Download Loop Selective Direction Measurement for Distance Protection

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Stepper motor wikipedia , lookup

Electrical ballast wikipedia , lookup

Immunity-aware programming wikipedia , lookup

History of electric power transmission wikipedia , lookup

Ground loop (electricity) wikipedia , lookup

Rectifier wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Ohm's law wikipedia , lookup

Ground (electricity) wikipedia , lookup

Current source wikipedia , lookup

Schmitt trigger wikipedia , lookup

Power electronics wikipedia , lookup

Metadyne wikipedia , lookup

Triode wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Three-phase electric power wikipedia , lookup

Voltage regulator wikipedia , lookup

Opto-isolator wikipedia , lookup

Buck converter wikipedia , lookup

P–n diode wikipedia , lookup

Electrical substation wikipedia , lookup

Islanding wikipedia , lookup

Surge protector wikipedia , lookup

Voltage optimisation wikipedia , lookup

Protective relay wikipedia , lookup

Alternating current wikipedia , lookup

Stray voltage wikipedia , lookup

Mains electricity wikipedia , lookup

Fault tolerance wikipedia , lookup

Earthing system wikipedia , lookup

Transcript
Journal of Electrical Engineering & Technology, Vol. 1, No. 4, pp. 423~426, 2006 423
Loop Selective Direction Measurement for Distance Protection
Gustav Steynberg* and Gerhard Koch*
Abstract - Distance relays achieve selective tripping by measurement of all short circuit fault
conditions inside set reaches. The direction of the fault, forward or reverse is commonly determined
with a dedicated measurement to ensure selectivity under all conditions. For the direction decision
(measurement) a number of alternatives are available. This paper describes a loop selective direction
measurement and illustrates by means of a typical fault why this is superior to a non loop selective
direction measurement such as that based on negative sequence quantities.
Keywords: Distance protection, Direction measurement, Polarization, Memory voltage, Faulted loop
voltage, Negative sequence
Table 1 Alternatives for direction measurement
1. Introduction
Distance relays must measure all short circuit fault
conditions inside the set reaches. The set reach typically
covers the protected plant (feeder, cable etc.) plus adjacent
circuits in the forward direction as well as reverse reach
covering the busbar and feeders and transformers in the
reverse direction. Selective tripping depends on the
individual zone settings and the correct direction decision.
Direction
measurement
alternatives
Advantage
Disadvantage
Faulted loop
current and
faulted loop
voltage
z Always valid, even
during power swing
z Valid for all loops
z Valid during single
pole open condition
z Very small voltage
(0 V) during close in
faults returns invalid
results
z Not valid close to
series compensation
z Large transients in the
first sampled voltages
after fault inception
may return invalid
result
Faulted loop
current and prefault memory
voltage
z Not affected by
z Only limited validity
transient voltages
during power swings
during the fault
z Memory voltage is
z Valid even if fault
only valid for a
voltage = 0 V
limited time due to
z Valid also in series
frequency deviation
compensated system
during fault
z Valid during single
pole open condition
Faulted loop
current and unfaulted phase
voltages
z Valid even if fault
voltage = 0 V
z Validity is not
affected by
frequency drift
during fault
Negative
sequence
current and
voltage
z Valid even if fault
voltage = 0 V
z Validity is not
affected by
frequency drift
during fault
z Always valid, even
during power swing
Vpol
Forward
I
Reverse
Vpol
Fig. 1. Phasor diagram of current and voltage for direction
measurement
For the direction decision (measurement) a number of
alternatives are available, but the basic direction decision is
obtained from the comparison of the angle between two
phasors. In Fig. 1 this is represented by the current phasor I
(fault loop current) and the polarizing voltage Vpol. The
forward and reverse areas are defined by an angular range
that the polarizing voltage may assume relative to the
current. In Table 1 various polarizing signals are listed and
compared with respect to their relative advantage and
disadvantage.
* Siemens AG PTD PA([email protected])
Received July 19, 2006 ; Accepted November 19, 2006
z Only valid for 1 ph
and 2 ph faults
z Cannot be used
during power swings
z Not valid during
single pole open
condition
z Not valid during
single pole open
condition
z Not valid for three
phase faults
z Not valid for multiple
faults (cross country
fault)
z Not valid close to
series compensation
424
Loop Selective Direction Measurement for Distance Protection
2. Best Choice For Direction Measurement
To achieve the best results under all system conditions
more than one of the alternatives in Table 1 must be used.
The negative sequence direction measurement is however
not one of the first choices of a modern numerical distance
protection because it is not suitable for a full scheme
distance relay that requires a separate direction decision for
each of the six measured loops. For the other alternatives
in Table 1 the current used for the direction measurement
is always the measured fault loop current. The choice of
the voltage depends on the prevailing condition as shown
in Fig. 2 below:
Start
Yes
Series Comp. = No
AND tjump>50ms
AND Vloop > 4 V
Yes
Use faulted
loop voltage
U loop = I loop ⋅ Z loop
(1)
During the forward fault, the voltage Uloop will therefore
lead the current Iloop by the angle of the loop impedance
Zloop.
3. Negative Sequence Direction Measurement
No
Vmem = OK
AND
tjump < 2s
Yes
Use faulted
loop memory
voltage
direction decision is available at this point, an emergency
measurement with Vloop < 4 V but > 1V is attempted if
series compensation is not present. Ultimately if all other
selections fail the forward direction is selected by default.
With the measurement using the faulted loop current and
a polarizing voltage having an angle equivalent to the
faulted loop voltage, the forward fault is defined the
faulted loop equation:
No
1pole DT = NO
AND
Vunfaulted = OK
Use unfaulted
phase voltage
No
Apply existing
result or use
emergency
measurement
tjump = instant of fault inception
Vloop = faulted loop voltage (actual)
Vmem = memory voltage of the faulted loop
Vunfaulted = un-faulted loop voltage corresponding to the faulted loop
Fig. 2. Direction measurement voltage selection flowchart
The best signals for direction measurement depend on
the prevailing conditions (see Table 1). In the modern
distance relay the best signal is selected automatically (see
Fig. 2). The first choice is the faulted loop voltage, and it is
used unless the relay is applied close to a series
compensation, the transients in the measured voltage are
too large (tjump< 50ms) or the measured voltage is too small
(Vloop<4 V). Alternative to this the memory voltage is used
as the next choice. It is always applied during the first
50 ms after jump detection and as first choice with series
compensation. If both these alternatives are not successful
(e.g. because of series compensation and a fault duration of
longer than 2 seconds), the un-faulted loop voltage is next
in line. It is applied if the fault is a single phase or phase to
phase fault and if a single pole open condition is not
present. Ultimately, if none of the previous selections can
be applied the available direction decisions that were
previously obtained are maintained (frozen). If no previous
With negative sequence direction measurement the angle
between the negative sequence current and voltage are
used to determine the fault direction. During unbalanced
forward faults (single phase to ground, phase to phase and
phase to phase to ground faults), the following relationship
exists:
U 2 = −I 2 ⋅ Z 2
(2)
Here Z2 is the negative sequence source impedance at
the relay location and I2 and U2 are the respective negative
sequence current and voltage measured at the relay
location during the forward fault. Therefore U2 leads -I2 by
the angle of the negative sequence source impedance Z2 .
This can also be expressed as U2 lags I2 by the 180ْ minus
the angle of the negative sequence source impedance Z2 .
4. Importance Of Loop Selective Direction
Measurement
The example below will be used to show the importance
of loop selective direction measurement, as described
above and used in Siemens distance relays 7SA522 and
7SA6. For comparison the same fault will also be applied
to a relay using negative sequence based direction
measurement, which is the only further alternative
according to Table 1. When loop selection is done with
negative sequence current and voltage, only one direction
decision is available for all six measured loops in the relay.
Example 1: Fault on the tower of a double circuit line
that results in L2-E in Circuit 2. This is a reverse fault
Gustav Steynberg and Gerhard Koch
for the relay in Circuit 1. The arc of this fault is then
blown into the adjacent circuit where it causes a further
fault L1-E in Circuit 1. This evolved fault is now a
forward fault for the relay under investigation on circuit 1:
E
L
L1
425
decision after the fault evolves to include the forward fault.
In the phasor diagram (Fig. 6) this is apparent. The initial
fault, in the left diagram, is clearly in the reverse direction
as the negative sequence current lags the voltage by
approximately 90ْ . After the fault evolves to include the
forward fault on circuit 1, the negative sequence current
and voltage are almost in phase as shown on the right in
Fig. 6. With these signals, the negative sequence cannot
provide a conclusive direction result. As a result no trip is
issued as shown in Fig. 5.
I/A
2,5
L
L
L2'
L3
0,0
-0,02
-0,01
-0,00
0,01
0,02
0,03
0,04
0,05
0,06
0,07
0,02
0,03
0,04
0,05
0,06
0,07
t/s
-2,5
Circuit 1
Circuit 2
-5,0
K1:IAW A
K1:IBW B
K1:ICW C
U/V
50
0
-0,02
-0,01
-0,00
0,01
t/s
-50
-100
K1:VAY A
Fig. 3. Schematic diagram of faulted tower
The difficulty presented to the distance protection by
this fault becomes apparent when the fault pattern is shown
in the single line diagram below.
The relay is presented with the difficulty of detecting the
L1-E fault in the forward direction and the L2-E fault in
the reverse direction – at the same time. With negative
sequence direction measurement this is not possible as only
one decision for all 6 loops is made!
K1:VBYB
ONLY REVERSE
FAULT DETECTION
K1:VCY C
NO TRIP
FIDEN
TPC
TPB
TPA
R32P
F32P
R32QG
F32QG
-0,02
-0,01
-0,00
0,01
0,02
0,03
0,04
+90°
ZLR
0,07
t/s
+90°
I2*
U2*
I2*
±180°
ZSL
0,06
Fig. 5. Distance relay with negative seq. direction
measurement
U2*
ZLL Circuit 2
0,05
0° ±180°
0°
ZSR
L2-E
relay
ZLL
Circuit 1 ZLR
1,5 A
L1-E
Fig. 4. Single line diagram of example fault distribution
I2*
-90°
30,0 V1,5 A
-90°
30,0 V
U2*
Fig. 6. Phasor diagram of negative sequence signals; left
diagram of initial fault, and right hand diagram of
evolved fault
5. Simulation Of Example 1
The fault pattern of Example 1 was simulated with a
computer tool (Netomac) and injected into a relay with
negative sequence direction measurement and then for
comparison into the 7SA522 which uses the dedicated
direction measurement per loop as shown above in Fig. 2.
As seen in Fig. 5, the initial reverse fault in phase L2 is
followed 30 ms later by the evolved fault that includes the
simultaneous forward fault in L1. The relay with negative
sequence direction measurement detects the reverse fault
condition correctly, but is not able to reach a direction
The response if the same fault is applied to a 7SA522
relay is shown in Fig. 7 below. The relay response
dynamically follows the evolving fault:
The reverse fault in ph L2 is detected correctly. As
shown in Fig. 8 below, the current in phase L2 clearly
leads the voltage (faulted loop voltage uL2 in the right
hand diagram and memory voltage recorded prior to the
fault on the left) by approximately 90ْ which clearly
indicates a reverse fault.
When the fault evolves to include ph L1 in the forward
direction the 7SA522 detects this and issues a correct
426
Loop Selective Direction Measurement for Distance Protection
single pole trip.
6. Conclusion
I/A
2,5
0,0
-2,5
-0,02
-0,01
-0,00
0,01
0,02
0,03
0,04
0,05
0,06
0,07
0,08
0,09
-0,02
-0,01
-0,00
0,01
0,02
0,03
0,04
0,05
0,06
0,07
0,08
0,09
-0,02
-0,01
-0,00
0,01
0,02
0,03
0,04
0,05
0,06
0,07
0,08
0,09
t/s
-5,0
U/V
50
0
-50
t/s
-100
Dis.Pickup L1
Dis.Pickup L2
Dis.Pickup L3
Dis.Pickup E
Dis. forward
Dis. reverse
Relay TRIP L1
Relay TRIP L2
Relay TRIP L3
t/s
Correct detection
and single pole trip
of evolved forward
Initial reverse fault
detected
References
[1] G. Ziegler, Numerical Distance Protection. Erlangen:
Publicis-MCD-Verl., 1999.
[2] Siemens, SIPROTEC 7SA522 V4.3 Manual.
Fig. 7 Response of 7SA522
+90°
+90°
uL1
uL1
iL2
uL2
±180°
0° ±180°
80,0 V
0°
uL2
uL3
uL3
3,0 A80,0 V
-90°
iL2
uL1
3,0 A
-90°
uL2
uL3
Fig. 8. Phasor diagram of initial reverse fault; on the left
the prefault voltage that is used for memory
voltage polarizing
After the fault evolves, the reverse fault is still present
and still detected in reverse as iL2 still leads uL2. The
forward fault detection is however obtained at the same
time for phase L1as the current iL1 clearly lags uL1
(memory and faulted). Thereby correct phase selective
tripping is achieved as shown in Fig. 7 above.
+90°
+90°
iL2
uL1
iL1
uL2
±180°
0° ±180°
uL3
3,0 A
uL1
uL2
0°
uL3
-90°
80,0 V3,0 A
iL1
iL2
uL2
uL3
Particularly in meshed systems with double circuit
overhead lines, distance protection with loop selective
direction measurement is essential to ensure correct
selective tripping. Other methods such as negative
sequence direction measurement are shown to be
insufficient.
-90°
80,0 V
uL1
Fig. 9. Phasor diagram of the evolved fault
Gustav Steynberg
He was born in Cape Town in South
Africa, on December 18, 1959. He
graduated from the University of Cape
Town with a BSc in Electrical Engineering.
His employment experience includes
the South African National Utility,
Eskom, and after immigrating to
Germany in 1993, Siemens AG PTD PA. His special fields
of interest are power system protection, and in particular
distance protection.
Gerhard Koch
He holds a German Diploma Engineer
degree. He has some 34 years experience in protection and substation
control with Messrs. SIEMENS AG,
Germany. Within his carrier he has
held various positions in product and
project management, sales as well as in marketing.
Currently he is director strategic planning in the Power
Automation Division of Siemens AG.