BATCH CONTROLLER
WITH TWO STAGE CONTROL AND ANALOG OUTPUT
DATASHEET F136 - BATCH CONTROLLER
IN RELATION TO THE BATCH PROCESS
Advantages
Signal output
• Robust IP67 (NEMA Type4X) field enclosure.
It is so rugged, you can even stand on it!
• Intrinsically Safe available - ATEX and IECEx
approval for gas and dust applications.
• Programming can be done by your own crew, with
the sensible menu-driven structure, saving cost and
irritation. Know one, know them all!
• Very diverse mounting possibilities: walls, pipes,
panels or directly onto outdoor sensors!
• Two configurable control outputs: for two-stage or
one-stage control.
• (0)4 - 20mA / 0 - 10V DC according to the batch
process.
• Scaled pulse output according to acc. total.
Features
• Large display shows preset value and running
batch value simultaneously.
• The analog output value reflects the course of the
batch process; fourteen different profiles can be
selected.
• Self-learning overrun correction.
• Easy operation to enter a batch value and to control
the process.
• Count-up and count-down function available.
• Explosion/flame proof available.
• Full Modbus communication RS232/485/TTL.
• Loop or battery powered, 8 - 24V AC/DC or
115 - 230V AC power supply.
• Sensor supply 3 / 8.2 / 12 / 24V DC.
1
Signal input
Flow
• Ability to process all types of flowmeter signals:
Reed-switch, NAMUR, NPN/PNP pulse, Sine wave
(coil), Active pulse signals, (0)4 - 20mA, 0 - 10V DC.
Remote control
• Start / Pause / Stop.
Applications
• The F-Series is your first and safest choice for field
mount indicators in safe and hazardous area
applications. Especially in harsh weather
conditions like rain, snow, salty atmosphers and
temperatures between -40°C up to +80°C
(-40°F up to 176°F).
• For batch applications where retransmission of
the course of the proces is required. Alternative
basic model: F030, F130 and F131 or more
sophisticated models: 300-Series or the D-Series
DIN panel mount indicators and controllers.
General information
Signal input
Introduction
The F136 will accept most pulse and analog input
signals for volumetric flow or mass flow
measurement. The input signal type can be
selected by the user in the configuration menu
without having to adjust any sensitive mechanical
dip-switches or jumpers. The analog input is
available with lineair and square root calculation
and even as 4 - 20mA input loop powered.
The F136 offers in addition to the standard
functions an analog output signal in relation to the
batch proces. This to transmit the course of the
process. The operator can enter a batch quantity
easily or execute repeating batches. During the
batch, the preset value is displayed as well as the
batched (or remaining) quantity. The automatic
self-learning overrun correction ensures an
accurate result after each batch.
Communication
All process data and settings can be read and
modified manually or through the Modbus
communication link (RS232 / RS485). If desired,
the batch process can even be started and
stopped through communication.
Full Modbus functionality remains available for the
Intrinsically Safe version (TTL).
Display
The display has large 17mm (0.67”) and 8mm
(0.31”) digits. Besides the proces information, a
seven digit resettable "day total" is available as
well as an eleven digit non-resettable accumulated
total. All values are backed-up in EEPROM memory
every minute.
Hazardous areas
Configuration
This model has been ATEX and IECEx certified
Intrinsically Safe for gas and dust applications,
with an allowed ambient temperature of
-40°C to +70°C (-40°F to +158°F). A flame proof
All configuration settings are accessed via a
simple operator menu which can be password
protected. Each setting is clearly indicated with an
alphanumerical description, therefore avoiding
confusing abbreviations and baffling codes. All
settings are safely stored in EEPROM memory in
the event of sudden power failure.
Ex d enclosure with ATEX certification is also
available.
Enclosures
Various types of enclosures can be selected, all
ATEX and IECEx approved. As standard the F136 is
supplied in an GRP panel mount enclosure, which
can be converted to an field mount enclosure.
Most popular is our rugged aluminum field mount
enclosure with IP67 / NEMA Type4X rating. Both
European or U.S. cable gland entry threads are
available.
Analog output signal
The (0)4 - 20mA or 0 - 10V DC output signal is
related to the batch process. For example, a 4mA
will be generated when START has been pressed
and this value will increase smootly to 18.7mA
when the overrun correction closes the valve. The
end value will be 20mA when the batch is finished.
Fourteen different profiles are available to
re-transmit the course of the process (see section
profiles). The output signal can be passive, active
or isolated where the passive output type will loop
power the F136 as well.
Overview application F136
Pulse output R2
(with 1-stage control only)
Analog output
Communication link
Remote control:
START
PAUSE / STOP
Control outputs
Two outputs are available which can be configured
to operate as two stage control for large batch
quantities or as one stage control for smaller
batches, where the second output is available as a
scaled pulse output. The output signals can be
passive NPN, active PNP or an isolated electromechanical relay.
Control output R1
Control output R2
Flowmeter
input
2
F136
F136
0.9"
14mm
1 2
/ "NPT
15mm
38mm
24mm 24mm
36mm
36mm
1 2
/ "NPT
15mm
HP
1 2
/ "NPT
HT
6 x M12
HJ
Ø22 ( 7/8") Ø22 ( 7/8") Ø22 ( 7/8")
HK
1.18" 1.18"
Flat bottom, no holes available.
1
/2"NPT
HU
4 x M20 x 1.5
HV
HZ
3
+
Display example - 90 x 40mm (3.5” x 1.6”)
+
+
=
PL: input loop powered
(terminals GND - 1 - 2 are not available)
PB / PC: battery powered
Internal long life Lithium battery
AP: 8 - 30V DC
Output loop powered
-
ZB: Backlight: 12 - 24V DC
-
PX: 8 - 30V DC
PM: 115 - 230V AC
-
PF: 24V DC
+
30mm (1.18") 30mm (1.18")
+
Ø12
-
24mm 24mm
36mm
36mm
+
=
OR: mech. relay
HH
PF: 24V AC
M20 x 1,5
Ø20
+
12mm 12mm
-
Ø20
PD - XI: 16 - 30V DC
M20 x 1,5
=
=
OR: mech. relay
+
OT: passive trans.
HG
07
08
I+
I+
I+
I+
I+
U
U+
AU: 0 - 10V
I
AP: 4 - 20mA
I-
AI: 4 - 20mA
I-
AF: 4 - 20mA
I
AB: 0 - 20mA
I
-
-
+
I+
I+
A - PL: 4 - 20mA
U+
U: 0- 1 0V
A: (0)4 - 20mA
+
P: active signal
P: namur
P: PNP
+
+
+
+
P: reed switch / NPN
11
IR: Start
12
+
14
13
Ø16
10
09
P: coil
Ø22 ( 7/8")
OT: passive trans.
25mm 25mm
AA: 4 - 20mA
HF
06
M16 x 1,5
Ø20
05
Ø16
OA: active 24V DC
HE
04
30mm 30mm
03
HO
IR: Stop
15
+
16
ADDITIONAL INPUT
HD
OA: active 24V DC
M20 x 1,5 PG9
ADDITIONAL INPUT
GRP
PD: 8 - 24V DC
12mm 12mm
HN
17
112 mm (4.40")
02
M20 x 1,5
HM
18
19
20
21
Ø 7mm (0.27")
01
25mm
22
23
24
panel cut-out
00
25mm
25
26
27
A
A
DTR
+12V
RXD
CT: TTL Intrinsically Safe
CI: RS485 - 4 wire
28
RXD
CH: RS485 - 2 wire
DTR
+12V
CB: RS232
TXD
B
B
TXD
29
COMMUNICATION
98 (3.86")
115 (4.53")
FLOWMETER INPUT
60 mm (2.36")
130 mm (5.12")
PD: 8 - 24V AC
M20 x 1,5
HL
ANALOG OUTPUT
/2"NPT
CONTROL
OUTPUT R1
1
CONTROL / PULSE
OUTPUT R2
M16 x 1,5
1.18"
22,50mm
Aluminum
POWER REQUIREMENTS
30mm 30mm
HA
22,50mm (0.9")
30mm 30mm
22,50mm
75 mm (2.95")
22,50mm
/ "NPT
Ø 7mm (0.27")
17mm
0.9"
130 mm (5.12")
14mm
1 2
22,50mm
HB & HC enclosures
22,50mm (0.9")
22,50mm
1.18"
22,50mm
PG9
17mm
29 mm
(1.14")
+
0.9"
31 mm
(1.22")
15mm
120 mm (4.72")
Y
30
Z
31
Aluminum & GRP panel mount enclosure
+
16mm
120 mm (4.72")
Dimensions enclosures
Terminal connections
Aluminum & GRP field / wall mount enclosures
Typical wiring diagram F136-P-AP-CH-OT-PX
Typical wiring diagram F136-A-AA-CB-OA-PD
OUTPUT LOOP POWERED
TERMINAL CONNECTORS
F100 - series
24V AC / DC POWER SUPPLY
TERMINAL CONNECTORS
F100 - series
Modbus communication type CB: RS232
26
16
+ 3.2V 1M
low-pass
filter
15
Common ground
+ 3.2V 1M
low-pass
filter
+ 3.2V 1M
low-pass
filter
Additional input type IR:
START
12
Common ground
Common ground
Common ground
29
28
27
08
01
Common ground
00
01
Main supply
Power supply type PX:
8 - 30V DC
(not used in this example)
09
10
-
03
04
04
+
Common ground
06
Common ground
e.g. relay or solenoid
*Supply voltage: 1.2 / 3.2V DC to sensor
e.g. relay
Control output type OA:
active 24V DC pulse
123456
e.g. counter
Control or pulse output type OA:
active 24V DC pulse
03
Control or pulse output type OT:
passive transistor
Analog output type AA:
active 4 - 20mA
05
-
05
06
+
Common ground
07
Common ground
e.g. indicator
02
-
07
-
08
+
+
8 - 30V DC
8 - 24V AC
Power supply type PD:
8 - 24V AC / DC
00
10
Common ground
e.g. relay or solenoid
Flowmeter input type A:
(0)4 - 20mA
Signal
Analog output type AP: passive 4 - 20mA (loop powered)
e.g. indicator
Common ground
Additional input type IR:
START
11
Flowmeter input
type: P
pulse
Signal
Common ground
Additional input type IR:
PAUSE / STOP
Supply *
11
Supply *
09
Circuit depends on
type of signal
Common ground
13
Common ground
14
Additional input type IR:
PAUSE / STOP
8 - 24V DC
-
+ 3.2V 1M
low-pass
filter
Common ground
+
Common ground
26
DTR
12V
16
28
RXD
15
A
13
29
TXD
12
B
27
Modbus communication type CH: RS485 - 2 wire
*Supply voltage: 3.2 / 8.2 / 12 / 24V DC to sensor
4
F136
Typical wiring diagram F136-P-AP-CH-OR-PF
Typical wiring diagram F136-A-AI-CI-OR-PM
24V AC / DC POWER SUPPLY
29
29
A
28
A
B
115 - 230V AC POWER SUPPLY
Modbus communication type CI: RS485 - 4 wire
26
16
15
13
11
Flowmeter input
type: P
pulse
10
09
Common ground
e.g. indicator
08
08
+
8 - 30V DC
07
05
05
e.g. relay or solenoid
03
Main supply
Power supply type PM:
115 - 230V AC
00
01
02
24V AC
Common ground
00
Power supply type PF:
24V AC / DC
01
02
03
e.g. relay or solenoid
*Supply voltage: 1.2 - 3.2 - 8.2 - 12 - 24V DC to sensor
F136
Control or pulse output
type OR:
mechanic relay
04
04
Control or pulse output
type OR:
mechanic relay
e.g. relay or solenoid
Common ground
Analog output type AI:
8 - 30V DC
passive isolated 4 - 20mA
06
06
07
e.g. relay or solenoid
Main supply
Flowmeter input type A:
(0)4 - 20mA
Signal
Analog output type AP: passive 4 - 20mA (loop powered)
e.g. indicator
Common ground
Additional input type IR:
START
Supply *
11
Common ground
10
Signal
Additional input type IR:
PAUSE / STOP
12
16
15
Common ground
Supply *
09
Circuit depends on
type of signal
Common ground
+ 3.2V 1M
low-pass
filter
Additional input type IR:
START
13
+ 3.2V 1M
low-pass
filter
Common ground
12
Common ground
+ 3.2V 1M
low-pass
filter
Additional input type IR:
PAUSE / STOP
-
+ 3.2V 1M
low-pass
filter
Common ground
+
Common ground
26
27
B
Y
28
Modbus communication type CH: RS485 - 2 wire
Z
31
TERMINAL CONNECTORS
F100 - series
30
TERMINAL CONNECTORS
F100 - series
*Supply voltage: 3.2 / 8.2 / 12 / 24V DC to sensor
5
N
L1
Hazardous area applications
Certificate of conformity KEMA 03ATEX1074 X
• IECEx DEK 11.0042X
The F136-XI has been certified according ATEX
and IECEx by DEKRA for use in Intrinsically Safe
applications with an ambient temperature of
-40°C to +70°C (-40°F to +158°F).
• The ATEX markings for gas and dust
applications are:
II 1 G Ex ia IIB/IIC T4 Ga
II 1 D Ex ia IIIC T100 °C Da.
• The IECEx markings for gas and dust
applications are: Ex ia IIC/IIB T4 Ga and
Ex ia IIIC T100 °C Da.
Besides the I.S. power supplies for the control
outputs, it is allowed to connect up to three I.S.
power supplies in IIB/IIIC applications or one in
IIC applications. Consult the certificate for the
maximum input and output values of the
circuits. Full functionality of the F136 remains
available, including two stage control,
4 - 20mA output, pulse output and Modbus
communication (type CT). Power supply type
PD-XI offers a 8.2V sensor supply e.g. for one
Namur sensor.
An ATEX approved flame proof Ex d enclosure is
available as well. Please contact your supplier
for further details.
Configuration example IIB / IIIC and IIC - F136-P-AP-(CT)-OT-PX-XI - Output loop powered unit
16
Additional input type IR:
PAUSE / STOP
Ci is negligibly
small
Additional input type IR:
START
SAFE AREA
15
Ci is negligibly
small
HAZARDOUS AREA
11
Supply *
Flow meter input
type: P
pulse
10
09
e.g. indicator
Uo=max 30V
Po=max 750mW
08
Common ground
Ci is negligibly
small
-
Signal
+
Circuit depends on
type of signal
Common ground
13
Common ground
+ 3.2V 1M
low-pass
filter
Modbus communication type CT: TTL (not used in this example).
12
+ 3.2V 1M
low-pass
filter
Io=max 100mA
07
Analog output type AP: passive 4 - 20mA (output loop powered)
Common ground
05
04
Uo=max 30V
-
03
Po=max 750mW
+
Common ground
Control output type OT: passive transistor
Po=max 750mW
e.g. relay
Ci is negligibly
small
Control or pulse output type OT: passive transistor
Uo=max 30V
Io=max 100mA
-
06
+
Common ground
e.g. relay
Ci is negligibly
small
POWER SUPPLY
and / or REPEATER
Io=max 100mA
For example
MTL 5525 / MTL 5541
e.g. indicator
POWER SUPPLY
e.g. MTL 5525
or
SWITCH INTERFACE
e.g. MTL 5511
e.g. relay
POWER SUPPLY
e.g. MTL 5525
or
SWITCH INTERFACE
e.g. MTL 5511
e.g. relay
Note: above values are safety values.
Consult the technical specification for operational values.
* Note sensor supply voltage: 1.2V DC for coil sensors or 3.2V DC for other pulse sensors.
6
F136
Configuration example IIB / IIIC - F136-A-AF-CT-OT-(PC)-(PD)-XI - Power requirement 16 - 30V DC or battery powered
HAZARDOUS AREA
TERMINAL CONNECTORS
F100 - series
SAFE AREA
TXD
29
Modbus communication type CT: TTL
28
Uo=max 30V
RXD
26
16
Additional input type IR:
PAUSE / STOP
Ci is negligibly
small
Additional input type IR:
START
15
Ci is negligibly
small
11
Supply *
+
e.g. indicator
Analog output type AF:
passive floating 4 - 20mA
07
06
05
04
03
02
01
Due to analog output type AF, the unit has to be powered with
battery type PC or with external power supply type PD.
Power supply type PD: 16 - 30V DC
00
Common ground
Po=max 750mW
e.g. relay
Uo=max 30V
POWER SUPPLY
Uo=max 30V
Io=max 100mA
Io=max 100mA
-
Main supply
Control output type OT:
passive transistor
-
Common ground
Po=max 750mW
Io=max 100mA
e.g. relay or counter
Ci is negligibly
small
e.g. relay
POWER SUPPLY
e.g. MTL 5525
or
SWITCH INTERFACE
e.g. MTL 5511
Uo=max 30V
+
Common ground
e.g. indicator
POWER SUPPLY
e.g. MTL 5525
or
SWITCH INTERFACE
e.g. MTL 5511
Po=max 750mW
Control output type OT:
passive transistor
REPEATER
For example
MTL 5541
POWER SUPPLY
e.g. MTL 5525
and / or
REPEATER
e.g. MTL 5541
Uo=max 30V
-
e.g. relay
Ci is negligibly
small
Po=max 750mW
Io=max 100mA
+
Ci = 17nF
Uo=max 30V
Io=max 100mA
+
08
09
Flow meter input type: A
(0)4 - 20mA
-
Ci is negligibly
small
+
Common ground
10
Signal
-
Circuit depends on
type of signal
Common ground
For example: MTL5051
14
+ 3.2V 1M
low-pass
filter
13
Common ground
Po=max 850mW
12
+ 3.2V 1M
low-pass
filter
e.g. PC
-
Common ground
27
+
DTR
+12V
Io=max 250mA
ISOLATOR:
I.S. Certified Isolator
TTL to
RS232 / RS422 / TTL
Po=max 750mW
For example
MTL 5525
Note: above values are safety values.
Consult the technical specification for operational values.
* Note power supply type PD: the supply voltage to pulse sensors is maximum 8.7V (Uo=max 8.7V Io=max 25mA Po=max 150mW) and to analog sensors as connected to terminal 1 (internally linked).
F136
7
Profiles increasing output
Selectable profiles analog output signal:
Overrun Up
20
20
15
15
0-20mA
0-20mA
Stay
10
10
5
5
0
0
-25
0
25
50
75
100
-25
125
0
Batchprocess %
25
100
125
75
100
125
75
100
125
End Up
20
20
15
15
10
10
5
5
0
0
-25
0
25
50
75
100
-25
125
0
Batchprocess %
25
50
Batchprocess %
End Down
Bounce Up
20
20
15
15
0-20mA
0-20mA
75
0-20mA
0-20mA
Overrun Down
10
10
5
5
0
0
-25
0
25
50
75
100
125
-25
Batchprocess %
0
25
50
Batchprocess %
Bounce Down
-25%:
0%:
75%:
100%:
125%
20
15
0-20mA
50
Batchprocess %
Situation before a next batch start.
The moment after START has been pressed.
Valve will be closed due to the overrun correction.
End of overrun-time which is end-of-batch.
Situation after end-of-batch.
10
5
0
-25
0
25
50
75
100
125
Batchprocess %
8
F136
Profiles decreasing output
Selectable profiles analog output signal:
Stay
Overrun Up
15
15
0-20mA
20
0-20mA
20
10
10
5
5
0
0
-25
0
25
50
75
100
125
-25
0
Batchprocess %
25
Overrun Down
75
100
125
75
100
125
100
125
End Up
15
15
0-20mA
20
0-20mA
20
10
10
5
5
0
0
-25
0
25
50
75
100
125
-25
0
Batchprocess %
25
50
Batchprocess %
End Down
Bounce Up
15
15
0-20mA
20
0-20mA
20
10
10
5
5
0
0
-25
0
25
50
75
100
-25
125
Batchprocess %
-25%:
0%:
75%:
100%:
125%
20
0-20mA
15
10
5
0
-25
0
25
50
0
25
50
75
Batchprocess %
Bounce Down
75
100
125
Batchprocess %
F136
50
Batchprocess %
9
Situation before a next batch start.
The moment after START has been pressed.
Valve will be closed due to the overrun correction.
End of overrun-time which is end-of-batch.
Situation after end-of-batch.
Directives & Standards
Technical specification
EMC
Low voltage
RoHS
ATEX / IECEx
IP & NEMA
General
Display
Type
Dimensions
Digits
Refresh rate
Option ZB
Note ZB
High intensity reflective numeric and
alphanumeric LCD, UV-resistant.
90 x 40mm (3.5” x 1.6”).
Seven 17mm (0.67") and eleven 8mm (0.31") digits.
Various symbols and measuring units.
User definable: fast, 1sec , 3sec, 15sec, 30sec, off.
Transflective LCD with white LED-backlight.
Good readings in full sunlight and darkness.
Only available for safe area applications.
Directive 2014/30/EU, FCC 47 CFR part 15.
Directive 2014/35/EU
Directive 2011/65/EU
Directive 2014/34/EU, IEC 600079-0, IEC 60079-11.
EN 60529 & NEMA 250
Enclosure
General
Window
Sealing
Control keys
Polycarbonate window.
Silicone.
Three industrial micro-switch keys. UV-resistant
silicone keypad.
Ambient temperature
Safe areas
-40°C to +80°C (-40°F to +176°F).
Intrinsically Safe -40°C to +70°C (-40°F to +158°F).
Aluminum wall / field mount enclosures
General
Power requirements
Dimensions
Weight
Type AP
Analog output loop powerd, 8 - 30V DC.
Power consumption max 0.5 Watt.
Type PB
Long life Lithium battery - life-time depends upon
settings and configuration - up to 5 years.
(requires PD, PL or PX)
Type PC
Intrinsically Safe long life lithium battery - life-time
depends upon settings and configuration - up to 5
years. (requires XI and PD or PX)
Type PD
8 - 24V AC / DC ± 10%. Power consumption max. 10
Watt. Intrinsically Safe: 16 - 30V DC; power
consumption max. 0.75 Watt.
Type PF
24V AC / DC ± 10%. Power consumption max. 15 Watt.
Type PL
Input loop powered from sensor signal 4 - 20mA
(type “A”) - requires types AI and OT (not Xi).
Type PM
115 - 230V AC ± 10%. Power consumption max. 15 Watt.
Type PX
8 - 30V DC. Power consumption max. 0.5 Watt.
Type ZB
12 - 24V DC ± 10%. Power consumption max. 1 Watt.
Note PB/PF/PM Not available Intrinsically Safe.
Note PF/PM
The total consumption of the sensors and outputs
may not exceed 400mA @ 24V.
Note
For Intrinsically Safe applications, consult the safety
values in the certificate.
Type HA
Type HL
Type HM
Type HN
Type HO
Type HP
Type HT
Type HU
Type HV
Type HZ
GRP wall / field mount enclosures
General
Dimensions
Weight
Type HD
Type HE
Type HF
G
Type H
Type HH
Type HJ
Type HK
Sensor excitation
Type PB/PC/PX
Note
Type PD
Type PD-XI
Note
Type PF / PM
Die-cast aluminum wall/field mount enclosure IP67 /
NEMA Type4X with 2-component UV-resistant coating.
130 x 120 x 75mm (5.12" x 4.72" x 2.95") - W x H x D.
1100 gr.
Cable entry: 2 x PG9 and 1 x M20.
Cable entry: 3 x 1/2" NPT.
Cable entry: 2 x M16 and 1 x M20.
Cable entry: 1 x M20.
Cable entry: 2 x M20.
Cable entry: 6 x M12.
Cable entry: 1 x 1/2" NPT.
Cable entry: 3 x 1/2" NPT.
Cable entry: 4 x M20.
Cable entry: no holes.
3V DC for pulse signals and 1.2V DC for coil pick-up.
This is not a real sensor supply. Only suitable for
sensors with a very low power consumption like coils
(sine wave) and reed-switches.
1.2 / 3 / 8.2 / 12 / 24V DC - max. 50mA @ 24V DC.
1.2 / 3 / 8.2V DC - max. 7mA @ 8.2V DC and mains
power supply voltage (as connected to terminal 1).
In case PD-XI and signal A or U: the sensor supply
voltage is according to the power supply voltage
connected to terminal 1. Also terminal 2 offers the
same voltage.
1.2 / 3 / 8.2 / 12 / 24V DC - max. 400mA @ 24V DC.
GRP wall/field mount enclosure IP67 / NEMA Type4X,
UV-resistant and flame retardant.
130 x 120 x 75mm (5.12" x 4.72" x 2.95") - W x H x D.
600 gr.
Cable entry: no holes.
Cable entry: 2 x Ø 16mm and 1 x Ø 20mm.
Cable entry: 1 x Ø 22mm (7/8").
Cable entry: 2 x Ø 20mm.
Cable entry: 6 x Ø 12mm.
Cable entry: 3 x Ø 22mm (7/8").
Flat bottom, cable entry: no holes.
Panel mount enclosures
Dimensions
Panel cut-out
Type HB
Weight
Type HC
Weight
130 x 120 x 60mm (5.12" x 4.72" x 2.36") - W x H x D.
115 x 98mm (4.53" x 3.86") L x H.
Die-cast aluminum panel mount enclosure IP65 /
NEMA Type4X.
600 gr.
GRP panel mount enclosure IP65 / NEMA Type4X,
UV-resistant and flame retardant.
450 gr.
Terminal connections
Type
Removable plug-in terminal strip.
Wire max. 1.5mm2 and 2.5mm2.
Data protection
Type
Password
EEPROM backup of all settings. Backup of running
totals every minute. Data retention at least 10 years.
Configuration settings can be password protected.
10
F136
Analog output
Hazardous area
Intrinsically Safe (Type XI)
ATEX
certification
IECEx
certification
Ambient Ta
Function
Accuracy
II 1 G Ex ia IIB/IIC T4 Ga.
II 1 D Ex ia IIIC T100 °C Da.
Ex ia IIC/IIB T4 Ga.
Ex ia IIIC T100 °C Da.
-40°C to +70°C (-40°F to +158°F).
Update time
Type AA
Type AB
Type AF
Explosion proof (Type XF)
ATEX certification
Type XF
Weight
Note
Type AI
II 2 G / Ex d IIB T5 Gb.
II 2 D / Ex t IIIB T100 °C Db.
Dimensions of enclosure: 300 x 250 x 200mm
(11.8" x 9.9" x 7.9") L x H x D.
Appr. 15kg.
IECEx available on request.
Type AP
Type AU
Transmitting process situation.
10 bit. Error < 0.05%. Analog output signal can be
scaled to any desired range.
Eight times per second.
Active 4 - 20mA output (requires PD, PF, PM or PX).
Active 0 - 20mA output (requires PD, PF, PM or PX).
Passive floating 4 - 20mA output for Intrinsically
Safe applications (requires XI + PD or PX).
Passive galvanically isolated 4 - 20mA output - also
available for battery powered models.
Passive 4 - 20mA output - not isolated. Unit will be
loop powered.
Active 0 - 10V DC output (requires PD, PF, PM or PX).
Digital outputs
Function
Signal inputs
Flowmeter
Type P
Coil / sine wave (HI: 20mVpp or LO: 80mVpp sensitivity selectable), NPN/PNP, open collector, reedswitch, Namur, active pulse signals 8 - 12 and 24V DC.
Frequency
Minimum 0Hz - maximum 7kHz for total and flow rate.
Maximum frequency depends on signal type and
internal low-pass filter. E.g. reed switch with
low-pass filter: max. frequency 120Hz.
K-Factor
0.000010 - 9,999,999 with variable decimal position.
Low-pass filter Available for all pulse signals.
Option ZF
coil sensitivity 10mVpp.
Type A
(0)4 - 20mA. Analog input signal can be scaled to any
desired range within 0 - 20mA.
Type U
0 - 10V DC. Analog input signal can be scaled to any
desired range within 0 - 10V DC.
Accuracy
Resolution: 14 bit. Error < 0.025mA / ± 0.125% FS.
Low level cut-off programmable.
Span
0.000010 - 9,999,999 with variable decimal position.
Update time
Four times per second.
Voltage drop
Type A: 2.5V @ 20mA.
Load impedance Type U: 3kOhm.
Relationship
Linear and square root calculation.
Note
For signal type A and U: external power to sensor is
required; e.g. type PD.
Frequency
Type OA
Type OR
Type OT
User defined: batch process one or two stage control
- scaled pulse output according the running batch or
according accumulated total.
Max. 500Hz. Pulse length user definable between
0.001 second up to 9.999 seconds.
Two active 24V DC transistor outputs (PNP);
max. 50mA per output (requires PD, PF, PM or PX).
Two electro-mechanical relay outputs (N.O.) - isolated;
max. switch power 230V AC - 0.5A per relay
(requires PF or PM).
Two passive transistor outputs (NPN) - not isolated.
Max. 50V DC - 300mA per output.
Operational
Operator functions
Displayed
functions
• Preset value - can be entered by the operator.
• Batched quantity or remaining quantity.
• Total and accumulated total.
• Total can be reset to zero by pressing the STOPkey twice.
Preset / total
Digits
Units
Decimals
Note
7 digits.
L, m3, GAL, USGAL, kg, lb, bbl, no unit.
0 - 1 - 2 or 3.
Total can be reset to zero.
Additional inputs
Accumulated total
Function
Digits
11 digits.
Units / decimals According to selection for total.
Note
Can not be reset to zero.
Type IR
Duration
Remote control: Two terminal inputs to start, stop
and reset the batch process.
Internally pulled-up switch contact - NPN.
Minimum pulse duration 100msec.
Accessories
Mounting accessories
Signal outputs
Communication option
Function
Protocol
Speed
Addressing
Type CB
Type CH
Type CI
Type CT
F136
ACF02
ACF05
Reading display information, reading / writing all
configuration settings.
Modbus RTU.
1200 - 2400 - 4800 - 9600 baud.
Maximum 255 addresses.
RS232
RS485 2-wire
RS485 4-wire
TTL Intrinsically Safe.
ACF06
ACF07
ACF08
ACF09
ACF11
11
Stainless steel wall mounting kit.
Stainless steel pipe mounting kit (worm gear clamps
not included).
Two stainless steel worm gear clamps Ø 44 - 56mm.
Two stainless steel worm gear clamps Ø 58 - 75mm.
Two stainless steel worm gear clamps Ø 77 - 95mm.
Two stainless steel worm gear clamps Ø 106 - 138mm.
Swivel with 25° movement from center axis for direct
flowmeter mounting: 1” NPT to 1/2” NPT.
Ordering information
Standard configuration: F136-P-AP-CX-HC-IR-OT-PX-XX-ZX.
Ordering information:
F136
Flowmeter input signal
A
P
U
(0)4 - 20mA input.
Pulse input: coil, npn, pnp, namur, reed-switch.
0 - 10V DC input.
AA
AB
AF
AI
AP
AU
Active 4 - 20mA output - requires PD, PF, PM or PX.
Active 0 - 20mA output - requires PD, PF, PM or PX.
I.S. floating 4 - 20mA output - requires XI + PD or PX.
Isolated 4 - 20mA output.
Passive 4 - 20mA output, loop powered unit.
Active 0 - 10V DC output - requires PD, PF, PM or PX.
CB
CH
CI
CT
CX
Communication RS232 - Modbus RTU.
Communication RS485 - 2wire - Modbus RTU.
Communication RS485 - 4 wire - Modbus RTU.
Intrinsically Safe TTL - Modbus RTU.
No communication.
HB
HC
Aluminum enclosure.
GRP enclosure.
-_
-A _
-C _
-H _
-IR
-O _
-P _
-X _
-Z _
Analog output signal
Communication
Panel mount enclosures - IP65 / NEMA Type4X
GRP field / wall mount enclosures - IP67 / NEMA Type4X
HD
HE
HF
G
H
HH
HJ
HK
Cable entry: no holes.
Cable entry: 2 x Ø 16mm & 1 x Ø 20mm.
Cable entry: 1 x Ø 22mm (7/8”).
Cable entry: 2 x Ø 20mm.
Cable entry: 6 x Ø 12mm.
Cable entry: 3 x Ø 22mm (7/8”).
Flat bottom, cable entry: no holes.
Aluminum field / wall mount enclosures - IP67 / NEMA Type4X
HA
HL
HM
HN
HO
HP
HT
HU
HV
HZ
Cable entry: 2 x PG9 + 1 x M20.
Cable entry: 2 x 1/2”NPT.
Cable entry: 2 x M16 + 1 x M20.
Cable entry: 1 x M20.
Cable entry: 2 x M20.
Cable entry: 6 x M12.
Cable entry: 1 x 1/2”NPT.
Cable entry: 3 x 1/2”NPT.
Cable entry: 4 x M20.
Cable entry: no holes.
IR
Remote control input to start, pause or stop.
OA
OR
OT
Two active transistor outputs - requires PD, PF, PM or PX.
Two mechanical relay outputs - requires PF or PM.
Two passive transistor outputs - standard configuration.
PD
PF
PL
PM
PX
8 - 24V AC/DC + sensor supply - with XI: 16 - 30V DC.
24V AC/DC + sensor supply.
Input loop powered from sensor signal type “A” - requires AI and OT (not Xi).
115 - 230V AC + sensor supply.
Basic power supply 8 - 30V DC (no real sensor supply).
PB
PC
Lithium battery powered - requires PD, PL or PX.
Lithium battery powered - Intrinsically Safe - requires XI, and PD or PX.
XI
XF
XX
Intrinsically Safe, according ATEX and IECEx.
Ex d enclosure - 3 keys according ATEX.
Safe area only.
ZB
ZF
ZX
Backlight.
Coil input 10mVpp.
No options.
Additional input signal
Digital output signals
Power requirements
Additional battery supply (optional)
Other options
The bold marked text contains the standard configuration.
Available Intrinsically Safe.
Specifications are subject to change without notice.
Fluidwell bv
P.O. Box 6
5460 AA - Veghel - The Netherlands
Telephone: +31 (0)413 343 786
Telefax: +31 (0)413 363 443
email: [email protected]
Internet: www.fluidwell.com
12
Copyright: Fluidwell bv - 2017 - F136-DATA-EN-V1704
Hazardous area