Download 1.2kV thru 44kV Class Dry-Type Medium Voltage (Power)

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Islanding wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Current source wikipedia , lookup

Power inverter wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Rectifier wikipedia , lookup

Stray voltage wikipedia , lookup

Voltage regulator wikipedia , lookup

Metadyne wikipedia , lookup

Power engineering wikipedia , lookup

Electrical substation wikipedia , lookup

Buck converter wikipedia , lookup

Surge protector wikipedia , lookup

Opto-isolator wikipedia , lookup

Three-phase electric power wikipedia , lookup

Single-wire earth return wikipedia , lookup

History of electric power transmission wikipedia , lookup

Voltage optimisation wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Rectiverter wikipedia , lookup

Resonant inductive coupling wikipedia , lookup

Mains electricity wikipedia , lookup

Alternating current wikipedia , lookup

Transformer wikipedia , lookup

Transcript
1.2kV thru 44kV Class
Dry-Type Medium Voltage (Power)
Distribution Transformer
Typical Specification for the
UNITED STATES
United States
1100 Lake Street
Baraboo, Wisconsin
53913-2866
Phone: 1-866-705-4684
Fax: 1-608-356-2452
E-mail: [email protected]
www.hammondpowersolutions.com
CSI-2004 (Section 26 12 16)
Page 1 of 4
SPS# 26, Rev: 02
1
GENERAL
1.1 SCOPE
A
This section defines dry-type, enclosed and ventilated medium voltage (power) transformers as
indicated.
Transformers shall be designed, constructed and rated in accordance with UL and NEMA/ANSI
standards.
Transformers shall be designed, constructed and rated (where applicable) in accordance with
U.S. Department of Energy, Energy Conservation Program for Commercial Equipment;
Distribution Transformers Energy Conservation Standards (DOE 10 CFR Part 431).
B
C
1.2 RELATED DOCUMENTS
A
Drawing and general provisions of the Contract, including General and Supplementary
Conditions and Division 1 Specification Sections, apply to this Section
1.3 REFERENCES
A
B
C
D
ANSI C57.12.01, C57.12.91, C57.110 for non-linear loads, C57.18.10 for rectifier duty
UL 1562
NEMA ST-20
DOE 10 CFR Part 431
1.4 SUBMITALS
A
i
ii
Submit shop drawing and product data for approval and final documentation in the quantities
listed according to the Conditions of the contract.
Customer name. Customer location and customer order number shall identify all
transmittals.
Product Data including KVA rating, Temperature Rise, Detailed enclosure dimensions,
Primary & Secondary nominal voltages, primary voltage taps, no load & full load losses,
impedances, unit weight, warranty; Efficiency (where applicable) per DOE 10 CFR Part 431.
1.5 STORAGE AND HANDLING
A
B
Store and handle in strict compliance with manufacturer’s instructions and recommendations.
Protect from potential damage from weather and construction operations. Store so condensation
will not form on or in the transformer housing and if necessary, apply temporary heat where
required to obtain suitable service conditions.
Handle transformer using proper equipment for lifting and handling, use when necessary lifting
eye and/or brackets provided for that purpose.
1.6 WARRANTY
A
The transformer shall carry a 1 year limited warranty.
(For details, refer to the manufacturers published warranty)
2
PRODUCTS
2.1 GENERAL CONSTRUCTION:
A
Transformer core shall be manufactured from quality non-aging, cold rolled, fully processed
silicon steel laminations. Cores are to be precisely cut to close tolerances to eliminate burrs and
improve performance. Typically they would be step-lap, fully mitered construction for optimum
energy efficiency and low noise level. Cores are to be carefully assembled and rigidly held secure
with structural steel clamps to minimize gaps. Glass resin I beams that can withstand 2000lbs
per square inch shall be used as blocking coil supports for superior resistance to axial short
circuit forces. Primary and secondary terminations to be mounted on separate insulated supports.
CSI-2004 (Section 26 12 16)
Page 2 of 4
SPS# 26, Rev: 02
2.2 VOLTAGE AND KVA REQUIREMENTS:
A
B
C
D
E
F
Primary Voltage: [44000][34500][25000][13800][12470][6900][4160][2400][1200][other]
Primary Voltage BIL Rating: [10][20][30][45][60][95][110][125][150][other]
Secondary Voltage: [120/208][277/480][347/600][other]
Secondary Voltage BIL Rating: [10][20][30][45][other]
kVA rating: [750][1000][1250][1500][2000][2500][3000][4000][5000][7500][other]
System Frequency: 60 [50] [other] Hertz
2.3 KEY REQUIREMENTS:
A
B
C
D
E
The manufacturer will provide third party test results verifying short circuit capability on the
standard design construction concept used by the manufacturer.
The following production tests must be completed on all transformers. Pass fail criteria will be
per ANSI C57.12.01 and C57.12.91.
i
Polarity
ii
Ratio
iii
Resistance of coils
iv
Insulation resistance test
v
Power frequency voltage-withstand tests on each winding.
vi
Induced voltage test
vii
No load loss
viii
Load loss
ix
Impedance test
For the following type tests please refer to job-specific data sheet.
i
Temperature rise test
ii
BIL
iii
Partial Discharge
iv
Sound level
Standard impedance at 60Hz: [5% to 8.5%] [other]
Name Plate Rating: Linear load, 60Hz
2.4 BASIC REQUIREMENTS:
A
B
C
i
ii
iii
iv
D
E
F
G
H
I
J
Three-phase, common core construction. Convection air cooled [Fan Cooled]
Average winding rise by resistance shall not exceed 150 °C [115°C] [80°C] in a maximum 40
deg. C ambient.
Efficiencies: (where applicable)
Meets or exceeds DOE 10 CFR Part 431 (and/or NEMA TP1) efficiencies at 50% of rated
load on units having a primary voltage BIL rating greater than 1.2kV.
Efficiencies are calculated under a linear load profile.
Efficiencies, no-load losses, load losses and impedance values will be calculated at
temperature reference of 75°C at Unity Power Factor (UPF).
Refer to the DOE 10 CFR Part 431 Energy Efficiency Standards for product exemption
criteria.
Four high voltage taps shall be provided; two at 2.5% FCAN and two at 2.5% FCBN. Off circuit
tap selection shall be by tap links.
Impregnation: vacuum impregnated polyester resin.
Sound level to meet NEMA ST-20
Enclosure: ventilated NEMA 1 [NEMA 2][NEMA 3R][NEMA 3R c/w filters][totally enclosed]
[other].
Enclosure Finish: [ANSI 61 Grey] [ANSI 61 Grey suitable for UL50 outdoor applications] [other].
Anti-vibration pads/isolators shall be used between the transformer core and coil and the
enclosure.
UL listed.
OPTIONS:
CSI-2004 (Section 26 12 16)
Page 3 of 4
SPS# 26, Rev: 02

























Fan mounted provisions only for future forced air-cooling.
Forced air-cooling. 120V Power will be supplied/ not supplied.
Forced air cooling with 30% overload capacity without exceeding natural cool kVA rating.
Taps shall be FCAN XX%., FCBN XX%, and RCBN XX%.
Lightning arrestors: Station class, Intermediate class or Distribution class.
A grounding resistor shall be provided. (Rating to be specified by customer.)
A Neutral Ground Monitor shall be provided.
Thermometers: [dial 2 contacts][dial 3 contacts][4-20mA o/p thermocouple input][other]
Trip Thermostat (1 per phase): [N.O. 200°C][N.C. 200°C][other]
Alarm Thermostat (1 per phase): [N.O. 180°C][N.C. 180°C][other]
Nameplate shall be Aluminium or Stainless Steel.
A Kirk key interlock to prevent unauthorized access shall be provided. (Option: Kirk key interlock
with indicating signal light that indicates doors are open shall be provided).
A current transformer on the HV or LV windings shall be provided to the specification in job-specific
data sheet. (customer to provide ratio and accuracy requirement)
An electrostatic shield shall be provided.
Transformer shall be designed to handle the current harmonics provided in job-specific data sheet.
Duty Cycle shall be to attached job-specific data sheet.
Potential transformer shall be provided to the specification provided in job-specific data sheet.
(customer to provide ratio and accuracy requirement)
A strip heater powered from separate source shall be provided.
Seismic: Meets all seismic parameters for IBC 2009 and NBCC 2005 for ground level installations
only for all locations in North America.
Anti-vibration options: [Anti-vibration Pads][Super W Pads][Spring Isolators][Springs & Snubbers]
Low Sound Level: [-3 dB][ -5 dB][-8 dB][other]
Manufacturer has the ability to guarantee EMF levels as low as 10mG on the enclosure top and four
sides from a distance of 1 meter for most units and kVA ranges. (Contact manufacturer for details on
pricing and availability.)
SPD (Surge Protection Device)
Rolling and Skidding Base: [2 directions] [4 directions].
Provision for Lifting and Jacking.
2.5 ACCEPTABLE PRODUCT AND MANUFACTURER:
A
B
3
Hammond Power Solutions Inc. (U.S.: 1-800-537-0500).
Substitutions are permitted, subject to meeting all requirements of this specification and also
having written approval by engineering 10 days prior to bid closing.
EXECUTION
3.1 INSTALLATION
A
The installing contractor shall install the Dry-Type Medium Voltage (Power) Transformer per the
manufacturer's recommended installation practices as found in the installation, operation, and
maintenance manual and comply with all applicable codes.
Make sure that the transformer is level.
B
C
D
E
F
G
H
I
J
The transformer shall be mounted on a concrete pad unless otherwise indicated.
i
ii
Check for damage and loose connections.
Mount transformer on suitable isolation pad to minimize vibrations.
Install seismic restraint where indicated on the drawing.
Coordinate all work in this section with all work of other sections.
Take Infrared Picture to verify connections accuracy or deficiencies.
Prior to energizing transformer, verify secondary voltages and if necessary adjust secondary taps.
Report of the Commission of the transformer shall include:
Primary & Secondary Voltages
Primary & secondary THDi & THDv
CSI-2004 (Section 26 12 16)
Page 4 of 4
SPS# 26, Rev: 02