOKOGAWA MIDDLE EAST & AFRICA B.S.C(c)
Phone: +1-770-253-7000
Phone: +31-88-4641000
Phone: +86-21-6239-6363
Phone: +82-2-2628-3810
Phone: +65-6241-9933
Phone: +91-80-4158-6000
Phone: +7-495-737-7868
Phone: +55-11-5681-2400
Phone: +61-2-8870-1100
Phone: +973-17-358100
Subject to Change without notice.
Copyright © 2015, Yokogawa Meters & Instruments Corporation
[Ed: 01/b]
Printed in Japan, 510(KP)
Facsimile: +1-770-254-0928
Facsimile: +31-88-4641111
Facsimile: +86-21-6880-4987
Facsimile: +82-2-2628-3899
Facsimile: +65-6241-2606
Facsimile: +91-80-2852-8656
Facsimile: +7-495-737-7869
Facsimile: +55-11-5681-4434
Facsimile: +61-2-8870-1111
Facsimile: +973-17-336100
http://tmi.yokogawa.com/