Download Functional Profile: Analog Input

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Public address system wikipedia , lookup

Buck converter wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Linear time-invariant theory wikipedia , lookup

Control system wikipedia , lookup

Signal-flow graph wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Flip-flop (electronics) wikipedia , lookup

Oscilloscope wikipedia , lookup

Schmitt trigger wikipedia , lookup

Oscilloscope types wikipedia , lookup

Multimeter wikipedia , lookup

Oscilloscope history wikipedia , lookup

Analog-to-digital converter wikipedia , lookup

Opto-isolator wikipedia , lookup

Transcript
Version 1.0
Analog Input: 0520
®
LONMARK
Functional Profile:
Analog Input
LONMARK Functional Profile: Analog Input
0520-10 © 1996, LONMARK Interoperability Association.
Echelon, LON, LONW ORKS, LONMARK, and the LONMARK logo are trademarks of Echelon Corporation
registered in the United States and other countries.
2
Analog Input: 0520
Version 1.0
Overview
The Analog Input functional profile is designed to allow all general purpose analog
signals to be represented by a common object. Analog Input signals include current
(i.e. 4 - 20 ma), voltage, thermocouple, RTD, etc. These signals may actually
represent measurements such as flow rate, temperature, capacity, pressure, etc.
The Analog Input functional profile is used when integrating devices that do not
have the ability to interface directly to LONWORKS, but rather utilize an analog
input conversion device that is LONMARK compliant.
Analog Input
Object
Figure 1.1 Analog Input Functional Profile
Example Usage
Devices implementing this function will be sending out SNVTs that are used to
control actuator devices. An example of this would a device controlling value
position is monitoring SNVT_lev_percent from a flow meter. The only
connectivity required is to the mandatory network variable SNVT_lev_percent.
Object Details
Analog Input
Object
Mandatory Network
Variables
nv1
nvoAnalog
SNVT_lev_percent
Configuration Properties
None
Figure 1.2 Analog Input Object Details
LONMARK Functional Profile
3
Mandatory Network Variables
Analog Percent of Full Scale Output
network output SNVT_lev_percent nvoAnalog;
This input network variable provides a value of an analog input signal from 163.84% to 163.84% of full scale.
Valid Range
The valid range is from -163.84% to 163.84%.
When Transmitted
Time of transmission is manufacturer defined.
Update Rate
The maximum update rate is application specific.
Default Service Type
The default service type is acknowledged.
Configuration Properties
None specified.
Data Transfer
None specified.
Power-up State
The network variable nvoAnalog should be set to zero scale until the first reading
is available.
Boundary and Error Conditions
If the A/D converter is not able to perform then the variable nvoAnalog should be
set to negative full scale (-163.84%). This value should be interpreted as an invalid
reading and that there is a problem with the sensor. For inputs that are below zero
scale or above full scale, the variable nvoAnalog should track the input signal as
far as the hardware will permit. If the input signal is below the electrical limits of
the A/D converter, the value for nvoAnalog should be set to -163.83%. Any input
4
Analog Input: 0520
Version 1.0
that is above the maximum input rail of the A/D converter should be represented as
163.84%.
Additional Considerations
If calibration or linearization are required, or if the variable nvoAnalog
(SVNT_lev_percent) does not have the required resolution, please review the
Extended Analog Input functional profile.
LONMARK Functional Profile
5