* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Download ASCO 7000 SERIES MVATS GB IEC Suggested Specifications
Electrical ballast wikipedia , lookup
Power inverter wikipedia , lookup
Power over Ethernet wikipedia , lookup
Pulse-width modulation wikipedia , lookup
Immunity-aware programming wikipedia , lookup
Power engineering wikipedia , lookup
Current source wikipedia , lookup
Resistive opto-isolator wikipedia , lookup
History of electric power transmission wikipedia , lookup
Variable-frequency drive wikipedia , lookup
Power MOSFET wikipedia , lookup
Stray voltage wikipedia , lookup
Three-phase electric power wikipedia , lookup
Surge protector wikipedia , lookup
Electrical substation wikipedia , lookup
Power electronics wikipedia , lookup
Voltage optimisation wikipedia , lookup
Buck converter wikipedia , lookup
Alternating current wikipedia , lookup
Switched-mode power supply wikipedia , lookup
SUGGESTED SPECIFICATION For Automatic Transfer Switches PART 1 - GENERAL 1.01 Scope Furnish and install automatic transfer switches (ATS) with 3 poles, amperage, voltage, and withstand ratings as shown on the plans. Each automatic transfer scheme shall consist of a medium voltage circuit breaker transfer pair and a microprocessor controller to provide automatic operation. 1.02 Codes and Standards The automatic transfer switchgear shall conform to the requirements of: A. IEC62271-200 – AC Metal Enclosed Switchgear and Control Gear for rated voltages above 1kV and up to 52kV B. IEC 60694 – Common Specification for High Voltage Switchgear and Control Gear C. IEC 62271-100 High Voltage alternating current circuit breakers D. IEC 60529 Degrees of protection provided by enclosures (IP Codes) E. GB3906-2006 Alternating-current metal-enclosed switchgear and controlgear for rated voltages above 3.6kV and up to and including 40.5kV 1.03 Acceptable Manufacturers Automatic transfer switches shall be ASCO 7000 Series. Any alternate shall be submitted for approval to the consulting engineer at least 10 days prior to bid. Alternate bids must list any deviations from this specification. The equipment to be supplied shall provide the highest reliability and the greatest ease of maintenance. The manufacturer shall have experience in the design, building, testing and service of this type equipment and be able to document their qualifications. Only suppliers with the ability and experience to provide this type of system shall be acceptable. 1.04 Ratings The rating of the transfer system shall be 12 kilo Volts, 2500 A, 31.5 kA Short Circuit Rating 1.05 Documentation A. Submittals for approval shall include the following: a. Outline drawing showing conduit entry areas and anchoring information. b. Sequence of operation. c. One Line Drawing B. Operation and maintenance manuals shall be supplied when the equipment is shipped. A quantity of four (4) shall be required. The manuals shall contain: a. Sequence of Operation b. Installation Instructions c. Maintenance Instructions d. Material Summary e. Complete Drawings f. Component Instructions 3/1/2015 Page 1 g. Spare Parts Information 1.06 Testing The equipment shall be factory tested to simulate a complete and integrated system. The circuit breakers supplied shall be installed in their actual positions and electrically and mechanically tested. A narrative of the system operation shall be provided and shall be utilized when testing the equipment. Copies of the test reports shall be submitted to the engineer. 1.07 Warranty – See separate Warranty Document. PART 2 – PRODUCTS 2.01 Mechanically Held Transfer Switch A. The transfer switch shall consist of two electrically operated medium voltage circuit breakers and be mechanically held. The switch shall not be electrically interlocked if Closed Transition operation is desired. B. All standard door-mounted switches and pilot lights shall be 16-mm industrial grade type or equivalent for easy viewing & replacement. Standard Automatic Transfer Switch Door controls shall be provided. C. The switch shall be positively locked and unaffected by momentary outages, so that contact pressure is maintained at a constant value and contact temperature rise is minimized for maximum reliability and operating life. D. Structure a. All equipment bases shall be fabricated with an adequate number of anchor bolt holes designed to put the base in direct contact with the concrete pad when bolted. b. All doors shall be pan type and be provided with sufficient hinges and stiffeners to support the door and components for an absolute minimum deflection and wobbling when opening or closing. Doors must operate more than 90 degrees. E. Layout - All equipment shall be arranged in a logical manner to facilitate ease of operation and maintenance of the equipment. F. Paint - The complete assembly shall be thoroughly cleaned and treated prior to painting. The unit shall be painted light gray with paint suitable for indoor locations. G. Bus - Main bus shall be rated 2500 amps and shall be fabricated from copper. . H. Locks - Front doors shall be supplied with a lockable handle. All door locks shall be keyed alike to operate from a single key and one key shall be supplied for each lock 2.02 Microprocessor Controller A. The controller's sensing and logic shall be provided by a single built-in microprocessor for maximum reliability, minimum maintenance, and the ability to communicate serially through an optional serial communication module. B. Voltage sensing shall be true RMS type and shall be accurate to 1% of nominal voltage. Frequency sensing shall be accurate to 0.2%. The panel shall be capable of operating over a temperature range of -20 to +60 degrees C and storage from -55 to +85 degrees C. C. The controller shall be connected to the transfer switch by an interconnecting wiring harness. The harness shall include a keyed disconnect plug to enable the controller to be disconnected from the transfer switch for routine maintenance. Sensing and control logic shall be provided on multi-layer printed circuit boards. Interfacing relays shall be industrial grade plug-in type with dust covers. The panel shall be enclosed with a protective cover and be mounted separately from the transfer switch unit for safety and ease of 3/1/2015 Page 2 maintenance. The protective cover shall include a built-in pocket for storage of the operator’s manuals. D. All customer connections shall be wired to a common terminal block to simplify field-wiring connections. E. The controller shall meet or exceed the requirements for Electromagnetic Compatibility (EMC) as follows: a. EN 55011:1991 Emission standard - Group 1, Class A b. EN 50082-2:1995 Generic immunity standard, from which: c. EN 61000-4-2:1995 Electrostatic discharge (ESD) immunity d. ENV 50140:1993 Radiated Electro-Magnetic field immunity e. EN 61000-4-4:1995 Electrical fast transient (EFT) immunity f. EN 61000-4-5:1995 Surge transient immunity g. EN 61000-4-6:1996 Conducted Radio-Frequency field immunity PART 3 - OPERATION 3.01 Sequence of Operation A. When the normal side voltage drops to a preset value (adjustable from 70% to 98%), the phase sensing relay(s) open and from the transfer control panel, after a one second delay (adjustable from 0 to 6 sec.), a signal is sent to start the engine generator. B. When the engine generator reaches 90% of the rated voltage (adjustable from 85% to 100%) and 95% of rated frequency (adjustable from 90% to 100%), the normal side breaker is tripped open. Immediately the emergency side breaker is closed (adjustable time delay 0 to 1 minute supplied standard, set at 0). The transfer switch load is now connected to the emergency source. C. When normal source voltage is restored to 90% of rated value, the normal side phase sensing relays pick up (adjustable from 85% to 100%). After an adjustable time delay (0 to 60 minutes), the transfer control panel directs the emergency side breaker to open and immediately after that the normal side breaker closes. D. At the moment of retransfer to normal source, an adjustable time delay (0 to 60 minutes) initiates, and after cool down timing period, the engine is stopped. 3.01 Controller Display and Keypad A. A four line, 20 character LCD display and keypad shall be an integral part of the controller for viewing all available data and setting desired operational parameters. Operational parameters shall also be available for viewing and limited control through the serial communications input port. The following parameters shall only be adjustable via DIP switches on the controller: a. Nominal line voltage and frequency b. Single or three phase sensing c. Operating parameter protection d. Transfer operating mode configuration e. (Open transition, Closed transition, or Delayed transition) B. All instructions and controller settings shall be easily accessible, readable and accomplished without the use of codes, calculations, or instruction manuals. 3.02 Voltage, Frequency and Phase Rotation Sensing A. Voltage and frequency on both the normal and emergency sources (as noted below) shall be continuously monitored, with the following pickup, dropout, and trip setting capabilities (values shown as % of nominal unless otherwise specified): 3/1/2015 Page 3 B. C. D. E. F. a. Undervoltage N&E, 3 Phase - 70 to 98% Dropout / Reset 85 to 100% of Dropout b. Overvoltage N&E, 3 Phase -102 to 115% Dropout / Reset 2% below trip c. Under frequency N&E - 85 to 98% / Reset 90 to 100% of trip d. Over frequency N&E - 102 to 110% / Reset 2% below trip e. Voltage unbalance N&E - 5 to 20% / Reset 1% below trip Repetitive accuracy of all settings shall be within ± 0.5% over an operating temperature range of -20C to 60C. Voltage and frequency settings shall be field adjustable in 1% increments either locally with the display and keypad or remotely via serial communications port access. The controller shall be capable (when activated by the keypad or through the serial port) of sensing the phase rotation of both the normal and emergency sources. The source shall be considered unacceptable if the phase rotation is not the preferred rotation selected (ABC or CBA). Source status screens shall be provided for both normal & emergency to provide digital readout of voltage on all 3 phases, frequency, and phase rotation. The controller shall include a user selectable algorithm to prevent repeated transfer cycling to a source on an installation which experiences primary side, single phase failures on a Grounded Wye – Grounded Wye transformer which regenerates voltage when unloaded. The algorithm shall also inhibit retransfer to the normal (utility) source upon detection of a single phasing condition until a dedicated timer expires, the alternate source fails, or the normal source fails completely and is restored during this time delay period. The time delays associated with this feature shall be adjustable by the user through the controller keypad and LCD. 3.03 Time Delays A. An adjustable time delay of 0 to 6 seconds shall be provided to override momentary normal source outages and delay all transfer and engine starting signals. Capability shall be provided to extend this time delay to 60 minutes by providing an external 24 VDC power supply. B. A time delay shall be provided on transfer to emergency, adjustable from 0 to 60 minutes, for controlled timing of transfer of loads to emergency. C. Two time delay modes (which are independently adjustable) shall be provided on retransfer to normal. One time delay shall be for actual normal power failures and the other for the test mode function. The time delays shall be adjustable from 0 to 60 minutes. Time delay shall be automatically bypassed if the emergency source fails and the normal source is acceptable. D. A time delay shall be provided on shut down of engine generator for cool down, adjustable from 0 to 60 minutes. E. A time delay activated output signal shall also be provided to drive an external relay(s) for selective load disconnect control. The controller shall have the ability to activate an adjustable 0 to 5 minute time delay in any of the following modes: a. Prior to transfer only. b. Prior to and after transfer. c. Normal to emergency only. d. Emergency to normal only. e. Normal to emergency and emergency to normal. f. All transfer conditions or only when both sources are available. F. The controller shall also include the following built-in time delays for optional Closed Transition and Delayed Transition operation: a. 1 to 5 minute time delay on failure to synchronize normal and emergency sources prior to closed transition transfer. 3/1/2015 Page 4 b. 0.1to 9.99 second time delay on an extended parallel condition of both power sources during closed transition operation. c. 0 to 5 minute time delay for the load disconnect position for delayed transition operation. G. All time delays shall be adjustable in 1 second increments, except the extended parallel time, which shall be adjustable in .01 second increments. H. All time delays shall be adjustable by using the LCD display and keypad or with a remote device connected to the serial communications port. 3.04 Additional Features A. A three position momentary-type test switch shall be provided for the test / automatic / reset modes. The test position will simulate a normal source failure. The reset position shall bypass the time delays on either transfer to emergency or retransfer to normal. B. A SPDT contact, rated 5 amps at 30 VDC, shall be provided for a low-voltage engine start signal. The start signal shall prevent dry cranking of the engine by requiring the generator set to reach proper output, and run for the duration of the cool down setting, regardless of whether the normal source restores before the load is transferred. C. Auxiliary contacts, rated 10 amps, 250 VAC shall be provided consisting of one contact, closed when the ATS is connected to the normal source and one contact closed, when the ATS is connected to the emergency source. D. LED indicating lights (16 mm industrial grade, type 12) shall be provided; one to indicate when the ATS is connected to the normal source (green) and on to indicate when the ATS is connected to the emergency source (red). E. LED indicating lights (16 mm industrial grade, type 12) shall be provided and energized by controller outputs. The lights shall provide true source availability of the normal and emergency sources, as determined by the voltage sensing trip and reset settings for each source. F. Two-pole double throw contacts that operate when: (1) emergency source voltage is present at transfer switch terminals equivalent to ASCO accessory 18B and; (2) normal source voltage is present at transfer switch terminals. This feature shall be equivalent to ASCO accessory 18B & 18G. G. Standard load-shedding circuit initiated by removal of customer supplied control voltage as specified by user. This feature shall be equivalent to ASCO accessory 30B H. Selective load disconnect control contacts (two provided) which operate with time delay prior to and/or after load transfer and retransfer. The feature shall be equivalent to ASCO 31Z. The following features shall be built-in to the controller, but capable of being activated through keypad programming or the serial port only when required by the user: Provide the ability to select “commit/no commit to transfer” to determine whether the load should be transferred to the emergency generator if the normal source restores before the generator is ready to accept the load. J. The controller shall be capable of accepting a normally open contact that will allow the transfer switch to function in a non-automatic mode using an external control device. K. Engine Exerciser - The controller shall provide an internal engine exerciser. The engine exerciser shall allow the user to program up to seven different exercise routines. For each routine, the user shall be able to: a. Enable or disable the routine. b. Enable or disable transfer of the load during routine. c. Set the start time, . I. 3/1/2015 Page 5 i. time of day ii. day of week iii. week of month (1st, 2nd, 3rd, 4th, alternate or every) d. Set the duration of the run. At the end of the specified duration the switch shall transfer the load back to normal and run the generator for the specified cool down period. A 10-year life battery that supplies power to the real time clock in the event of a power loss will maintain all time and date information. The following feature shall be built - into the controller, but capable of being activated through keypad programming or the communications interface port. Note: The transfer switch will operate in a non-automatic mode with this feature activated. L. Terminals shall be provided for a remote contact which opens to signal the ATS to transfer to emergency and for remote contacts which open to inhibit transfer to emergency and/or retransfer to normal. Both of these inhibit signals can be activated through the keypad or serial port. M. System Status - The controller LCD display shall include a “System Status” screen which shall be readily accessible from any point in the menu by depressing the “ESC” key a maximum of two times. This screen shall display a clear description of the active operating sequence and switch position. For example, Normal Failed Load on Normal TD Normal to Emerg 2min15s Controllers that require multiple screens to determine system status or display “coded” system status messages, which must be explained by references in the operator’s manual, are not permissible. N. Self-Diagnostics - The controller shall contain a diagnostic screen for the purpose of detecting system errors. This screen shall provide information on the status input signals to the controller which may be preventing load transfer commands from being completed. O. Communications Interface – The controller shall be capable of interfacing, through an optional serial communication module, with a network of transfer switches, locally (up to 4000 ft.) or remotely through modem serial communications. Standard software specific for transfer switch applications shall be available by the transfer switch manufacturer. This software shall allow for the monitoring, control and setup of parameters. P. Data Logging – The controller shall have the ability to log data and to maintain the last 99 events, even in the event of total power loss. The following events shall be time and date stamped and maintained in a nonvolatile memory: a. Event Logging i. Data and time and reason for transfer normal to emergency. ii. Data and time and reason for transfer emergency to normal. iii. Data and time and reason for engine start. iv. Data and time engine stopped. v. Data and time emergency source available. vi. Data and time emergency source not available. b. Statistical Data i. Total number of transfers. ii. Total number of transfers due to source failure. iii. Total number of days controller is energized. iv. Total number of hours both normal and emergency sources are available. 3/1/2015 Page 6 Q. Optional Communications Module - A full duplex RS485 and/or Ethernet interface shall be installed in the ATS controller to enable serial or Ethernet communications. The communications module shall be capable of a direct connect or multi-drop configured network. This module shall allow for the seamless integration of existing or new communication transfer devices. The serial communication interface shall be equal to ASCO Accessory 72EE2. R. External DC Power Supply – An optional provision shall be available to connect an external 24 VDC power supply to allow the Control Panel and indicators to function when both power sources are dead. This option shall be equivalent to ASCO accessory 1G. Part 4 - Switchgear Description 4.1 Switchgear Type The offered switchgear is an air-insulated, type-tested, metal-enclosed and metal-clad medium voltage switchgear for indoor installation. This switchgear complies with IEC 62271-200 and therefore fulfils the following classifications: Loss of service continuity category: LSC 2B (metallic partition, i.e. separate partitions for busbar, switching device and connection compartments) Partition class PM (metallic partition) Internal arc classification: IAC A FLR 4.2 Panel Design in Modular Construction, Partitions A switchgear panel consists of the following compartments: Busbar compartment Switching device compartment Connection compartment Low-voltage compartment The individual sheet-steel compartments are bolted together to one switchgear panel. Separation walls to the adjacent panels are always double. Doors and lateral switchgear end walls are powder-coated with resistant epoxy resin, all other walls are galvanized. The complete enclosure and the partitions between the individual compartments and covers are metallic and earthed. This guarantees the highest possible service continuity category LSC 2B of the switchgear (metal-clad design) and the highest possible personal safety with partition class PM according to IEC 62271-200. The loss of service continuity category LSC 2B allows access to compartments while other adjacent compartments remain in operation. For example, it is possible to maintain the connection compartment or switching device compartment of one panel, without de-energizing all other compartments of the adjacent panels including the busbar. In this way, the category LSC 2B provides the highest possible service continuity. The individual compartments are pressure-resistant, so that - in case of an internal fault (arc fault) no burn through of partitions and no re-ignition in adjacent compartments occur. 3/1/2015 Page 7 In case of an arc fault, pressure is generally relieved upwards in all three compartments. The switchgear is tested for resistance to internal faults according to IEC 62271-200 and fulfills all criteria of the internal arc classification IAC A FLR according to IEC 62271-200. It is therefore adequate for universal installation and access from all sides. The partition class PM ensures that only earthed steel sheets can be touched during access to the individual compartments. This guarantees the highest possible personal safety during maintenance work. 4.3 Busbar compartment The busbar compartment contains the three-phase busbars made of round-edge standard profile copper, the panel bars and the bushing-type insulators with the fixed contacts. The shutter for visual inspection of the fixed contacts can be opened and closed individually in the switching device compartment. Busbars are bolted from panel to panel. Accessibility of busbar is possible after removing of partitions. In this way, access to the busbar compartment is “tool-based” according to IEC 62271-200. Possible additional components (voltage transformers, earthing switch, and bus riser) are mounted in a separate additional compartment. 4.4 Switching Device Compartment The switching-device compartment can be equipped with the following devices: Vacuum circuit-breaker withdrawable Disconnecting link withdrawable Metering device withdrawable. It is mandatory that the mechanical position indicators and control elements of the respective switching devices are visibly integrated in a mimic diagram in the door of the switching device compartment. In connection with the logical mechanical interlocking system. While racking from the service to the test position or vice versa, the withdrawable part opens or closes the metal shutters (positively driven) covering the fixed contacts in the connection and busbar compartments. The connection of the low-voltage wiring between the withdrawable part and the fixed part of the panel is done via a 64-pole plug connection. Generally, the low-voltage wiring is laid in metallic ducts with removable covers. In connection with the door interlock, access to the switching device compartment is “interlockbased” according to IEC 62271-200. The application of maintenance-free vacuum circuit-breakers reduces the maintenance and shutdown times. In comparison with other switching technologies, this increases the switchgear availability and reduces the maintenance costs. Using the vacuum technology as quenching medium, arc quenching in the circuit-breaker does not produce any highly toxic decomposition products. 4.5 Interlocks 3/1/2015 Page 8 Following interlocking conditions specified according to IEC 62271-200 / VDE 0671-200 are fulfilled: Feeder earthing switch can only be operated with switching device in disconnected position Switching device can only be racked on the movable part with the associated switching device in OPEN position and with feeder earthing switch OPEN Switching device can only be operated in interlocked disconnected or service position Switching of switching device in ON position only possible with plugged low voltage Connection Beyond the specification of standards: Moving of withdrawable part only possible with closed high voltage door Coding prevents insertion of switching device with a lower rated normal current into panels with higher rated normal current optionally electromagnetic interlocks, mechanical key interlocking systems or padlocks Operator safety is guaranteed by the above mentioned interlocks and operations The circuit-breaker and make-proof earthing switch are type-tested in the panel according to IEC 62271-200. 4.6 Connection Compartment The connection compartment can contain the following components: Cable sealing ends resp. bar connection Current transformers or bushing type insulators Make-proof earthing switch Voltage transformers Surge arresters or limiters Earthing busbar Zero-sequence current transformers The shutter for visual inspection of the fixed contacts can be opened and closed individually in the switching device compartment. The lower partition is bolted and offers access to the connection compartment from the front during installation. Cable connection is optionally possible from the front or the rear. With cable connection from the front, the connection compartment is an “interlock-based and tool-based accessible compartment” according to IEC 62271-200. With cable connection from the rear, access is “tool-based”. Cable testing equipment respectively cable testing adapters can be easily connected without detaching the cables. For this purpose, the shutters can be opened and locked separately. To guarantee personal safety, the shutters of the busbar compartment are optionally equipped with a padlock. 4.7 Low-Voltage Compartment 3/1/2015 Page 9 The low-voltage compartment is located at the front. It is completely partitioned off the rest of the panel and can be removed from the panel. Electrical connections between the withdrawable part and the fixed part of the panel are performed with flexible wires and a 64-pole low-voltage plug connection. Current transformer leads are wired to terminals in the low-voltage compartment. All other panel-internal circuits are wired to 10-pole connectors and plugged in the low-voltage compartment. Bus wires are laid from panel to panel in the upper part of the low-voltage compartment and are pluggable. Secondary devices are installed in the door of the low-voltage compartment and on a mounting plate with a top-hat rail system. The wires are laid in wiring ducts with a sufficient cross-section. Part 5 - Standards IEC-Standards GB3906-2006 Name Alternating-current. metal-enclosed switchgear and controlgear for rated voltages above 3.6 kV and up to and including 52 kV IEC 62271-200 A.C. metal-enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 52 kV IEC 62271-1 Common clauses for high-voltage switchgear and controlgear standards IEC 62271-100 High-voltage alternating current circuit-breakers IEC 60529 Degree of protection provided by enclosures (IP-code) IEC 62271-102 High-voltage alternating current disconnectors and earthing switches IEC 62 271-105 High-voltage alternating current switch-fuse Combinations IEC 60 071 - 1 Insulation co-ordination for equipment in three-phase systems above 1 kV IEC 60 282 - 1 Current limiting fuses IEC 61 243-5 Working under voltage - Voltage detectors – Part 5: Voltage detection systems 3/1/2015 Page 10 Part 6 - Switchgear Data Installation........................................................................................................................Indoor Number of phases ................................................................................................................... 3 Busbar system..................................................................................................... Single busbar Rated voltage...................................................................................................................12 kV Operating voltage .......................................................................................................... 10 kV Rated frequency ...........................................................................................................50/60 Hz System neutral earthing................................................................ Isolated or resonant-earthed Rated short-duration power-freq. withstand voltage .........................................................20 kV Rated lightning impulse withstand voltage ........................................................................60 kV Ambient air temperature ................................................................................................... 40 °C Rated normal current of busbar......................................................................................2500 A Max permissible busbar current at 40 °C........................................................Same as Above A Busbar insulation .................................................................................................................with Bus bar transverse partition............................................................................................without Rated short-time withstand current................................................................................ 31.5 kA Rated duration of short-circuit............................................................................................... 4 s Rated peak withstand current ...........................................................................................80 kA Rated short-circuit breaking current............................................................................... 31.5 kA Rated short-circuit making current.....................................................................................80 kA Degree of protection for enclosure .................................................................................... IP4X Degree of protection for partitions ..................................................................................... IP2X Loss of service continuity category.................................................................................LSC2B Partition class .......................................................................................................................PM Internal arc classification ..................................................................................................... IAC Type of accessibility front / lateral / rear ..........................................................................A FLR Type of Installation.................................................................................................Wallstanding Internal arc fault current.................................................................................................31.5 kA Arc-fault duration ............................................................................................................... 1,0 s Cable access from ............................................front (wallstanding) or front/rear (freestanding) Panel width .............................................................................................................see drawing Panel depth.............................................................................................................see drawing Panel height................................................................................................................ 2300 mm Height of switchgear room ( min. ).............................................................................. 2800 mm Type of packing Seaworthy crate for 6 months transport and storage Acceptance test No Factory acceptance test included. Color of switchgear....................................................................................................RAL 7035 Other details as per scope of supply, single-line diagram and/or constructional data. 3/1/2015 Page 11 Part 7 - Scope of Supply The switchgear is designed as single-busbar switchgear. In case of customer-specific designs, some points of the switchgear description might not be valid anymore. The offered scope of supply is listed in detail as follows: Qty Description 2 1 1 Lot Switching device panel 2500 A - Maximum permissible current at 40°C: 2500 A Busbar connection panel 2500 A Switchgear accessories 7.1. Switching device panel 7.1.1. Busbar Compartment - Busbar cross-section Cu 1x100x10 mm, Insulated. 7.1.2. Switching Device Compartment - Circuit Breaker withdrawable part 7.1.2.1. Operating mechanism withdrawable part: Hand operated 7.1.2.2. Auxiliary switch withdrawable part: 4 NC + 4 NO 7.1.2.3. Electromagnetic interlocking: DC 220 V 7.1.2.4. Mechanical padlocking 7.1.2.5. Vacuum circuit breaker 7.1.2.6. Technical data: 12.0 kV / 31.5 kA / 2500 A 7.1.2.7. Operating mechanism circuit breaker: motor 7.1.2.8. Voltage of motor operating mechanism: DC 220 V 7.1.2.9. Voltage of closing solenoid: DC220 V 7.1.2.10. One shunt release 7.1.2.11. Voltage 1st tripping coil: DC 220 V 7.1.2.12. Auxiliary switch circuit breaker: 12 NC + 12 NO 7.1.3. Connection Compartment 7.1.3.1. Panel connection 7.1.3.1.1. Cable connection from bottom 7.1.3.1.2. 2 cables per phase 7.1.3.1.3. Single-core cable 300 to 500 mm2 7.1.3.2. Capacitive voltage indicator on the connection side – N.A 7.1.3.3. Earthing switch on the cable connection (Optional) 7.1.3.3.1. Earthing switch with short-circuit making capability 7.1.3.3.2. Short-circuit current and duration: 31.5 kA / 3s 7.1.3.3.3. Auxiliary switch: 4 NO + 4 NC 7.1.3.3.4. Operating mechanism: Hand operated 7.1.3.4. Quantity (3) Voltage transformer on cable connection(Optional) 7.1.3.4.1. Voltage transformer, fixed-mounted 7.1.3.4.2. 3 x 1-pole with earth-fault winding 7.1.3.4.3. Primary voltage 12 / v3 kV 7.1.3.4.4. Voltage of secondary winding 120 V / v3 7.1.3.4.5. Rating and class of secondary winding 100 VA / Cl. 1 7.1.3.4.6. Voltage of earth-fault winding 120 V / v3 3/1/2015 Page 12 7.1.3.4.7. Rating and class of earth-fault winding For damping, limit current 6 A 7.1.3.5. Quantity (3) Current transformers 2500:5 Ratio (Optional) 7.1.3.6. Low Voltage Compartment - Height 630 mm 7.1.3.6.1. Protective Relay (Optional) 7.2. Busbar connection panel 7.2.1. Busbar Compartment - Busbar cross-section Cu 1x100x10 mm, insulated 7.2.2. Switching Device Compartment – Empty 7.2.3. Connection Compartment 7.2.3.1. Cable connection from bottom 7.2.3.2. 2 cables per phase 7.2.3.3. Single-core cable 300 to 500 mm2 7.2.3.4. Quantity (3) Current transformers - 2500:5 Ratio (Optional) 7.2.4. Low Voltage Compartment – Height 630 mm 7.2.4.1. All ATS Controls 7.2.4.2. Load Power Meter Accessory 135L (Optional) 7.3. Switchgear accessories 7.3.1. One Standard accessory set consisting of: 7.3.1.1. 1 hand crank for charging spring of circuit breaker 7.3.1.2. 1 Push rod for actuating the ON/OFF push buttons 7.3.1.3. 1 Hand lever for moving withdrawable part 7.3.1.4. 1 socket spanner for high voltage and low voltage door 7.3.1.5. 1 Installation manual and operation manual (in selected language) 7.3.2. Two end walls 7.3.3. 1 Hand lever for shutter mechanism 7.3.4. 1 Wall panel for accessories 7.3.5. 1 Tube of Vaseline (250 g) for connecting coppers 7.3.6. 1 Touch-up pen for minor paint damages, colour RAL7035 3/1/2015 Page 13 *Note Spec Writer: The following sections are optional and the section should be deleted if not used. 5. OPTIONAL FEATURES 5.1 Optional Power Meter – Accessory 135L A. SCOPE - Provide a power metering device for collecting real-time power system information. The meter shall be plug and play with all ASCO PowerQuest CPMS systems and support open protocols. B. CODES AND STANDARDS - The Power Meter shall conform to the requirements of: 1. UL 3111-1 – Electrical Measuring and Testing Equipment 2. CAN/CSA-C22.2 No. 23-M89 – CSA Safety Requirements for Electrical and Electronic Measuring and Test Equipment. 3/1/2015 C. PRODUCT 1. The power meter shall be capable of operating without modification at a nominal frequency of 45 to 66 Hz. 2. The Power Meter shall be rated for an operating temperature of -4° F to 158° F and a storage temperature of -22° F to 176° F. And shall be rated for an 85% non-condensing, relative humidity. 3. The Power Meter shall accept inputs from industry standard instrument transformers (120 VAC secondary PT’s and 5A secondary CT’s). Direct phase voltage connections, 0 to 600VAC nominal, shall be possible without the use of PT’s. 4. The Power Meter shall accept single, 3 phase, or three & four wire circuits. A fourth CT input shall be available to measure neutral or ground current. The Power Meter shall contain a built-in discrete contact to wire an ATS 14A auxiliary contact to indicate switch position. 5. The Power meter shall accept AC voltage from the sensing lines for operation. Additional provisions shall be provided for external DC voltage input range 9-36VDC with a nominal of 24VDC. 6. The power meter shall be equipped with a continuous duty, long-life, 4 line x 20 character green backlit LCD. 7. All setup parameters required by the Power Meter shall be stored in nonvolatile memory and retained in the event of a control power interruption. 8. The Power Meter shall be flush mountable on a surface. 9. The power meter enclosure shall be sealed to IP-51 (NEMA 1) and the faceplate shall be sealed to IP-65 (NEMA 4). All push buttons shall be sealed tact switches. D. COMMUNICATION 1. The Power Meter shall send, when prompted, information to a central location equipped with a manufacturer supplied critical power management system or 3rd party monitor through manufacturer supplied Page 14 communication modules. All 3rd party monitors must utilize industry standard open protocols Modbus/RTU, Modbus/TCP or SNMP. 2. An embedded RS-485 port will be provided which will enable communication at 9600, 19.2K, 38.4K or 57.6K baud. DIP switches will be provided on the RS-485 port allowing a user to select 2-wire or 4-wire communication as well as the option to activate a terminating resistor on the port. E. OPERATION 1. NEC 220 Compliance - The meter shall help facilities comply with NEC 220. It shall provide Maximum Demand calculations for the past 24 months, as per standards with 15 minute averages. Monitored and Calculated Data The following data will be available on the display and Modbus registers of the Power Meter: Line-to-neutral voltages (VAN, VBN and VCN) Line-to-neutral voltage average (VAVE) Line-to-line voltages (VAB, VBC and VCA) Line-to-line voltage average (VLAVE) Current on each phase (IA, IB and IC) Current on the neutral conductor(IN) Average current(IAVE) Active power, KW per phase and total (W A, W B, WC and WT) Reactive power, KVAR per phase and total (VARA, VARB, VARC and VART) Apparent power, KVA per phase and total (VAA, VAB, VAC and VAT) KW Hours importing, exporting and net (KWHIMP, KWHEXP, and KWHNET) KVAR Hours leading, lagging and net (KVARHLEAD, KVARHLAG, and KVARHNET) Power factor (PF) Signal frequency (Hz) Digital Input F. 3/1/2015 COMMUNICATIONS INTERFACE 1. Ethernet - The meter shall be plug and play via ACAN and TTL ports to a 72E (5150) to provide Ethernet capability. 2. Languages: The Power Meter shall offer an LCD which can display no less than nine different languages. 3. Interface: A. Displaying each of the metered values shall be done through the use of menu scroll buttons. There will be an escape button which will be used to take the user back to the previous page or to cancel a setting change. Pressing escape no more than three times will return the user to the home screen. B. For ease of operator viewing, the display can be configured to remain on continuously, with no detrimental effect on the life of the Power Meter Page 15 C. The display’s contrast shall be configurable in intervals of 10 % (ranging 0%-100%). D. Setup of system requirements shall be allowed from the front of the Power Meter 5.2 PROTECTIVE RELAYS - Accessory 118FN (On Normal Side) & 118FE (On Emergency Side) A. B. C. D. E. F. Shall be NR NSR612RF-DS or XJ (is coming..) Feeder Protection System Provides primary circuit protection on distribution networks at any voltage level Three Phase & Ground Time Overcurrent Phase & Ground Instantaneous overcurrent IEC/BS142 Curves RS 485 2-Wire Communication Standard 5.3 ASCO Communications Interface - Accessory 72EE2 Connectivity Module: For direct interfacing with vendor’s Transfer Switches. Shall allow the vendor’s monitoring products to monitor and control the transfer switch equipment with the implementation of 128-Bit AES encryption standard. An embedded webpage shall be provided for switch status, metered values and list of up to 99 events in the log. Modbus TCP and Simple Network Management Protocol (SNMP) shall be shall be supported for open monitoring of ASCO products. Hardware will include: A. B. C. D. E. 3/1/2015 QTY (1) – 10/100 Mbps Ethernet port QTY (1) – RS-485 port QTY (1) – 24 VDC power input for optional usage DIN Rail Mountable Onboard Status LED’s shall be provided for the following: a. Power b. Transmitting Data c. Receiving Data d. Communication Failure Page 16