Download Synchronous Generator.

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Wireless power transfer wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Spark-gap transmitter wikipedia , lookup

Voltage optimisation wikipedia , lookup

Coilgun wikipedia , lookup

Buck converter wikipedia , lookup

Utility frequency wikipedia , lookup

History of electric power transmission wikipedia , lookup

Electric power system wikipedia , lookup

Mains electricity wikipedia , lookup

Resonant inductive coupling wikipedia , lookup

Three-phase electric power wikipedia , lookup

Rectiverter wikipedia , lookup

Amtrak's 25 Hz traction power system wikipedia , lookup

Brushless DC electric motor wikipedia , lookup

Alternating current wikipedia , lookup

Electrification wikipedia , lookup

Brushed DC electric motor wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Power engineering wikipedia , lookup

Commutator (electric) wikipedia , lookup

Stepper motor wikipedia , lookup

Electric motor wikipedia , lookup

AC motor wikipedia , lookup

Induction motor wikipedia , lookup

Electric machine wikipedia , lookup

Transcript
DKT 123
AC Machine
AC Machine
 Alternating current (ac) is the primary source of electrical
energy.
 It is less expensive to produce and transmit than direct
current.
 For this reason, and because ac voltage is induced into the
armature of all generators, ac machines are generally more
practical.
 May function as a generator (mechanical to electrical) or a
motor (electrical to mechanical)
DC Machine & AC machine
• DC motor - ends of the coil
connect to a split ring to 'rectify'
the emf produced
• AC motor - no need rectification,
so don't need split rings.
AC Motor
As in the DC motor case,
• a current is passed through
the coil, generating a torque
on the coil.
• Since the current is
alternating, the motor will
run smoothly only at the
frequency of the sine wave.
AC Generator
• This process can be described in terms of Faraday's law
when you see that the rotation of the coil continually
changes the magnetic flux through the coil and therefore
generates a voltage
Generator and Motor
How Does an Electric Generator Work?
Classification of AC Machines
 Two major classes of machines;
i) Synchronous Machines:
• Synchronous Generators: A primary source of
electrical energy.
• Synchronous Motors: Used as motors as well as
power factor compensators (synchronous condensers).
ii) Asynchronous (Induction) Machines:
• Induction Motors: Most widely used electrical motors in
both domestic and industrial applications.
• Induction Generators: Due to lack of a separate field
excitation, these machines are rarely used as generators.
Synchronous Machine
 Origin of name: syn = equal, chronos = time
 Synchronous machines are called ‘synchronous’ because
their mechanical shaft speed is directly related to the power
system’s line frequency.
 the rotating air gap field and the rotor rotate at the same
speed, called the synchronous speed.
 Synchronous machines are ac machine that have a field
circuit supplied by an external dc source.
– DC field winding on the rotor,
– AC armature winding on the stator
Synchronous Machine
 Synchronous machines are used primarily as generators of
electrical power, called synchronous generators or
alternators.
 They are usually large machines generating electrical power
at hydro, nuclear, or thermal power stations.
 Synchronous motors are built in large units compare to
induction motors (Induction motors are cheaper for smaller
ratings) and used for constant speed industrial drives
 Application as a motor: pumps in generating stations, electric
clocks, timers, and so forth where constant speed is desired.
Synchronous Machine
The frequency of the induced voltage is related to the rotor speed by:
where P is the number of magnetic poles
fe is the power line frequency.
Typical machines have two-poles, four-poles, and six-poles
Synchronous Machine
Construction
• Energy is stored in the inductance
• As the rotor moves, there is a change in
the energy stored
• Either energy is extracted from the
magnetic field (and becomes mechanical
energy – motor)
• Or energy is stored in the magnetic field
and eventually flows into the electrical
circuit that powers the stator – generator
Synchronous Machine
Construction
• DC field windings are mounted on the (rotating) rotor
- which is thus a rotating electromagnet
• AC windings are mounted on the (stationary) stator
resulting in three-phase AC stator voltages and
currents
 The main part in the synchronous machines are
i) Rotor
ii) Stator
Synchronous Machine
Rotor
 There are two types of rotors used in synchronous
machines:
i) cylindrical (or round) rotors
ii) salient pole rotors
 Machines with cylindrical rotors are typically found in
higher speed higher power applications such as
turbogenerators. Using 2 or 4 poles, these machines
rotate at 3600 or 1800 rpm (with 60hz systems).
 Salient pole machines are typically found in large (many
MW), low mechanical speed applications, including
hydrogenerators, or smaller higher speed machines (up to
1-2 MW).
 Salient pole rotors are less expensive than round rotors.
Synchronous Machine – Cylindrical rotor
D1m
Turbine
L  10 m
Steam

High speed

3600 r/min  2-pole

Stator
winding
N
Uniform air-gap
Stator
1800 r/min  4-pole
 Direct-conductor cooling (using
hydrogen or water as coolant)

d-axis
q-axis
Rotor
winding
Rotor
Rating up to 2000 MVA
S
Turbogenerator
Synchronous Machine – Cylindrical rotor
Stator
Cylindrical rotor
Synchronous Machine – Salient Pole
1. Most hydraulic turbines have to turn at low speeds
(between 50 and 300 r/min)
2. A large number of poles are required on the rotor
d-axis
Non-uniform
air-gap
N
D  10 m
q-axis
S
S
Turbine
Hydro (water)
Hydrogenerator
N
Synchronous Machine – Salient Pole
Stator
 Synchronous machine rotors are simply rotating electromagnets built
to have as many poles as are produced by the stator windings.
 Dc currents flowing in the field coils surrounding each pole magnetize
the rotor poles.
 The magnetic field produced by the rotor poles locks in with a rotating
stator field, so that the shaft and the stator field rotate in synchronism.
 Salient poles are too weak mechanically and develop too much wind
resistance and noise to be used in large, high-speed generators driven
by steam or gas turbines. For these big machines, the rotor must be a
solid, cylindrical steel forging to provide the necessary strength.
 Axial slots are cut in the surface of the cylinder to
accommodate the field windings.
 Since the rotor poles have constant polarity they must be
supplied with direct current.
 This current may be provided by an external dc generator or
by a rectifier.
 In this case the leads from the field winding are connected to insulated
rings mounted concentrically on the shaft.
 Stationary contacts called brushes ride on these slip rings to carry
current to the rotating field windings from the dc supply.
 The brushes are made of a carbon compound to provide a good
contact with low mechanical friction.
 An external dc generator used to provide current is called a
“ brushless exciter “.
Synchronous Machine
Stator
 The stator of a synchronous machine carries the armature or load
winding which is a three-phase winding.
 The armature winding is formed by interconnecting various
conductors in slots spread over the periphery of the machine’s stator.
Often, more than one independent three phase winding is on the
stator. An arrangement of a three-phase stator winding is shown in
Figure below. Notice that the windings of the three-phases are
displaced from each other in space.
Synchronous Machine
Construction
 Stator
Synchronous Machine
Magnetomotive Forces (MMF’s) and Fluxes Due to Armature
and Field Windings
Flux produced by a stator winding
Synchronous Machine
Magnetomotive Forces (MMF’s) and Fluxes Due to Armature
and Field Windings
Synchronous Machine
Magnetomotive Forces (MMF’s) and Fluxes Due to Armature
and Field Windings
Two Cycles of mmf around the Stator
Synchronous Generator
Equivalent circuit model – synchronous generator
 If the generator operates at a terminal voltage VT while supplying a
load corresponding to an armature current Ia, then;
 In an actual synchronous machine, the reactance is much greater
than the armature resistance, in which case;
 Among the steady-state characteristics of a
synchronous generator,
its voltage regulation and power-angle characteristics are the most
important ones. As for transformers, the voltage regulation of a
synchronous generator is defined at a given load as;
Synchronous Generator
Phasor diagram of a synchronous generator
The phasor diagram is to shows the relationship among the
voltages within a phase (Eφ,Vφ, jXSIA and RAIA) and the current IA in
the phase.
Unity P.F (1.0)
Synchronous Generator
Lagging P.F
Leading P.F.
Synchronous Generator
Power and Torque
In generators, not all the mechanical power going into a
synchronous generator becomes electric power out of the machine
The power losses in generator are represented by difference between
output power and input power shown in power flow diagram below
Synchronous Generator
Losses
Rotor
- resistance; iron parts moving in a magnetic field causing
currents to be generated in the rotor body
- resistance of connections to the rotor (slip rings)
Stator
- resistance; magnetic losses (e.g., hysteresis)
Mechanical
- friction at bearings, friction at slip rings
Stray load losses
- due to non-uniform current distribution
Synchronous Generator
The input mechanical power is the shaft power in the generator given by equation:
The power converted from mechanical to electrical form internally is given by
The real electric output power of the synchronous generator can be expressed in line
and phase quantities as
and reactive output power
Synchronous Generator
In real synchronous machines of any size, the armature resistance
RA is more than 10 times smaller than the synchronous reactance
XS (Xs >> RA). Therefore, RA can be ignored
Synchronous Motor
Synchronous Motor
Power Flow
Example : Synchronous Generator.

A three-phase, wye-connected 2500 kVA and 6.6 kV generator
operates at full-load. The per-phase armature resistance Ra and the
synchronous reactance, Xd, are (0.07+j10.4).
Calculate the percent voltage regulation at
(a) 0.8 power-factor lagging, and
(b) 0.8 power-factor leading.
Solution.