AX-GS-CD-ST8013
Carbon Dioxide Switch for Ventilation Control
Product Overview
The AX-GS-CD-ST8012 Is a low cost wall mounted CO2
switch for ventilation control. The unit incorporates an
intuitive Visual Level Indicator display for CO2 thresholds
to maintain air quality in enclosed spaces (i.e. school
classrooms, offices, gymnasiums, theatres etc)
Features
•
Wall mounting
•
230V 8A rated output relay
•
Monitors CO2 over range 600 to 2,000 ppm
•
15year calibration interval
•
230Vac Power supply
•
Intuitive Light Display
Product Specifications
Sensor Type:
Range:
Calibration Interval:
Accuracy:
Stability:
Temperature Dependance:
Power Supply:
Consumption:
Ambient Temp. Range:
Switch:
LED Displays:
<600
<800
<1000
<1500
<2000
>2000
Housing:
Dimensions:
Outputs:
Output Switch Levels:
Anti Recycle Time:
Conformity:
Country of Origin:
Non-dispersive Infra-red
600-2000ppm standard,
15 Years
+/- 20ppm
Self Calibrating <2% FS over life of sensor (typical 15yrs)
0.2% FS per ’C
85Vac to 265Vac 50/60Hz
<1.5 W @nominal voltage of 230Vac
0 to +50’C , 0-95% RH non condensing
Auto-On-Off
1st single Blue
2nd single blue
Green
Yellow
Single Red
Double Red
Flame retardant ABS
100 x 80 x 28 mm
Switched Live
User selectable at 1000ppm(default) or 1500ppm with hysteresis of 300ppm
Min On/Off period 10 minutes in Auto
CE marked, EMC, LVD.
Mexico
Order Codes
AX-GS-CD-ST8013
Space Mounted CO2 Switch
- Switched Live output
AX-GS-CD-ST8013 - Issue 1.2 - Date 28/3/2012
Unit 21, Highview, High Street, Bordon, Hampshire. GU35 0AX.
Tel: +44 (0)1420 487788 Fax: +44 (0)1420 487799
Email: [email protected]
www.axio.co.uk
© Copyright Axio 2004. All Rights Reserved
Page 1 of 4
AX-GS-CD-ST8013
Carbon Dioxide Switch for Ventilation Control
Mounting Instructions
The Room sensor has mounting provisions to install directly on a standard electrical box and should be mounted at a
height about five feet from the floor of the area to be controlled. For best operation, do not mount the sensor near
doors, opening windows, supply air diffusers or other known air disturbances.
ABC Software and Lifetime Guarantee
ABC Software
ABC (Automatic Background Calibration) Program utilises the computing power in the sensors onboard
microprocessor to remember the lowest CO2 concentration that takes place every 24hours. The sensor assumes this low
point is at outside levels. The sensor is also smart enough to discount periodic elevated readings that might occur if for
example a space was used 24 hours a day over a few days. Once the sensor has collected 14 days worth of low
concentration points, it performs a statistical analysis to see if there has been any small changes in the sensor reading
over background levels that could be attributable to sensor drift. If the analysis concludes there is drift, a samll
correction factor is made to the sensor calibration to adjust to this change.
Lifetime Calibration Guarantee
Based on the results of years of testing of ABC software, we now offers a lifetime calibration guarantee on all the
AX-GS-CD-T81 series. If the sensor is found to be out of calibration more than 150ppm as compared to a calibration Gas
or recently calibrated reference. This guarantee only applies if the sensor is operated in an environment where inside
levels periodically drop to outside concentrations ( i.e. during evenings or weekends when there is no occupancy) as is
required by the ABC software. If a space does not experience a periodic drop to outside levels (i.e. where occupancy is
24Hrs/7days/week),ABC software should be deactivated. With ABC deactivated, calibration may be required every 2
years.
Dimensions
Every effort has been taken in the production of this data sheet to ensure it’s accuracy. Axio can not, however, accept responsibility for any damage, expense, injury, loss or consequential loss
resulting from any errors or omissions. Axio has a policy of continuous improvement and reserves the right to change this specification without notice.
AX-GS-CD-ST8013 - Issue 1.2 - Date 28/3/2012
Unit 21, Highview, High Street, Bordon, Hampshire. GU35 0AX.
Tel: +44 (0)1420 487788 Fax: +44 (0)1420 487799
Email: [email protected]
www.axio.co.uk
© Copyright Axio 2004. All Rights Reserved
Page 2 of 4
AX-GS-CD-ST8013
Carbon Dioxide Switch for Ventilation Control
Wiring Diagram
Terminals
1
L (85 to 265Vac)
Input
2
N (85 to 265Vac) Input
3
N
4
ON (85 to265Vac) FAN-RELAY Normally Open
(N.O.) when the CO2 < threshold
Switched Live
5
OFF(85 to265Vac) FAN-RELAY Normally Closed
(N.C.) when the CO2 < threshold
Switched Live
Output
AX-GS-CD-ST8013 - Issue 1.2 - Date 28/3/2012
Unit 21, Highview, High Street, Bordon, Hampshire. GU35 0AX.
Tel: +44 (0)1420 487788 Fax: +44 (0)1420 487799
Email: [email protected]
www.axio.co.uk
© Copyright Axio 2004. All Rights Reserved
Page 3 of 4
AX-GS-CD-ST8013
Carbon Dioxide Switch for Ventilation Control
AX-GS-CD-ST8013 - Issue 1.2 - Date 28/3/2012
Unit 21, Highview, High Street, Bordon, Hampshire. GU35 0AX.
Tel: +44 (0)1420 487788 Fax: +44 (0)1420 487799
Email: [email protected]
www.axio.co.uk
© Copyright Axio 2004. All Rights Reserved
Page 4 of 4