Download Investigating the Effects of Grid Equivalent Circuit at a Point of

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Ground loop (electricity) wikipedia , lookup

Transistor wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Ground (electricity) wikipedia , lookup

Electrical ballast wikipedia , lookup

Power inverter wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Metadyne wikipedia , lookup

Amtrak's 25 Hz traction power system wikipedia , lookup

Power engineering wikipedia , lookup

Current source wikipedia , lookup

Ohm's law wikipedia , lookup

Islanding wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Rectifier wikipedia , lookup

Two-port network wikipedia , lookup

Triode wikipedia , lookup

Three-phase electric power wikipedia , lookup

Schmitt trigger wikipedia , lookup

Power MOSFET wikipedia , lookup

History of electric power transmission wikipedia , lookup

Electrical substation wikipedia , lookup

Power electronics wikipedia , lookup

Voltage regulator wikipedia , lookup

Buck converter wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Surge protector wikipedia , lookup

Network analysis (electrical circuits) wikipedia , lookup

Opto-isolator wikipedia , lookup

Alternating current wikipedia , lookup

Stray voltage wikipedia , lookup

Voltage optimisation wikipedia , lookup

Mains electricity wikipedia , lookup

Transcript
Observations of Thevenin Equivalent Parameters and Their Effects on the Long-Term Dynamics of Bus
Voltage
Submission Type: Research
Author: Sean Zilberdrut ([email protected], 704-942-1314)
Major: Electrical Engineering
School: University of North Carolina at Charlotte
Education Level: Undergraduate
Faculty Advisor: Dr. Valentina Cecchi ([email protected], 704-687-8730)
Increasing amounts of distributed generation, specifically renewables such as solar and wind, are
presenting distribution systems with a variety of problems. One of those problems is voltage variation in
the system. Distribution systems supply power to loads that depend on a steady voltage, therefore, a
photovoltaic array that has a large rise and fall in output during the course of a day could cause a
protective element to bring load offline. To avoid this, something must be done to minimize the variation
in the long-term variation of the voltage over the course of the day, which shall be termed the long-term
dynamics of the voltage.
A well-known practice in the analysis of circuits is to utilize the Thevenin equivalent of a circuit from a pair
of terminals of interest [1]. This simplifies the rest of the circuit into an equivalent voltage, impedance
and the load or source connected to those terminals. Utilizing this tool, the voltage characteristics at the
terminals of interest can be easily observed. Thus, the Thevenin equivalent parameters can be related to
the voltage at any bus in a distribution system.
Changes to the Thevenin equivalent parameters can be caused by a reconfiguration of the topology of the
system. Distribution systems have switches and sectionalizers that will change the topology of the
network in the event of a fault or extreme loading condition. Utilizing these devices will change the
Thevenin voltage and impedance as seen from each bus and could possibly reduce the long-term voltage
variation caused by a photovoltaic array.
Simulating a power system to find the voltages at its buses requires power flow calculations. The GaussSeidel equation is one method at finding an iterative solution to bus voltages. It was found that through
the Gauss-Seidel equation, a mathematical relationship could be made between the Thevenin equivalent
parameters and the original system voltages. Therefore, it is possible to predict the bus voltages on the
original system from its Thevenin parameters for a given configuration.
This relationship was verified through a 9-Bus Test System, in which graphical relationships between the
Thevenin parameters and the long-term dynamics of the bus voltages were shown. The results revealed
several observations: (1) the long-term dynamics of the bus voltage were negatively related to the
Thevenin voltage, (2) the long-term dynamics of the bus voltage were directly related to the Thevenin
impedance and (3) in some cases the Thevenin voltage and impedance would work against one another;
the parameter with the largest effect would then cause the long-term dynamics of the bus voltage to
behave in (1) and (2).
With these observations in mind, this research could be extended into an optimization problem. If given
a system with a known configuration and a number of switches that connect different buses together that
could form loops, then what configuration would lend towards an optimal voltage profile across the
system? This can be taken another step towards the addition of constraints on how many and which
switches could be closed at any time.
Word Count: 498
References
[1] Nilsson, James William, and Susan A. Riedel. 2011. Electric circuits. Boston: Prentice Hall.
[2] Saadat, Hadi. 2010. Power system analysis. [United States]: PSA Pub.