* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project
Download section 264313 - surge protection for low
Opto-isolator wikipedia , lookup
Mercury-arc valve wikipedia , lookup
History of electric power transmission wikipedia , lookup
Electrician wikipedia , lookup
Voltage optimisation wikipedia , lookup
Ground loop (electricity) wikipedia , lookup
Power engineering wikipedia , lookup
Buck converter wikipedia , lookup
Switched-mode power supply wikipedia , lookup
Stray voltage wikipedia , lookup
Protective relay wikipedia , lookup
Electrical substation wikipedia , lookup
Three-phase electric power wikipedia , lookup
Mains electricity wikipedia , lookup
Earthing system wikipedia , lookup
Alternating current wikipedia , lookup
Ground (electricity) wikipedia , lookup
Industrial and multiphase power plugs and sockets wikipedia , lookup
Electrical wiring in the United Kingdom wikipedia , lookup
Copyright 2011 AIA
MasterSpec Premium
PRODUCT MASTERSPEC LICENSED BY ARCOM TO SSI, AN ILSCO COMPANY.
6/11
This Product MasterSpec Section is licensed by ARCOM to SSI, an ILSCO Company ("Licensee").
This Product MasterSpec Section modifies the original MasterSpec text, and does not include the
full content of the original MasterSpec Section.
Revisions made to the original MasterSpec text are made solely by the Licensee and are not endorsed by,
or representative of the opinions of, ARCOM or The American Institute of Architects (AIA). Neither
AIA nor ARCOM are liable in any way for such revisions or for the use of this Product MasterSpec
Section by any end user. A qualified design professional should review and edit the document to suit
project requirements.
For more information, contact SSI, an ILSCO Company, 15424 Flight Path Drive, Brooksville, Florida
34604;
Phone:
1-888-987-8877;
Website:
www.surgesuppression.com;
Email:
[email protected].
For information about MasterSpec contact ARCOM at (800) 424-5080 or visit www.MasterSpec.com.
SECTION 264313 - SURGE PROTECTION FOR LOW-VOLTAGE ELECTRICAL POWER
CIRCUITS
TIPS:
To view non-printing Editor's Notes that provide guidance for editing, click on MasterWorks/Single-File
Formatting/Toggle/Editor's Notes.
To read detailed research, technical information about products and materials, and coordination
checklists, click on MasterWorks/Supporting Information.
PART 1 - GENERAL
1.1
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
SUMMARY
A.
1.3
Section includes Surge Protective Devices (SPD) for the protection of electrical circuits from
the effects of externally generated lightning-induced currents, substation switching transients,
and internally generated transients resulting from inductive or capacitive load switching,
motors, drives.
DEFINITIONS
A.
In: Nominal Discharge Current.
SURGE PROTECTION
CIRCUITS
FOR
LOW-VOLTAGE
ELECTRICAL
POWER
264313 - 1
Copyright 2011 AIA
MasterSpec Premium
PRODUCT MASTERSPEC LICENSED BY ARCOM TO SSI, AN ILSCO COMPANY.
6/11
B.
MCOV: Maximum Continuous Operating Voltage.
C.
Mode(s), also Modes of Protection: The pair of electrical connections where the VPR applies.
D.
MOV: Metal Oxide Varistor; an electronic component with a significant non-ohmic currentvoltage characteristic.
E.
OCPD: Overcurrent Protective Device.
F.
SCCR: Short Circuit Current Rating.
G.
SPD: Surge Protective Device.
H.
VPR: Voltage Protection Rating.
1.4
ACTION SUBMITTALS
A.
Product Data: For each type of product.
1.
2.
1.5
Include rated capacities, operating characteristics, electrical characteristics, and furnished
specialties and accessories.
Copy of UL Category Code VZCA certification, as a minimum, listing the tested values
for VPRs, In ratings, MCOVs, type designations, OCPD requirements, model numbers,
system voltages, and modes of protection.
CLOSEOUT SUBMITTALS
A.
1.6
Maintenance Data: For SPDs to include in maintenance manuals.
WARRANTY
A.
Manufacturer's Warranty: Manufacturer agrees to repair or replace SPDs (product only) that fail
in materials or workmanship within specified warranty period.
1.
Warranty Period: [Five] [Fifteen] [Twenty-Five] <Insert number> years from date of
Substantial Completion.
PART 2 - PRODUCTS
2.1
GENERAL SPD REQUIREMENTS
A.
Comply with NFPA 70.
B.
Comply with ANSI/UL 1449.
C.
Comply with ANSI/UL 1283 if the SPD is a Type 2 device.
SURGE PROTECTION
CIRCUITS
FOR
LOW-VOLTAGE
ELECTRICAL
POWER
264313 - 2
Copyright 2011 AIA
MasterSpec Premium
PRODUCT MASTERSPEC LICENSED BY ARCOM TO SSI, AN ILSCO COMPANY.
D.
MCOV of the SPD shall be the nominal system voltage.
E.
SCCR: Equal or exceed 200 kA.
F.
In Rating: 20 kA
G.
VPR ratings should not exceed the values listed below for the applicable voltage:
Power Distribution System
120 V, 2W + ground
240 V, 2W + ground
120/240 V, 3W + ground
208Y/120 V, WYE 4W + ground
480Y/277 V, WYE 4W + ground
480Y/277 V, WYE 4W + HRG
600Y/347 V, WYE 4W + ground
240 V, DELTA 3W + ground
240 V, DELTA 3W (ungrounded)
480 V, DELTA 3W + ground
480 V, DELTA 3W (ungrounded)
2.2
L-N
700
1000
700
700
1200
1200
1800
L-G
700
1000
1500
1500
2500
2500
1800
1000
1000
1800
1800
N-G
700
1000
700
700
1200
1200
1800
6/11
L-L
1500
1500
2500
2500
4000
1000
1000
1800
1800
ACCEPTABLE MANUFACTURERS
A.
Basis-of-Design Product: Subject to compliance with requirements, provide SSI, an Ilsco
Company (www.ssipq.com); [Advantage] [Specified Series] [Surgency] or a comparable
product by one of the following:
1.
2.
3.
4.
5.
2.3
Advanced Protection Technologies Inc. (APT).
Current Technology Inc.
LEA International.
Liebert; a brand of Emerson Electric Co.
<Insert manufacturer's name>.
SERVICE ENTRANCE SPD
A.
Peak Surge Current Rating: The minimum single-pulse surge current withstand rating per phase
shall not be less than [300 kA] [200 kA] [100 kA] <Insert value>. The peak surge current
rating shall be the arithmetic sum of the ratings of the individual MOVs in a given mode.
B.
SPD Features and Options:
1.
2.
3.
4.
5.
6.
Integral Disconnect Switch: Optional if there is no provision for a dedicated 30 A
breaker.
Indicator Lights: One per phase for protection status.
Contacts: Form-C.
SPD Type: [Type 1][Type 2].
Alarm: Audible.
Additional Options: <Insert option>.
SURGE PROTECTION
CIRCUITS
FOR
LOW-VOLTAGE
ELECTRICAL
POWER
264313 - 3
Copyright 2011 AIA
MasterSpec Premium
PRODUCT MASTERSPEC LICENSED BY ARCOM TO SSI, AN ILSCO COMPANY.
2.4
6/11
EMERGENCY PANEL OR CRITICAL OPERATIONS POWER SYSTEMS (COPS) PANEL
SPD
A.
Peak Surge Current Rating: The minimum single-pulse surge current withstand rating per phase
shall not be less than [180 kA] [120 kA] [50 kA] <Insert value>. The peak surge current
rating shall be the arithmetic sum of the ratings of the individual MOVs in a given mode.
B.
SPD Features and Options:
1.
2.
3.
4.
5.
6.
2.5
Integral Disconnect Switch: Optional if there is no provision for a dedicated 30 A
breaker.
Indicator Lights: One per phase for protection status.
Contacts: Form-C.
SPD Type: [Type 1][Type 2].
Alarm: Audible.
Additional Options: <Insert option>.
BRANCH PANEL/PANELBOARD SPD
A.
Peak Surge Current Rating: The minimum single-pulse surge current withstand rating per phase
shall not be less than [120 kA] [80 kA] [100 kA] <Insert value>. The peak surge current rating
shall be the arithmetic sum of the ratings of the individual MOVs in a given mode.
B.
SPDs: Comply with UL 1449, Type 2.
C.
SPD Features and Options:
1.
2.
3.
4.
5.
6.
2.6
Integral Disconnect Switch: Optional if there is no provision for a dedicated 30 A
breaker.
Indicator Lights: One per phase for protection status.
Contacts: Form-C.
SPD Type: [Type 1][Type 2].
Alarm: Audible.
Additional Options: <Insert option>.
SPD ENVIRONMENTAL RATING
A.
Indoor Enclosures: The NEMA rating of the SPD should be suitable for the environment in
which it is being installed. [NEMA 1] [NEMA 4X] <Insert NEMA rating>.
B.
Outdoor Enclosures: The NEMA rating of the SPD should be suitable for the environment in
which it is being installed. [NEMA 4X] [NEMA 4X Stainless steel] <Insert NEMA rating>.
SURGE PROTECTION
CIRCUITS
FOR
LOW-VOLTAGE
ELECTRICAL
POWER
264313 - 4
Copyright 2011 AIA
MasterSpec Premium
PRODUCT MASTERSPEC LICENSED BY ARCOM TO SSI, AN ILSCO COMPANY.
6/11
PART 3 - EXECUTION
3.1
INSTALLATION
A.
Install in accordance with manufacturers installation instructions, applicable NEC codes, local
codes, and the requirements of the authority having jurisdiction.
B.
Install SPDs with conductors between suppressor and points of attachment as short and straight
as possible. Adjust circuit-breaker positions to achieve shortest and straightest leads.
C.
Use ILSCO® Cool Seal® connectors and splices when additional lead length may be needed.
Wire nuts are unacceptable. Do not exceed 36-inches (914-mm) combined lead length without
consulting a factory representative.
3.2
FIELD QUALITY CONTROL
A.
Perform the following tests:
1.
2.
If applicable, compare equipment nameplate data for compliance with drawings and
specifications.
Verify that electrical wiring installation complies with manufacturer's written installation
requirements.
END OF SECTION 264313
SURGE PROTECTION
CIRCUITS
FOR
LOW-VOLTAGE
ELECTRICAL
POWER
264313 - 5