* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Download A Method to Enhance Ground
Electronic engineering wikipedia , lookup
Mercury-arc valve wikipedia , lookup
Pulse-width modulation wikipedia , lookup
Electrical ballast wikipedia , lookup
Power inverter wikipedia , lookup
Power over Ethernet wikipedia , lookup
Electric power system wikipedia , lookup
Current source wikipedia , lookup
Resistive opto-isolator wikipedia , lookup
Variable-frequency drive wikipedia , lookup
Opto-isolator wikipedia , lookup
Voltage regulator wikipedia , lookup
Power MOSFET wikipedia , lookup
Protective relay wikipedia , lookup
Amtrak's 25 Hz traction power system wikipedia , lookup
Immunity-aware programming wikipedia , lookup
Power engineering wikipedia , lookup
Ground loop (electricity) wikipedia , lookup
Distribution management system wikipedia , lookup
History of electric power transmission wikipedia , lookup
Buck converter wikipedia , lookup
Switched-mode power supply wikipedia , lookup
Single-wire earth return wikipedia , lookup
Power electronics wikipedia , lookup
Surge protector wikipedia , lookup
Voltage optimisation wikipedia , lookup
Electrical substation wikipedia , lookup
Rectiverter wikipedia , lookup
Stray voltage wikipedia , lookup
Ground (electricity) wikipedia , lookup
Mains electricity wikipedia , lookup
Fault tolerance wikipedia , lookup
Alternating current wikipedia , lookup
Page 1 of 3 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 IEEE PES Letters A Method to Enhance Ground-Fault Computation Shyh-Jier Huang, Senior Member, IEEE, and Hsing-Ho Wan Abstract—This letter presents a simple criterion for reviewing balanced three-phase fault and unbalanced ground-fault current using the ratio of zero sequence impedance to positive sequence impedance as seen from the fault location, which can be employed to enhance the power system design and protection. The method has been verified by real power systems in Taiwan with satisfactory results. Index Terms—Balanced three-phase ground-fault, sequence impedance. fault, unbalanced A A B B C C Ib Ia Ia Ic Zf (a) (b) Fig. 1 The unbalanced ground fault (a) single line-to-ground fault (b) double line-to-ground fault A A B B HORT circuit faults in a power system include single line-to-ground (SLG), line-to-line (LL), double line-to-ground (DLG), and three-phase short-circuit (3SC). Among these types of faults, the SLG occurs most often while the 3SC is commonly deemed the most severe one with largest magnitude of fault current, significantly influencing the decision on the equipments and protective relays setting for power system planning and operation. However, exceptions do exist. The magnitude of SLG current may exceed 3SC current when they occur in the vicinity of a solidly grounded machine or transformer [1]-[2]. Meanwhile, since a ground fault would cause a voltage shift between neutral and ground, the voltage insulation of neutral needs to evaluate more prudently. In this letter, a fast measure is proposed to investigate the relationships among unbalanced ground fault, balanced three-phase fault, and neutral voltage shift, anticipating serving as a more reliable design for power systems protection. C C II. PARADIGM AND METHODOLOGY The symmetrical components analysis is an effective way to evaluate an unbalanced system by using positive, negative, and zero sequence impedances seen from the fault point. Fig. 1 shows unbalanced ground faults, including single line-to-ground and double line-to-ground fault. In the figure, the SLG current in term of sequence impedances can be expressed as I SLG = 3 Z1 + Z 2 + Z 0 where Z1 , Z2 , and Z0 are positive, negative, and zero sequence impedances in ohms per phase. By neglecting fault impedance Zf as well as assuming Z1=Z2 [3], (1) can be rewritten as I SLG 1 3 Z = 1 Z 2+ 0 Z1 Zf (2) The authors are with the Department of Electrical Engineering, National Cheng Kung University, Tainan, Taiwan, R. O. C. Ib Ia Ic Zf Ib Ia Ic (a) (b) Fig. 2 The balanced three-phase fault (a) short-circuit without ground (b) short-circuit with ground The expressions in (1) and (2) are the per-unit currents by assuming that voltage is one per-unit at the fault point. Next, for a balanced three-phase fault, Fig. 2 depicts a short circuit connected with and without the ground. The ratio of SLG current to 3SC current can be expressed as I SLG = I 3SC 3 Z 2+ 0 Z1 (3) The voltage shift between neutral and ground is accordingly derived to be equal to zero-sequence voltage [4], hence the following equation is written Z0 Z V0 = 1 VN Z 2+ 0 Z1 (4) where VN is the phase-to-neutral voltage in the system. Similarly, the ratio of the magnitude of DLG to 3SC becomes I DLG = I 3SC (1) Ic Zf I. INTRODUCTION S Ib 3 Z 1+ 2 0 Z1 2 Z Z × 0 + 0 +1 Z1 Z1 (5) Meanwhile, the neutral voltage shift can be expressed as Z0 V0 Z1 = VN Z 1+ 2× 0 Z1 (6) Equations (3)-(6) illuminate the relationships of currents and neutral voltage shift under unbalanced ground fault scenario using the ratio of Z0 to Z1 . Note that since the resistance values can be neglected for fault current calculations in real power systems, impedances are approximately seen as inductance in IEEE PES Letters this study. Fig. 3 delineates the graphical relationships. From the plot of Fig. 3 (a), contrary to the common knowledge that three-phase fault is the worst possible case, the magnitudes of unbalanced ground fault currents are occasionally larger than those of I 3SC . It seems only when X0 becomes larger than X1 , then unbalanced ground fault currents would be smaller than three-phase fault ones [5]. This observation is very beneficial to determine the interrupt capacity of breakers. Meanwhile, through the investigation of neutral voltage shift as Fig. 3(b) plots, when the condition of X0/X1=3 is encountered [6], the neutral voltage shifts of SLG and DLG is 0.6 and 0.428 per unit, respectively. 1 1.5 DLG / 3SC 1 SLG / 3SC 0.5 0 0 1 2 3 4 5 6 7 8 9 10 X0/X1 Ratio of Voltages (pu) 2 Ratio of Currents (pu) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 0.8 0.6 Vo/Vn (SLG) 0.4 Vo/Vn (DLG) 0.2 0 0 1 2 3 4 5 6 7 8 9 10 X0/X1 taking that SLG fault currents may be larger than 3SC ones into consideration, this letter suggests that a simple condition of X0/X1>1may consider to add. TABLE I: SEVERAL LOCATIONS WITH I3SC>ISLG IN TAIPOWER SYSTEM (2008) Single Three-Phase Impedance Ratio Line-Ground Location Fault Current ISLG V0 R0/X1 X0/X1 I3SC(kA) (kA) (kV) Nantou E/S 33.73 31.08 35.9 0.141 1.249 Tienlun E/S 37.93 32.41 40.0 0.236 1.491 Ermei E/S 46.83 44.80 33.6 0.124 1.128 Renwu E/S 42.28 38.89 36.0 0.126 1.257 Nangkang P/S 34.55 31.91 35.9 0.211 1.236 Hsinchu P/S 35.57 28.50 43.3 0.319 1.716 Tainan P/S 31.71 22.18 49.6 0.486 2.238 Wujia P/S 39.70 28.99 47.7 0.333 2.083 Yingtsai D/S 38.34 37.07 33.2 0.226 1.085 Sanju D/S 25.22 21.82 39.4 0.213 1.455 Hsiaobei D/S 26.71 20.88 44.6 0.355 1.806 Kenting D/S 8.19 5.72 49.3 0.403 2.243 REMARKS: TAIPOWER REQUIRES THE EFFECTIVE GROUNDING SATISFY R0/X1<1 AND X0/X1<3 TABLE II: LOCATIONS WITH I3SC<ISLG IN TAIPOWER SYSTEM (2008) Single Three-Phase Impedance Ratio Line-Ground Location Fault Current ISLG V0 R0/X1 X0/X1 I3SC(kA) (kA) (kV) (a) (b) Fig. 3 Relationships in term of X0/X1 (a) Unbalanced ground faults and balanced three-phase fault currents. (b) Neutral voltage shifts. III. REAL CASES VALIDATION To validate the effectiveness of the method, this study has employed the approach to analyze the fault current data recorded at Taipower in the year of 2008. Both SLG and 3SC faults occurred at 161 kV side of primary transmission system have been extensively surveyed. Table I and II list the fault data, where E/S, P/S and D/S individually stand for extra high-voltage, primary, and distribution substations. From the list of Table I, it indicates that 3SC currents are larger than SLG ones at most locations; yet from that of Table II, the recorded data at seven substations have demonstrated different features in which 3SC are smaller than SLG. Next, with a closer observation, all ratios of X0/X1 in Table 2 are found to be smaller while those of X0/X1 in Table 1 are larger than one. This outcome implies that the ratio of X0/X1 could serve as a useful indicator as all of cases tested in Taipower come with no misidentification found. In the mean time, this proposed method has been applied to compute neutral voltage shifts. Consider a SLG fault occurred at 161 kV side of Sijhih E/S in Table II as an example. By substituting the value of X0/X1 into (4), the magnitude of neutral voltage shift is computed to be 0.946/(2+0.946)= 0.3211 per unit, meaning that the calculated value is equal to 29.84 kV in terms of 161/ 3 kV base. This computed value is very close to the on-site measure of 29.9 kV listed in Table II, further confirming the feasibility and practicality of the method. IV. CONCLUSION Inspection of effective grounding is always an important task from the perspectives of scheduled maintenance of utilities. In practice, the conditions of R0/X1< 1 and X0/X1< 3 are often recommended to justify the effective grounding. However, by Page 2 of 3 Sijhih E/S 36.33 36.96 29.9 0.083 0.946 Banciao E/S 35.59 36.13 30.1 0.122 0.949 Jongke E/S 19.69 19.74 30.8 0.078 0.989 Hsingyi E/S 12.61 13.07 28.7 0.031 0.892 Hsinmin D/S 29.74 30.41 29.6 0.189 0.914 Jingsing D/S 32.12 33.17 29.1 0.148 0.896 Hserho D/S 30.07 31.14 28.8 0.172 0.880 In other words, rather than solely adopt the conditions of X0/X1<3, it may be more prudent to express the conditions as 1<X0/X1<3 when the effective grounding is performed. Besides, the letter has concluded that for effective grounding system, the neutral voltage shift can only reach 0.6 per unit at most. These test results are beneficial to enhance the short-circuit fault computation, anticipating that the forewarning signals can be flagged at an early stage such that system damage can be more effectively restricted. V. ACKNOWLEDGMENT The authors are greatly indebted to technical assistance from System Operation Department in Taiwan Power Company. [1] [2] [3] [4] [5] [6] REFERENCES IEEE Recommended Practice for Industrial and Commercial Power Systems Analysis, IEEE Std. 399, 1997. M. Mitolo, “Grounding the Neutral of Electrical Systems through Low-Resistance Grounding Resistor: An Application Case,” IEEE Trans. Ind. Appl., vol. 44, no. 5, pp. 1311-1316, Sep./Oct. 2008. Paul M. Anderson, Analysis of Faulted Power Systems, IEEE Power System Engineering Series, Piscataway, NJ: IEEE Press, 1995. J. Lewis Blackburn, Symmetrical Components for Power Systems engineering. New York: M. Dekker, c 1993. M. J. Lantz, "Analysis of Fault Currents for High-Voltage Circuit-Breaker Interruption," AIEE Trans. PAS, vol. 74, no. 3, pp. 41-45, Jan. 1955. IEEE Recommended Practice for Grounding of Industrial and Commercial Power Systems, IEEE Std. 142, 2007.