Download Annex (A), Technical Specifications

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Ground (electricity) wikipedia , lookup

Power engineering wikipedia , lookup

Rectifier wikipedia , lookup

Stray voltage wikipedia , lookup

Opto-isolator wikipedia , lookup

Buck converter wikipedia , lookup

Electrical substation wikipedia , lookup

Portable appliance testing wikipedia , lookup

Voltage optimisation wikipedia , lookup

History of electric power transmission wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Single-wire earth return wikipedia , lookup

Mains electricity wikipedia , lookup

Rectiverter wikipedia , lookup

Three-phase electric power wikipedia , lookup

Alternating current wikipedia , lookup

Metadyne wikipedia , lookup

Distribution management system wikipedia , lookup

Transformer wikipedia , lookup

Transcript
Annex (A)
Technical Specifications for
Distribution Transformers
PART 1: GENERAL
1.
Scope
This specification covers the design, manufacturing, testing, supply, delivery and
performance requirements of three phase 11/0.416 kV outdoor type distribution
transformers for use in the electricity distribution networks of Iraq.
2.
Standards
The equipment shall comply with the latest editions and amendments of the
international standards listed below as a minimum.
IEC International Electrotechnical Commission:

IEC 60071: Insulation co-ordination

IEC 60076: Power transformers

IEC 60137: Bushing for alternating voltages above 1,000V

IEC 60156: Method for the determination of the electric strength of
insulting oils

IEC 60296: Specification for unused mineral insulating oils for
transformer and switchgear

IEC 60354: Loading guide for oil-immersed power transformers

IEC 60437: Radio interference test on high-voltage insulators

IEC 60551: Determination of transformer and reactor sound levels

IEC 60616: Terminal and tapping markings for power transformers

IEC 60722: Guide to the lightning impulse and switching impulse
testing of power transformers and reactors
ISO International Organization for Standardization:

ISO 1459: Metallic coatings - Protection against Corrosion by Hot
Dip Galvanising - Guiding Principles

ISO 1460: Metallic coatings - Hot dip galvanized coatings on
ferrous materials. Gravimetric determination of the
mass per unit area

ISO 2178: Non-magnetic coatings on magnetic substrates Measurements of coating thickness - Magnetic method

ISO 9000: Quality management and quality assurance standards Guidelines for selection and use
CENELEC/CEN Harmonized European Standards:

HD 428:
Distribution Transformers
ASTM American Society for Testing and Materials:

D 202:
Methods of sampling and testing untreated paper used for
electrical insulation.
Where any provision of this specification differs from those of the standards
listed above, the provision of this specification shall apply. In case of conflict,
the order of precedence shall be:




This specification
IEC standards
ISO standards
Other standards
Equipment confirming to alternative standards may be accepted provided it is
demonstrated that they give a degree of quality and performance equivalent or
better than that of the reference standards. Acceptability of any alternative
standard is at the discretion of the Employer.
3.
Service Conditions
Transformers will be installed outdoors, at ambient conditions given below.
3.1
Outdoor
Item
Altitude above sea level:
Ambient Temperature:
Maximum outdoor - shade
Minimum outdoor
Maximum outdoor daily average
Maximum outdoor yearly average
Maximum ground at depth 1 m
Maximum Black Body (black objects in direct sun)
Relative Humidity:
Maximum
Minimum
Yearly Average
Maximum wind velocity:
Rainfall per year:
Maximum
Minimum
Maximum in one day
Yearly Average
Description
Up to 1,000m above sea-level
+55 °C for 6 hours a day
-10 °C
+40 °C
+30 °C
+35 C
+80 C
92 %
12 %
44 %
140 kilometre per hour
500 mm
50 mm
65 mm
150 mm
Subject to sand storms and
Atmosphere:
wind blown dust
Average number of days per year of dust storms
30
Average number of days per year of thunder storms 15
4.
System Conditions
The network design information is as follows;
Voltage
Description
Nominal Voltage
Highest System Voltage
Number of Phases
Frequency
Neutral Point
3 Phase Short Circuit Level
Duration of Short Circuit
Insulation Levels:
Impulse
Power Frequency 1 min
11 kV
11 kV
12 kV
3
50 Hz
See Note below
25 kA
1 sec
400 V
400/230 V
416 V
3
50 Hz
Directly Earthed
10 kA
-
75 kV
28 kV
3 kV
Note: The 11 kV networks are normally operated with the neutral point earthed
through a resistor to limit earth fault current. However, the 11 kV networks
may also be operated with the neutral isolated from earth during abnormal
conditions. The unearthed 11 kV equipment shall be suitable for continuous
operation with an earth fault on one phase and shall be designed to
withstand the over voltage that may occur due to arcing to earth.
5.
Inspection, Testing and Quality Assurance
5.1 Inspection
The Contractor shall submit a detailed program covering the design,
manufacture and testing of the Distribution Transformers within one month of
receipt of the contract award. Reports shall subsequently be submitted at
intervals, outlining progress.
The Employer or its nominated entity shall have free entry at all times, while
work on the contract is being performed, to all parts of the manufacturer’s
works which concern the processing of the work. The manufacturer shall
afford the Employer without charge, all reasonable facilities to verify that the
equipment being furnished is in accordance with this specification.
5.2
Testing
The equipment shall have been type tested and successfully passed all type
tests referred to in Part 2 “Technical”, and in the most recent editions of the
standards referenced in Clause 2. Certificates of type tests already carried out
shall be submitted with the bid for evaluation.
Fresh type tests shall be carried out if required by the Employer at an
independent certified/accredited testing laboratory and witnessed by the
Employer or some other representative acceptable to the Employer. If the
Employer wishes to witness tests, then the Contractor shall give the Employer
a minimum of one-month notice that the equipment/material is ready for
testing. If the Employer does not indicate an intention to participate in the
testing, the manufacturer shall carry out the tests and the Contractor shall
furnish the results thereof to the Employer for review and acceptance. Cost of
type tests shall be included in the Price Schedule.
All routine tests required by the relevant standards shall be carried out even
though they are not listed in this specification, at the expense of the Contractor
and these tests shall be carried out at the manufacturer’s works. The
Contractor shall submit full details of the proposed methods of testing,
including connection diagrams to the Employer for approval, at least one
month before testing.
The Contractor shall submit to the Employer five signed copies of the test
certificates, giving results of the prescribed tests. Equipment shall not be
dispatched until the Employer has received the test certificates and the
Contractor has been informed that they are acceptable. The Employer
reserves the right to reject any item of the equipment if the test results do
not comply with the values specified or with the data given in the Schedule
of Technical Data.
5.3
Quality Assurance
The manufacturer must operate a quality assurance system that complies with
ISO 9000. The Contractor shall provide current certification showing the
manufacturers’ compliance with ISO 9000 or equivalent national standard.
The certificate must have been issued by an independent, accredited issuing
authority.
6.
Spare Parts
Not required.
7.
Packing, Shipping and Hazardous Substances
7.1
Packing
All equipment, including accessories, shall be packed and securely clamped
against movement in robust, non-returnable packing cases to ensure safe transit
from the manufacturer's works to the agreed point of delivery. The base of the
packing case shall be strong enough to carry the weight of the transformer and be
large enough so that no part of the transformer and accessories such as pipes,
valves, etc extends beyond the edge of the pallet.
Transformers shall be supplied filled with oil. The weight and volume of oil in
the transformer shall be clearly stated.
All the spare parts shall be packed for long storage.
Internal surfaces of equipment and accessories shall be sealed off by means of
gaskets and blanking off plates. Equipment and surfaces liable to deterioration
due to condensation shall be protected by packs of silica gel or other approved
desiccant.
Each transformer shall have 2 suitable plywood labels tied to it on adjacent sides.
Each label shall contain the following information indelibly marked on it:










Individual serial number
Employer’s name
Contract number
Contractor's name
Manufacturer’s name
Description of contents
Country of origin
Case measurements
Gross and net weights in kilograms
All necessary slinging and stacking instructions
The label and ties shall be fixed such that no damage or abrasion is caused to the
paintwork.
Each transformer shall contain a fully detailed packing list in a sealed waterproof
envelope robustly attached to it. Five (5) copies of each packing list shall be sent
to the Employer prior to dispatching the equipment.
7.2
Hazardous Substances
The Contractor shall submit safety data sheets for all hazardous substances used
with the equipment. These substances shall be classified in accordance with the
European Union SI 426.
If such substances are not used in with the equipment, the Contractor shall
give an assurance that there are no substances classified as hazardous in the
equipment supplied.
8.
Submittals Required by Employer after Contract Award
The Contractor shall submit a detailed programme covering the manufacture,
testing and delivery of the materials and equipment within the time stated in the
following table.
#
1.
2.
Description
Programme for production and
testing
Detailed dimension drawings for
all components, general
arrangement drawings showing
detailed component layout and
overall assembly drawings
Delivery Time
Objective
Within one month
Approval
of contract award
No. of
Copies
3
#
3.
4.
Description
Progress reports
6.
Notification of inspection and
tests
8.
9.
10.
11.
12.
13.
Objective
No. of
Copies
Detailed drawing of mounting
arrangements
Certificates of compliance and
certificates of origin
5.
7.
Delivery Time
List of tests and description of
the tests to be performed
Test reports for all type tests,
routine tests and special tests
and inspection reports
Technical Data Schedule with
approved revisions if any
Detailed schematic and wiring
drawings for all components
General description of the
equipment and all components
including brochures
Installation and commissioning
instructions
Operation and maintenance
instructions manual
At agreed
intervals
Monitoring
Review and
One month before necessary
action
inspection /
testing
Approval
Immediately after
tests/inspection
are completed
Approval
3
3
3
5
5
5
One month before
Approval
delivery
5
5
5
The programme for production and testing should be in the form of a Gantt
chart.
The Contractor shall submit progress reports detailing progress against this
programme and explaining any variations. The progress reports shall be
submitted at defined intervals agreed by the Employer.
At each of the approval stages indicated in above table, the Contractor should
not proceed to the next step in the programme until the Employer gives
approval.
PART 2: TECHNICAL
9.
General
This specification covers the design, manufacturing, testing, supply, delivery and
performance requirements of three phase, 50 Hz, 11/0.416 kV distribution power
transformers with accessories.
All transformers shall have separate primary and secondary windings and be
hermetically sealed, oil immersed with natural oil and air cooling (ONAN).
The design of the tank, fittings, bushings, etc. shall be such that it will not be
necessary to keep the transformer energized to prevent deterioration as the
transformers may be held in reserve, outdoors, for many years.
10.
Technical Requirements
Description
Rated Voltage
10.1
Requirement
HV
11 kV
LV
416 V
Frequency
50 Hz
Number of Phases
3
Power ratings
100kVA, 250 kVA, 400 kVA and 630 kVA
Type
Oil immersed, hermetically sealed (bolted type)
Standard
IEC 60076
Cooling
Self-cooled (ONAN)
Voltage Variation
Off-load tap changer with 5 positions in the HV winding
giving + 2 x 2.5 %.
Windings
Copper only
Core
Grain orientated silicon steel, step-lap mitered joints
HV and LV Bushings
Outdoor type
Vector Group
Dyn11
Rated Power
The continuous rating of the distribution Transformers shall be 100kVA, 250
kVA, 400 kVA and 630 kVA.
Each Transformer shall be capable of supplying its rated power being the product
of rated voltage and rated current on the line side winding (at center tap)
expressed in kVA, as defined in IEC 60076-1.
The transformer shall also be capable of delivering rated current at an applied
voltage equal to 105% of the rated voltage.
-
10.2
Likewise, each transformer shall be capable of supplying its rated power
continuously under ambient temperature conditions without the
temperature rise of the top oil exceeding 50 C and without the temperature
rise of the windings as measured by resistance exceeding 55 C.
Overload Capacity
The transformer shall be capable of operating in accordance with the loading
guidelines of IEC 60354 without exceeding the normal daily use of life and
without the transformer winding hot spot temperature exceeding 140 C.
The Contractor shall submit calculations demonstrating that above requirements
are met. These calculations shall disregard the effect of winding thermal
capacity.
Importance is attached to overload capacity. Transformers incapable of meeting
the overload performance specified will not be considered.
10.3
Impedance Voltage
The guaranteed value of impedance measured at 75 C and center tap shall be
4% for the transformers of 100kVA, 250 kVA and 400 kVA capacities and 6%
for the distribution transformers of 630 kVA capacity and it shall be subject to
the tolerance specified in IEC 60076.
The resistance component of impedance measured at 75 C on the center tap
shall not exceed 25 % for all kVA ratings
10.4
Short Circuit Performance
The transformer shall be capable of withstanding the thermal and dynamic
effects of short circuits. System short circuit level and the withstanding duration
are given in table “system conditions” in section 3.2.
The short circuit characteristics shall be as follows;

The X/R ratio shall conform to HD 398 / HD 428

The initial winding hot spot temperature shall be 98 C

The final winding hot spot temperature shall be 250 C
The ability to withstand the thermal and dynamic effects of a short circuit shall
be demonstrated in accordance with IEC 60076 and IEC 60354. Calculations /
test certificates shall be submitted for approval.
10.5
Flux Density
The flux density at any point of the magnetic circuit when the transformer is
connected on the centre tap and operating at normal voltage and frequency shall
not exceed 1.65 Tesla. Saturation must not occur at 10 % over voltage.
10.6
Noise Level
The average noise level of the transformers shall not exceed the values given in
IEC 60551. The measurements shall be carried out in accordance with the above
standard at a distance of 300 mm from the envelope of the transformer.
10.7
Tap Changing Characteristics
Each transformer shall be fitted with 5 taps with ± 2x2.5% voltage variation. Tap
changing and the tap changing mechanism shall have the following
characteristics:
11.
11.1

Tap changing shall be carried out with the transformer off-load. An
externally operated self-positioning tapping switch shall be provided.

Provision shall be made for locking the tap switch handle with a padlock
having a 6 mm diameter hasp.

Tap changer handles shall be fitted with gasketed covers, so that sealing
of the transformer under normal conditions is independent of the switch
shaft gland.
Materials and Construction
Core and Coils
The HV and LV windings shall be made of high conductivity copper. Copper
foil may be used for the LV winding.
The windings shall be uniformly insulated and the LV neutral point shall be
insulated for full voltage. The insulation material of windings and connections
shall be high quality, free from insulation softening, shrinking or collapsing
during service. Moreover none of the material used shall disintegrate, carbonize
or become brittle under the action of hot oil, under all load conditions.
The core shall be manufactured from non-aging, grain-orientated silicon steel of
high permeability with step-lap mitered joints.
The core and coil assembly shall have the core and coils rigidly connected to the
tank and suitable closed lugs shall be provided for removing the core and coil
assembly from the tank.
11.2
Bushings and Terminals
All bushings shall be so designed that there will be no excessive stressing of
any parts due to temperature changes and adequate means shall be provided to
accommodate conductor expansion. Insulation levels for bushings shall be at
least equal to those specified for the windings.
The Bushings shall be so installed that they are easy to be checked and
removed without removing the tank cover and the pipe work.
The creepage distances for the bushings and the insulators shall not be less than
25 mm/kV for maximum phase to phase system voltage.
Both HV and LV Bushings shall be complete with Brass terminals suitable for
terminating Copper conductors as details given below:

HV: outdoor bushings with clamp for terminating 50-95 mm2 Copper
Conductor

LV: outdoor bushings with terminals suitable for terminating copper cables
as specified below.
100 kVA – 1x1C 95 mm2
250 kVA – 2x1C 95 mm2
400 kVA – 3x1C 150 mm2
630 kVA – 4x1C 150 mm2
The HV and LV bushings shall be:

Easily replaceable and cemented in bushings are not acceptable.

Sufficiently robust to withstand normal transport hazards.
The HV bushings shall be labeled in accordance with IEC 60076. Letters shall be
at least 12 mm high. The means of marking shall be either:
11.3

Engraved metal plate or etched anodized aluminium. Identification by
adhesive stickers is not acceptable.

If labeling is to be carried out on the tank, it is preferred that one plate be
used rather than individual markings for each phase, in order to prevent
incorrect phase markings.
Earthing Terminals
All transformers shall be provided with a main earthing terminal of stainless steel
welded to the tank and be fitted with a stainless steel M12 bolt, nut, spring
washer and a lock washer.
11.4
Tank Fabrication
The transformer tank shall be of rigid construction, shall not leak and shall be
designed so that the completed transformer can be lifted and transported without
permanent deformation or oil leakage. The Contractor shall state what method
of leak testing is used.
The tank shall be fabricated of mild steel or stainless steel. If stainless steel is
used it shall not discolour or corrode; a minimum grade 304 L is required.
The minimum thickness of the steel tank shall be 3 mm for mild steel and an
equivalent thickness for stainless steel such that its mechanical strength shall be
the same as that of the 3 mm thick mild steel tank. Thickness below the
minimum value will be considered only in exceptional cases, such as where
special protective finishes are used. The Contractor shall provide full information
about any such special finish, including any field experience.
The transformer tank and the top cover shall be designed in such a manner as to
leave no external pockets in which water can lodge or dust deposits can build up.
The top cover shall be of the bolted type and fitted with neoprene bonded cork
seals suitable for temperature as stipulated in this specification. Surfaces at
gasketed joints shall be such that an even face is presented to the gasket, thereby
eliminating the necessity for the gasket to take up surface irregularities.
The cooling surfaces may be oil filled fins or radiators. Only larger faces of the
transformer shall be used to attach cooling surfaces.
All pipes and radiators, which are welded to the tank wall, shall be welded
externally.
100kVA, 250 kVA and 400 kVA transformers shall be pole mounted and 630
kVA transformers shall be wheel mounted. Skids shall be aligned at right angles
to the line of the HV bushings.
11.5
Surface Treatment
The transformer tank, radiators and accessories should be adequately protected
against corrosion and the Contractor shall submit details of the proposed method
of protection.
All surfaces shall be thoroughly cleaned of rust, scale, grease and dirt and other
foreign matter and all imperfections shall be removed by means of approved
methods.
The transformer tank and its steel attachments shall be hot dip galvanized or
metallized, followed by painting. The painting system used should be proven and
documented.
The outside of the tank shall be painted Gray.
The inside of the tank shall be painted with an approved oil resisting varnish so
that the oil cannot come into contact with the tank metal at any time.
11.6
Tank Fittings and Attachments
The following fittings and attachments shall be provided in all transformers:











11.7
Tap changer (off-circuit with pad lockable switch)
HV bushing assembly
LV bushings assembly
Oil filling and drain valves
Main earthing terminal
Lifting eyes pulling eyes and jacking pads
Stainless steel engraved rating and connection plate in both Arabic and
English languages
Pressure relief valve
Protecting irons
Oil level indicator
Terminal marking
Transformer Assembly
The core and winding shall be dried in a vacuum drying oven. The heating and
vacuum drying cycle shall be approved by the Employer. The tank, complete
with core and windings, shall be filled with oil under a vacuum.
11.8
Transformer Oil
The transformers shall be supplied filled with class 1 mineral oil conforming to
IEC 60296. The Contractor shall submit a detailed specification for the type of
oil proposed. The oil shall not contain polychlorinated biphenyls (PCB). The
Employer may require evidence that the oil is not contaminated by PCB. If an
anti oxidant is recommended, its use shall be subject to the Employer's approval.
12.
Transformer Losses
The Contractor shall state the guaranteed losses. No positive tolerance is
allowable on the guaranteed values. Transformers supplied with losses exceeding
the guaranteed values will be rejected.
The Contractor shall also state the value of guaranteed magnetizing current,
subject to the tolerance specified in IEC 60076.
12.1
Loss Evaluation
The admissible tolerances for component and total losses of transformer after
testing shall be according to IEC 60076.
The Employer may at its sole discretion reject any transformer with Copper
losses or Iron losses exceeding the relevant tolerances.
For the purpose of evaluation the transformer shall be evaluated according to the
total price plus the capitalized value of losses. The formula to be used in
evaluation will be:
Capitalized Cost = $T + (Fe x $5,000) + (Cu x $1,200) Where,
$T =
The total cost of the transformer as tendered.
Fe =
No load loss in kW
Cu =
Load loss in kW at full rated load and maximum operating
temperature.
13.
Tests
The tests listed hereinafter shall be carried out in accordance with provisions
in the referenced standards in the specification.
13.1
Routine Tests
Routine tests shall be carried out on all transformers and the tests shall be
conducted in accordance with IEC 60076 /other standards as applicable.
The following routine measurements and tests shall be carried out:












13.2
Measurement of winding resistance
Measurement of voltage ratio and check of polarity and vector group
Measurement of impedance voltages
Measurement of load losses
Measurement of no load losses and no load current, including
measurement of harmonics
Induced overvoltage withstand test
Separate source voltage-withstand tests on HV and LV windings
Bushing routine tests
Oil leakage test
Relief Device test
Dielectric Routine Tests
Galvanizing tests.
Type Tests
Following shall be regarded as type tests:





Temperature Rise Test. This test shall be carried out on the tap
having maximum losses
Short Circuit Withstand test
Measurement of zero-sequence Impedances
Impulse Voltage Test and Power Frequency Test
Acoustic Sound Level Measurement

13.3
Tank Vacuum Test

Measurement of Harmonic Level in no load condition

Oil Analysis
Galvanizing Tests
Galvanizing tests shall be carried out on transformer tanks prior to painting.
Those shall be routine tests, which shall be part of the routine tests
documentation and shall not be charged to the Employer. Testing shall be in
accordance with ISO 1460 and is summarized as follows.
The following tests, measurements or inspections shall be carried out on each of
the selected samples:



Visual inspection
Thickness of galvanizing coat
Uniformity of galvanizing coat
In the event of disagreement or dispute over the results of the above tests a
coating mass test shall be carried out. The result of this test shall be definite and
binding.
14.
Label and Rating Plates
Labels, name plates, markings and instructions shall be clear and indelible and
in the English language. A weatherproof rating plate shall be provided in
accordance with IEC 60076 and showing the following items, indelibly
marked:
-
Type of transformer
Specification to which standard it was manufactured
Manufacturer’s name
Serial number
Year of manufacturer
Number of phases
Rated power
Rated frequency
Rated voltage
Rated currents
Vector group
Percentage impedance voltage at rated current
Type of cooling
Continuous ambient temperature at which ratings apply
Top oil temperature rise at rated load
Total weight
Volume of oil
Weight of core and windings
15.
-
Table of primary voltages at the 5 tapping positions
-
Employer’s name
Connection diagram
Drawings
Typical mounting arrangement of pole-mounted transformers is shown in the following
drawings.
15.1 100kVA - 250 kVA Transformer
15.2 400 kVA Transformer
SCHEDULES TO BE COMPLETED BY THE BIDDERS
1. Technical Data Schedule
The following Technical Schedule shall be filled out separately for each transformer
rating.
1.1 Technical Data Schedule for 100 kVA Distribution Transformer
#
Description
Unit
1
2
International standards transformer complies with
Nominal frequency
3
Rated Power
4
Nominal primary voltage
kV
5
Nominal secondary voltage
V
6
Rated primary voltage
kV
7
Rated secondary voltage
V
8
Type of cooling
9
Vector group
-
10
Tap changing
11
Hz
kVA
Number of steps
± steps
Tapping range
±%
Current
kA
Duration
s
12
Rated short circuit current
and withstanding duration
13
Impedance measured at 75 C and center tap
%
14
X/R ratio
25 % overload
15
Duration of overload
50% overload
C
minutes
C
minutes
16
Design maximum outdoor temperature
C
17
Design continuous ambient temperature
C
18
Thermal Characteristics
Average winding temperature rise
C
Maximum average temperature rise
C
Maximum hot spot temperature rise
C
Hot-spot to top-oil temperature gradient
19
20
21
22
23
24
Magnetic flux density
Core Losses
Winding losses
No load current
Regulation: full load, PF=1
full load, PF=0.85
Manufacturer
Silicon steel
Type and grade
C
Tesla
W
W
A
%
%
Data
#
Description
Operating flux density
Losses kW/kg at operating flux density
Manufacturer’s data sheet supplied
#
Description
25
Unit
Tesla
kW/kg
Yes/No
Data
Unit
Data
Manufacturer/Supplier and type
Conductor for HV winding
Conductor Material
Shape and cross sectional area
26
Manufacturer/Supplier and type
Conductor for LV winding
Conductor Material
Shape and cross sectional area
27
Manufacturer/Supplier
HV Bushing
Type and grade
Bushing catalogue number
28
Manufacturer/Supplier
LV Bushing
Type and grade
Bushing catalogue number
29
30
Bushing basic impulse
level
Bushing power frequency
withstand voltage
31
HV Bushing
kV
HV Bushing
kV
LV Bushing
kV
Type and metal used in HV terminal
Terminals
Type and metal used in LV terminal
Type of metal used in Earth terminal
32
Minimum phase to phase clearance
mm
33
Minimum phase to earth clearance
mm
34
Spring and lock washers included
Yes/No
35
Manufacturer/supplier
Tap changer
36
37
Catalogue details attached
Yes/No
Manufacturers data sheet attached
Yes/No
Can tap changer switch be locked
Tank material
Tank Fabrication
38
Tank Dimensions
39
Type
Transformer weights
Yes/No
Thickness of the metal sheet
Painting method details attached
Width
Height
Depth
Weight of core and windings
Yes/No
mm
mm
mm
kg
Weight of tank
kg
Weight of oil at 20 C
Total weight of transformer, ready for
service
Shipping weight of transformer
Signature: ______________
Company Seal
kg
kg
kg
Date:
1.2 Technical Data Schedule for 250 kVA Distribution Transformer
#
Description
Unit
1
2
International standards transformer complies with
Nominal frequency
3
Rated Power
4
Nominal primary voltage
kV
5
Nominal secondary voltage
V
6
Rated primary voltage
kV
7
Rated secondary voltage
V
8
Type of cooling
-
9
Vector group
-
10
Tap changing
11
Hz
kVA
Number of steps
± steps
Tapping range
±%
Current
kA
Duration
s
12
Rated short circuit current
and withstanding duration
13
Impedance measured at 75 C and center tap
%
14
X/R ratio
25 % overload
15
Duration of overload
50% overload
C
minutes
C
minutes
16
Design maximum outdoor temperature
C
17
Design continuous ambient temperature
C
18
Thermal Characteristics
Average winding temperature rise
C
Maximum average temperature rise
C
Maximum hot spot temperature rise
C
Hot-spot to top-oil temperature gradient
19
20
21
22
23
24
Magnetic flux density
Core Losses
Winding losses
No load current
Regulation: full load, PF=1
full load, PF=0.85
Manufacturer
Type and grade
Operating flux density
Silicon steel
Losses kW/kg at operating flux density
Manufacturer’s data sheet supplied
C
Tesla
W
W
A
%
%
Tesla
kW/kg
Yes/No
Data
#
Description
25
Unit
Manufacturer/Supplier and type
Conductor for HV winding
Conductor Material
Shape and cross sectional area
26
Manufacturer/Supplier and type
Conductor for LV winding
Conductor Material
Shape and cross sectional area
27
Manufacturer/Supplier
HV Bushing
Type and grade
Bushing catalogue number
28
Manufacturer/Supplier
LV Bushing
Type and grade
Bushing catalogue number
29
30
Bushing basic impulse
level
Bushing power frequency
withstand voltage
31
HV Bushing
kV
HV Bushing
kV
LV Bushing
kV
Type and metal used in HV terminal
Terminals
Type and metal used in LV terminal
Type of metal used in Earth terminal
32
Minimum phase to phase clearance
mm
33
Minimum phase to earth clearance
mm
34
Spring and lock washers included
Yes/No
35
Manufacturer/supplier
Tap changer
36
37
Type
Catalogue details attached
Yes/No
Manufacturers data sheet attached
Yes/No
Can tap changer switch be locked
Tank material
Tank Fabrication
38
Tank Dimensions
39
Transformer weights
Yes/No
Thickness of the metal sheet
Painting method details attached
Width
Height
Depth
Weight of core and windings
Weight of tank
Weight of oil at 20 C
Total weight of transformer, ready for
service
Yes/No
mm
mm
mm
kg
kg
kg
kg
Data
Shipping weight of transformer
kg
Signature: ___________________ Company Seal
1.3 Technical Data Schedule for 400 kVA Distribution Transformer
#
Description
Unit
1
2
International standards transformer complies with
Nominal frequency
3
Rated Power
4
Nominal primary voltage
kV
5
Nominal secondary voltage
V
6
Rated primary voltage
kV
7
Rated secondary voltage
V
8
Type of cooling
9
Vector group
-
10
Tap changing
11
Hz
kVA
Number of steps
± steps
Tapping range
±%
Current
kA
Duration
s
12
Rated short circuit current
and withstanding duration
13
Impedance measured at 75 C and center tap
%
14
X/R ratio
25 % overload
15
Duration of overload
50% overload
C
minutes
C
minutes
16
Design maximum outdoor temperature
C
17
Design continuous ambient temperature
C
18
Thermal Characteristics
Average winding temperature rise
C
Maximum average temperature rise
C
Maximum hot spot temperature rise
C
Hot-spot to top-oil temperature gradient
19
20
21
22
23
24
Magnetic flux density
Core Losses
Winding losses
No load current
Regulation: full load, PF=1
full load, PF=0.85
Manufacturer
Type and grade
Silicon steel
Operating flux density
Losses kW/kg at operating flux density
C
Tesla
W
W
A
%
%
Tesla
kW/kg
Data
#
Description
Manufacturer’s data sheet supplied
#
Description
25
Unit
Yes/No
Data
Unit
Data
Manufacturer/Supplier and type
Conductor for HV winding
Conductor Material
Shape and cross sectional area
26
Manufacturer/Supplier and type
Conductor for LV winding
Conductor Material
Shape and cross sectional area
27
Manufacturer/Supplier
HV Bushing
Type and grade
Bushing catalogue number
28
Manufacturer/Supplier
LV Bushing
Type and grade
Bushing catalogue number
29
30
Bushing basic impulse
level
Bushing power frequency
withstand voltage
31
HV Bushing
kV
HV Bushing
kV
LV Bushing
kV
Type and metal used in HV terminal
Terminals
Type and metal used in LV terminal
Type of metal used in Earth terminal
32
Minimum phase to phase clearance
mm
33
Minimum phase to earth clearance
mm
34
Spring and lock washers included
Yes/No
35
Manufacturer/supplier
Tap changer
36
37
Type
Catalogue details attached
Yes/No
Manufacturers data sheet attached
Yes/No
Can tap changer switch be locked
Tank material
Tank Fabrication
Thickness of the metal sheet
Painting method details attached
Width
38
Tank Dimensions
39
Transformer weights
Yes/No
Height
Depth
Weight of core and windings
Weight of tank
Yes/No
mm
mm
mm
kg
kg
Weight of oil at 20 C
Total weight of transformer, ready for
service
Shipping weight of transformer
kg
kg
kg
Signature: ___________________ Company Seal
2. Schedule of Non Compliance
On this schedule, the Contractor shall provide a list of non-compliances with this
specification, documenting the effects that such non-compliance is likely to have
on the equipment's life and operating characteristics. Each non-compliance shall
be referred to the relevant specification clause.
2.1 Schedule of Non Compliance - 100 kVA Distribution Transformer
Clause No
Non Compliance
2.2 Schedule of Non Compliance - 250 kVA Distribution Transformer
Non Compliance
Claus
e No
2.3 Schedule of Non Compliance - 400 kVA Distribution Transformer
Clause No
Non Compliance
Signature: ___________________ Company Seal
Date: _____________________
3. Schedule of Test Certificates
On this schedule, a list of the test certificates shall be provided. This list shall
include type test certificates and sample routine test reports. Each certificate
listed shall be referred to the relevant specification clause.
3.1 Schedule of Test Certificates for 100 kVA Distribution Transformer
Clause No
Type Test Certificate and Routine Test Report
3.2 Schedule of Test Certificates for 250 kVA Distribution Transformer
Clause No
Type Test Certificate and Routine Test Report
3.3 Schedule of Test Certificates for 400 kVA Distribution Transformer
Clause No
Type Test Certificate and Routine Test Report
Signature: ________________________
Date: ______________________
Company Seal