* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Download 1.7 Design, manufacture, assembly and installation requirement
Survey
Document related concepts
Ground (electricity) wikipedia , lookup
History of electric power transmission wikipedia , lookup
Opto-isolator wikipedia , lookup
Stray voltage wikipedia , lookup
Three-phase electric power wikipedia , lookup
Electrical substation wikipedia , lookup
Buck converter wikipedia , lookup
Voltage optimisation wikipedia , lookup
Switched-mode power supply wikipedia , lookup
Alternating current wikipedia , lookup
Distribution management system wikipedia , lookup
Mains electricity wikipedia , lookup
Transcript
Volume-III of IV Table of Contains 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 1.10 1.11 1.12 2.0 2.1 2.2 2.3 2.4 3.0 3.1 3.2 3.3 3.4 3.5 4.0 4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 4.9 4.10 4.11 4.12 4.13 4.14 4.15 4.16 4.17 4.18 4.19 General ............................................................................................................................ 214 Scope of Work ................................................................................................................ 214 Standard .......................................................................................................................... 214 Climatic Condition .......................................................................................................... 215 Operating Condition ....................................................................................................... 215 System Data .................................................................................................................... 216 Insulation Co-ordination ................................................................................................. 216 Design, manufacture, assembly and installation requirement ........................................ 216 Name plates, Identification and Miscellaneous items .................................................... 217 Corrosion and Deterioration Protection .......................................................................... 218 Panting and Finishing ..................................................................................................... 218 Earthing ........................................................................................................................... 218 Test and Approval ........................................................................................................... 218 THREE PHASE POWER TRANSFORMER ................................................................ 221 Technical Requirement ................................................................................................... 221 Windings ......................................................................................................................... 222 LOW TENSION SWITCHGEAR .................................................................................. 224 AUTOMATIC POWER FACTOR IMPROVEMENT (PFI) PANELS ......................... 228 BUS-BAR TRUNKING (BBT) ...................................................................................... 231 Technical Requirement ................................................................................................... 231 Specification of BBT System ......................................................................................... 232 Construction and Assembly of BBT ............................................................................... 232 Test …………………………………………….233 Installation ...................................................................................................................... 233 DIESEL GENERATOR ................................................................................................. 233 Engine ............................................................................................................................. 233 Cooling............................................................................................................................ 234 Filter ................................................................................................................................ 234 Engine Protection ............................................................................................................ 234 Fuel Injection Equipment................................................................................................ 234 Exhaust............................................................................................................................ 234 Lubrication ...................................................................................................................... 235 Silencer ........................................................................................................................... 235 Radiator ........................................................................................................................... 235 Governor ......................................................................................................................... 235 Coupling.......................................................................................................................... 235 Mounting ......................................................................................................................... 235 Fuel storage ..................................................................................................................... 235 Starting ............................................................................................................................ 235 Battery Charger ............................................................................................................... 236 Generator ........................................................................................................................ 236 Voltage Regulator ........................................................................................................... 236 Wave form ...................................................................................................................... 236 Insulation ........................................................................................................................ 236 E. Sub-Station & Generator 211 Volume-III of IV 4.20 4.21 4.22 4.23 4.24 Control Panel .................................................................................................................. 237 Finish .............................................................................................................................. 237 Country of origin ............................................................................................................ 237 The tenderer must furnish the following......................................................................... 237 Automatic Change over Switch ...................................................................................... 238 E. Sub-Station & Generator 212 Volume-III of IV E. SUB-STATION EQUIPMENT, BUS-BAR TRUNKING AND GENERATOR E. Sub-Station & Generator 213 Volume-III of IV E. Sub-Station Equipment, Bus-Bar Trunking and Generator 1.0 General The specification for the part of the contract mentioned below cover design, manufacture, assemble, testing and commissioning of Sub-station equipment, Bus-bar trunking up to 22nd floor roof level and supply, installation, testing and commissioning of diesel generator at Padma Oil Company Ltd. Head Office Building, Agrabad, Chittagong. 1.1 Scope of Work The scope of work and obligation of the specification consists the following as minimum: 1.2 Design, manufacture, assemble, test and delivery at site, installation, testing and commissioning of sub-station equipment, bus-bar trunking and generator in accordance with all requirement of specification, design and standard. Supply and delivery of all consumables, equipment and spares needed for installation, testing and commissioning. Assemble, pre-wire .and test at factory of all necessary equipment and accessories i.e. controls, protection relays, space heater, interfacing tem1inals etc. Supply and delivery of spare parts according to the requirement for one year or for agreeable period. Carry out of all routine workshop tests and its complete documentation for all equipment and machine and to provide all necessary documentation for site testing and commissioning. Complete documentation of Sub-Station equipment, bus-bar trunking and generator and its additional equipment and spares including revision up to the end of commissioning. Type test certificate for manufacture/fabrication/assembly of all major equipment must be attached with the bid. Standard The sub-station equipment, bus-bar trunking and diesel generator must be of the latest International Standard. Particular attention is to be paid to the Electricity Act 1910 and Electricity Rules 1937 (as amended in 1946). The following main standard shall be followed for design, manufacture, assemble, installation, test and commissioning of this project: International Electro technical Commission Institute of Electrical and Electronics Engineers Institute of Electrical Engineers British Standard E. Sub-Station & Generator -IEC -IEEE -IEE -BS 214 Volume-III of IV 1.3 Japan International standard American National Standard Institute National Electrical Manufacturers Association German International Standard International Standard Organization Bangladesh National Building Code -J.I.S -ANSI -NEMA -VDE -ISO -BNBC Climatic Condition The following site conditions shall be considered. If there are specific design conditions given in the specification, design and data sheet, they shall take preference. 1.4 Ambient temperature: Maximum temperature occurs during the period from April to May reaching 45°C (110°F), Annual mean temperature: approximately 29°C (84°F) Relative humidity: April to May 60% to 70% during rainy season, from June to September, the average Relative Humidity is 80% and reaches extreme values up to saturation point during longer periods. Rainfall: Maximum intensity from June to September is 200mm to 250mm. The climate is tropical and has Marked Monsoon character with seasonal changes from humid and warm in rainy season to cool and dry in winters. Operating Condition The High tension (HT) switch gear, Transformer, Low tension (LT) switch gear, power factor correction capacitor, Bus-bar trunking and Diesel Generator shall be suitable for continuous operation at above mentioned climatic condition. The equipment, except bus-risers, will be located at Ground Floor level of the office complex and the bus bar trunking will run from sub-station L.T. panel through the bus-duct along lift core at the middle of main tower building upto 22nd floor roof level. The main power supply shall be controlled from Sub-station or Electrical room and each floor area or consumer will have their local control switches at their respective floor. The local unit control equipment is described at later part of this specification. All protective system shall be functional at all times. The equipment and distribution boards described in the specification shall have guaranteed standard and of safe and secured supply condition at all possible operation condition. E. Sub-Station & Generator 215 Volume-III of IV 1.5 System Data The following values for power supply distribution system are standard In Bangladesh. Normal System voltage (HT) Maximum system Voltage (HT) Normal system voltage (LT) Operating voltage (LT) Maximum permissible (LT) Frequency 1.6 : 11KV : 12 KV : 15/231 V : 400/231 V : 457/263 V : 50 Hz Insulation Co-ordination The insulation level for vacuum Circuit Breaker, dropout fuse, load break switch, lightning arrester and transfom1er are specified below. Max. Service voltage and rated voltage shall be according to IEC standard. According to IEC standard service voltage Maximum service voltage shall be considered The respective test voltage shall be Impulse withstands test voltage (BIL) Power frequency withstands test voltage Lightning arrestor standard voltage 1.7 : 11 KV : 12 KV : 75 KV : 28 KV : 12 KV Design, manufacture, assembly and installation requirement All materials, equipment, accessories shall be designed, manufactured, installed, tested and commissioned according to standard indicated in item 1.2 of this specification, and modem Engineering practice. All parts of equipment & installation must be suitable in every respect for continuous operation at maximum out put under various pem1issible load and climatic condition. The Switchgear shall meet the following recommendations: 1.7.1 H.T. switchgear IEC 298/694 L.T. switchgear assemblies IEC 439-1 Circuit Breakers IEC 56 Voltage Transformer IEC 186 Current Transformer IEC 185 Relays IEC 255 LV wires IEC 695 Country of Origin The country of origin of all components to be supplied under this contract shall be: UK/ USA/ GERMANY/ FRANCE/JAPAN E. Sub-Station & Generator 216 Volume-III of IV 1.7.2 Pre-Shipment Inspection The Contractor shall be obliged to arrange pre-shipment inspection of all major equipment, such as Transformer, Bus-bar trunking, HT & LT Switchgear component and Generator at the factory where those equipment are manufactured and assembled. The inspection shall be done by the Employer or Consultant or by any authorized representative of the Employer, to the factory or factories, which country of origin, the Contractor mentioned in their bid as country of origin of such equipment. 1.8 Name plates, Identification and Miscellaneous items The Contractor shall supply and install the following in the Padma Oil Company Ltd. Head Office Building Sub-station: 1.8.1 Name Plates The final identification of all parts of the system shall be done after commissioning. Engraved nameplates shall be provided on each part of the system, For example, for each switchgear line up and for each compartment in each line up. The nameplates shall be of approved design and type. During commissioning, all equipment shall be provided with temporary identification sticker. The Contractor shall indicate same identification of all parts in their as-built drawings. 1.8.2 Identification All functional devices such as circuit breakers, bus-bars, feeders etc shall be provided with standard and approved type of identification. The Contractor shall indicate same identification of devices, feeders etc. in their as-built drawings. 1.8.3 Danger Sing Regulation type "DANGER" sign, "NO ADMITTANCE" notices etc. shall be installed in all switch room entry door as per requirement of BPDB/ DESA/ DESCO. 1.8.4 Rubber Mat The Contractor shall provide in front of all the High Voltage switchgear a rubber mat of 6mm thickness and. 1000mm width in continuous roll for the full length of the switchgear room. 1.8.5 Single Line Diagram A copy of single line diagram shall be suitably framed and mounted in the switchgear room. 1.8.6 Audible Alarms Audible alarms shall be provided in the Switchgear room. They shall be manually switching off type. E. Sub-Station & Generator 217 Volume-III of IV 1.9 Corrosion and Deterioration Protection The Contractor shall provide protection against corrosion and deterioration protection of all materials supplied and installed. 1.10 Panting and Finishing Protective painting shall be done for all equipment in accordance with general practice and recognized methods as per the paint manufactures and in according to the current edition of DIN 55928 "Corrosion protection of steel structure" to meet the tropical condition at site. The cubicle shall be epoxy polyester power finish, finely structured and color shall be RAL 7032 (pebble-grey) 1.11 Earthing Each electrical equipment must be provided with minimum one earth terminal of sufficient size as per IEE, IEC standard and specification of equipment manufacturer. The sub-station equipment, bus-bar trunking, and all other electrical installation shall be provided with earthing, earth pit as per design, standard schedule and direction of Engineer. 1.12 Test and Approval All equipment, material and workmanship which require any form of approval by the Bangladesh Government or a Local Authority, like BPDB, DESA, DESCO, Bangladesh Licensing Board, Bangladesh T & T Board, Bangladesh Fire Department, and so on, must be appropriately approved and satisfactorily passed all necessary inspection and test procedure imposed by them. The test personnel must be qualified and approved by the concerned department of Bangladesh Government. The Test procedure, Test equipment, etc., must satisfy the requirement of international standards [item 1.2 of this specification] as well as, the respective department of Bangladesh Government. The switchgear shall be provided with earth switch to be interlocked with VCB. Provision shall be made for earthing of cables by means of earthing switch of quick make type, able to earth the cables when CB is in the disconnected position. The earthing switch shall be located in the cable compartment and shall be operated from the front to any cubicle and independent on the action of the operator. The earthing device shall be able to close against the rated S.C. current. Padlock facilities shall be fitted to enable the earthing switch to be locked in both positions. The position of the integral earthing shall be visible from the front of the switch board. Mechanical interlocks shall be provided to avoid any mal operation such as: a) Closing of the earthing switch when breaker is in service position E. Sub-Station & Generator 218 Volume-III of IV b) Inserting the breaker when the earthing switch is in closed position. Integral earthing of the breaker transfer type shall not be accepted. A capacitor divider shall be fitted near the earthing switch. It shall be connected to a neon bulb indicator of the potential tester located in the front side of the panel. 1.12.1 Disconnecting Switches The disconnecting switches shall have rated voltage of 12KV and rated current 630A with rated S.C current 16KA. The disconnector switch shall only operate under no load conditions, suitable interlocks with C.B. shall be provided and indication as well of no load (OFF) and load (ON) conditions. There shall be interlocks so as to prevent the cable being earthed when the disconnecting switch is in ON position. Similarly there shall be interlock to prevent any operation when the disconnecting switch is in Earthing position to ON position. The switch shall not operate direct from ON to Earth position. Disconnecting switch shall be simple, robust, maintenance free, life expectancy over 20 years and as per JEC 196 and ANSI 37.32 or equivalent standard. 1.12.2 Vacuum Switch Rated voltage 12 KV Operating voltage 11 KV No. of Pole =3 Interrupting chamber = Vacuum at 10-5 to 10-6 Torr Life = Over 20 years S.C. current = 16 KA Closing coil and Trip coil shall operate at 100 Volt AC/DC Standard JIS C460S or ANSI-C 37 1.12.3 Current Transformer (C.T) The transformer must comply with BS 3938, VDE 0414 and IEC 185 The C.T. should be cast resin insulated with class 5P10 for protection and class 0.5 for metering. The rated over current factor and burden should be matching with operating burden of the connected equipment to prevent the instruments from being damaged. 1.12.4 Potential Transformer (P.T) Potential transformer must comply with IEC 186. The P.T. should be cast resin insulated with class 0.5 for metering and class 1 for protection and burden minimum 50VA. E. Sub-Station & Generator 219 Volume-III of IV They shall be on one phase, connected phase to earth Auxiliary contacts shall be connected in series in the secondary circuits so as to open these circuits when the voltage transformer are in the isolated position. The secondary windings shall be suitably insulated and shall be protected by MCB's. 1.12.5 IDMT Relay The relay for over current and earth fault protection should be of solid state (microcomputer operated). Minimum setting for over current, earth fault and short circuit protection including the A.C/D.C converter should be fitted on a draw-out Double Europe Format (DEF) module. This draw-out module can be housed in a standard case, in which the module is plugged, should have one screw and one snap on each terminal for the plant connections. The heavy-duty current plug connector should provide automatic shorting of the C.T circuits whenever the module is withdrawn. A make-before-break earth contact should be there to ensure protective earthing, before the other plug connections can be made. The relay should be suitable for D.C. shunt tripping to be operated by 100V D.C. voltage from PT. secondary through a rectifier. 1.12.6 Under Voltage Relay These shall be such that the breaker is arranged to trip on a falling Voltage of between 85% and 60% of the rated voltage. The relays shall automatically reset when the voltage recovers to above 85% of the rated voltage. The relay shall be operated by 100V or 100V D.C. as the type may be from P.T. secondary through rectifier. 1.12.7 Wiring and Instrumentation Wiring cable inside the cubicles shall be minimum 1.5sq. mm and with tinned copper conductors. Current circuits shall be made with minimum 2.5 sq. mm and with tinned copper conductors. The HT switchgear shall have voltmeter, ammeter, frequency meter, and all other meters and indicating lamps as per design and standard. All cubicles, frames, transformers, measuring and relay circuits shall have protective earthing with provision for external earth connection. The VCB/ SF-6 shall be provided with recorder for its operation The protection system shall consist of over current and earth fault protection and under voltage as well. E. Sub-Station & Generator 220 Volume-III of IV The bidder shall enclose details of system they proposes, along with single line diagram, detailed technical specification, manufacturers catalogue and mode of operation of protection system, with their offer. Complete physical dimensions and electrical characteristics of the equipment offered shall be furnished along with the offer. 1.12.8 KWH Meter Digital type three phase energy meter for recording 11 kv supply voltage from BPDB/ DESA/ DESCO is to be installed in the 11kv switchgear panel as it is shown in the 11kv switchgear design. The meter shall have maximum Demand Indicator (MDI) and shall be capable of recording energy consumption at two-part tariff, peak hours and off peak hours. Necessary accessories for installation and for complete function of the meter, such as CT, PT, conductors, mounting devices, protection items, earthing terminals etc complete shall be inclusive of this item. The meter, its installation and function must comply with the requirement of BPDB, DESA, DESCO or any other related Authority. 2.0 THREE PHASE POWER TRANSFORMER The Transformer shall be dry type, cast resin insulated and suitable for parallel operation. 2.1 Technical Requirement The dry type transformer shall comply with BS 171, IEC 726, VDE 0532 etc. and the general specification as a minimum will be as follows: Installation Transformer Rated frequency Terminals : Indoor type power : 50 Hz : HT and L T to be brought out in separate. HT suitable for XLPE/ PVC Cable of size 185 sq.mm LT suitable for BBR Connection Rated primary voltage Rated secondary voltage Tap changing Vector group L.V. neutral Bill Level (H.T side) Maximum system voltage E. Sub-Station & Generator : 11 KV : 0.415 KV : ± 2.5%, ±5% (Off Load) : Dyn 11 : Brought out : 75 KV : 12 KV (H.T. side) 221 Volume-III of IV 0.5 KV (L.T. side) Cooling Degree of Protection : Air Natural : IP20 2.1.1 Insulation The transformer shall be manufactured with class F insulation on the high tension side (permissible average winding temperature rise l00K) and class F on Low Tension side (permissible average winding temperature rise l00K). The transformer shall be supplied with a degree of protection IP20. The basic insulation level for HT side and LT side shall be 75 KV and 2.5 KV respectively. Clamping parts and chases: RAL 5009, coils RAL 3016 or any other approved color. 2.1.2 Iron Core The three limbs of the Iron core shall be arranged in the same plan and interconnected by yokes. The core shall consist of grain oriented laminations which will be insulated on both sides. The core limb laminations shall be mitered at the joints to the yoke. . 2.2 Windings 2.2.1 High Tension Winding The high-tension coils should be wound together with a high-grade insulation sheet from aluminium strip and potted under vacuum up to the terminals. The external insulation shall comprise of mixture of epoxy resin and quartz powder to make the winding maintenance free, damp proof and suitable for service in the tropical atmosphere. Re-connectable tapping links in the high-tension winding shall permit adjustment to the system condition. They shall be mounted on the low-voltage side of the transformer. 2.2.2 Low Tension Winding Aluminium shall be used for low-tension strip winding. The width of the aluminium strip shall be equal to the coil length to considerably reduce the axial short circuit forces. The conductor and insulating material shall be bonded together by heat treatment and form a compact unit which will be scaled against moisture. 2.2.3 Winding Clamping A clamping frame shall hold the iron core and coils together. The coils shall be supported by resilient spacer blocks, which shall provide effective coil-to-coil and core-to-core damping. Lifting eyes and earthing bolts will be fitted to the top and bottom clamping frame members respectively. E. Sub-Station & Generator 222 Volume-III of IV 2.2.4 Temperature Monitoring The temperature monitoring system shall protect the transformer winding against overheating due to increased ambient temperature or overload and shall permit utilization of the full transformer power at any required load cycle without hazard to the transformer. The transformer shall be fitted with two temperature monitoring system as standard equipment. One shall be connected to give an alarm & the other for tripping. The response temperature difference between the two systems shall be 20º K. The tripping unit required for the monitoring system shall be located in the medium or low-voltage distribution cubicles. 2.2.5 Time- delay relay As the control supply for the temperature monitoring system will be taken from the secondary side of the protected transformer, it will be necessary to incorporate a time delay relay. This relay shall bridge the time that elapses from the instant of transformer switch on unit to the relay in the tripping unit picks up and will interrupt the tripping circuit. 2.2.6 Temperature Sensor The response temperature of the sensor shall be, selected by the manufacturer according to the class of insulation involved and the mounting position in the winding. The sensors shall be connected to terminals mounted on the top of the clamping frame. The temperature sensors shall be temperature sensitive resistors connected in series and shall be embedded in the three low-tension windings. A specific increase in their resistance shall cause the contacts to operate (1 NO + 1 NC). 2.2.7 Noise Special design measure shall reduce the noise level of cast-resin dry type transformer. 2.2.8 Terminal Connection High Voltage As special safety, precaution shall be required against accidental contact with live parts, the terminal link strip shall be equipped with contacts to receive cable lugs. All unquoted and live metal parts on the high-tension side of the transformer shall be protected with flame inhibiting polycarbonate. Low Voltage The low-tension phase and neutral terminals shall be arranged at the top for Bus-Bar Trunking (BBT) or cable connection as per design. 2.2.9 Transformer Earthing E. Sub-Station & Generator 223 Volume-III of IV The brought out transformer neutral shall be, solidly earthed by same size earth conductor, to the separate earth pit. 2.2.10 Structure Borne Noise Suppression The transformer shall have structure borne noise reduction unit and it will be a metal/rubber element, which shall be shaped to securely anchor the transfom1er at the point of installation. 2.2.11 Truck The transformer shall be equipped with a truck with plain wheels for travel lengthways or sideways. The truck shall be bolted to the lower clamping frame members and shall have four towing eyes. 2.3 LOW TENSION SWITCHGEAR The Low Tension Switchgear shall be prefabricated, pre-wired, freestanding, type tested, locally assembled by approved assembler conforming to IEC 439-1 and ISO 9001 for 415V, 3-Phase, 4-wire, 50Hz operation. 2.3.1 Switchgear Design The switchgear shall be pre-fabricated, complete and ready for erection on the site. The switchgear shall be totally enclosed, and suitable for indoor installation. All parts shall be adequately and efficiently protected against accidental touching. The switchgear cubicles shall confom1 to relevant provisions of BSIIECNDE and shall be adequate in all respect to accommodate the cables, circuit breakers, meters, cable termination's and interconnection as indicated in the schedule, specifications, design, and be provided with lockable doors. All apparatus & components shall be easily accessible from the front as required for inspection, replacement and repair. The switchgear shall be of tropical design, suitable for climatic condition (item-1.3) The switchgear shall conform to the following data: Operating voltage Frequency Frequency Number of bus-bars Bus-bar materials Degree of protection of Bus-bar chamber Maximum protective current (Cos. phai = 0.2, t = 0.1 see) of bus-bar Rated short time withstands Current of bus-bar Maximum protective peak Current of bus bar Rated Impulse withstand voltage Rated Insulation voltage E. Sub-Station & Generator : 415 V : 50 Hz : 5(LI, L2, L3 N & PE) : Copper (HDBC) : IP41 : 80 KA : 40 KA : 17 KA : 8 KV : 1000 V 224 Volume-III of IV The Switchgear shall be designed to withstand internal arcing faults confom1ing to PEHLA guideline No.2 i.e. 50KA (m1s), Coso=0.2, t=0.2 sec. for a symmetrical short circuit current of 50KA during 1 second as a minimum. All parts of the switchgear including apparatus shall be designed to withstand without being damaged, the mechanical and thermal strain of the prospective short circuit current or, where protected by circuit breaker, the interrupting current of the circuit breaker. As Type and Routine Tests laid down in IEC form the basis for verifying the characteristics of tested switchgear assemblies, the bidder shall submit the necessary type test results of the proposed LT switch gear. Routine tests shall be, done in manufacturer's factory in presence of the Employers representative before shipment of the equipment. 2.3.2 All cables, feeders, buses shall be provided with approved type of identification Outgoing cables shall be arranged in separate spacious cable chambers. Protective screens shall be arranged between main bus-bar and cable space. Terminals for power cables shall be protected against accidental touch. Interior control writing shall be accommodated in flexible plastic conduits. Wiring inside the cubicles shall be made with minimum l.5mm2 and with tinned conductors. The switchgear shall be suitable for bus-bar trunking entry, if required as per design and schedule. The switchgear shall be suitable for additional space of approximately 20% for future extension. The switchgear shall be arranged strictly in accordance with the layout drawing and direction of Engineer. The switchgear shall be of modular type design. The apparatus of each functional group shall be assembled on a common base. Cubicle Construction The distribution sections shall be of carcass construction and the carcass shall be augmented with various cladding plates as required. The cubicle shall be dust and vermin proof. The sheet steel metal thickness shall be minimum (16SWG) 1.5mm for door, top plate, bottom plate, side, back plate and 14SWG (2.0mm) for frame, module mounting plate respectively. The top plate, bottom plate and side plates shall be possible to pull for easy removal. Rear access door shall be provided. The paint of the plate shall be semi-textured powder spray finish with polyester compound, color RAL 7032-pebble gray or other approved color. The paint thickness shall be minimum 0.5mm and chemical resistant to paraffin benzola petrol. Dilute acids (10%), dilute alkalis (10%) E. Sub-Station & Generator 225 Volume-III of IV Creepage and clearance paths shall conform to VDE0l10 insulation group C or UL508 table 18.1 and BS 162 table 4. The electrical equipment inside the panel shall be finger proof. Cubicles shall be of frame structure fully metal enclosed internal sub-division in to Bus-bar compartment Equipment compartment Cable compartment Each vertical compartment shall be furnished with space heater to prevent condensation of moisture. 2.3.3 Cable Entry and Termination All cables to be connected to the panels shall come from bottom. The cable compartment shall have enough space for all incoming and outgoing cables and also for its assembly and maintenance of panels. The bottom plate shall be split and removable type to facilitate cable entry. Plates for cable glands for incoming and outgoing cables are to be provided with accessories. 2.3.4 Bus-Bar (Main and Secondary) The bus-bar shall be installed with rigid non-tracking, non-flammable and 110nnhygroscopic insulating supports capable to withstand magnetic forces imposed by short circuit current at least equal to the interrupting of the switchgear bus main breaker. The switchgear bus-shall be of HDBC copper designed to carry continuously the rated current, operating at its maximum future rating, without exceeding temperature rise requirement specified in referenced standards. All joints in bus-bar shall have non-oxidizing contact surfaces minimum contact resistance and shall be insulated with removable insulating fittings, which will provide insulation at least equal to that of the bus-bar insulation. The bus-bar shall be manufactured and tested to comply with B.S 159 or equivalent continental standard to withstand a fault level of 65KA r.m.s. for one second. 2.3.5 Ground Bus An uninstalled copper ground bus shall be furnished throughout the entire length of the switchgear and connected to the transformer neutral. All switchgear equipment requiring grounding shall be connected to this bus. Copper cross-section of ground bus shall not be less than half of phase bus. The ground bus shall be connected with the earth pits as per design and direction of Engineer. 2.3.6 Circuit Breakers The circuit breakers shall comply with IEC157, BS4752 with horizontal isolation. E. Sub-Station & Generator 226 Volume-III of IV The ACB/MCCB shall be quick make, quick break, trip free, indicating type and shall have inverse time limit characteristics with adjustable overload, short circuit and instantaneous magnetic trip element functioning on overload above the normal operating range. All circuit breakers shall be trip-free. ACB's shall be motorized operated type. Each breaker shall be capable of carrying rated full load current continuously without exceeding the temperature rise specified in the referenced IEC standard. Circuit breaker insulation shall be co-ordinated with that of the switchgear structure and shall be designed for use on a 600-Volt system. All circuit breaker lugs shall be of solder less mechanical type. Breaker main contact surfaces and all secondary device contact surfaces shall be silver-to-silver, designed and fabricated to be self-aligning and to resist burning and deterioration. All breakers of L.V Switchgear system shall be of same manufacturer. Padlocking facilities shall be provided for main incoming circuit breakers, bus coupler and all main circuit breakers in local panels. All main breakers shall be equipped with solid state phase over-current tripping devices to provide interchangeable and independently adjustable over-current and. short circuit protection. Trip settings will be co-ordinated to provide selective trip over-current protection. The Contractor shall furnish tripping devices with characteristics and trip ranges, which will permit this co-ordination. The MCCB’s shall have the following minimum symmetrical interrupting capacity as per B.S and IEC at 415V A.C., if not indicated otherwise: Upto 50 ATP 51 ATP to 100 ATP 101 ATP to 300 ATP 301 ATP to 800 ATP 801 ATP to1600 ATP 1601 ATP to above 2.3.7 : 15 KA : 25 KA : 35 KA : 50 KA : 65 KA : 80 KA Current Transformer All current transformers shall comply with IEC185, BS3938 and shall be of suitable class, rating and accuracy depending on the duty. 2.3.8 The LT switchgear shall be complete with all meters, indicators, switches, relays, and so on as per design, standard and direction of Engineer. E. Sub-Station & Generator 227 Volume-III of IV 2.4 AUTOMATIC POWER FACTOR IMPROVEMENT (PFI) PANELS The Power Factor Improvement panel (PFI) shall be sheet steel clad dust and vermin proof, freestanding, floors mounting indoor type, type tested, locally assembled by approved assembler confirming to IEC-439-1. 2.4.1 Construction The metalized dielectric capacitors should be construction as follows: The metalized coatings to be vapor-deposited on a plastic folium. The folium should act both as a support and dielectric. The capacitors should be of single wound section design; i.e. the sections for each of the three phases should be wound round the core successively and isolated by a separation folium. The wound section is to be fitted in an aluminum jacket. The capacitor shall not contain any liquid impregnate. They shall be with SF6 or N2 gas to stop entrapped air from oxidizing the vapor deposited inside in order to improve life expectancy, capacitance stability, overload capacity and switching durability. 2.4.2 Operating Characteristics Capacitors shall have the following operating characteristics: 2.4.3 High reliability High overload capacity (l.5x rated current for harmonic loading) High capacitance stability High switching durability High temperature class (ambient temp. upto +55 degree C) Long life expectancy Touch-proof terminals Low losses Maximum up to 0.5 W/KVAR at terminals Maximum up to 0.2 W/KVAR in the dielectric Self-healing: Switching peaks may overload capacitors and lead to flash-over in the dielectric. The resultant arc evaporates the metalized layer near the puncture. Faulty points in the dielectric should thus be isolated and the capacitor can continue operating without any trouble. Easy to install, operation, inspection etc. Low weight Maximum Safety for Personnel and Plant The capacitor housing shall have expansion seam that opens and lengthens the housing. This should break the lead between the wound section and the terminal at the rupture joint and the capacitor should thereby be isolated from the system. E. Sub-Station & Generator 228 Volume-III of IV 2.4.4 Regulation The capacitors shall be in compliance with requirement with following regulations: DIN EN 60831-1 IEC 70 IEC 831-1 2.4.5 Technical Data The PFI plant shall comply with the following technical data as a minimum: Rated voltage Max. Permissible operating voltage Max. Permissible current Rated frequency Capacitance tolerances Degree of protection Foil/Foil test voltage Foil/enclosure test voltage Life Time Cooling Housing/Color : 415 V : 460 V : 1.5 x rated current : 50 Hz : -5 to +10% : IP 54 : AC Test with 2.15 x rated Voltage : 3 KV : Min 80000 hours : Self-cooled : Ral 7032 (Light Gray) Electrotating applaud powder coating Details of Capacitors such as manufacturers catalogue, operation and maintenance manual, type test certificate etc. must be submitted with the offer otherwise the bids shall be rejected. E. Sub-Station & Generator 229 Volume-III of IV 2.4.6 Power Factor Correction Relay 2.4.6.1 Construction The digital type controller should be fitted in housing for door mounting. Degree of protection should be IP54 (front) and IP20 (rear), safe to touch. The front should have two operating buttons and a measured value display. The terminals and their diagram should be on the rear side. 2.4.6.2 Connection The controller should be suitable for system voltages from 200V to 690V at 50 to 60Hz & for 1 A & 5A current transformers. The control voltage is in all cases 230V (15 to 20%). 2.4.6.3 Automatic setting of the set point range The Controller shall have self-adaptation facility. Self-adaptation means that it is no longer necessary to set the c/k value (c: power rating of the first capacitor bank k: transformation ratio of the current transformer) during commissioning of the Control Unit, after plant extension or when a current transformer is modified .A maximum of 6 capacitor branches can be controlled in any order via 6 output relays (indication by LED's). Two further output terminals can be used for fault indication (P.F. too low or too high). 2.4.6.4 Technical Data of PFC Relay The PFC shall comply with following technical data as a minimum: Standard Rated Voltage Supply Voltage Rated frequency Consumption No of steps Step function ratio Response time (increase) Response time (decrease) Extension of response time C/K value Housing of Relay Connection Ambient temp Altitude 2.4.6.5 : DIN, VDE 0106, 0160 IEC 0348 : 200V to 690V : 230 V (±10%) : 50Hz : 2VA : Max. 31 at step function ratio: 1,2,4,8,16 : Variable : 30 second : 3 second : Under fast changing load situation the response to be delayed to 2/3 min. : Automatically adjusted in the controller Range 0.01 to 0.1 : Droplets, IP20 : Wire Terminals (SIGUT) : 40 degree. C. : up to 1000 m above see level Display In automatic operation of the PFI panel, the following measured variables must be shown on the display: E. Sub-Station & Generator 230 Volume-III of IV 2.4.6.6 Cos phi (P.F) Apparent current (A) Measuring circuit voltage (V) Active power (KW) Apparent power (KVA) Reactive power, actual (KVAR) Harmonic voltage The Magnetic Contractor of PFI unit shall incorporate following technical data Air contractors shall comply to DIN, VDE 0660 and IEC 158-1 Insulation rating : 750 volt (minimum) Ambient temperature : -25 to 55°C Coil voltage tolerances : 0.85 to 1.1 times rated control voltage Switching frequency in make/break operations per hour- when switching-on to discharged capacitors 90 : 90 Contact endurance (make/break operations) : 100000 Discharge Coil The coils should be suitable for discharging of 25 KV AR and 50 KYAR capacitor banks in less than 5 and 10 second respectively. 2.4.6.7 LV HRC Fuse HRC Fuses with non-insulated gripping lugs shall comply with DIN, VDE 0636 and IEC 269 and shall have breaking capacity 120 KA. Dimension of HRC fuse should be in conformity to DIN 43620 3.0 BUS-BAR TRUNKING (BBT) Fully enclosed by insulated housing, the compact bus-bar trunking system shall be installed from ground floor electrical room low voltage (BNA) and essential (BSA) panels upto 22nd floor roof level of the building to facilitate power distribution system to the DBS of all floor, lifts etc. There shall be two bus-bar trunking, one for normal power (BBT-N) and the other for essential power (BBT-S) supply, common for all floors. 3.1 Technical Requirement The low impedance prefabricated rising main bus-bar trunking shall be suitable for use in installation conforming to IEC-439.1. E. Sub-Station & Generator 231 Volume-III of IV The bus-bar trunking system shall be comprising bus-bar riser, elbow, tee, expansion unit, tap off box connection, circuit breaker, bend, flange, maintenance plug, closed type transformer connection unit, and all other accessories complete for proper installation on wall, with roof and in bus-bar riser duct. The BBT system must have minimum 120 minutes fire barriers. 3.2 Specification of BBT System 1 2 3 4 5 6 7 8 Standard Climatic test 2.3 2.30 Maximum ambient Temperature Degree of protection Color Rated insulation voltage Frequency Rated current of bus-bar 9 Phase configuration 10 Rated short circuit current capacity (KA), 6 cycle BBT-N/BBT-S 11 Bus-bar materials 12 Fire withstand Capacity 13 Special features 14 Drawing and catalogue 15 Type test certificate 3.3 : IEC 439-1 & VDE0660 Pt500 : Damp heat, constant, to IEC 68 Pt : Damp heat cycle to IEC 68 Pt : 45º C : IP54 : Approved color : Minimum 1000 Volt A/C : 50 Hz : 2500A (BBT -N), 1250A(BBT -N), 630A (BBT-S), 1250A (BBT-S) : TP-N-E, (100% neutral) : 150 KA/85 KA : (HDHC) Copper : 120 minutes fire rating : Single bolt clamping : Drawings supported by catalogue to be submitted for the proposed riser system with detailed information, dimension etc. : Valid type test certificate for manufacture & assembly is to be attached. Construction and Assembly of BBT Tap-off units must be designed in such a way that the units can be fitted or removed while the system i.e. the main bus-bar trunking is energized. The BBT shall have 120 minutes fire barrier. . Circuit breakers in the Tap-off units shall be of quick-make, quick break, trip-free, indicating type having adjustable thermal over-current and adjustable/instantaneous Electro-magnetic short circuit release having the rated interrupting capacity. All the components of the BBT i.e. main bus-bar reduction unit, fire barrier, fixing bracket, tap-off boxes, circuit breakers, elbow, tee, feed nut, end cover, expansion unit, reduction unit, etc. shall be from the same manufacturer. E. Sub-Station & Generator 232 Volume-III of IV 3.4 Test Manufacturers test certificate for manufacturing and assembly are to be attached along with valid type test certificate. 3.5 Installation The BBT system shall be installed on floor, ceiling, walls, bus-duct etc, with all necessary cutting, breaking, cleaning, making good in all respect with nuts, bolts, lugs, isolation joint stacks, hangers etc. complete accessories. The bus-bar trunking shall be installed, tested & commissioned as per design standard, specification and instruction of the Engineer/Employer. The Contractor shall be responsible for supplying all materials, equipment, tools, etc required for installation, testing and commissioning of the bus-bar trunking system, starting from sub-station LT panel upto 22nd floor roof level of the building. The Contractor shall put their attention by keeping co-ordination with other Contractors of this project for installation of BBT system as per design and direction of Engineer, so that no conflict arises for BBT system installation. The Contractor at their own cost shall break and make good of any part of the building, if required for installation of BBT. But before proceeding with any of such breaking, the Contractor must take written permission from Authorized Engineer. 4.0 DIESEL GENERATOR The diesel generator with super sound proof Acoustic Canopy (75 to 80 dB @ 1 meter) is required for essential power supply in the Padma Oil Company Ltd. building at Agrabad, Chittagong. The generator shall be located at the ground floor of the building. Essential light, lift, fire pump, water pump, telephone PABX etc. shall be connected to this generator. The diesel generator shall have rating min. 1100 KVA, 415V, 3-phase, 4-wire, 50Hz and will be driven by diesel engine. 4.1 Engine The engine shall be 4 stroke six cylinder (min), vertical line direct injection, water cooled, turbo charged, diesel fired, with inter coolers, of generating capacity not less than 1100 KW under standard condition of 29.92 inches of mercury barometer pressure and 35°C air temperature. The engine overload capacity shall be 10% (min) for one hour operation at conditions specified under B.S. 649, 1958. The engine is to be incorporated with the protection system to shut down automatically in the event of low oil pressure, high water temperature, or reverse power. The engine shall also have replaceable cylinder liners of the wet sleeve type and replaceable valve seat inserts. Exhaust manifold should be water-cooled. E. Sub-Station & Generator 233 Volume-III of IV 4.2 Cooling The engine shall be provided with tropical duty radiator in conjunction with belt driven system, separate core for the inter coolers radiator fan and air duct adapter. Coolant water shall be circulated by centrifugal water pump controlled by thermostat with full flow by pass. 4.3 Filter 4.1.1 Air Filter Dry paper replaceable element type, and designed for easy maintenance are to be provided. The turbocharger shall be of such design as to be of self-cleaning. Turbocharger requiring periodic cleaning will not be acceptable. 4.1.2 Oil Filter Multi-bowl, replaceable element, full flow type. 4.1.3 Fuel Filter Multi-bowl, replaceable element, full flow type. 4.4 Engine Protection The engine shall be equipped with pre-warming alarm devices, which will actuate visible and audible alarms in the event of low oil pressure or excessive jacket water temperature and over speed. The engine shall be equipped with automatic safety shutdown controls which shut-down controls and thereby shut-down the engine in the event of low lubricating oil pressure or high jacket water temperature, Over speed, and reverse power, units shall have auxiliary contacts for a future remote alarm. 4.5 Fuel Injection Equipment This system should be comprised of multiple plunger injection pumps, fuel lines, primary and secondary fuel oil filter, fuel transfer pumps and injectors. 4.6 Exhaust Exhaust manifolds are to be ducted to the turbocharger mounted by the side of the engine through silencer and flexible exhaust pipes. All exhaust components are to be finished with heat resistant aluminum paint. E. Sub-Station & Generator 234 Volume-III of IV 4.7 Lubrication A gear type lubricating oil pump shall supply oil under pressure to main bearings, pistons, turning gears, and camshaft bearings and valve rocker mechanisms. Pistons shall be sprays cooled. Full flow lubricating oil filters shall be provided and so located that lubricating oil is continuously filtered, except during periods when oil is bypassed to protect vital parts such as when filters are clogged. Replaceable resin impregnated cellulose type filter elements shall be accessible and easily removable. Filter system shall be equipped with spring loaded bypass valve as an insurance against stoppage of lubricating oil circulation in the event filters become clogged. A suitable water-cooled engine-mounted lubricating oil cooler shall be furnished. 4.8 Silencer The engine shall be equipped with low noise type silencer, preferable hospital type. 4.9 Radiator Radiator shall be filled up with distilled water and anti-corrosive coolant. 4.10 Governor The electronic governor shall be supplied as per manufacturer’s standard. 4.11 Coupling A substantial cast iron flange and the alternator driven by means of suitable flexible coupling, to dampen the shock should couple engine and Alternator. 4.12 Mounting The engine shall be mounted on a steel skid type base frame suitably strong for rigidity and to withstand vibration and shock. The frame shall have arrangement for fixing the generator on the floor. 4.13 Fuel storage A full load running 8-hour capacity fuel tank is to be supplied along with the generator. Convenient arrangement shall be made by the Contractor for automatic passing of fuel from fuel tank to the engine. 4.14 Starting Electric starting motor with solenoid and overrunning clutch drive shall be furnished on the engine. The starting motor shall be of the required voltage recommended by the engine manufacturer. Batteries shall be provided, and shall be of lead acid type of sufficient capacity for at least 90 seconds at firing times speed, and also with capacity E. Sub-Station & Generator 235 Volume-III of IV for starting the engine a minimum of four times, mounted on the unit or in separate rack located beside engine, including hydrometer, rack and other necessary item. The engine shall start automatically after receiving normal power failure signal from normal bus LT panel. 4.15 Battery Charger A completely automatic battery charger shall be provided, which shall maintain the starting batteries always at full charge. It shall have a high charging rate (12 amps) compatible with the batteries and, when the batteries are brought up to full charge, it shall automatically reduce the charge rate to a continuous trickle charge. An ammeter indicating the high charge rate and fuses on input and output to protect the rectifier and transformer shall be incorporated. 4.16 Generator The generator shall have a continuous rating as indicated 1100 KVA at 0.80 P.F 415V, three phase, 4 wire, 50 Hz, brushless, self- exciting, self regulating, single bearing screen protected, drip proof, fan ventilated with conventional wound stator and salient pole rotating field system, incorporating both the A.C. exciter armature and three phases full wave silicon diode with surge absorber main field rectifier on a common shaft and built in permanent magnet poles. The alternator is to be self excited from its output through a static automatic voltage regulator. Under speed protection and short circuit current protection equipment are to be incorporated with the generator. 4.17 Voltage Regulator The terminal voltage should be maintained within ± 2% of its value at any balanced load, at any power factor between unity and 0.80 lagging inclusive of both resistance variations with temperature and of the usual engine speed regulation with load. A voltage adjusting rheostat shall be provided for field adjustment of ± 5% of rated voltage. 4.18 Wave form The output voltage waveform shall be within B.S. 2613 and B.S 4999 limits. 4.19 Insulation Insulation shall be of class H. All windings should be impregnated with Class-H thermo-setting insulating varnish for use in tropical climates. E. Sub-Station & Generator 236 Volume-III of IV 4.20 Control Panel A cubicle type enclosure of substantial gauge (1.5mm min.) pre-stressed sheet steel construction with lockable front door, two removable side entry gland plates and fitted on the top of the alternator includes. 1 - Voltmeter 0-500V scaled flush mounting moving iron type 1 - Voltmeter phase selector switch 1 - Ammeter 0-2000A flush mounting moving iron type 1 - Ammeter selector switch 3 Current transformer 1500 A with adequate burden for metering and protection 1 - Frequency meter 1 - 1500A or suitably rated circuit breaker with OFF/ON switch with both magnetic and thermal protective device for short circuit and overload protection 1 - Set of push button/key for start, stop and shutdown circuit test 1 - Set of indicating lamps and audible alarms for shut- down on:Low lube oil pressure High water temperature Over speed Fail to start Reverse power supply 1 - Duty selector switch for Auto / Manual start. 1 - Mains voltage off modes sensing relay 1 - Cancel alarm push button 1 - Emergency stop button 1 - Battery charge indicator 1 - Set of automatic mains failure detecting unit and auto start-up system for the generating set. 4.21 Finish Standard finish is to be given with two layers of under coat/primer finished with oil resistant industrial enamel paint. 4.22 Country of origin Country of origin of the generating set shall be USA/ UK/ GERMANY/ FRANCE/ SWITZERLAND/ JAPAN. 4.23 The tenderer must furnish the following 1. Detailed Technical Catalogue including the fuel consumption per hour, model nos. of engine and generator, size of fuel tank etc. 2. Certificate from Manufacturer about the country of origin, quality, genuinely and standard which, support the manufacture of generator. E. Sub-Station & Generator 237 Volume-III of IV 3. Detailed list of spares shall be supplied along with the generating set (with no extra cost) for trouble free operation of the generating set for at least 2000 hrs., and one set of tool box with list of tools. 4. Valid type test certificate 4.24 Automatic Change over Switch The automatic change over switch shall be 1500A, 4-pole, 4ISV, 50Hz and short circuit breaking capacity of 65KA. The ACS shall be mounted in a panel; free standing floor mounted type, dust and vermin proof. It shall automatically transfer the load from main supply to generator in the event of main failure. Display lamps indicating the healthy condition of generator and main supply shall be provided on the panel. Suitable earthing block shall be provided with automatic change over switch. The panel for ACS shall be equipped with indicating lamps, push buttons, etc. complete. In the even of main failure, the following sequence of activities would follow: The generator shall start automatically after a pre-determined time delay adjustment period of 0-10 seconds (3 attempt cranking with lockout features) and when reached up to the required speed and voltage, the changeover contractor shall switch from the mains supply to the generator supply. The generator set shall continue to supply load until such time when the mains supply returns and following an adjustable period of 0-10 minutes, the load shall be transferred back to the mains supply and the generator will continue to run on no load for an adjustable cooling period of 0-10 minutes, after which it shall shut-down and remain in readiness for any future mains failure. Detailed catalogue of automatic change over switch including its drawings showing dimensions shall be supplied along with tender. The country of origin of the auto-change over switch shall be USA/ GERMANY/ FRANCE/ SWITZERLAND/ JAPAN. The Contractor shall be responsible for supply, installation testing and commissioning of the generator change over switch and all other consumables items etc. required for proper functioning as per design, specification and instruction of the Engineer /Employer. E. Sub-Station & Generator 238