Switchboard General Information Pow-R-Line Xpert - Specifications Quantity: 1 Alignment: Front Access/ Front and Rear Align Service: 208Y/120V 3-Phase 4-Wire Minimum Interrupt Rating: 100 kA Bus Specifications Bus Amps: 4000 Bus Bracing Rating: 100kA Neutral Amps: 4000 Bus Material: Aluminum Heat Test Ground Bus Material: Aluminum Ground Bus Bolted To Frame, (1) #6-350 kcmil Ground Lug Incoming Information Terminals, Mechanical, Bottom, (11) 3/0-750 kcmil ta nc ac ce p Structure Specifications Service Entrance Enclosure Type: Type 1 e Incoming Entry: Bottom Incoming Location: Right Incoming Qty & Size: (11) #4-500 kcmil Incoming Qty & Size: Terminals, Mechanical, Bottom, (11) 3/0-750 kcmil Qty Description Catalog Number rd Utility Specfications er Special Notes rO Struct # 5 en fo 4000 Amps Util. Mtr. Compt. - Public Service Electric & Gas (New Jersey) Plant Drawing: 42C1192 Code PSE& G op Enclosure properties ty et Struct # 1 50x chassis mounted feeders (Feeder Structure) no 2 Main device (Main Structure) Vertical isolating barrier ar e 3 Bussed structure with lugs for outgoing cable (Auxiliary Structure) es 4 Incoming Utility Structures (Incoming Utility Section) Horizontal isolating barrier Q uo te d pr ic 5 Description/Modifications Individually mounted feeder BREAKER exiting top (Feeder Structure) Vertical isolating barrier The information on this document is created by Eaton Corporation. It is disclosed in confidence and it is only to be used for the purpose in which it is supplied. NEG-ALT Number NARF1006X1K1-0000 PREPARED BY DATE WIN VANDERZEE APPROVED BY 10/7/2021 Eaton DATE JOB NAME DESIGNATION REVISION 0 SumterSC Rehabilitation of Existing School- Charter School 278 SUSSEX AVE NEW SWBD-C1 VERSION TYPE DRAWING TYPE 9.0.30.1 Switchboards CustAppr DWG SIZE G.O. DwgA ITEM SHEET 1 of 5 Please move (6) breakers from this structure and create a separate structure for south core feeder breakers. The intent is to create one structure for north and another for south. Please refer to last page for north vs south panelboards breakdown 1 1- Please see last page for desired arrangement. We would like the incoming section to be on the right side of the elevation (looking at front). PXM 1100 3 PD5 PD3-P 5 PD3 PD3 7 8 PD3 PD3 9 10 PD3 PD3 11 12 PD2 PD2 13 14 PD2 PD2 15 16 PD2 PD2 17 18 PD2 PD2 19 20 PD2 PD2 21 PD2 23 22 Front View Struct Depth 36 Width 30 PD2 * 1 SBN-C4N * 2 36 2- There will be no fire pump. Please delete tap section. However, the incoming pull section will be on the right hand-side. Bottom Outgoing Mechanical Terminals (11) #4-500 kcmil 3- Why cant we use 4000A fused pressure switch in lieu of 4000A main circuit breaker? e PD3 6 3 36 36 * 4 36 * 5 36 30 45 er ac 45 * ce p Frame 6 4 rO rd Power Flow fo For panels with 36 breakers, we will use 48" backboxes and make them all 42 breakers. ty et Top Cable Exit en See 1A32044 For Floor Plan Detail Top/Bottom Cable Exit For panelboard submittal but noted here as a reminder, for 54 breakers,can we use 48" backboxes? op Rear Floor Plan ta nc 2 24.00 12.00 24 3.00 39 30.00 3.00 24 3.00 3.00 39 3.00 pr ic es 3.00 30.00 no 2.50 ar e 2.50 te The information on this document is created by Eaton Corporation. It is disclosed in confidence and it is only to be used for the purpose in which it is supplied. NEG-ALT Number NARF1006X1K1-0000 2 45.00 1143 45.00 1143 36.00 914 36.00 914 90.00 2286 1451 658 d 1 30.00 762 30.00 762 36.00 914 36.00 914 90.00 2286 702 318 uo Q Structure Ship-Inches Ship-MM Wdth-Inches Wdth-MM Depth(Inner)-In. Depth(Inner)-MM Depth(Outer)-In. Depth(Outer)-MM Height-Inches Height-MM Weight-Lbs.(Est.) Weight-Kg.(Est.) PREPARED BY 3 36.00 914 36.00 914 36.00 914 36.00 914 90.00 2286 1098 498 APPROVED BY 10/7/2021 5 45.00 1143 45.00 1143 36.00 914 36.00 914 90.00 2286 990 449 Eaton DATE JOB NAME DESIGNATION 0 4 30.00 762 30.00 762 36.00 914 36.00 914 90.00 2286 644 292 DATE WIN VANDERZEE REVISION Total of 5 Structures, Total Weight of 4885 Weight-Lbs. Total of 5 Structures, Total Width of 186 Inches SumterSC Rehabilitation of Existing School- Charter School 278 SUSSEX AVE NEW SWBD-C1 VERSION TYPE DRAWING TYPE 9.0.30.1 Switchboards CustAppr DWG SIZE G.O. DwgA ITEM SHEET 2 of 5 Switchboard Units Information Str# Unit Description/Modifications Nameplate 1 Feeder Breaker - Ind Mtd-1600A 3P Frame 6 Breaker [2000A Frame], Trip 1600A., PXR20 LSI w/ ARMS, None ARMS Operation - Local using breaker interface Terminals, Mechanical, (6) #4-500 kcmil, Top Neutral Terminal, (6) #4-500 kcmil Blank Cover -1 X 2 PXM1100 Meter, 4000 Amp CTs, with Display 3 Feeder Breaker - Chassis Mtd-1200A, 3P Frame 5 Branch Breaker, [1200A Frame], Trip 1200A., PXR20 LSI w/ ARMS, None ARMS Operation - Local using breaker interface Terminals, Mechanical, (4) 4/0-500 kcmil Neutral Terminal, (4) #4-500 kcmil ce p ta nc 1 e 2 Feeder Breaker - Chassis Mtd-250A, 3P Frame 3 Branch Breaker [400A Frame], Trip 250A., Thermal Mag Terminals, Mechanical, (1) 2/0-500 kcmil Is it possible to Neutral Terminal, (1) #4-500 kcmil designate each feeder breaker with the 5 Feeder Breaker - Chassis Mtd-3P Frame 3 Provision, PROVISIONS FOR BREAKER ONLY corresponding panel Neutral Terminal, (1) #4-500 kcmil name to be served so we can check the lugs? 6 Feeder Breaker - Chassis Mtd-225A, 3P Frame 3 Branch Breaker [400A Frame], Trip 225A., Thermal Mag Terminals, Mechanical, (1) 2/0-500 kcmil Neutral Terminal, (1) #4-500 kcmil why upsize the frame to 400A? Question for Win: cant we have 225A frame 7 Feeder Breaker - Chassis Mtd-225A, 3P Frame 3 Branch Breaker [400A Frame], Trip 225A., is there a cheat instead and keep the LSI? Thermal Mag sheet that I can get Typical for other incidents Terminals, Mechanical, (1) 2/0-500 kcmil so I can determine Neutral Terminal, (1) #4-500 kcmil the backbox size vs the number of 8 Feeder Breaker - Chassis Mtd-225A, 3P Frame 3 Branch Breaker [400A Frame], Trip 225A., breakers which PXR10 LSI needs to be Terminals, Mechanical, (1) 2/0-500 kcmil provided? Neutral Terminal, (1) #4-500 kcmil ic es ar e no ty et op en fo rO rd er ac 4 Feeder Breaker - Chassis Mtd-225A, 3P Frame 3 Branch Breaker [400A Frame], Trip 225A., Thermal Mag Terminals, Mechanical, (1) 2/0-500 kcmil no ground fault protection. only Neutral Terminal, (1) #4-500 kcmil ground fault alarm. 10 Feeder Breaker - Chassis Mtd-250A, 3P Frame 3 Branch Breaker [400A Frame], Trip 250A., PXR20 LSIG/A, None Terminals, Mechanical, (1) 2/0-500 kcmil Neutral Terminal, (1) #4-500 kcmil Q uo te d pr 9 11 Feeder Breaker - Chassis Mtd-225A, 3P Frame 3 Branch Breaker [400A Frame], Trip 225A., Thermal Mag Terminals, Mechanical, (1) 2/0-500 kcmil which panel is this one for? Not sure we have 400/225? same for other breakers The information on this document is created by Eaton Corporation. It is disclosed in confidence and it is only to be used for the purpose in which it is supplied. NEG-ALT Number NARF1006X1K1-0000 PREPARED BY DATE WIN VANDERZEE APPROVED BY 10/7/2021 Eaton DATE JOB NAME DESIGNATION REVISION 0 SumterSC Rehabilitation of Existing School- Charter School 278 SUSSEX AVE NEW SWBD-C1 VERSION TYPE DRAWING TYPE 9.0.30.1 Switchboards CustAppr DWG SIZE G.O. DwgA ITEM SHEET 3 of 5 Feeder Breaker - Chassis Mtd-150A, 3P Frame 2 Branch Breaker [225A Frame], Trip 150A., Thermal Mag Terminals, Mechanical, (1) #4-4/0 Neutral Terminal, (1) #6-350 kcmil 13 Feeder Breaker - Chassis Mtd-150A, 3P Frame 2 Branch Breaker [225A Frame], Trip 150A., Thermal Mag Terminals, Mechanical, (1) #4-4/0 Neutral Terminal, (1) #6-350 kcmil 14 Feeder Breaker - Chassis Mtd-150A, 3P Frame 2 Branch Breaker [225A Frame], Trip 150A., Thermal Mag Terminals, Mechanical, (1) #4-4/0 Neutral Terminal, (1) #6-350 kcmil 15 Feeder Breaker - Chassis Mtd-150A, 3P Frame 2 Branch Breaker [225A Frame], Trip 150A., Thermal Mag Terminals, Mechanical, (1) #4-4/0 Neutral Terminal, (1) #6-350 kcmil 16 Feeder Breaker - Chassis Mtd-150A, 3P Frame 2 Branch Breaker [225A Frame], Trip 150A., Thermal Mag Terminals, Mechanical, (1) #4-4/0 Neutral Terminal, (1) #6-350 kcmil 17 Feeder Breaker - Chassis Mtd-150A, 3P Frame 2 Branch Breaker [225A Frame], Trip 150A., Thermal Mag Terminals, Mechanical, (1) #4-4/0 Neutral Terminal, (1) #6-350 kcmil 18 Feeder Breaker - Chassis Mtd-150A, 3P Frame 2 Branch Breaker [225A Frame], Trip 150A., Thermal Mag Terminals, Mechanical, (1) #4-4/0 Neutral Terminal, (1) #6-350 kcmil 19 Feeder Breaker - Chassis Mtd-150A, 3P Frame 2 Branch Breaker [225A Frame], Trip 150A., Thermal Mag Terminals, Mechanical, (1) #4-4/0 Neutral Terminal, (1) #6-350 kcmil 20 Feeder Breaker - Chassis Mtd-60A, 3P Frame 2 Branch Breaker [225A Frame], Trip 60A., PXR20 LSIG/A, None Terminals, Mechanical, (1) #14-1/0 Auxiliary switch: 1 NO & 1 NC Aux Contact (Integral) Neutral Terminal, (1) #14-1/0 21 Feeder Breaker - Chassis Mtd-150A, 3P Frame 2 Branch Breaker [225A Frame], Trip 150A., Thermal Mag Terminals, Mechanical, (1) #4-4/0 Neutral Terminal, (1) #6-350 kcmil Q uo te d pr ic es ar e no ty et op en fo rO rd er ac ce p ta nc 12 e Neutral Terminal, (1) #4-500 kcmil 22 Feeder Breaker - Chassis Mtd-100A, 3P Frame 2 Branch Breaker [225A Frame], Trip 100A., PXR20 LSIG/A, None Terminals, Mechanical, (1) #14-1/0 Auxiliary switch: 1 NO & 1 NC Aux Contact (Integral) Neutral Terminal, (1) #14-1/0 The information on this document is created by Eaton Corporation. It is disclosed in confidence and it is only to be used for the purpose in which it is supplied. NEG-ALT Number NARF1006X1K1-0000 PREPARED BY DATE WIN VANDERZEE APPROVED BY 10/7/2021 Eaton DATE JOB NAME DESIGNATION REVISION 0 SumterSC Rehabilitation of Existing School- Charter School 278 SUSSEX AVE NEW SWBD-C1 VERSION TYPE DRAWING TYPE 9.0.30.1 Switchboards CustAppr DWG SIZE G.O. DwgA ITEM SHEET 4 of 5 23 Feeder Breaker - Chassis Mtd-150A, 3P Frame 2 Branch Breaker [225A Frame], Trip 150A., Thermal Mag Terminals, Mechanical, (1) #4-4/0 Neutral Terminal, (1) #6-350 kcmil 3 Main Breaker - Ind Mtd-4000A 3P Magnum SB Brkr SBN-C4N [Fixed-Manual], Trip 4000A., Digitrip 520MC LSI, 100 % rated ARMS Operation - Local using breaker interface Auxiliary Switch: 4A/4B 4 5 ta nc e 4000A Utility Metering - Public Service Electric & Gas (New Jersey) ac no ty et op en fo rO rd SOUTH CORE PANELS STRUCTURE: PPL1-C, PPL1-D PPL2-C, PPL2-D PPL3-C, PPL3-D, PPL3-F er Why cant we use a fused pressure switch in lieu of Main Circuit Breaker? ce p NORTH CORE PANELS STRUCTURE: PPLB-1 PPL1-A, PPL1-B PPL2-A, PPL2-B PPL3-A, PPL3-B, PPL3-E PPL4-C south core north core ct & fire pump service disconnect Q uo te d pr ic es ar e ats breakers The information on this document is created by Eaton Corporation. It is disclosed in confidence and it is only to be used for the purpose in which it is supplied. NEG-ALT Number NARF1006X1K1-0000 PREPARED BY DATE WIN VANDERZEE APPROVED BY 10/7/2021 Eaton DATE JOB NAME DESIGNATION REVISION 0 SumterSC Rehabilitation of Existing School- Charter School 278 SUSSEX AVE NEW SWBD-C1 VERSION TYPE DRAWING TYPE 9.0.30.1 Switchboards CustAppr DWG SIZE G.O. DwgA ITEM SHEET 5 of 5