Download Field Testing Morningstar SunGuard Controllers

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Power engineering wikipedia , lookup

Ohm's law wikipedia , lookup

Three-phase electric power wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Electrical substation wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

History of electric power transmission wikipedia , lookup

Islanding wikipedia , lookup

Rectifier wikipedia , lookup

Opto-isolator wikipedia , lookup

Stray voltage wikipedia , lookup

Surge protector wikipedia , lookup

Buck converter wikipedia , lookup

Alternating current wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Electric battery wikipedia , lookup

Voltage optimisation wikipedia , lookup

Mains electricity wikipedia , lookup

Transcript
Field Testing Morningstar SunGuard Controllers
Updated 8/27/99
Notes:
• This testing procedure was developed for use in field conditions where no external
power sources are available.
• Due to the construction of the SunGuard controllers, it is possible only to determine
whether the unit is functioning properly. It is not always apparent what component
has failed or the cause for the failure. It is left up to the technician to determine the
cause for the controllers failure based on evidence present at the site (i.e. burned
leads, excessive loads, evidence of short circuits on system wiring, over PV current
rating, etc)
• The procedures outlined below assume a basic knowledge of electrical circuits and
the necessary safety precautions to be used when working with live circuits present in
solar energy systems.
• You will need a Digital multi-meter (frequency and duty cycle measurements are
helpful) for this procedure.
Testing Procedure:
1. No power applied to the SunGuard
a) With no power applied to the SunGuard, check for short circuits to ground
between the following leads:
i. PV(+) and PV(-)
ii. Battery(+) and Battery(-)
b) Check for continuity between the ground connections on the PV(-) and Battery(-)
leads.
2. Battery power applied to the Battery leads only.
a) Measure the voltage at the battery leads
b) Measure the voltage at the array leads. The voltage should be less than 1.5 Vdc
(negative due to the diode drop across the input FETs). If battery voltage is
measured, the input FETs are damaged and the unit will not regulate the battery
voltage properly.
3. PV and battery power applied to the controller.
a) The voltage across the PV leads should be the same as the voltage across the
battery leads if the batteries are not fully charged.
b) If the batteries are charged, there will be a voltage difference between the
Battery(+) lead and the PV(+) lead. If your DVM has a frequency measuring
option, a 300 Hz AC signal should be measured between Battery (+) and PV (+).
The duty cycle of this signal can also be measured to give a rough indication of
the battery state of charge. The lower the duty cycle, the more fully charged the
battery.
Morningstar Corporation
Columbia, MD USA
page 1 of 2
email: [email protected]
www.morningstarcorp.com
c) Disconnect the PV array from the PV input leads of the controller. After
approximately one minute, the voltage on the PV input leads should drop
significantly lower than the battery voltage.
Final System Checks:
a) Ensure that all connections are secure and weather-protected and that the
controller is housed from the elements.
b) Check the condition of any fuses that might be in the power path.
c) Verify the system wiring is correct and intact.
d) Check all connections and terminals for good electrical contact.
Morningstar Corporation
Columbia, MD USA
page 2 of 2
email: [email protected]
www.morningstarcorp.com