Download Three-phase monitoring relay for grid feeding CM-UFS.1, CM

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Sound level meter wikipedia , lookup

Fault tolerance wikipedia , lookup

Control system wikipedia , lookup

History of electric power transmission wikipedia , lookup

Ground (electricity) wikipedia , lookup

Electrical ballast wikipedia , lookup

Current source wikipedia , lookup

Ohm's law wikipedia , lookup

Power inverter wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Power MOSFET wikipedia , lookup

Relay wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Earthing system wikipedia , lookup

Surge protector wikipedia , lookup

Electrical substation wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Electrical grid wikipedia , lookup

Rectifier wikipedia , lookup

Stray voltage wikipedia , lookup

Alternating current wikipedia , lookup

Voltage regulator wikipedia , lookup

Protective relay wikipedia , lookup

Triode wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Power electronics wikipedia , lookup

Metadyne wikipedia , lookup

Schmitt trigger wikipedia , lookup

Three-phase electric power wikipedia , lookup

Buck converter wikipedia , lookup

Electrical wiring in the United Kingdom wikipedia , lookup

Voltage optimisation wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Islanding wikipedia , lookup

Mains electricity wikipedia , lookup

Opto-isolator wikipedia , lookup

Transcript
Three-phase monitoring relay for grid feeding
CM-UFS.1, CM-UFS.13, CM-UFS.14
2CDC 251 014 F0t09
Data sheet
Features
CM-UFS.1, CM-UFS.1x
 R/T: yellow LED relay status,
timing
 F1: red LED fault message
 F2: red LED fault message
 Adjustment of the threshold
value for the 10 minutes
average value
 Selection of neutral
conductor, connected or
not
6 Marker label
Monitoring of three-phase mains for grid feeding
Type-tested in accordance with
DIN V VDE V 0126-1-1: February 2006 (CM-UFS.1)
DIN V VDE V 0126-1-1/A1 VFR 2013 (CM-UFS.13)
DIN V VDE V 0126-1-1/A1 VFR 2014 (CM-UFS.14)
Neutral conductor connection configurable
Can also be used to monitor single-phase mains
Threshold value for the 10 minutes average value adjustable (110-115% of Us)
Start-up delay tS1 prior to first grid connection and after a short-term interruption, 30 s fixed
Restart delay tS2, 30 s fixed
Powered by the measuring circuit
True RMS measuring principle
2 c/o (SPDT) contacts
3 LEDs for status indication
Approvals
E
CCC 1)
Marks
a
CE
1) CM-UFS.1
only
Order data
Type
Rated control supply voltage = Measuring voltage
Order code
CM-UFS.1
3 x 400 V AC (L-L) / 230 V AC (L-N); 50.2 Hz acc. to
DIN V VDE V 0126-1-1: February 2006
1SVR 630 736 R0300
CM-UFS.13
3 x 400 V AC (L-L) / 230 V AC (L-N); 50.4 Hz acc. to DIN V VDE
V 0126-1-1 and DIN V VDE V 0126-1-1/A1 VFR 2013
1SVR 630 736 R2300
CM-UFS.14
3 x 400 V AC (L-L) / 230 V AC (L-N); 50.6 Hz acc. to DIN V VDE
V 0126-1-1 and DIN V VDE V 0126-1-1/A1 VFR 2014
1SVR 630 736 R3300
Order data - Accessories
Type
Description
Order code
Adapter for screw mounting
1SVR 430 029 R0100
MAR.01
Marker label
1SVR 366 017 R0100
COV.01
Sealable transparent cover
1SVR 430 005 R0100
ADP.01
Application
The CM-UFS.1/CM-UFS.1x are monitoring relays for feeding in three-phase mains. The devices are connected
between the grid connected, decentral electrical energy source such as photovoltaic systems, wind turbines,
block-type thermal power stations, and the public grid. In case the public grid is disconnected due to any
reason, for instance during maintance work, the CM-UFS.1/CM-UFS.1x recognize this powerless situation.
Then, in conjunction with a switching device, the CM-UFS.1/CM-UFS.1x disconnect the decentral electrical
energy source from the public grid.
The devices detect overvoltage and undervoltage (voltage increase and decrease protection) as well as any
changes in grid frequency (frequency increase and decrease protection) in accordance with DIN V VDE V
0126-1-1 and DIN V VDE V 0126-1-1/A1 VFR 2013 / VFR 2014. The connection of the neutral conductor is
configurable. The threshold value for the 10 minutes average value is adjustable.
The CM-UFS.1/CM-UFS.1x are also suitable for monitoring single-phase mains. For this, all three external
conductors (L1, L2, L3) have to be jumpered and connected as one single conductor.
ABB1
Three-phase monitoring relay for grid feeding
CM-UFS.1, CM-UFS.13, CM-UFS.14
Data sheet
L1
L2
L3
N
2CDC 252 022 F0209
Automatized grid connection instead of a permanently accessible switching point with a disconnection function
Low voltage grid
L1 L2 L3 N
25
15
CM-UFS.x
<U<
<f<
16 18
Coordination
of short-circuit
protection,
welding free
26 28
K1
K2
External
switch-off
conditions
2
May also be the inverter output.
In this case, apply the signal of
relay R2 to the relevant input
Inverter(s)
Generator(s)
Power plant
ABB
Three-phase monitoring relay for grid feeding
CM-UFS.1, CM-UFS.13, CM-UFS.14
Data sheet
Operating mode
Configuration of the device is made by means of setting elements accessible on the front of the unit and
signalling is made by means of front-face LEDs.
Adjustment potentiometer
Threshold value for the 10 minutes average value
The threshold value for the 10 minutes average value can be adjusted within a range of 110-115 % of the
rated control supply voltage Us by means of the potentiometer „Average %“ with a linear scale. The value
specified by the network provider has to be set!
Rotary switch
Neutral conductor connection
The connection of the neutral conductor is configurable by means of the rotary switch „Function“.
Neutral conductor not connected
N
Neutral conductor connected
To avoid any faulty tripping, the selection has to be made prior to commissioning. Do not change the
switch setting during operation!
Threshold values
Threshold value
Overvoltage
> 115 % of Us
Undervoltage
< 80 % of Us
Overfrequency
CM-UFS.1
> 50.2 Hz (acc. to DIN V VDE 0126-1-1: February 2006)
CM-UFS.13
> 50.4 Hz (acc. to VFR 2013 of DIN V VDE 0126-1-1/A1)
CM-UFS.14
> 50.6 Hz (acc. to VFR 2014 of DIN V VDE 0126-1-1/A1)
Underfrequency
10 minutes average value
< 47.5 Hz
110-115 % of Us, adjustable
Attention: The threshold value is specified by
the network provider!
LEDs
Function
R/T:
yellow LED
F1:
red LED
F2:
red LED
Output relay energized
V
-
-
Delay active
W
-
-
Overvoltage
-
V
-
Undervoltage
-
-
V
Overfrequency
-
W
-
Underfrequency
-
-
W
Exceedance of the average value
-
V
V
Phase failure
-
V
W
ABB3
Three-phase monitoring relay for grid feeding
CM-UFS.1, CM-UFS.13, CM-UFS.14
Data sheet
Function description / diagrams
Function diagram legend
G Control supply voltage not applied / Output contact open / LED off
B Control supply voltage applied / Output contact closed / LED glowing
Function of the yellow LED
The yellow LED is flashing during timing and turns steady as soon as the output relays are energized.
Phase failure monitoring
Applying control supply voltage begins the fixed start-up delay tS1. When tS1 is complete and all phases
are present with correct voltage and frequency, the output relays energize.
They de-energize instantaneously if a phase failure occurs. The fault is indicated by LEDs.
As soon as all 3 phases are present again, the output relays re-energize automatically after the fixed restart delay tS2 is complete.
L1, L2, L3
L1, L2
L3
tS1
2CDC 252 018 F0209
L1, L2, L3 (N)
Measuring value
L1, L2, L3
tS2
15-18, 25-28
15-16, 25-26
F1: red LED
F2: red LED
R/T: yellow LED
tS1 = Start-up delay prior to first grid connection and after a short-term interruption,
30 s fixed
tS2 = Restart delay, 30 s fixed
Over- and undervoltage monitoring
Applying control supply voltage begins the fixed start-up delay tS1. When tS1 is complete and all phases
are present with correct voltage and frequency, the output relays energize.
If the voltage to be monitored exceeds or falls below the fixed threshold value, the output relays de-energize instantaneously. The fault type is indicated by LEDs.
As soon as the voltage returns to the tolerance range, taking into account a fixed hysteresis of 5 %, the
output relays re-energize after the fixed restart delay tS2 is complete.
2CDC 252 016 F0209
L1, L2, L3 (N)
>U
> U - Hyst.
Measuring value
< U + Hyst.
<U
tS1
tS2
< tS2
< tS2
15-18, 25-28
15-16, 25-26
F1: red LED
F2: red LED
R/T: yellow LED
tS1 = Start-up delay prior to first grid connection and after a short-term interruption,
30 s fixed
tS2 = Restart delay, 30 s fixed
4
ABB
Three-phase monitoring relay for grid feeding
CM-UFS.1, CM-UFS.13, CM-UFS.14
Data sheet
Over- and underfrequency monitoring
L1, L2, L3 (N)
>f
> f - Hyst.
Measuring value
< f + Hyst.
<f
tS1
tS2
< tS2
< tS2
2CDC 252 020 F0209
Applying control supply voltage begins the fixed start-up delay tS1. When tS1 is complete and all phases
are present with correct voltage and frequency, the output relays energize.
If the frequency to be monitored exceeds or falls below the fixed threshold value, the output relays deenergize instantaneously. The fault type is indicated by LEDs.
As soon as the frequency returns to the tolerance range, taking into account a fixed hysteresis, the output
relays re-energize after the fixed restart delay tS2 is complete.
15-18, 25-28
15-16, 25-26
F1: red LED
F2: red LED
R/T: yellow LED
tS1 = Start-up delay prior to first grid connection and after a short-term interruption,
30 s fixed
tS2 = Restart delay, 30 s fixed
10 minutes average value monitoring
L1, L2, L3 (N)
>U
> U - Hyst.
Measuring value
tS1
2CDC 252 002 F0209
Applying control supply voltage begins the fixed start-up delay tS1. When tS1 is complete and all phases
are present with correct voltage and frequency, the output relays energize.
The voltages of the individual phases are measured over a period of 10 minutes and the average value is
calculated. If the 10 minutes average value of a phase exceeds the set threshold value, the output relays
de-energize instantaneously. The fault is indicated by LEDs.
As soon as the 10 minutes average value drops again below the set threshold value, the output relays reenergize instantaneously.
15-18, 25-28
15-16, 25-26
F1: red LED
F2: red LED
R/T: yellow LED
tS1 = Start-up delay prior to first grid connection and after a short-term interruption,
30 s fixed
ABB5
Three-phase monitoring relay for grid feeding
CM-UFS.1, CM-UFS.13, CM-UFS.14
Data sheet
L1
N
L2
L1 L2 L3
N
26
16
15
L3
25
16 18
26 28
25
15
28
18
2CDC 252 036 F0b08
Connection diagram
L1, L2, L3, N
15-16/18
25-26/28
Control supply voltage = Measuring voltage
Output contacts closed-circuit principle
CM-UFS.1, CM-UFS.1x
6
ABB
Three-phase monitoring relay for grid feeding
CM-UFS.1, CM-UFS.13, CM-UFS.14
Data sheet
Data at Ta = 25 °C and rated values, unless otherwise indicated
Type
Input circuit - Supply circuit
Rated control supply voltage Us = Measuring voltage
Rated control supply voltage Us tolerance
Control supply voltage range
Rated frequency
Frequency range
Typical current / power consumption
Power failure buffering time
Input circuit - Measuring circuit
Monitoring functions
Measuring range
Threshold values
Phase failure
Over-/undervoltage
Over-/underfrequency
10 minutes average value
Voltage range
Frequency range
Overvoltage
Undervoltage
Overfrequency
Underfrequency
10 minutes average value
Hysteresis related to
Over-/undervoltage
the threshold value
Over-/underfrequency
Rated frequency of the measuring signal
Frequency range of the measuring signal
Maximum measuring cycle
Maximum reaction time (time between
Over-/undervoltage
fault detection and change of switchOver-/underfrequency
ing status of the relay)
10 minutes average value
Accuracy within the rated control supply voltage tolerance
Accuracy within the temperature range
Measuring method
Timing circuit
Start-up delay tS1 prior to first grid connection and after
a short-term interruption
Restart delay tS2
Accuracy within the rated control supply voltage tolerance
Accuracy within the temperature range
Indication of operational states
Outpur circuits
Kind of output
Operating principle 1)
Contact material
Rated operational voltage Ue (IEC/EN 60947-1)
Minimum switching voltage / switching current
Maximum switching voltage / switching current
Rated operational current Ie
AC12 (resistive) 230 V
(IEC/EN 60947-5-1)
AC15 (inductive) 230 V
DC12 (resistive) 24 V
DC13 (inductive) 24 V
Mechanical lifetime
Electrical lifetime (AC12, 230 V, 4 A)
CM-UFS.1, CM-UFS.13, CM-UFS.14
L1, L2, L3
L-N
3 x 400 V AC
3 x 230 V AC
-20...+20 %
3 x 300-500 V AC
3 x 180-280 V AC
50 Hz
45-55 Hz
23 mA / 16 VA
min. 20 ms
L1, L2, L3
L-N
J
J
J
J
3 x 320-460 V AC
3 x 184-264.5 V AC
45-55 Hz
115 % of Us, fixed
80 % of Us, fixed
50.2 Hz fixed (CM-UFS.1)
50.4 Hz fixed (CM-UFS.13)
50.6 Hz fixed (CM-UFS.14)
47.5 Hz fixed
110-115% of Us, adjustable
5 % fixed
20 mHz fixed
50 Hz
45-55 Hz
50 ms
< 120 ms
< 100 ms
without delay
iU  0.5 %
iU  0.06 % / °C
True RMS
30 s fixed
30 s fixed
it  0.5 %
it  0.06 % / °C
1 yellow LED, 2 red LEDs
Details see operating mode and function description/diagrams
15-16/18, 25-26/28
Relay, 1 x 2 c/o (SPDT) contacts
closed-circuit principle
AgNi alloy, Cd free
250 V
24 V / 10 mA
see load limit curve
4A
3A
4A
2A
30 x 106 switching cycles
0.1 x 106 switching cycles
ABB7
Three-phase monitoring relay for grid feeding
CM-UFS.1, CM-UFS.13, CM-UFS.14
Data sheet
Data at Ta = 25 °C and rated values, unless otherwise indicated
Type
Max. fuse rating to achieve
short-circuit protection
n/c contact
n/o contact
General data
Mean time between failures (MTBF)
Duty time
Repeat accuracy (constant parameters)
Dimensions (W x H x D)
Weight
Monting
Mounting position
Minimum distance to other units
Degree of protection
enclosure / terminals
Electrical connection
Wire size
fine-strand with/without wire end ferrule
rigid
Stripping length
Tightening torque
Environmental data
Ambient temperature range
operation / storage
Damp heat, cyclic (IEC/EN 60068-2-30)
Climatic category (IEC/EN 60721-3-1)
Vibration, sinusoidal (IEC/EN 60255-21-1)
Shock (IEC/EN 60255-21-2)
Isolation data
Rated insulation
input circuit / output circuit
voltage Ui
output circuit 1 / output circuit 2
Rated impulse withstand voltage Uimp
input circuit
(VDE 0110, IEC/EN 60664)
output circuit
Test voltage between all isolated circuits (type test)
Basis isolation
input circuit / output circuit
Protective separation (VDE 0106 part
input circuit /
101 and 101/A, IEC/EN 61140)
output circuit
Pollution degree (VDE 0110, IEC/EN 60664)
Overvoltage category (VDE 0110, IEC/EN 60664)
Standards
Product standard
Further standards
Low Voltage Directive
EMC Directive
RoHS Directive
Electromagnetic compatibility
Interference immunity to
electrostatic discharge radiated, radio-frequency, electro-
magnetic field
electrical fast transient (burst)
surge
conducted disturbances, induced
by radio-frequency fields
harmonics and interharmonics
Interference emission
high-frequency radiated
high-frequency conducted
1)
8
IEC/EN 61000-4-2
IEC/EN 61000-4-3
CM-UFS.1, CM-UFS.13, CM-UFS.14
6 A fast-acting
10 A fast-acting
100 %
< w 0,5 %
22.5 x 78 x 100 mm
(0.89 x 3.07 x 3.94 in)
0.14 kg (0.31 lb)
DIN rail (IEC/EN 60715), snap-on mounting without any tool
any
not necessary
IP50 / IP20
2 x 0.75-2.5 mm² (2 x 18-14 AWG)
2 x 0.5-4 mm² (2 x 20-12 AWG)
7 mm (0.28 in)
0.6-0.8 Nm (5.31-7.08 in.lb)
-25...+60 °C / -40...+85 °C
2 x 12 h cycle, 55 °C, 95 % RH
3K3
Class 2
Class 2
600 V
300 V
6 kV; 1.2/50 µs
4 kV; 1.2/50 µs
2.5 kV, 50 Hz, 1 s
600 V
yes
3
III
IEC/EN 60255-6, DIN V VDE V 0126-1-1: February 2006, DIN V VDE V
0126-1-1-/A1 VFR 2013 / VFR 2014
EN 50178, EN 61727
2006/95/EC
2004/108/EC
2002/95/EC
IEC/EN 61000-6-1, IEC/EN 61000-6-2
Level 3 (6 kV / 8 kV)
Level 3 (10 V/m)
IEC/EN 61000-4-4
IEC/EN 61000-4-5
IEC/EN 61000-4-6
Level 3 (2 kV / 5 kHz)
Level 4 (2 kV L-L, L-N)
IEC/EN 61000-4-13
Class 3
IEC/EN 61000-6-3, IEC/EN 61000-6-4
Class B
Class B
IEC/CISPR 22, EN 50022
IEC/CISPR 22, EN 50022
Level 3 (10 V)
Closed-circuit principle: Output relay(s) de-energize(s), if measured value exceeds or falls below the adjusted threshold value
ABB
Three-phase monitoring relay for grid feeding
CM-UFS.1, CM-UFS.13, CM-UFS.14
Data sheet
Techical diagrams
Load limit curve
DC load (resistive)
2CDC 252 194 F0105
V
300
U 200
100
80
60
50
40
30
V
300
2CDC 252 193 F0105
AC load (resistive)
U 200
100
80
60
50
40
30
20
20
10
0,1
0,2
1
0,5
2
I
4
6
10
0,1
10
A
Derating factor F
0,2
0,5
1
2
I
4
6
10
A
Contact lifetime
0.8
F
0.7
0.6
0.5
250 V
resistive load
2CDC 252 148 F0206
2CDC 252 192 F0205
1.0
0.9
Switching cycles
at inductive AC load
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
cos ϕ
Switching current [A]
Dimensions
in mm
109.5
22.5
0.886”
4.02”
1
0.039”
100
3.94”
5.5
0.216”
2CDC 252 031 F0003
78
3.07”
102
4.31”
ABB9
Three-phase monitoring relay for grid feeding
CM-UFS.1, CM-UFS.13, CM-UFS.14
Data sheet
Dimensions - Accessories
6.5
0.256”
11.5
0.453”
in mm
ADP.01 - Adapter for screw mounting
2CDC 252 186 F0005
20
0.787”
MAR.01 - Marker label
7 0.275”
3.5 0.138”
front-to-back
size 107
2CDC 252 185 F0005
68.5
2.70 ”
22.5
0.886”
3A11
8
0.315”
60 2.362”
70 2.756”
2CDC 252 008 F0010
10
0.394”
20
0.787”
62.5 2.461”
COV.01 - Sealable transparent cover
Further documentation
Document titel
Document type
Document number
Electronic Products and Relays
Technical catalogue
2CDC 110 004 C020x
CM-UFS.1, CM-UFS.13, CM-UFS.14,
CM-UFS.2
Instruction manual
1SVC 630 540 M0002
You can find the documentation online at www.abb.com/lowvoltage R Control Products R Electronic
Relays and Controls
10
ABB
Contact us
Document number. 2CDC 112 141 D0201 (10/2013)
ABB STOTZ-KONTAKT GmbH
P. O. Box 10 16 80
69006 Heidelberg, Germany
Phone: +49 (0) 6221 7 01-0
Fax: +49 (0) 6221 7 01-13 25
E-mail: [email protected]
You can find the address of your
local sales organisation on the
ABB home page
http://www.abb.com/contacts
-> Low Voltage Products and Systems
Note:
We reserve the right to make technical changes or
modify the contents of this document without prior
notice. With regard to purchase orders, the agreed
particulars shall prevail. ABB AG does not accept
any responsibility whatsoever for potential errors or
possible lack of information in this document.
We reserve all rights in this document and in the
subject matter and illustrations contained therein.
Any reproduction, disclosure to third parties or
utilization of its contents – in whole or in parts – is
forbidden without prior written consent of ABB AG.
Copyright© 2013 ABB
All rights reserved