Download Busbars PS…BP-C and accessories For Miniature Circuit Breakers

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Resistive opto-isolator wikipedia , lookup

Rectifier wikipedia , lookup

Mercury-arc valve wikipedia , lookup

Stepper motor wikipedia , lookup

Ohm's law wikipedia , lookup

Electrical substation wikipedia , lookup

Buck converter wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Current source wikipedia , lookup

Three-phase electric power wikipedia , lookup

Voltage optimisation wikipedia , lookup

Stray voltage wikipedia , lookup

Mains electricity wikipedia , lookup

Metadyne wikipedia , lookup

Circuit breaker wikipedia , lookup

Distribution management system wikipedia , lookup

Alternating current wikipedia , lookup

Opto-isolator wikipedia , lookup

Surge protector wikipedia , lookup

Electrical wiring in the United Kingdom wikipedia , lookup

Transcript
Busbars PS…BP-C and accessories
For Miniature Circuit Breakers SU200 M, S200 UDC,
S200 U and S200 UP
Busbars type PS…BP-C are used
for fast and easy line side wiring
of miniature circuit breakers type
SU200 M, S200 UDC, S200 U and
S200 UP.
The entire product line, including the
accessories, is approved according to
UL 508 (cULus) and can be used for
applications in branch circuits as well
as supplementary protection in the US
and Canada.
Application and installation:
− − cULus listing according to UL508
− − Applicable in UL and CSA applications
− − For use with MCB types acc. UL489 (SU200 M, S200 UDC,
S200 U and S200 UP)
− − Fast and easy installation
− − Can be cut to length by the customer, as needed
− − Global use - can be used in UL, CSA, and IEC
applications
Product range:
−− 1-, 2-, 3-pole types
−− 25 mm² cross section
−− For MCBs with or without auxilliary contact
−− Can be cut to any length, as needed for each individual
application
−− Touch safe with the use of plastic covers installed over unused busbar pins
−− Rated current 100 A
−− Rated voltage 600 V AC/DC
− − End caps, tooth covers and feeder terminals as accessories
Technical data
Busbars PS…BP-C
Electrical data
Standards
UL508
EN 60947-1 / IEC 60947-1:2004
Rated voltage Ue
V
600 V AC/DC
Rated frequency
Hz
50 Hz (IEC) / 60 Hz (UL)
Rated impuls withstand voltage U imp.
kV
≥ 10 kV
A
100 A
A
200 A
kA
10 kA 3 cycles @ 600 V / 140 kA Fuse Class J 200 A
Rated current / phase
End fed
1)
Center fed
1)
Short circuit current rating
Mechanical data
Housing
grey, RAL 7035
Resistance to climatic conditions
acc. to DIN EN 60068
Isolation coordination
Overvoltage category
III
Pollution degree
2
Installation
Cross section
mm²
25 mm²
Mounting position
Optional
Supply
Feedin via cable or feeder terminal
Accessories
Shock protection caps
BSK BP-C
Endcaps
PS-END 3 BP-C
Feeder terminals
AST 35/58 BP-C
Approvals
conform to CE and RoHS
UL 508: cULus Listed
1)
Independently from the current rating of the feeder terminal or busbar, the current-carrying capacity/current rating of the MCB terminal must not be exceeded
Installation/assembly
Attention!
When busbars are cut, they must be deburred and completely cleaned of any dust and residual particles/parts from cutting
process. Touch-safe only when used with the required end caps.
Dimensional drawing
2 - 1SXP403004B0201
Ordering data
Cuttable
Busbars PS…BP-C for use with end caps PS-END 3 BP-C
No. Phase secquence
of
phases
No. of
pins
1
L1-L1-L1…
57
PS 1/57/25 BP-C
0.775
L1-Aux (free)-L1-Aux (free)…1)
37
PS 1/37/25 H BP-C
0.661
L1-L2-L1-L2…
56
PS 2/56/25 BP-C
0.969
2
pcs.
Weight
1 pc.
kg
L1-L2-Aux (free)-L1-L2-Aux (free)…
46
PS 2/46/25 H BP-C
0.943
L1-L2-L3-L1-L2-L3…
57
PS 3/57/25 BP-C
1.198
L1-L2-L3-Aux (free)-L1-L2-L3-Aux (free)…1)
48
PS 3/48/25 H BP-C
1.129
L1-Aux (free)-L2-Aux (free)-L3-Aux (free)…
39
PS 3/39/25 H BP-C
1.115
Description
Type
Weight
1 pc.
Tooth covers, for 3 pins
BSK BP-C
0.005
End caps
PS-END 3 BP-C
0.001
Feeder terminal
AST 35/58 BP-C
0.045
1)
3
1)
1)
Type
for devices with auxiliary contact (half module) after each phase sequence
Accessories
kg
1SXP403004B0201 - 3
ABB Canada
2117, 32e Avenue
Lachine, QC H8T 3J1
Tel: 514-420-3100
Toll free: 1-800-567-0283
Fax: 514-420-3137
Website: www.abb.ca
While all care has been taken to ensure that the information
contained in this publication is correct, no responsibility
can be accepted for any inaccuracy. The Company reserves
the right to alter or modify the information contained herein
at any time in the light of technical or other developments.
Technical specifications are valid under normal operating
conditions only. The Company does not accept any
responsibility for any misuse of the product and cannot be
held liable for indirect or consequential damages.
© Copyright 2016 ABB Inc. All rights reserved.
Brochure number 1SXP403004B0201 June 2016