Switchboard General Information
Pow-R-Line Xpert - Specifications
Quantity: 1
Alignment: Front Access/ Front and Rear Align
Service: 208Y/120V 3-Phase 4-Wire
Minimum Interrupt Rating: 100 kA
Bus Specifications
Bus Amps: 4000
Bus Bracing Rating: 100kA
Neutral Amps: 4000
Bus Material: Aluminum
Heat Test
Ground Bus Material: Aluminum Ground Bus Bolted To Frame, (1)
#6-350 kcmil Ground Lug
Incoming Information
Terminals, Mechanical, Bottom, (11) 3/0-750 kcmil
ta
nc
ac
ce
p
Structure Specifications
Service Entrance
Enclosure Type: Type 1
e
Incoming Entry: Bottom
Incoming Location: Right
Incoming Qty & Size: (11) #4-500 kcmil
Incoming Qty & Size: Terminals, Mechanical, Bottom, (11) 3/0-750
kcmil
Qty Description
Catalog Number
rd
Utility Specfications
er
Special Notes
rO
Struct # 5
en
fo
4000 Amps Util. Mtr. Compt. - Public Service Electric & Gas (New
Jersey)
Plant Drawing: 42C1192
Code PSE& G
op
Enclosure properties
ty
et
Struct #
1
50x chassis mounted feeders (Feeder Structure)
no
2
Main device (Main Structure)
Vertical isolating barrier
ar
e
3
Bussed structure with lugs for outgoing cable (Auxiliary
Structure)
es
4
Incoming Utility Structures (Incoming Utility Section)
Horizontal isolating barrier
Q
uo
te
d
pr
ic
5
Description/Modifications
Individually mounted feeder BREAKER exiting top (Feeder
Structure)
Vertical isolating barrier
The information on this document is
created by Eaton Corporation. It is
disclosed in confidence and it is only to
be used for the purpose in which it is
supplied.
NEG-ALT Number
NARF1006X1K1-0000
PREPARED BY
DATE
WIN VANDERZEE
APPROVED BY
10/7/2021
Eaton
DATE JOB NAME
DESIGNATION
REVISION
0
SumterSC
Rehabilitation of Existing School- Charter School 278 SUSSEX AVE NEW
SWBD-C1
VERSION
TYPE
DRAWING TYPE
9.0.30.1
Switchboards
CustAppr
DWG SIZE G.O.
DwgA
ITEM
SHEET
1 of 5
Please move (6) breakers
from this structure and
create a separate structure
for south core feeder
breakers. The intent is to
create one structure for north
and another for south.
Please refer to last page for
north vs south panelboards
breakdown
1
1- Please see last
page for desired
arrangement. We
would like the incoming
section to be on the
right side of the
elevation (looking at
front).
PXM
1100
3
PD5
PD3-P
5
PD3
PD3
7
8
PD3
PD3
9
10
PD3
PD3
11
12
PD2
PD2
13
14
PD2
PD2
15
16
PD2
PD2
17
18
PD2
PD2
19
20
PD2
PD2
21
PD2
23
22
Front View
Struct
Depth
36
Width
30
PD2
*
1
SBN-C4N
*
2
36
2- There will be no fire
pump. Please delete
tap section. However,
the incoming pull
section will be on the
right hand-side.
Bottom
Outgoing
Mechanical
Terminals
(11) #4-500 kcmil
3- Why cant we use
4000A fused pressure
switch in lieu of 4000A
main circuit breaker?
e
PD3
6
3
36
36
*
4
36
*
5
36
30
45
er
ac
45
*
ce
p
Frame 6
4
rO
rd
Power Flow
fo
For panels with 36 breakers,
we will use 48" backboxes and
make them all 42 breakers.
ty
et
Top
Cable Exit
en
See 1A32044 For
Floor Plan Detail
Top/Bottom
Cable Exit
For panelboard submittal but
noted here as a reminder, for
54 breakers,can we use 48"
backboxes?
op
Rear
Floor Plan
ta
nc
2
24.00
12.00
24
3.00
39
30.00
3.00
24
3.00
3.00
39
3.00
pr
ic
es
3.00
30.00
no
2.50
ar
e
2.50
te
The information on this document is
created by Eaton Corporation. It is
disclosed in confidence and it is only to
be used for the purpose in which it is
supplied.
NEG-ALT Number
NARF1006X1K1-0000
2
45.00
1143
45.00
1143
36.00
914
36.00
914
90.00
2286
1451
658
d
1
30.00
762
30.00
762
36.00
914
36.00
914
90.00
2286
702
318
uo
Q
Structure
Ship-Inches
Ship-MM
Wdth-Inches
Wdth-MM
Depth(Inner)-In.
Depth(Inner)-MM
Depth(Outer)-In.
Depth(Outer)-MM
Height-Inches
Height-MM
Weight-Lbs.(Est.)
Weight-Kg.(Est.)
PREPARED BY
3
36.00
914
36.00
914
36.00
914
36.00
914
90.00
2286
1098
498
APPROVED BY
10/7/2021
5
45.00
1143
45.00
1143
36.00
914
36.00
914
90.00
2286
990
449
Eaton
DATE JOB NAME
DESIGNATION
0
4
30.00
762
30.00
762
36.00
914
36.00
914
90.00
2286
644
292
DATE
WIN VANDERZEE
REVISION
Total of 5 Structures, Total Weight of 4885 Weight-Lbs.
Total of 5 Structures, Total Width of 186 Inches
SumterSC
Rehabilitation of Existing School- Charter School 278 SUSSEX AVE NEW
SWBD-C1
VERSION
TYPE
DRAWING TYPE
9.0.30.1
Switchboards
CustAppr
DWG SIZE G.O.
DwgA
ITEM
SHEET
2 of 5
Switchboard Units Information
Str#
Unit
Description/Modifications
Nameplate
1
Feeder Breaker - Ind Mtd-1600A 3P Frame 6 Breaker [2000A Frame], Trip 1600A., PXR20 LSI w/
ARMS, None
ARMS Operation - Local using breaker interface
Terminals, Mechanical, (6) #4-500 kcmil, Top
Neutral Terminal, (6) #4-500 kcmil
Blank Cover -1 X
2
PXM1100 Meter, 4000 Amp CTs, with Display
3
Feeder Breaker - Chassis Mtd-1200A, 3P Frame 5 Branch Breaker, [1200A Frame], Trip 1200A.,
PXR20 LSI w/ ARMS, None
ARMS Operation - Local using breaker interface
Terminals, Mechanical, (4) 4/0-500 kcmil
Neutral Terminal, (4) #4-500 kcmil
ce
p
ta
nc
1
e
2
Feeder Breaker - Chassis Mtd-250A, 3P Frame 3 Branch Breaker [400A Frame], Trip 250A.,
Thermal Mag
Terminals, Mechanical, (1) 2/0-500 kcmil
Is it possible to
Neutral Terminal, (1) #4-500 kcmil
designate each feeder
breaker with the
5
Feeder Breaker - Chassis Mtd-3P Frame 3 Provision, PROVISIONS FOR BREAKER ONLY
corresponding panel
Neutral Terminal, (1) #4-500 kcmil
name to be served so
we can check the lugs?
6
Feeder Breaker - Chassis Mtd-225A, 3P Frame 3 Branch Breaker [400A Frame], Trip 225A.,
Thermal Mag
Terminals, Mechanical, (1) 2/0-500 kcmil
Neutral Terminal, (1) #4-500 kcmil
why upsize the frame to 400A?
Question for Win:
cant we have 225A frame
7
Feeder Breaker - Chassis Mtd-225A, 3P Frame 3 Branch Breaker [400A Frame], Trip 225A.,
is there a cheat
instead and keep the LSI?
Thermal Mag
sheet that I can get
Typical for other incidents
Terminals, Mechanical, (1) 2/0-500 kcmil
so I can determine
Neutral Terminal, (1) #4-500 kcmil
the backbox size
vs the number of
8
Feeder Breaker - Chassis Mtd-225A, 3P Frame 3 Branch Breaker [400A Frame], Trip 225A.,
breakers which
PXR10 LSI
needs to be
Terminals, Mechanical, (1) 2/0-500 kcmil
provided?
Neutral Terminal, (1) #4-500 kcmil
ic
es
ar
e
no
ty
et
op
en
fo
rO
rd
er
ac
4
Feeder Breaker - Chassis Mtd-225A, 3P Frame 3 Branch Breaker [400A Frame], Trip 225A.,
Thermal Mag
Terminals, Mechanical, (1) 2/0-500 kcmil
no ground fault protection. only
Neutral Terminal, (1) #4-500 kcmil
ground fault alarm.
10
Feeder Breaker - Chassis Mtd-250A, 3P Frame 3 Branch Breaker [400A Frame], Trip 250A.,
PXR20 LSIG/A, None
Terminals, Mechanical, (1) 2/0-500 kcmil
Neutral Terminal, (1) #4-500 kcmil
Q
uo
te
d
pr
9
11
Feeder Breaker - Chassis Mtd-225A, 3P Frame 3 Branch Breaker [400A Frame], Trip 225A.,
Thermal Mag
Terminals, Mechanical, (1) 2/0-500 kcmil
which panel is this one for? Not
sure we have 400/225? same
for other breakers
The information on this document is
created by Eaton Corporation. It is
disclosed in confidence and it is only to
be used for the purpose in which it is
supplied.
NEG-ALT Number
NARF1006X1K1-0000
PREPARED BY
DATE
WIN VANDERZEE
APPROVED BY
10/7/2021
Eaton
DATE JOB NAME
DESIGNATION
REVISION
0
SumterSC
Rehabilitation of Existing School- Charter School 278 SUSSEX AVE NEW
SWBD-C1
VERSION
TYPE
DRAWING TYPE
9.0.30.1
Switchboards
CustAppr
DWG SIZE G.O.
DwgA
ITEM
SHEET
3 of 5
Feeder Breaker - Chassis Mtd-150A, 3P Frame 2 Branch Breaker [225A Frame], Trip 150A.,
Thermal Mag
Terminals, Mechanical, (1) #4-4/0
Neutral Terminal, (1) #6-350 kcmil
13
Feeder Breaker - Chassis Mtd-150A, 3P Frame 2 Branch Breaker [225A Frame], Trip 150A.,
Thermal Mag
Terminals, Mechanical, (1) #4-4/0
Neutral Terminal, (1) #6-350 kcmil
14
Feeder Breaker - Chassis Mtd-150A, 3P Frame 2 Branch Breaker [225A Frame], Trip 150A.,
Thermal Mag
Terminals, Mechanical, (1) #4-4/0
Neutral Terminal, (1) #6-350 kcmil
15
Feeder Breaker - Chassis Mtd-150A, 3P Frame 2 Branch Breaker [225A Frame], Trip 150A.,
Thermal Mag
Terminals, Mechanical, (1) #4-4/0
Neutral Terminal, (1) #6-350 kcmil
16
Feeder Breaker - Chassis Mtd-150A, 3P Frame 2 Branch Breaker [225A Frame], Trip 150A.,
Thermal Mag
Terminals, Mechanical, (1) #4-4/0
Neutral Terminal, (1) #6-350 kcmil
17
Feeder Breaker - Chassis Mtd-150A, 3P Frame 2 Branch Breaker [225A Frame], Trip 150A.,
Thermal Mag
Terminals, Mechanical, (1) #4-4/0
Neutral Terminal, (1) #6-350 kcmil
18
Feeder Breaker - Chassis Mtd-150A, 3P Frame 2 Branch Breaker [225A Frame], Trip 150A.,
Thermal Mag
Terminals, Mechanical, (1) #4-4/0
Neutral Terminal, (1) #6-350 kcmil
19
Feeder Breaker - Chassis Mtd-150A, 3P Frame 2 Branch Breaker [225A Frame], Trip 150A.,
Thermal Mag
Terminals, Mechanical, (1) #4-4/0
Neutral Terminal, (1) #6-350 kcmil
20
Feeder Breaker - Chassis Mtd-60A, 3P Frame 2 Branch Breaker [225A Frame], Trip 60A.,
PXR20 LSIG/A, None
Terminals, Mechanical, (1) #14-1/0
Auxiliary switch: 1 NO & 1 NC Aux Contact (Integral)
Neutral Terminal, (1) #14-1/0
21
Feeder Breaker - Chassis Mtd-150A, 3P Frame 2 Branch Breaker [225A Frame], Trip 150A.,
Thermal Mag
Terminals, Mechanical, (1) #4-4/0
Neutral Terminal, (1) #6-350 kcmil
Q
uo
te
d
pr
ic
es
ar
e
no
ty
et
op
en
fo
rO
rd
er
ac
ce
p
ta
nc
12
e
Neutral Terminal, (1) #4-500 kcmil
22
Feeder Breaker - Chassis Mtd-100A, 3P Frame 2 Branch Breaker [225A Frame], Trip 100A.,
PXR20 LSIG/A, None
Terminals, Mechanical, (1) #14-1/0
Auxiliary switch: 1 NO & 1 NC Aux Contact (Integral)
Neutral Terminal, (1) #14-1/0
The information on this document is
created by Eaton Corporation. It is
disclosed in confidence and it is only to
be used for the purpose in which it is
supplied.
NEG-ALT Number
NARF1006X1K1-0000
PREPARED BY
DATE
WIN VANDERZEE
APPROVED BY
10/7/2021
Eaton
DATE JOB NAME
DESIGNATION
REVISION
0
SumterSC
Rehabilitation of Existing School- Charter School 278 SUSSEX AVE NEW
SWBD-C1
VERSION
TYPE
DRAWING TYPE
9.0.30.1
Switchboards
CustAppr
DWG SIZE G.O.
DwgA
ITEM
SHEET
4 of 5
23
Feeder Breaker - Chassis Mtd-150A, 3P Frame 2 Branch Breaker [225A Frame], Trip 150A.,
Thermal Mag
Terminals, Mechanical, (1) #4-4/0
Neutral Terminal, (1) #6-350 kcmil
3
Main Breaker - Ind Mtd-4000A 3P Magnum SB Brkr SBN-C4N [Fixed-Manual], Trip 4000A.,
Digitrip 520MC LSI, 100 % rated
ARMS Operation - Local using breaker interface
Auxiliary Switch: 4A/4B
4
5
ta
nc
e
4000A Utility Metering - Public Service Electric & Gas (New Jersey)
ac
no
ty
et
op
en
fo
rO
rd
SOUTH CORE PANELS STRUCTURE:
PPL1-C, PPL1-D
PPL2-C, PPL2-D
PPL3-C, PPL3-D, PPL3-F
er
Why cant we use a fused
pressure switch in lieu of Main
Circuit Breaker?
ce
p
NORTH CORE PANELS STRUCTURE:
PPLB-1
PPL1-A, PPL1-B
PPL2-A, PPL2-B
PPL3-A, PPL3-B, PPL3-E
PPL4-C
south
core
north core
ct &
fire pump
service
disconnect
Q
uo
te
d
pr
ic
es
ar
e
ats
breakers
The information on this document is
created by Eaton Corporation. It is
disclosed in confidence and it is only to
be used for the purpose in which it is
supplied.
NEG-ALT Number
NARF1006X1K1-0000
PREPARED BY
DATE
WIN VANDERZEE
APPROVED BY
10/7/2021
Eaton
DATE JOB NAME
DESIGNATION
REVISION
0
SumterSC
Rehabilitation of Existing School- Charter School 278 SUSSEX AVE NEW
SWBD-C1
VERSION
TYPE
DRAWING TYPE
9.0.30.1
Switchboards
CustAppr
DWG SIZE G.O.
DwgA
ITEM
SHEET
5 of 5