Download 16264-Static uninterruptible power supply

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Utility frequency wikipedia , lookup

Power factor wikipedia , lookup

Electrical ballast wikipedia , lookup

Mercury-arc valve wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Electric power system wikipedia , lookup

Electrification wikipedia , lookup

Power over Ethernet wikipedia , lookup

Audio power wikipedia , lookup

Current source wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Electrical substation wikipedia , lookup

Stray voltage wikipedia , lookup

History of electric power transmission wikipedia , lookup

Power engineering wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Schmitt trigger wikipedia , lookup

Three-phase electric power wikipedia , lookup

Amtrak's 25 Hz traction power system wikipedia , lookup

Surge protector wikipedia , lookup

Voltage regulator wikipedia , lookup

Islanding wikipedia , lookup

Alternating current wikipedia , lookup

Rectifier wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Voltage optimisation wikipedia , lookup

Opto-isolator wikipedia , lookup

Solar micro-inverter wikipedia , lookup

Buck converter wikipedia , lookup

Power inverter wikipedia , lookup

Mains electricity wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Uninterruptible power supply wikipedia , lookup

Transcript
<Project Title>
PROJECT STANDARD SPECIFICATION
SECTION 16264 - STATIC UNINTERRUPTIBLE POWER SUPPLY
PART 1 - GENERAL
1.1
RELATED DOCUMENTS
A.
Drawings and general provisions of the Contract, including Conditions of Contract and
Division 1 Specification Sections, apply to this Section.
B.
Related Sections include the following:
1.
2.
3.
4.
5.
6.
C.
1.2
A.
The UPS Contractor shall become familiar with the Integrated Intelligent Building Solution
(I2BS) specification and shall comply with all of the requirements of the I2BS specification
that are relevant to the UPS. In particular the UPS shall meet the requirements with regard
to software protocol and shall be able to output and receive data in a BACnet, LonWorks,
Modbus, OPC or EIB format. Coordinate with the I2BS Contractor to ensure that there is
full interoperability between the UPS and the I2BS.
SUMMARY
This Section includes 3 phase, on-line, static-type, uninterruptible power supply (UPS)
system installation, comprising the following:
1.
2.
3.
4.
5.
6.
7.
8.
1.3
Division 16, Section "Basic Electrical Materials and Methods".
Division 16, Section "Grounding and Bonding".
Division 16, Section "Conductors and Cables".
Division 15, Section “Building Management System (BMS), Instrumentation And
Controls - For Large Scale Projects”
Division 15, Section “Building Management System (BMS), Instrumentation And
Controls - For Small Scale Projects”
Division 16, Section “Integrated Intelligent Building Solution”.
Complete rectifier/charger-battery-inverter system with automatic static switch and
maintenance by-pass circuit.
Output panelboard.
Software and hardware as necessary for the transfer of data from the UPS to the
I2BS.
Input isolation transformer for UPS units rated at 80 kVA and above.
Power conditioner.
Interplant power and control cabling.
Connection of normal a.c. power from assigned terminals/switch/circuit breaker, as
shown on the Drawings.
Earthing system.
ABBREVIATIONS
A.
EMI: Electromagnetic interference.
B.
ELV: Extra Low Voltage
STATIC UNINTERRUPTIBLE POWER SUPPLY
16264 - Page 1/23
<Project Title>
PROJECT STANDARD SPECIFICATION
C.
I2BS: Integrated Intelligent Building Solution
D.
LCD: Liquid-crystal display.
E.
LED: Light-emitting diode.
F.
UPS: Uninterruptible power supply.
1.4
A.
SUBMITTALS
Equipment Data: Submit full technical data of equipment for approval including, but not
limited to, the following:
1.
2.
3.
B.
Manufacturers’ catalogs, detailed description, Standards to which the UPS complies,
dimensions and weights, system operation, operating characteristics, methods of
operation, protective and control provisions, heat losses, ambient conditions and
limitations on electronic components etc. beyond which such components may suffer
partial or permanent damage.
Batteries.
Point-wise compliance statement to the specifications, duly signed by the
manufacturer/ manufacture’s authorized representative and the contractor.
Shop and Construction Drawings: Submit Drawings for approval including, but not limited
to, the following:
1.
2.
3.
4.
5.
Plans and front and side elevations, with indication of built-on control and indicating
devices and instruments, exact dimensions and weights, cabling etc.
One-line diagram with ratings of each piece of equipment, cabling, grounding etc.
Control and elementary diagrams, wiring diagrams and the like.
Installation and mounting details.
Batteries arrangement and mounting details.
Rating/derating selection calculations to be included
C.
Manufacturer Certificates: Signed by manufacturers certifying that they comply with
requirements.
D.
Certificate of origin.
E.
Qualification Data: For firms and persons specified in "Quality Assurance" Article.
F.
Test Certificates: Submit type test and routine test certificates. System is to undergo a
functional and load test program approved by the Engineer, and is to undergo a minimum 72
hours 'burn-in' test, under site simulated conditions, prior to shipment.
G.
Field Test Reports: Indicate test results compared with specified performance requirements,
and provide justification and resolution of differences if values do not agree.
H.
Maintenance Data: For UPS units to include in maintenance manuals specified in Division 1.
Include the following:
1.
Lists of spare parts and replacement components recommended being stored at
Project site for ready access.
2.
Detailed operating instructions covering operation under both normal and abnormal
conditions.
STATIC UNINTERRUPTIBLE POWER SUPPLY
16264 - Page 2/23
<Project Title>
PROJECT STANDARD SPECIFICATION
I.
Warranties: Special warranties specified in this Section.
J.
As-Built (Record) Drawings: At Project close-out, submit Record Drawings of installed
UPS, in accordance with requirements of the Specification, Division 1.
K.
System Graphics: Provide system schematics in AutoCAD format indicating the location of
monitoring and control points. Coordinate with the I2BS Contractor. These schematics
shall be provided within 30 days of the successful completion of the pre-acceptance tests at
the test facility as detailed below.
L.
The UPS Contractor shall provide all BACnet object IDs or Lon SNVT IDs or Modbus IDs
or OPC object IDs, as applicable, to the I2BS Contractor. Provide all necessary
documentation regarding the data Objects that are to be communicated to the I2BS. The
documentation shall be of such a standard that the DCA-EP/DWC’s staff that has received
training on the operation of the I2BS shall be able to add, delete and amend information that
is to be exchanged between the UPS and the I2BS without a requirement for additional
information or assistance from the MEP Contractor.
1.5
QUALITY ASSURANCE
A.
Installer Qualifications: Experienced installer who is an authorized representative of UPS
manufacturer for both installation and maintenance of units required for this Project.
B.
Local Representative: Provide evidence that proposed equipment manufacturer has a locally
established and authorized organization which can be called upon for professional advice and
maintenance as may be required, and which can immediately supply spare parts to support
day to day and emergency maintenance requirements. Failure to satisfy Engineer may
disqualify a manufacturer.
1.
C.
D.
Standards: Installation is to comply with relevant IEC, BS, EIA, NEMA and IEEE or equal
Standards. Materials and components are to be manufacturer's latest design, and Standards
used are to be approved prior to manufacture. Radio frequency interference (RFI) suppression
is to be in accordance with CISPR and IEC 50091-2 recommendations.
Standards: Installation is to comply with the following standards:
1.
2.
3.
4.
5.
E.
1.6
Service Center: UPS system manufacturer maintains a local service center within
160 km of Dubai airport, capable of providing training, parts, and emergency
maintenance and repairs at the Project site within 2 hours maximum response time,
round-the-clock, 7 days.
IEC 60623
Vented nickel cadmium prismatic rechargeable single cells.
BS 5634
Testing potassium hydroxide used in alkaline cells.
BS 4417
Specification for semiconductor rectifier equipments.
IEC 60410
Selection Criteria for sample collection from different cell lots.
IEEE Standard 1115-1992 Recommended Practice for Sizing Nickel-Cadmium
Batteries for Stationary Applications.
Products shall be sourced either directly from manufacturer, or from authorized
agent/representative.
DELIVERY, STORAGE, AND HANDLING
STATIC UNINTERRUPTIBLE POWER SUPPLY
16264 - Page 3/23
<Project Title>
PROJECT STANDARD SPECIFICATION
A.
Deliver equipment in fully enclosed vehicles after specified environmental conditions have
been permanently established in spaces where equipment is to be placed.
B.
Store equipment in spaces with environments controlled within manufacturers' ambient
temperature and humidity tolerances for non-operating equipment.
1.7
PROJECT CONDITIONS
A.
1.8
Temperature limits within which equipment is to be designed to operate are +10 to +40 deg.
C (50 to 104 deg. F) at 100 percent rated output. Equipment is to be capable of operating up
to 55 deg. C (131 deg. F) ambient conditions with derating factor of 1.25 percent per deg. C
over 40 deg. C (104 deg. F).
WARRANTY
A.
1.9
Provide 2 years warranty from the date of installation for the equipment specified in this
Section.
EXTRA MATERIALS
A.
Spare Parts List: Provide spare parts that match the product installed and packaged with
protective covering for storage and identified with labels describing contents, as per the
attached list (Annexure 1) at the end of this section.
B.
Tools and Instruments: Provide tools and instruments required for normal routine inspection,
testing, operation and general maintenance, as recommended by the manufacturer and as a
minimum as per the attached list at the end of this section.
1.10
A.
MAINTENANCE SERVICE
Maintenance Contract: Obtain an undertaking by the equipment manufacturer and his
authorized local representative to provide an annual maintenance contract, available after
substantial completion of the work, covering routine service and emergency service by
trained employees, and to ensure supply of necessary standard spare parts.
PART 2 - PRODUCTS
2.1
A.
2.2
A.
STANDARD COMMERCIAL PRODUCTS
Refer to Division 1 Section 01600, paragraph 2.1
SYSTEM DESCRIPTION
System is to be of the programmable type, microprocessor based with CPU and memory
capabilities for storage of alarms, faults, status change, etc. The UPS shall permit setting
parameters for the environment and type of usage to be specified by the Engineer. UPS is to
be of the self-diagnostic type, equipped with a self-test function to verify correct system
STATIC UNINTERRUPTIBLE POWER SUPPLY
16264 - Page 4/23
<Project Title>
PROJECT STANDARD SPECIFICATION
operation. The self-test shall identify the parts of the UPS requiring repair in case of a fault.
The system shall be provided with multi-password levels to limit access to software and data.
B.
General: System is to be interposed between normal a.c. power supply and critical load, to
secure a minimum period of continuity of no-break battery back-up for 15 minutes unless
otherwise shown on the Drawings, in case of failure of normal a.c. supply and maintain
output voltage, frequency and phase deviation within specified tolerances.
C.
System is to be [non-redundant][internally (50 percent) redundant (for 3-50 percent
units or chains)][internally 100 percent dual redundant with common battery (for 2-100
percent units or chains)][externally redundant which implies 2 complete UPS units with
2 sets of batteries operating in parallel]. UPS is to be maintained (continuously supplying
load through the inverter), with automatic no-break transfer to or retransfer from alternate
source (bypass) in case of failure or overload on rectifier- battery-inverter system.
D.
Normal a.c. power supply will be available from one protected source fed from either normal
a.c. network or from a.c. Characteristics of output of generator set (when provided) and UPS
system are to be coordinated for best results. Study and advise on special requirements of
generator characteristic output and stability.
E.
System Redundancy: System is to have parallel units interconnected so that normal a.c.
power feeds more than one rectifier/charger in parallel on a common d.c. bus, which in turn
feeds floated battery and more than one inverter in parallel, to give required power output at
critical load. Load sharing circuits are to ensure real and reactive load sharing and provide
reverse power protection between parallel units. Full rated capacity of UPS, in case of failure
of one of the rectifiers or one of the inverter units is to be equally shared by other healthy
units without overloading these units or disturbing operation. Separate filters are to be
provided for each rectifier/charger unit separately.
F.
System overall efficiency is not to be less than 92 percent at full load and [Insert Efficiency]
percent at half load.
G.
Noise level of complete assembly is not to exceed 65 dB(A) at 1.0 m distance anywhere
within UPS room, as per ISO 3746.
2.3
INTERFACE TO THE I2BS SYSTEM
A.
The UPS shall interface to the I2BS. Central monitoring and control of the UPS shall be
provided at the I2BS workstations in the Passenger Terminal Control Centre. This shall be
accomplished via the I2BS. . It is required that all the UPS monitoring and control functions
shall all be available at the I2BS workstation at the control centre in the Passenger Terminal
so that it shall not be necessary to be at the UPS location in order to implement these
monitoring and control functions.
B.
The UPS Contractor shall provide a BACnet, LonWorks or Modbus interface to a Network
Interface Unit that shall be provided by the I2BS Contractor. The I2BS shall provide
Management Level functions for the UPS. The interface shall be set up so as to provide, at
minimum, the following monitoring and control points:
1.
Bypass Voltage X-Y
2.
Bypass Voltage Y-Z
3.
Bypass Voltage Z-X
4.
Bypass Voltage X-N
STATIC UNINTERRUPTIBLE POWER SUPPLY
16264 - Page 5/23
<Project Title>
PROJECT STANDARD SPECIFICATION
5.
6.
7.
8.
9
10
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
33.
34.
35.
36.
37.
38.
39.
40.
41.
42.
43.
44.
Bypass Voltage Y-N
Bypass Voltage Z-N
Critical Voltage X-Y
Critical Voltage Y-Z
Critical Voltage Z-X
Critical Voltage X-N
Critical Voltage Y-N
Critical Voltage Z-N
Critical Current X
Critical Current Y
Critical Current Z
Critical Bus Frequency
Critical Bus kVA
Critical Bus kW
Critical Bus Capacity
UPM DC Voltage
UPM Battery Amperage
UPM Input Voltage X-Y
UPM Input Voltage Y-Z
UPM Input Voltage Z-X
UPM Battery Discharging
UPM Low Battery Warning
UPM Output Overload
UPM Fuse Failure
UPM Ambient over Temperature
UPM DC Ground
UPM Blower Failure
UPM Control Power Failure
UPM Overload Shutdown
SCC Output Overload
SCC Emergency off
SCC Load on Bypass
SCC Static Switch Disabled
SCC Output Over/under Voltage
SCC UPM Summary Alarm
UPS Common Fault
Incoming Power Fail
UPS on bypass
UPS Alarm
UPS in manual bypass mode
D.
The UPS Contractor shall prepare a list of all items of information that are available at the
UPS and shall present the information to the DCA-EP/DWC for the DCA-EP/DWC’s review.
The DCA-EP/DWC shall determine whether information in addition to that specified herein
shall be transferred from/to the UPS. The DCA-EP/DWC shall be able to amend, add and
delete information that is to be transferred from the UPS to the I2BS at any time up to
substantial completion.
E.
The UPS Contractor shall provide all BACnet object IDs or Lon SNVT IDs or Modbus IDs or
OPC Object IDs, as applicable, to the I2BS Contractor. Provide all necessary documentation
regarding the data Objects that are to be communicated to the I2BS. The documentation shall
be of such a standard that the DCA-EP/DWC’s staff who have received training on the
operation of the I2BS shall be able to add, delete and amend information that is to be
STATIC UNINTERRUPTIBLE POWER SUPPLY
16264 - Page 6/23
<Project Title>
PROJECT STANDARD SPECIFICATION
exchanged between the UPS and the I2BS without a requirement for additional information or
assistance from the UPS Contractor.
F.
The communication watchdog function at the I2BS shall send an “Are you there?” signal on
an operator determined frequency, which shall be set initially at 30 seconds, to the UPS and
the UPS shall respond within 5 seconds with an “I am here” signal. If the UPS does not
respond within 5 seconds the I2BS shall raise an alarm.
G.
The I2BS Contractor shall provide a schematic display of the points using the graphical user
interface. The UPS Contractor shall provide the appropriate graphics to the I2BS Contractor
in AutoCAD format. The graphics shall indicate the location of all monitored points. The
UPS Contractor shall meet with the I2BS Contractor within 4No. weeks of receiving
notification of award of contract to coordinate all interface requirements between the UPS and
the I2BS.
H.
The UPS Contractor shall provide a port at the UPS to enable the I2BS Contractor to establish
the interface with the I2BS.
I.
Coordinate the work with the I2BS Contractor so as to ensure that all requirements of the
above are attained and so as to ensure that all appropriate UPS related data is available in a
protocol compatible with the I2BS.
J.
Pre-Approval Testing of the UPS:
1. The data transfer between the UPS and the I2BS shall be demonstrated at a test facility
established by the I2BS Contractor in DWC prior to the award of contract to the UPS
Contractor. The tests shall be fully coordinated by the I2BS Contractor. The I2BS
Contractor shall liaise with each party concerned and shall ensure that the necessary test
facilities, including a data port to a 10-gigabit per second Ethernet network, are available
and operational. The IT & T/SCN Contractor shall provide the 10Gbps Data Network.
The I2BS Contractor shall provide an I2BS Applications Server, Operator Workstation
and a Network Interface Unit if required. It shall be conclusively demonstrated that the
UPS can communicate via the NIU with the I2BS Applications Server and vice versa. If
the test is successful a time shall be established that is acceptable to DCA-EP/DWC when
the interface can be demonstrated. This test must be completed within 60 days of the
issue of the letter of intent to award a contract for the UPS. Each party involved in the
test shall provide the applicable components necessary to perform the demonstration.
Ensure the presence of suitably skilled personnel at the tests. The components provided
for and the functions performed at the tests by each party shall be those that they are
required to provide for the actual installation. The testing of the interface between the
UPS and the I2BS Management Level shall verify, at minimum, that:
a. All points mapped from the UPS to the I2BS and vice versa are reported correctly at
the I2BS workstation.
b. All mapped points are identical with regard to value, the engineering units and
significant digits at both the UPS and the I2BS Management Level.
c. The communications watchdog is functioning correctly.
d. Communications speed between the I2BS and the UPS is satisfactory.
e. Communications between the systems are maintained following a power failure
without operator intervention.
f. All response times with respect to the annunciation of changes of state and equipment
alarms shall be shown to comply with the requirements detailed in these
specifications and in the associated I2BS specifications.
g. Watchdog functions.
2.
Subsequent to the Pre-Approval testing detailed above at the I2BS Test Facility, the I2BS
Contractor shall submit a report to DCA-EP/DWC detailing the results of the tests. If the UPS
Contractor cannot successfully demonstrate compliance with the requirements of this specification
STATIC UNINTERRUPTIBLE POWER SUPPLY
16264 - Page 7/23
<Project Title>
PROJECT STANDARD SPECIFICATION
and the I2BS specifications with respect to the exchange of information between the two systems
then the UPS Contractor shall not be awarded a contract.
2.4
SYSTEM OPERATION
A.
Under normal conditions inverter(s) are to be synchronized and phase locked to normal a.c.
supply. Upon loss of normal a.c. supply, battery is to continue supply of no-break power to
inverters, which then free-run on self- generated UPS frequency reference. Upon restoration
of normal a.c. supply, inverters are to re-synchronize to a.c. line, gradually (at slew rate), if
frequency and voltage deviation of normal a.c. supply is within preset limits specified.
B.
Automatic Transfer To Bypass: Static transfer switch is to automatically transfer critical (100
percent load from inverter to by-pass source (which is normal a.c. supply) if:
1.
2.
3.
4.
5.
C.
Inverter output voltage characteristics fall outside specified limits.
Critical load exceeds overload rating of UPS.
Over-temperature is sensed.
Manual (push button) command is given.
Transfer to by-pass mode is to be inhibited, and an alarm initiated if voltage,
frequency and/or phase shift of by- pass power is outside acceptable tolerances.
Re-Transfer To Inverter: Re-transfer of critical load from auto by-pass source to inverter
(UPS mode) is only to be possible under the following conditions:
6.
7.
8.
Inverter output voltage characteristics return to within specified tolerances.
Original load current reduces to within rated full load capacity of UPS.
Re-transfer selector switch is in automatic position.
D.
Lock-out feature is to inhibit re-transfer if by-pass source conditions are outside preset
tolerances or if UPS output and by-pass are not synchronized and phase locked or if UPS
output is not restored to normal conditions.
E.
Normal Power Restored: When normal power is restored following an outage,
rectifier/charger is to initially draw no power except for transformer in-rush current. After
approximately 15 seconds (walk-in time), input power requirements are to rise to power level
to drive critical load and recharge battery.
F.
Provide maintenance disconnecting switch fully rated to carry the full load input current of
the UPS.
G.
The LCS shall forward data to the I2BS within 1 seconds of a request from the I2BS or within
1 seconds of a status change for data on display at a workstation. The LCS shall initiate
action within 1 seconds of receiving a command from the I2BS.
2.5
G.
SYSTEM CHARACTERISTICS
Rectifier/Charger Input:
1.
2.
3.
4.
5.
Nominal input voltage: [Voltage]V, [single][3] phase, [2][4] wire, 50 Hz.
Voltage input variation: +10 percent, -15 percent from nominal.
Frequency: +/-5 percent from nominal.
Transformer exciting current in rush: less than 600 percent nominal current.
Power factor: 0.95 lagging smooth and stepless at full load and nominal input voltage.
STATIC UNINTERRUPTIBLE POWER SUPPLY
16264 - Page 8/23
<Project Title>
PROJECT STANDARD SPECIFICATION
6.
7.
8.
H.
Rectifier/Charger Output:
1.
2.
3.
I.
Total harmonic feedback: maximum 10 percent (total).
Current limiting: 115 percent max. of that required to operate inverters and charge
battery at full rated load, adjustment possible between 100 percent and 125 percent
Walk-in current in rush: 25 percent to 100 percent FLC in 15 seconds.
Float and equalize operation: Adjustable, automatic, compatible with battery.
Regulation: +/-1 percent max. from 0-100 percent load.
Ripple: +/-2 percent rms. (0 to 100 percent resistive load).
Static Inverters:
1.
2.
3.
Nominal net system power output rating: [Power Rating] with load power factor 0.7
lag to 0.9 lead.
Nominal output voltage: [Voltage] V, [single][3] phase, [2][4] wire, [50][60] Hz,
adjustable +/-5 percent of nominal.
Output voltage regulation:
a.
b.
4.
5.
6.
7.
8.
J.
A.
Phase displacement: 120 deg. (+/-5 deg.) at 100% load unbalance.
Output voltage waveform: 5 percent max. total harmonic, 3 percent max. single
harmonic.
Frequency stability: Normally synchronized to input line frequency over +/[1][2][5][6][other] adjustable range; free running at +/-0. Full battery voltage
variation, load and p.f. range; slew rate not to exceed 0.1 Hz/sec.
Dynamic output voltage tolerance sudden full load removal: [+10,-8][+/-10][other]
percent max. recovering application or to within 1 percent in less than
[100][40][other] milliseconds.
Over-load rating: 125 percent for 10 minutes, 150 percent for 60 seconds, 1000
percent for 5 seconds.
Automatic Static Transfer Switch:
1.
2.
3.
4.
5.
6.
7.
2.3
Balanced load: +/-[1][2][Other] percent (0 - 100 percent load)
Unbalanced load (3-phase output only): +/-[2][3][10][Other]% (at 100%
unbalance)
Transfer time: 150 microsecond (overlapping) maximum.
Total sensing and transfer/retransfer time: 2 milliseconds, maximum.
Retransfer mode: Automatic/inhibit (selectable).
Retransfer delay: 2 - 32 secs. in auto mode (selectable).
Transfer point: +/-10 percent of nominal output voltage (adjustable).
Retransfer point: +/-5 percent of nominal output voltage (adjustable).
Transfer inhibit point: +/-20 percent of nominal output voltage (adjustable).
COMPONENTS AND ACCESSORIES
Materials and Parts: Electronic devices are to be solid state, hermetically sealed. Indicator
lights are to be twin LED type, those denoting blown fuse conditions are to be seen by
operator without removing panels or opening cabinet doors. Power connections and remote
alarm and control wiring are to be accessible at terminal boards. Power semi-conductors are
to be fused. Metal surfaces including copper and aluminum heat sinks and busbars are to be
treated with permanent protective coating. Electro-mechanical power devices and relays are
STATIC UNINTERRUPTIBLE POWER SUPPLY
16264 - Page 9/23
<Project Title>
PROJECT STANDARD SPECIFICATION
to be vacuum impregnated, insulated for maximum operating voltage conditions, and
enclosed in dust-tight enclosures. Cables are to be fire resistant high temperature grade.
B.
UPS is to be provided with a port for a serial RS 485, RS 422 or Modbus interface so as to
permit communication between the I2BS and the UPS.
C.
Housing: Equipment is to be housed in a free-standing, well ventilated, totally enclosed
modular assembly with front accessible lockable doors, giving easy access for maintenance,
inspection and adjustments, and with provisions for handling and lifting during and after
installation. Enclosures are to be suitable for industrial, tropical environments, protection IP
[20][21][other] to IEC 60947-1, of galvanized sheet steel construction treated against
corrosion and with light grey RAL7032 baked paint or epoxy finish to approved standard.
D.
Sub-assemblies and components are to be mounted on pull- out and/or swing-out trays, of the
plug-in type where possible. Where it is not possible to mount components in pull-out or
swing-out trays, they are to be easily accessible inside the enclosure. Assemblies shall be
replaceable without requiring any adjustments or settings in the UPS. Modular design shall
be provided.
E.
Ventilation: Units rated over 5 kVA, an integral, forced-air, cooling system is to be provided
in each UPS module to remove dissipated heat efficiently, and ensure components operate
within environmental ratings. Air is to enter bottom of cabinet through replaceable filters,
and exhaust through the top. At least 2 fans are to be provided for ventilating each enclosure.
No degradation of performance is to occur in the event of a single fan failure. Temperature
sensors, mounted on semi-conductor heat sinks, are to initiate alarm if maximum working
temperature is exceeded.
F.
Rectifier/charger unit is to have mainline circuit breaker and 2 winding dry-type, Class H
insulated, class B temperature rise, with metallic electrostatic shielding, high efficiency (98
percent), regulating transformer and is to be automatic with soft start-up (walk-in) feature,
using silicon controlled rectifiers (thyristors) with control logic circuitry to control firing
angles to thyristors to suit power output requirements and protect against primary power
surges, lightning transients, under-voltage and over-voltage conditions. Output is to be
passed through LC filters to d.c. bus.
G.
Rectifier/charger unit is to be capable of supplying full load power to inverter, and to charge
the battery from a discharge condition to 95 percent charge within 10 times discharge period,
and maintain full charge at floating voltage until next operation. Charger current is to be
voltage regulated and current limited. Where three-phase supply is involved, rectifier is to be
at least 6 pulse type for UPS ratings up to 80 kVA, and 12 pulse type for 80 kVA ratings and
above.
H.
Inverter is to employ Insulated Gate Bipolar Transistors (IGBT) technology in 3 leg, pulse
width modulation (PWM) design with high frequency switching technique, and complete
with output transformer and filters. Inverter start-up is to be automatic, to reach full voltage
within milliseconds and deliver power to the load within 2 seconds. Inverter is to start at any
load including short-circuit. Output transformer is to be 2 winding dry-type, Class H
insulated, class B temperature rise, with metallic electrostatic shielding, high efficiency (98
percent).
I.
Inverter oscillator is to operate and maintain output frequency of inverter within specified
tolerances, and be capable of synchronization and phase-locking to normal power supply
frequency. When inverter is phase-locked to normal power supply, and latter fails, oscillator
is to automatically revert to free running state (quartz oscillator) and maintain specified
limits.
STATIC UNINTERRUPTIBLE POWER SUPPLY
16264 - Page 10/23
<Project Title>
PROJECT STANDARD SPECIFICATION
J.
Automatic static transfer switch is to be continuously rated at full load (100 percent FL),
hybrid type (make-before-break), solid-state transfer device with logic thyristor assembly
isolatable or completely withdrawable for maintenance. When signal to close switch is
initiated, thyristors are to instantaneously conduct power to prevent deviations and breaks in
load voltage outside specified tolerances.
K.
Maintenance By-Pass Switching: full externally mounted, in an IP 42 panel, manual (makebefore-break) by-pass switch is to allow load to be transferred to by-pass source without
interruption of output, and provide isolation of UPS and static switch during maintenance.
Test position is to permit testing of static switch while load is being fed from bypass power
circuit. Transfer inhibited warning circuit is to be provided to give an alarm indication in
case by-pass supply is beyond acceptable tolerances.
L.
Protection: UPS modules are to have built-in or inherent electronic current-limiting
protection against permanent self damage effective down to short-circuits. Fast acting,
current limiting devices are to protect against failure of any solid state component. Internal
failure in any UPS module is to cause immediate isolation from input and output by operation
of static interrupters or causing shut down of faulty module. Protection is to be provided
against, but is not limited to, the following:
1.
2.
3.
4.
5.
6.
Input over and under voltage and power line surges.
Output over voltage and voltage surges.
Sudden abnormal changes in output load conditions.
Short-circuits at output terminals.
Inverter and rectifier overcurrent.
Auxiliary Control Circuit Overcurrent.
M.
UPS Output Neutral: Designed to continuously carry twice the full load phase current.
N.
Input Filter Disconnection: UPS control system is to disconnect the input filters in case of
interruption of utility power supply failure while the UPS is operating at light loads (less than
25 percent).
O.
Battery: The battery shall be of the Nickel Cadmium pocket plate type complying with IEC
60623. The battery shall be designed for a life expectancy of 15 years under the conditions
specified in Section 16050.
Battery cases shall be indelibly marked with maximum and minimum electrolyte levels.
Translucent case of battery is preferred for visible from outside the electrolyte level and plate
condition.
The electrolyte shall be free from impurities and the Potassium Hydroxide used shall comply
with BS.5634. Dilution of the alkaline electrolyte and topping up of cells shall be carried out
using distilled water only.
Battery Cells shall be numbered consecutively. Numbering of cells shall be permanent or by
means of adhesive stickers. Stickers shall be of durable/alkaline – resistant material, which
shall be pasted on the battery racks subsequent to installation/commissioning at site.
Terminal cells shall be marked to indicate polarity as per IEC 60 623.
Cells shall be permanently marked with the following information as a minimum:
a)
b)
c)
Manufacturer’s reference number and code
Type of cell
Nominal Volts
STATIC UNINTERRUPTIBLE POWER SUPPLY
16264 - Page 11/23
<Project Title>
PROJECT STANDARD SPECIFICATION
d)
e)
f)
Nominal Capacity at 5 hour rate
Type of Electorlyte
Year of Manufacture
The electrolyte capacity and general design of the cells shall be such that inspection and
maintenance, including topping up of the electrolyte, shall be at intervals of not less than
twelve months. The Contractor shall be entirely responsible for carrying out and completing
the initial charge, test discharge and subsequent re-charge of the battery. The Contractor shall
provide resistors, instruments, leads, and the apparatus necessary for the initial charge, test
discharge and subsequent recharge of the battery.
The battery cells shall be of high rate of discharge (H) type complying to IEC 60623. The
final voltage shall be as per section 4 of IEC 60623. The AH capacity shall be determined on
the basis of the following consideration:
1.
A spare capacity of 25%
2.
An ageing factor of 1.25 shall be considered as a safety margin as per IEEE
Standard 1115-1992, Recommended Practice for Sizing Nickel-Cadmium
Batteries for Stationary Applications.
3.
Temperature de-rating factor shall be taken as per recommendations of the
battery manufacturer.
P.
Battery Cabinets: The battery enclosure shall match style and appearance of the UPS
enclosure, and shall be designed to be installed adjacent to the UPS. It shall be made of sheets
of material which shall be acid/alkaline resistant, with plastic insulating rails at points of
contact with battery cases. Cabinets are to be painted with electrolyte resistant paint. Cables
are to be rubber insulated electrolyte resistant type. The cabinet shall be provided with a
temperature sensor and connected to the charger in order to control the battery current
according to temperature. The cells shall be arranged so that each cell is readily accessible for
inspection and maintenance, and it shall be possible to remove any one cell without disturbing
the remaining cells.
Q.
Battery Cabinets: The battery enclosure shall match style and appearance of the UPS
enclosure and shall be designed to be installed adjacent to the UPS.
R.
Mimic Panel: UPS assembly is to include a mimic diagram with digital and LED displays,
indicating instruments and control devices, in true relative positions.
S.
Indications: Plain-language messages on a liquid crystal display.
T.
Local panel instruments are to include at least the following (digital readings):
1.
2.
3.
4.
U.
Inverter input voltmeter, measuring d.c. bus volts.
Battery ammeter, measuring charge/ discharge current.
A.C. voltmeter to measure inverter output voltage, normal supply voltage or system
output.
UPS output ammeter and frequency meter.
Local Panel Indicators are to include at least the following:
1.
2.
3.
System on battery supply.
Inverter phase locked to verify synchronization between inverter output and normal
a.c. supply input.
Static switch on normal a.c. supply (bypass mode).
STATIC UNINTERRUPTIBLE POWER SUPPLY
16264 - Page 12/23
<Project Title>
PROJECT STANDARD SPECIFICATION
4.
5.
6.
7.
V.
Local built-in controls are to include at least the following:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
W.
Inverter on/off.
Battery input circuit breaker.
Auto/manual reset-test switch.
Manual reset switch.
Hybrid switch transfer test push-button.
Re-transfer auto/inhibit selector switch to allow automatic re-transfer of load to
inverter after timed interval of normal operation and inhibit re-transfer of load to
inverter until hybrid switch is in auto-mode.
Battery automatic/equalize recharge timer, 0-30 hours adjustable, with
automatic/boost/equalize switch (accessible to maintenance personnel only and to be
used only with manufacturer's recommendation for type of battery specified).
Voltage and frequency adjustment controls with locking devices (accessible to
maintenance personnel only).
Indicator test/reset switch.
Control power supply isolator (accessible to maintenance personnel only).
Alarm test-accept-reset.
Local built-in alarms causing horn to sound, with tripping command if required, are to
include at least the following:
1.
2.
3.
4.
5.
6.
7.
8.
9.
X.
Static switch inhibited.
Over-temperature, indicating excessive temperature in heat sinks for transformers,
rectifer/charger and inverter (alarm to automatically transfer load to by-pass circuit).
Inverter output overload, indicating inverter output beyond specified rating failure of
any stage, d.c. bus earth fault, inverter output earth fault.
Event history display for the last 200 events.
Fan failure: Alarm only.
Over Temperature: Alarm with automatic transfer of load to by-pass after a safe
preset period.
D.C. Volts out of Limits: Alarm with indication.
Fuse Failure: Alarm.
Battery on Load/Disconnected: Alarm only.
Overloads: Alarm only with a trip command if prolonged, for each rectifier/inverter
unit.
Normal A.C. Supply Failure: Alarm only.
Hybrid Switch Operation to By-Pass Mode: Alarm only.
Low and High Output Voltage: Alarm only.
Remote panel control and indicators are to include at least the following:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
Audible alarm to sound for any alarm condition.
LED indicators for mains power available.
By-pass source available.
Inverter a.c. output available.
Inverter synchronized and phase locked.
Critical load connected to inverter.
Critical load connected to by-pass source.
Hybrid transfer switch inhibited.
High/low d.c. voltage.
Over-temperature.
Inverter output overload.
Alarm-indicator switch.
STATIC UNINTERRUPTIBLE POWER SUPPLY
16264 - Page 13/23
<Project Title>
PROJECT STANDARD SPECIFICATION
13.
14.
15.
2.4
Emergency system shutdown push-button.
Silence/test/reset switch.
Bypass circuit shall not have line filters.
UPS LOAD OUTPUT PANELBOARD
A.
Type: Separately mounted or built-in, sheet steel enclosed, generally in accordance with
Division 16 Section "Panelboards" of the Specification, MCB panelboard construction.
B.
Ratings: Main and branch circuit breaker selection and ratings are to be time-current
coordinated with inverter protection and overload requirements of critical loads to avoid
interruption of power to healthy circuits in case of faults. Provide 20 percent spare circuits
for additional loads.
2.5
POWER CONDITIONER
A.
Construction: Sheet steel encased, vented and fan cooled as necessary and is to include
combination of high leakage-reactance magnetic circuit and electronic sensing fast response
control circuits. Moving parts will not be allowed. Unit is to have manual automatic main
protective and disconnecting circuit breaker with pilot light. Conditioner is to consist of
high-grade core material and is to sustain heavy overloads (such as motor starting) without
undue heating.
B.
Protection: Power conditioner is to be protected with suppression against all types of
transients, spikes and power line noise, generally caused by lighting, switching, machine
operation, under-voltages or over-voltages caused by faults or fault-clearing devices and
voltage variations of mains input.
C.
Performance: Power conditioner is to regulate power line voltage to perform within the
following requirements:
1.
Nominal input voltage: [Voltage] V, [Frequency] Hz.
2.
Output rating: [Output] kW (0.7 lag to 0.9 lead PF).
3.
Nominal output voltage: [Voltage] V, [Phase] phase, [wire] wire.
4.
Input voltage variation: +/-20 percent.
5.
Output voltage adjustability range: +/-[5][other] percent.
6.
Noise level: Less than 55 dB at 1.0 m.
7.
Transient response time: 0.16 - 5 cycles.
8.
Total harmonics: Less than 5 percent.
9.
Attenuation of transients outside line voltage peak: 45:1 and better.
10. Overload capability: 1000 percent for 15 seconds.
11. Efficiency: Over 90 percent.
12. Regulation: +/-0.1 percent of nominal
output voltage (at any load and load
unbalance up to 33% in case of 3 phase units).
13. Ambient temperature: [Temperature] deg. C ([] deg. F) (average max.).
2.6
A.
SMALL UPS 5 kVA AND SMALLER
This Section includes Single-phase, on-line, static-type, uninterruptible power supply (UPS)
system installation of 5 kVA and smaller, comprising the following:
1.
Complete rectifier/charger-battery-inverter system with automatic static switch and
maintenance by-pass circuit
STATIC UNINTERRUPTIBLE POWER SUPPLY
16264 - Page 14/23
<Project Title>
PROJECT STANDARD SPECIFICATION
2.
3.
4.
5.
6.
7.
Remote monitoring section & necessary interface for data on faults and monitoring to
be connected to the Building Management Systems.
Power conditioner
Interplant power and control cabling
Connection of normal a.c. power from assigned terminals/switch/circuit breaker, as
shown on the Drawings
Earthing system connection.
Software and hardware as necessary for communication of data to the I2BS. The
interface requirements for the 5kVA and smaller UPS shall be the same as detailed
elsewhere in these documents.
B.
General: System is to be interposed between normal a.c. power supply and critical load, to
secure a minimum period of continuity of no-break battery back-up for 15 minutes in case
of failure of normal a.c. supply and maintain output voltage, frequency and phase deviation
within specified tolerances.
C.
System is to be non-redundant. UPS is to be maintained (continuously supplying load
through the inverter), with automatic no-break transfer to or retransfer from alternate source
(bypass) in case of failure or overload on rectifier- battery-inverter system.
D.
Normal a.c. power supply will be available from one protected source fed from normal a.c.
network.
E.
System overall efficiency is not to be less than 90 % at full load and 85 % at half load.
F.Noise level of complete assembly is not to exceed 50 dB (A) at 1.0 m distance anywhere within
UPS room.
G.
Rectifier/Charger Input:
1.
2.
3.
4.
5.
6.
7.
8.
H.
Nominal input voltage: 230 V, single phase, 2 wire, 50 Hz.
Voltage input variation: +10%, -15% from nominal.
Frequency: +/-5% from nominal.
Transformer exciting current in rush: less than 600 % nominal current.
Power factor: 0.92 lagging smooth and step less at full load and nominal input
voltage.
Total harmonic feedback: maximum 10 % (total).
Current limiting: 115% max. of that required to operate inverters and charge battery
at full rated load, adjustment possible between 100% and 125%.
Walk-in current in rush: 25% to 100% FLC in 15 seconds.
a.
Rectifier/Charger Output:
1.
2.
3.
Float and equalize operation: adjustable, automatic, and compatible with battery.
Regulation: +/-1% max. from 0-100% load.
Ripple: +/-2% rms. (0 to 100% resistive load).
I. Static Inverters:
1.
2.
3.
Nominal net system power output rating: [As stated in contract] with load power
factor 0.9- lag.
Nominal output voltage: 230 V, single phase, 2 wire, 50 Hz, adjustable +/-5% of
nominal.
Output voltage regulation:
STATIC UNINTERRUPTIBLE POWER SUPPLY
16264 - Page 15/23
<Project Title>
PROJECT STANDARD SPECIFICATION
a.
b.
4.
5.
6.
7.
8.
Balanced load: +/-2% (0 - 100% load)
Unbalanced load (3-phase output only): +/-10% (at 100% unbalance)
Phase displacement: 120 deg. (+/-5 deg.) at 100% load unbalance.
Output voltage waveform: 5% max. total harmonic, 3% max. single harmonic.
Frequency stability: Normally synchronized to input line frequency over +/-2 %
adjustable range; free running at +/-0. Full battery voltage variation, load and p.f.
Range; slew rate not to exceed 0.1 Hz/sec.
Dynamic output voltage tolerance sudden full load removal: +/-10 % max.
Recovering application or to within 1% in less than 100 milliseconds.
Over-load rating: 125% for 10 minutes, 150% for 60 seconds, 1000% for 5 cycles,
105% continuous.
J. Automatic Static Transfer Switch:
1.
2.
3.
4.
5.
6.
7.
Transfer time: 150 microsecond (overlapping) maximum.
Total sensing and transfer/retransfer time: 2 milliseconds, maximum.
Retransfer mode: automatic/inhibit (selectable).
Retransfer delay:
2 - 32 secs. in auto mode (selectable).
Transfer point: +/-10% of nominal output voltage (adjustable).
Retransfer point: +/-5% of nominal output voltage (adjustable).
Transfer inhibit point: +/-20% of nominal output voltage (adjustable).
K.
Materials and Parts: Electronic devices are to be solid state, hermetically sealed. Indicator
lights are to be LED type, those denoting blown fuse conditions are to be observable by
operator without removing panels or opening doors. Power connections and remote alarm
and control wiring are to be accessible at terminal boards. Power semi- conductors are to be
fused. Metal surfaces including copper and aluminum heat sinks and busbars are to be treated
with permanent protective coating. Electro-mechanical power devices and relays are to be
vacuum impregnated, insulated for maximum operating voltage conditions, and enclosed in
dust-tight enclosures. Cables are to be fire resistant high temperature grade.
L.
UPS is to be provided with a socket connection for a serial interface to be linked to a portable
PC, to a modem or to the I2BS system for communication with the UPS. It shall enable
interrogation of the UPS about status, faults, data stored, reprogramming, etc. Potential free
contacts shall be provided for common ‘Fault” alarm.
M.
Housing: Equipment is to be housed in a free-standing, well ventilated, totally enclosed
modular assembly with front accessible lockable doors, giving easy access for maintenance,
inspection and adjustments, and with provisions for handling and lifting during and after
installation. Enclosures are to be suitable for industrial, tropical environments; protection IP
20 to IEC 144, of galvanized sheet steel construction treated against corrosion and with light
gray RAL7032 baked paint or epoxy finish to approved standard.
N.
Sub-assemblies and components are to be mounted on pull- out and/or swing-out trays, of the
plug-in type where possible. Where it is not possible to mount components in pullout or
swing-out trays, they are to be easily accessible inside the enclosure. Assemblies shall be
replaceable without requiring any adjustments or settings in the UPS.
O.
Ventilation: Units rated are to be rated to project conditions specified in clause 1.7.
Temperature sensors, mounted on semi-conductor heat sinks, are to initiate alarm if
maximum working temperature is exceeded.
P.
Rectifier/charger unit is to be capable of supplying full load power to inverter, and to charge
the battery from a discharge condition to 95% charge within ten times discharge period, and
STATIC UNINTERRUPTIBLE POWER SUPPLY
16264 - Page 16/23
<Project Title>
PROJECT STANDARD SPECIFICATION
maintain full charge at floating voltage until next operation. Charger current is to be voltage
regulated and current limited. Where three-phase supply is involved, rectifier is to be at least
six-pulse type.
Q.
Inverter can employ Insulated Gate Bipolar Transistors (IGBT) or MOSFET technology in
three legs, pulse width modulation (PWM) design with high frequency switching technique,
and complete with output transformer and filters. Inverter start-up is to be automatic, to
reach full voltage within milliseconds and deliver power to the load within 2 seconds.
Inverter is to start at any load including short-circuit. Output transformer is to be two-winding
dry-type, Class H insulated, class B temperature rise, with metallic electrostatic shielding,
high efficiency (98%),
R.
Inverter oscillator is to operate and maintain output frequency of inverter within specified
tolerances, and be capable of synchronization and phase-locking to normal power supply
frequency. When inverter is phase-locked to normal power supply, and latter fails, oscillator
is to automatically revert to free running state (quartz oscillator) and maintain specified
limits.
S.
Automatic static transfer switch is to be continuously rated at full load (100% FL), hybrid
type (make-before-break), solid-state transfer device with logic thyristor assembly isolatable
or completely withdraw able for maintenance. When signal to close switch is initiated,
thyristors are to instantaneously conduct power to prevent deviations and breaks in load
voltage outside specified tolerances.
T.
Maintenance By-Pass Switching: Externally mounted, in an IP 20 panel, manual (makebefore- break) by-pass switch is to allow load to be transferred to by-pass route without
interruption of output, and provide total isolation of UPS and static switch for removal if
necessary, during maintenance. Test position is to permit testing of static switch while load
is being fed from normal power circuit through maintenance bypass. .
U.
Protection: UPS modules are to have built-in or inherent electronic current-limiting
protection against permanent self-damage effective down to short-circuits. Fast acting,
current-limiting devices are to protect against failure of any solid-state component. Internal
failure in any UPS module is to cause immediate isolation from input and output by operation
of static interrupters or causing shut down of faulty module. Protection is to be provided
against, but is not limited to, the following:
1.
2.
3.
4.
5.
6.
Input over and under voltage and power line surges.
Output over voltage and voltage surges.
Sudden abnormal changes in output load conditions.
Short-circuits at output terminals.
Inverter and rectifier overcurrent.
Auxiliary Control Circuit Overcurrent.
V.
UPS Output Neutral: Designed to continuously carry twice the full load phase current.
W.
Input Filter Disconnection: UPS control system is to disconnect the input filters in case of
interruption of utility power supply failure while the UPS is operating at light loads (less than
25%).
X.
Battery: High rate discharge, heavy duty, industrial, high impact resistant, clear plastic
encased, sealed lead- acid (gas recombination) type cells with automatically reclosing
explosion proof safety vents. Electrolyte specific gravity is not to exceed 1.25 when fully
charged at 25 deg. C. Ampere-hour rating is to be sufficient for emergency period specified
with all inverters operating at full rated output, to a discharge limit of not less than 1.65 V per
STATIC UNINTERRUPTIBLE POWER SUPPLY
16264 - Page 17/23
<Project Title>
PROJECT STANDARD SPECIFICATION
cell. Cells are to be normally maintained at 2.25 V per cell. Guaranteed life is not to be less
than 5 years, with a capacity drop down to not less than 80% under normal expected service.
Y.
Mimic Panel: UPS assembly is to include a mimic diagram with digital and LED displays,
indicating instruments and control devices, in true relative positions.
Z.
Indications: Plain-language messages on a liquid crystal display.
AA. Local panel instruments are to include at least the following (digital readings):
1.
2.
3.
4.
BB.
Local Panel Indicators are to include at least the following:
1.
2.
3.
4.
5.
6.
7.
CC.
Inverter input voltmeter, measuring d.c. bus volts.
Battery ammeter, measuring charge/ discharge current.
A.C. voltmeter to measure inverter output voltage, normal supply voltage or system
output.
UPS output ammeter and frequency meter.
“System on battery supply” indication.
“Inverter phase locked” indication to verify synchronization between inverter output
and normal a.c. supply input.
“Static switch on normal a.c. supply” (bypass mode) indication.
“Static switch inhibited” indication.
“Over-temperature”, indicating excessive temperature in heat sinks for transformers,
rectifier/charger and inverter (alarm to automatically transfer load to by-pass circuit).
“Inverter output overload”, indicating inverter output beyond specified rating failure
of any stage, d.c. bus earth fault, inverter output earth fault.
LED indicators for “Mains Power Available”.
Local built-in controls are to include at least the following:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
Inverter on/off.
Battery input circuit breaker.
Auto/manual reset-test switch.
Manual reset switch.
Hybrid switch transfer test push-button.
Re-transfer auto/inhibit selector switch to allow automatic re-transfer of load to
inverter after timed interval of normal operation and inhibit re-transfer of load to
inverter until hybrid switch is in auto-mode.
Battery automatic/equalize recharge timer, 0 - 30 hours adjustable, with
automatic/boost/equalize switch (accessible to maintenance personnel only and to be
used only with manufacturer's recommendation for type of battery specified).
Voltage and frequency adjustment controls with locking devices (accessible to
maintenance personnel only).
Indicator test/reset switch.
Control power supply isolator (accessible to maintenance personnel only).
Alarm test-accept-reset.
DD. Remote control and indicators are to include at least the following:
1.
Audible alarm to sound for any alarm condition.
Provide UPS identification plate with Approved details.
2.7
MASTER CLOCK INTERFACE
STATIC UNINTERRUPTIBLE POWER SUPPLY
16264 - Page 18/23
<Project Title>
PROJECT STANDARD SPECIFICATION
A.
The real time clocks shall be synchronised every 24 hours at minimum by the external
DWC Master Clock.
PART 3 - EXECUTION
3.1
INSTALLATION
A.
Install system components on 100 mm high concrete housekeeping bases. Cast-in-place
concrete, reinforcing as necessary, and formwork are specified in Division 3. Install systems
according to manufacturer's printed instructions, and arrange for manufacturer/supplier to
inspect and certify the installation.
B.
Equipment Bases: Ensure that concrete bases and foundations provided for installation of
equipment are constructed in accordance with approved shop and construction drawings and
equipment manufacturers' drawings and that holes for fixing bolts and provisions for passage
of cables etc. are provided as required.
C.
Built-In Items: Ensure that equipment supports, fixings and the like, and sleeves for passage
of feeders and cables which are to be built into concrete foundations, bases or building
structure are provided as and when required and that they are properly installed.
D.
Tools: Use only tools recommended by equipment manufacturers for installations,
particularly in making connections and adjustments.
E.
Supervision: Carry out equipment installation under the direct supervision of a qualified
technician, licensed by and trained at the factory. Final adjustments and putting into
satisfactory operation are to be made by a specialist delegated by the factory.
F.
Ensure installation in air-conditioned environment at all times.
3.2
A.
3.3
GROUNDING
Provide direct interference free grounding circuit “clean earth” in accordance with
Division 16 Section "Grounding and Bonding" of the Specification.
IDENTIFICATION
A.
Identify components and wiring according to Division 16 Section " Basic Electrical Materials
and Methods."
B.
Identify each battery cell and all UPS components individually.
C.
Provide UPS identification plate, of size 100mm X 100mm clearly stating UPS designation,
rating and “fed from” panel, fixed to independent of the UPS, on adjoining surface, at
suitable viewing location, to approval. Color shall be black lettering on white background and
fixed with steel “anchor” screws.
3.4
A.
BATTERY EQUALIZATION
Equalize charging of battery cells according to manufacturer's written instructions. Record
individual-cell voltages.
STATIC UNINTERRUPTIBLE POWER SUPPLY
16264 - Page 19/23
<Project Title>
PROJECT STANDARD SPECIFICATION
3.5
FIELD QUALITY CONTROL
A.
Electrical Tests and Inspections: In general the testing format shall be as per the NETA.
Perform tests and inspections according to manufacturer's written instructions and as listed
below to demonstrate condition and performance of each component of the UPS:
1.
Inspect interiors of enclosures, including the following:
a.
Integrity of mechanical and electrical connections.
b.
Component type and labeling verification.
c.
Ratings of installed components.
2.
Test manual and automatic operational features and system protective and alarm
functions.
3.
Test communication of status and alarms to remote monitoring equipment.
B.
Power Supply Output Disturbance: Provide microprocessor-based instrument, and monitor
and record power supply output disturbance of voltage and frequency when unit is loaded to
25 %, 50 % and 75 %. Instrument details and calibration certificates are to be submitted for
approval.
C.
Test Periods are to be prolonged (over 24 hours) and as requested by the Engineer, to verify
and obtain realistic voltage and frequency profile under any loading and switching conditions
within the criteria specified.
D.
Data logging is to include high and low average voltage, sags and surges, spikes and spike
bursts, dropouts, high and low frequencies etc. with printout and storage on cassette tape for
subsequent re-entry into instrument's memory for display or printout.
E.
Tests are to include loads from low-load to overload condition, and measurements of
temperature, heat losses, output voltage, wave shape, and harmonic content and frequency
stability.
F.
Retest: Correct deficiencies and retest until specified requirements are met.
G.
Record of Tests and Inspections: Maintain and submit documentation of tests and
inspections, including references to manufacturers' written instructions and other test and
inspection criteria. All test certificates to be individually identified with document number.
Include results of tests, inspections, and retests. Acceptable values of the measured
parameters, as per the relevant standards/regulations to be clearly identified in the test
certification.
H.
Product installed to be certified by manufacturers or authorized representative as “fit for
energisation”.
I.
Time between battery manufacture date and installation on site shall not exceed three months.
J.
Tests on site:
1.
2.
3.
4.
3.6
Battery discharge test on load up to deep discharge cut-off.
Load step response test.
Heat run tests.
Verification of all I/P, O/P, parameters like voltage, currents, power factor,
harmonics, voltage, currents, alarms, and protections.
DEMONSTRATION
STATIC UNINTERRUPTIBLE POWER SUPPLY
16264 - Page 20/23
<Project Title>
PROJECT STANDARD SPECIFICATION
A.
Participate in the Pre-Approval testing as detailed above.
Contractor.
B.
Engage a factory-authorized service representative to train the DCA-EP/DWC's maintenance
personnel to adjust, operate, and maintain the UPS.
1.
2.
3.
4.
Coordinate with the I2BS
Train the DCA-EP/DWC's maintenance personnel on procedures and schedules for
starting and stopping, troubleshooting, servicing, and maintaining equipment.
Review data in maintenance manuals. Refer to Division 1 Section "Operation and
Maintenance Data."
Schedule training with the DCA-EP/DWC, through the Engineer, with at least 7 days'
advance notice.
Provide service manual
END OF SECTION 16264
STATIC UNINTERRUPTIBLE POWER SUPPLY
16264 - Page 21/23
<Project Title>
PROJECT STANDARD SPECIFICATION
ANNEXURE 1
UPS
Sr
N
SPARES
o
1 Transformer By-pass
2 Capacitors (DC&AC)
3 Rectifier Module
4 SCRs for rectifier & State
switch
5 Relay solid State
Quantity
Sr.
No
1 of each type
1 of each type
1 of each type
1 of each type
41
42
43
5%
44
1 of each type
1 of each type
45
46
SPARES
Quantity
RC Board for SCR
Rectifier impulse PCB
Static Switch Impulse
PCB
High voltage interface
board
UPS Logic PCB
Micro Processor Display
PCB
Output side 3 phase
Transformers
Pulses + RC Static switch
PCB
Pulses + RC Rectifier
PCB
1 of each type
1 of each type
1 of each type
Quantity
One for each
UPS
One for each
UPS
One set
6
7
IGBT Module on converter
IGBT Module on inverter side
8
Dial codes on converter side
5%
47
9
Power side fuses (100 Amps to
400 Amps)
Control fuses
5%
48
5%
49
5%
12
13
Switch 32 A, 4 position, rotary
switch
Control Transformers
Converter side transformer
1 of each type
1 of each type
14
DC side choke
1 of each type
1
Tools
Fuse puller set
15
Converter inductor
1 of each type
2
Panel standard keys
16
Inverter choke
1 of each type
3
Diagnostic tool with main
software and necessary
hardware
17
18
Gate Drive mother Boars
Matched Pair GDD Board
1 of each type
1 of each type
4
UPS Battery maint.
toolkit
19
20
21
22
23
24
25
26
27
28
29
30
31
By-Pass Monitor Board
Micro Controller Board
Convector Controller board
Inverter boards
Battery Changer Board
Diode RC Network Board
Interface controller Board
RS 232 Option Board
RFI Capacitor Board
Display board
LED/LGD Front panel display
PCA Auxiliary PSU
Fan Axial phase 50 Hz 208/
240V
Output contactor 3 phase
1 of each type
1 of each type
1 of each type
1 of each type
1 of each type
1 of each type
1 of each type
1 of each type
1 of each type
5%
5%
5%
5%
10
11
32
STATIC UNINTERRUPTIBLE POWER SUPPLY
1 of each type
1 of each type
5%
1 of each type
1 of each type
1 of each type
One set
5%
16264 - Page 22/23
<Project Title>
PROJECT STANDARD SPECIFICATION
UPS
Sr
N
o
33
34
35
36
37
38
39
40
SPARES
440VDC
CURRENT Transducer
Axial fan
4 pate isolations (input& output
& By-pass)
DC power supply PCB
AC/DC Power Supply PCB
IGBT driver PCB
Rectifier Logic PCB
Inventer Logic PCB
Quantity
Sr.
No
SPARES
Quantity
5%
5%
5%
1 of each type
1 of each type
1 of each type
1 of each type
1 of each type
STATIC UNINTERRUPTIBLE POWER SUPPLY
16264 - Page 23/23